You are on page 1of 6

1

Novel Health Assessment Techniques for a Modern


Power Distribution System
Robert C. Ivans1∗ , Student-Member, IEEE, Pierce L. Russell1 , Tyler B. Phillips1 , Student-Member, IEEE,
2021 IEEE Symposium on Industrial Electronics & Applications (ISIEA) | 978-1-6654-1591-0/21/$31.00 ©2021 IEEE | DOI: 10.1109/ISIEA51897.2021.9509983

Vivek K. Singh1 , Member, IEEE, Timothy R. McJunkin1 , Senior Member, IEEE, and Craig G. Rieger1 , Senior
Member, IEEE

Abstract—Distribution systems are large and complex systems these metrics provide insightful information to system health,
that grow over time. When contingencies occur dispatchers, en- the authors of [18] determined that the system voltage profile,
gineers, and executives need to know the answer to the question, load, loss, and source power depend heavily on the load
“How bad is it?”, in order to make timely and meaningful
decisions. Therefore, a scalable method to add context to system model that is used when considering the distribution system
conditions is needed. In this paper we present novel deviation- and consequently, show that the incorporation of a voltage
based techniques which enable scaled bus voltage and line power dependent load model is essential. In addition, the 33-bus
measurement deviations to quickly assess local and global health, system we will be using for testing features a single generator,
and lend context to the severity of contingencies. The proposed invalidating the use of frequency stability analysis for our
techniques are demonstrated using simulations of line-to-line,
line-to-ground, and three-phases-to-ground fault conditions on purposes.
an IEEE 33-bus distribution model. In this paper, we present a novel approach to health as-
Index Terms—distribution system, heath metrics, line faults, sessment of the distribution system. Local health assessment
voltage stability. indicates the health of an individual aggregated system re-
source (ASR). In this work we define an ASR as a set of
assets that have common objectives. Note that the ASR can
I. I NTRODUCTION
be used for many scales. For example, the components of

T HE ability to assess the heath of a power system


facilitates an enhanced security focused environment
and promotes a more robust, health-centric system [1], [2].
a microgrid, a set of customers in a neighborhood on the
same distribution feeders, the whole distribution system, a
transmission operator area, a balancing authority, etc., could
Complex power distribution systems rely heavily on system all be ASRs. Global system health is analyzed over the
security and the system’s ability to maintain integrity during collection of ASRs. This approach provides system operators
contingent events, such contingencies could cause unforeseen with an enhanced health analysis awareness to facilitate a
consequences to the economic and safe operation of the power stronger security cognizance. By utilizing line power and bus
system [3], [4]. The security of a power system can be defined voltages as health assessment metrics, we avoid complications
as its capability to withstand disturbances in the face of these with traditional heath assessment techniques such as voltage
events as well as its ability to remain operable to its customers security and frequency stability. Testing of this methodology
without interruption [5]–[9]. Due to the complex and expan- was conducted on a model of the IEEE 33-bus distribution
sive nature of distribution systems, scalable system health system which provides a robust testing environment for the
assessment becomes a necessary tool to assist dispatchers, proposed health assessment techniques.
engineers, and executives, in making decisions relative to the
In order to provide meaningful local and global health
overall health of the system. Consequently, we present our
assessment, system operating points are sampled at set time
novel approach to health assessment of a power distribution
intervals to indicate system status. These operating points are
system using the IEEE 33-bus distribution model.
measurements of the bus voltages and line powers of the
Traditional health assessment, which is based on voltage
system. Operating points are then transformed by assessment
security and/or frequency stability, provides a deeper insight
functions into deviations used to calculate local and global
into the operational health of a system and provides indications
system health. In addition, to assist in the awareness of
of anomalous activity [10]. Voltage security is defined as
critical anomalies, importance factors are utilized to emphasize
the system’s capability to maintain system’s voltage within
significant busses, lines, or ASRs to highlight to a human or
acceptable limits during system stress, physical disturbances,
machine, critical faults in the system should they arise.
and cyber-attacks [11]–[15]. Similarly, frequency stability is
defined as a system’s ability to maintain a stable and syn- The rest of the paper is as follows: Section II is a literature
chronous frequency environment between generators amid review, Section III discusses our implementation of the IEEE
environmental and external disturbances [16], [17]. While 33-bus model, Section IV explains the proposed novel heath
assessment technique, and Section V presents our simulation
1 Idaho National Laboratory: {Robert.Ivans, Tyler.Phillips, VivekKu-
results demonstrating the proposed techniques using an IEEE
mar.Singh, Timothy.McJunkin, Craig.Rieger}@inl.gov
∗ Corresponding author. 33-bus distribution model. Finally, Section VI concludes the
Manuscript received December 28, 2020 paper.

Authorized licensed use limited to: National Renewable Energy Laboratory. Downloaded on February 23,2022 at 01:50:43 UTC from IEEE Xplore. Restrictions apply.
2

II. L ITERATURE R EVIEW TABLE I


A C OMPARISON OF T HIS W ORK AND I OANES, & T ÎRNOVAN [21]
Modern life depends on access to dependable and inexpen-
sive power. As such, numerous metrics to describe aspects This work Ioanes, & Tı̂rnovan
of the systems that facilitate power generation, transmission, Training required? No Yes
and distribution have been devised. The state of electric power Scaling through p? Yes No
infrastructure in response to abnormal events, such as voltage Health expressed as: A floating point ”OK”, ”Vigilance”,
and frequency disturbances, have been quantified using metrics number between or ”Critical”
0.0 and 1.0
including voltage stability (sometimes referred to as voltage
Health calculated from: Expected value LSTM prediction
security), power security, and frequency stability. deviation deviation
Ajjarapu defines voltage stability as, “... the ability of a
power system to maintain steady voltages at all the buses in Distribution line
Tieline (N.O.)
the system after being subjected to a disturbance from a given Circuit breaker
initial operating condition [19].” This definition implies that Tie-line recloser
Fault indicator
voltage stability is a quantity that is conditioned upon a power Bus fault

system’s capacity to handle a future transient. Health is distinct


from voltage stability in that it expresses nothing about future
transients.
Morison et al. describes power security as, “... the degree
of risk in a power system’s ability to survive imminent
disturbances (contingencies) without interruption to customer
service [20].” This definition implies that power security is
dependent on statistical analysis or probability calculation to
assess risk. Health is distinct from power security in that risk Fig. 1. Modified IEEE 33-bus distributed system separated into six ASRs.
is not taken into consideration. synchronous generator and the total connected active power
Frequency stability is defined as a system’s ability to main- load and the reactive power load demands are 3.715 MW
tain a stable and synchronous frequency environment between and 2.300 Mvar. The modeled distribution system is divided
generators amid environmental and external disturbances [16], into six ASRs. An ASR is a logically grouped set of assets
[17]. Health is distinct from frequency stability in that fre- which have a common goal. In distribution systems this often
quency is not used to calculate health. results in ASRs, which are grouped based on proximity such
Health, as used in this work, is a metric that quantifies the as a microgrid [22]. Further, this system includes 5 tie-lines,
systems deviation from normal or optimal line power flow and initially open, to support interconnection between multiple
bus voltage values. Health is an intuitive alternative assessment ASRs and it allows system reconfiguration under different
metric that executives can use to make informed decisions, scenarios, such as line faults.
which tries to answer the question ”How bad is it?” The system is modeled in ARTEMiS/SSN (eMEGASIM)
In [21] Ioanes, and Tı̂rnovan calculated another metric that in the MATLAB-Simulink environment and simulated in the
they called health to describe the state of a power grid using electromagnetic transient (EMT) domain at a smaller time
a long short-term-memory (LSTM) learning machine. This step of 50 microseconds. It also includes circuit breakers, tie-
work is different in at least four ways. First, in this work no line reclosers, fault indicators, and 400-kW grid-connected PV
training is required because a learning machine is not used. array on bus 25. In this work, the PV array is operating as
Second, in this work importance factors, denoted by p, allow a constant power factor mode or P-Q control mode where
executives to emphasize the effects of deviations on important the power factor is set to unity and it is only supplying the
buses, lines, and ASRs through scaling. Third, in this work active power of 400 kW. In this work, we present simulations
health is calcualted as floating point number between 0.0 of three types of faults, including single-line-to-ground fault
and 1.0, whereas in [21] health is presented as one of three (L-G), line-to-line fault (L-L), and 3-phases-to-ground fault
words–”OK”, ”Vigilance”, or ”Critical”. Fourth, in this work (LLL-G) in three ASRs, also shown in Fig. 1. All these faults
health is calculated from the difference between normal values are simulated at 1 second for 5 cycles and necessary data-
and measured values as opposed to [21] where the difference sets are generated for computing health assessment metrics,
between an LSTM’s predicted value and the measured value as discussed in the next section.
is used. The stated differences between this work and [21] are
summarized in Table I. IV. H EALTH A SSESSMENT T ECHNIQUES
The local and global health assessment techniques described
III. E XPERIMENTAL C ASE S TUDY in this section provide a fast indication of where deviations in
Fig. 1 presents the modified IEEE 33-bus distributed system the system are located, and thus increase situational awareness,
that is utilized for the experimental case study. This system is by taking raw data and converting it into meaningful informa-
modeled as a radial distribution system that consists of thirty- tion to be used by a human and/or a machine. To achieve this,
three buses and thirty-two connecting lines. All of the buses operating points consisting of bus voltages and line powers
have a voltage level of 12.66 kV. The network is fed by a are compared with optimum values and then transformed

Authorized licensed use limited to: National Renewable Energy Laboratory. Downloaded on February 23,2022 at 01:50:43 UTC from IEEE Xplore. Restrictions apply.
3

by assessment functions, α() and β(), into deviations which where θ is the threshold for the applicable line power upper
are then scaled and summed into local and global health limit, and m is the slope which controls the rate of conversion
assessments. from deviation to output beyond the threshold. Domain values
lesser than the threshold represents the region where normal
A. System operating points operation is expected to take place. As the power limits placed
System operating points are measurements of system pa- on lines are not directional, meaning one excess watt flowing
rameters taken at particular moments in time that represent out of a line has the same effect on the line as one excess
the status of the system. In this work, the operating points are watt flowing into a line, it is necessary to correct for direction
measures of the bus voltages and line powers of the system and of power prior to using the β function. Other functions, non-
are sampled at regular intervals. Each operating point in the linear functions for example, may be used depending on the
collection is unfiltered data, which when passed through as- desired performance of the assessment, provided that they
sessment functions, create deviation-based information about adhere to the requirement of producing a maximum value of
the state of the system. n sequential samples are used to assess 100.
local and global health.
D. Local health assessment
B. The α() function Local heath assessment provides a quick indication of
α() is an assessment function that takes a root-mean-square voltage or power deviation for a particular ASR. This is
(RMS) voltage as an input and returns a unit-less value accomplished by scaling and summing the deviations in the
between -100 and 100. The input value, ∆V , is the difference bus voltages and line power flows indicated by the assessment
between an actual voltage, from one of the phases of a bus, and functions for a given ASR. For example, λ1 , which represents
the optimal voltage of that bus. The purpose of the α function the local health of ASR1, is given by
is to quantify the extent of the deviation of a bus voltage. It Pn PASR1
produces both negative and positive values so that the output i=1 j=Bus pαj |αj (∆Vji )|
PASR1 
may be used to distinguish between under- and over-voltage + j=Line pβj βj (∆Pji )
conditions in other state assessment computations. Each bus in λ1 = 1 − P  (3)
ASR1 PASR1
the IEEE 33-bus model has its own α function characterized by 100n j=Bus pαj + j=Line pβj
upper and lower bus voltage limits and slopes. The stereotype where n is the number of sampled operating points taken into
for the α functions implemented in this work is described by consideration, pαj and pβj are importance factors for the jth
−100 : ∆V ≤ −100

 m1 + θ1 bus and line, respectively, in ASR1, ∆Vji is the difference
−100


 1
 m (∆V − θ 1 ) : m1 + θ 1 < ∆V ≤ θ1 between the bus voltage and the optimal bus voltage for the
α(∆V ) = 0 : θ1 < ∆V ≤ θ2 ith sample of the jth bus, and ∆Pji is the difference between
 m2 (∆V − θ2 ) : θ2 < ∆V ≤ 100 m2 + θ2
the line power and the optimal line power for the ith sample


 PASR1

100 100
: ∆V > m2 + θ2 , of the jth bus. The notation j=Bus means to sum over all
PASR1
(1) of the buses in ASR1; similarly, the notation j=Line means
where θ1 and θ2 are thresholds relating to the lower and upper to sum over all of the lines connected to ASR1. λ can vary
voltage limits, respectively, of the applicable bus, and m1 and between 0.0 and 1.0, where 1.0 indicates that all voltages and
m2 are the lower and upper slopes, respectively, which control line power flows are in their deadbands. A λ not equal to
the rate of conversion from deviation to output beyond the 1.0 indicates that a deviation exists in an ASR and should be
thresholds. Domain values between the thresholds represents investigated. Local health assessments for each of the other
a deadband where normal operation is expected to take place. ASRs are conducted a manner similar to (3).
Other functions, non-linear functions for example, may be
used depending on the desired performance of the assessment, E. Global health assessment
provided that they adhere to the requirement of producing The purpose of the global health assessment is to provide
maximum and minimum values of 100 and -100, respectively. a single point of reference with which to determine if all bus
voltages and line power flows are in their deadbands. This is
C. The β() function indicated by a global health assessment value (γ) of 1.0. The
β() is an assessment function that takes a power as an input global health assessment is given by
and returns a unit-less value between 0 and 100. The input Pλ
pλi λi
value, ∆P , is the difference between an actual line power and γ = Pi=1λ
, (4)
the usual power of that line. The purpose of the β function is i=1 pλi
to quantify the extent of the deviation of a line power. Each where pλi is the importance factor for the ith local health
phase of each line in the IEEE 33-bus model has its own β assessmentPλand λi is the ith local health assessment. The
function characterized by an upper power limit. The stereotype notation i=1 means to sum over all of the local health
for the β functions implemented in this work is described by assessments. The scaling performed by the importance factors
help to convey the severity or impact of deviations in different

 0 : ∆P ≤ θ
m(∆P − θ) : θ < ∆P ≤ 100 ASRs. A γ not equal to 1.0 indicates that a deviation exists
β(∆P ) = m +θ (2)
100 : ∆P > 100 in one of the ASRs which should be investigated.
m + θ,

Authorized licensed use limited to: National Renewable Energy Laboratory. Downloaded on February 23,2022 at 01:50:43 UTC from IEEE Xplore. Restrictions apply.
4

1.0
10 1.0
10

Global Health Local Health Bus 33 (kV)


Bus 6 (kV)
0 0
0.8 Phase A
Phase B 0.8 Phase A
Phase B
Phase C Phase C
10 10
1 1
0.6 0.6
Global Health Local Health

ASR1 ASR1
ASR2 ASR2
ASR3 ASR3
ASR4 ASR4
ASR5 ASR5
0.4 ASR6 0.4 ASR6
0 0
1 1
0.2 0.2

Global Global
0.00 0.00
0.00.950 0.975
0.2 1.000 0.41.025 1.050
0.6 1.0750.8 1.100 1.0 0.00.950 0.975
0.2 1.000 0.41.025 1.050
0.6 1.0750.8 1.100 1.0
Time (s) Time (s)

Fig. 2. The voltage of Bus 6, local healths for ASRs 1 through 6, and the Fig. 4. The voltage of Bus 33, local health assessments for ASRs 1 through
global health for a short between phase A and ground in Bus 6. 6, and the global health assessment for a 3-phase short to ground in Bus 33.

1.0
10 TABLE II
Global Health Local Health Bus 18 (kV)

M INIMUM H EALTH A SSESSMENTS FOR T HREE FAULTS


0
0.8 Phase A
Phase B
10 Phase C Fault 11 Fault 22 Fault 33
1 ASR1 0.681 0.775 0.681
0.6 ASR1
ASR2 ASR2 0.786 0.509 0.639
ASR3
ASR4
ASR5 ASR3 0.769 0.311 0.640
0.4 ASR6
0 ASR4 1.00 1.00 0.944
1
ASR5 0.777 0.923 0.923
0.2
ASR6 0.742 0.983 0.059
Global Global 0.794 0.750 0.652
0.00
0.00.950 0.975
0.2 1.000 0.41.025 1.050
0.6 1.0750.8 1.100 1.0 1 Fault 1 is the short between Phase A and ground in Bus 6
Time (s) depicted in Fig. 2.
2 Fault 2 is the short between Phase A and Phase B in Bus 18

Fig. 3. The voltage of Bus 18, local health assessments for ASRs 1 through depicted in Fig. 3.
3 Fault 3 is the three phase short to ground in Bus 33 depicted
6, and the global health assessment for a short between phases A and B in
Bus 18. in Fig. 4.

V. S IMULATION AND R ESULTS These are indications that those ASRs should be investigated
Simulations demonstrating the health assessment techniques first. As scaling is not performed in these simulations (All of
described in Section III were conducted in Python version the importance factors are 1.0.), the impact of the deviations
3.8.2 using fault data from the model described in Section on local and global healths are considered to be uniform. If
II. To achieve this, all local and global importance factors the bus voltage deviations were scaled by importance factors,
were set to 1.0, and then operating points produced by the then the impact of the deviations would also be scaled and
IEEE 33-bus distribution model described in Section II were reflect the relative detriment of each deviation. Next, the
evaluated under various fault conditions including phase-to- global healths lower due to the collective changes in the local
phase, phase-to-ground, and three-phase-to-ground faults. healths. After a short time, the transient effects of the faults
finish propagating through the system, which cause the local
A. Fault condition response and global healths to stabilize at non-optimal values. Finally,
after five cycles automatic corrective action is taken and the
For the simulations in this section, all importance factors
system normalizes, which is reflected in rising local and global
have been set equal to 1.0. Fig. 2, Fig. 3, and Fig. 4 depict
healths. Table II summarizes the minimum values of each of
the local and global health assessments for a L-G, L-L, and
the local healths and the minimum value of the global health
LLL-G faults, respectively. Fig. 2 depicts a phase-A-to-ground
for the faults described in this section.
fault in Bus 6, Fig. 3 depicts a phase-A-to-B short in Bus 18,
and Fig. 4 depicts a 3-phase-short-to-ground in Bus 33. In all
three figures, the fault occurs at 1 s, and causes deviations B. Importance factors
throughout the system which are reflected in the local and Importance factors scale the deviations of the local health
global health assessments. At first, when the fault occurs, the assessments, and the impact of each local health assessment
local healths are reduced due to the induced deviations in on the the global health assessment. The scaling performed
the system. Notice how in each figure the ASR where the by the local health importance factors, pα and pβ , emphasizes
faulty bus is located is affected most severely; In Fig. 2 Bus the deviations that occur in critical busses or lines, while the
6 is is affected most severely, in Fig. 3 Bus 18 is affected scaling performed by the global health importance factors,
most severely, and in Fig. 4 Bus 33 is affected most severely. pλ , emphasizes deviations in more important ASRs over less

Authorized licensed use limited to: National Renewable Energy Laboratory. Downloaded on February 23,2022 at 01:50:43 UTC from IEEE Xplore. Restrictions apply.
5

TABLE III emphasized by the pλ3 of 2.0. This results in an unchanged


T HE E FFECTS OF I MPORTANCE FACTORS ON λ3 AND γ FOR local health assessment, and a lower global health assessment,
A P HASE -A- TO -B S HORT IN B US 18
when compared to the case where pβ17−18 is 1.0 in the first
pα18 1 pβ17−18 2 pλ3 Minimum λ3 Minimum γ row.
1.0 1.0 1.0 0.311 0.750
2.0 1.0 1.0 0.235 0.738 VI. C ONCLUSION
1.0 2.0 1.0 0.273 0.744 In conclusion, a modified IEEE 33-bus distribution system
1.0 1.0 2.0 0.311 0.688 model, which was representative of a modern distribution
1 For each phase of Bus 18. system, was presented in Section II. This was used to produce
2 For the line connecting Bus 17 and Bus 18 operating points which were evaluated using novel techniques
for assessing local and global health which were presented
in Section III. These techniques, which produced a tiered
important ASRs. Thus, the role of importance factors is to add
indication of local and global health, were then demonstrated
emphasis to deviations–enabling the local and global health
in Section IV. These rapid and centralized health assessments
assessments to be more informative to a human or machine.
can be used by humans or machines to quickly ascertain
Any deviation expressed by the α and β functions will be
adverse conditions which require investigation or immediate
reflected in the local and global health assessments, but not
action.
all deviations have an equal effect on the system; the scaling
helps to convey the importance of a fault in one location versus
ACKNOWLEDGMENT
another.
As the purpose of importance factors are to add emphasis to This material is based upon work supported by the US
changes in bus voltages, line powers, or local health assess- Department of Energy’s Office of Energy Efficiency and Re-
ments, any logically consistent method for emphasising the newable Energy (EERE) under the Solar Energy Technology
system’s operational priorities can be used to select importance Office Award Number DE-0008775. Effort performed through
factors. Some potential selection methods include assigning all Department of Energy under U.S. DOE Idaho Operations
importance factors to 1.0, assigning ranked values based on the Office Contract DE-AC07-05ID14517, as part of the Resilient
the loads on each line and bus, and performing a contingency Control and Instrumentation Systems (ReCIS) program of
analysis to assign values. For simulations presented in the pre- Idaho National Laboratory.
ceding section, the busses, lines, and ASRs in the simulation
all have importance factors of 1.0–meaning that they are all R EFERENCES
equally important. [1] I. Bhatt, A. Dhandhia, and V. Pandya, “Static security assessment of
To demonstrate the effects of bus, line, and ASR importance power system using radial basis function neural network module,” in
2017 IEEE International WIE Conference on Electrical and Computer
factors on the minimum values of λ3 and γ, four assessments Engineering (WIECON-ECE), pp. 274–278, 2017.
of the phase-A-to-B short depicted in Fig. 3 were conducted. [2] T. Wang, P. Lu, X. Cao, X. Yang, W. Wang, H. Lv, C. Feng, T. Liu,
Table III summarizes the results of these assessments. The first and S. Li, “Static security risk assessment of power grid under planned
maintenance,” in 2019 IEEE 8th International Conference on Advanced
row represents the case where all importance factors are equal Power System Automation and Protection (APAP), pp. 1809–1813, 2019.
to 1.0. This row can be used to compare the results of the [3] N. Balu, T. Bertram, A. Bose, V. Brandwajn, G. Cauley, D. Curtice,
assessments where the importance factors were varied. The A. Fouad, L. Fink, M. G. Lauby, B. F. Wollenberg, and J. N. Wrubel,
“On-line power system security analysis,” Proceedings of the IEEE,
second row represents the case where all importance factors vol. 80, no. 2, pp. 262–282, 1992.
except for pα18 , the importance factor for Bus 18, are equal [4] D. S. Kirschen, “Power system security,” Power Engineering Journal,
to 1.0. As the fault occurred in Bus 18, the phase A and phase vol. 16, no. 5, pp. 241–248, 2002.
[5] K. Morison, Lei Wang, and P. Kundur, “Power system security assess-
B voltages experience the largest deviations, and the effects ment,” IEEE Power and Energy Magazine, vol. 2, no. 5, pp. 30–39,
of these deviations are emphasized by the pα18 of 2.0. This 2004.
results in a lower local health assessment for ASR3 and, in [6] S. R, R. S. Kumar, and A. T. Mathew, “Online static security assessment
module using artificial neural networks,” IEEE Transactions on Power
turn, a lower global health than the case where pα18 is 1.0 Systems, vol. 28, no. 4, pp. 4328–4335, 2013.
in the first row. The third row represents the case where all [7] P. Kundur, J. Paserba, V. Ajjarapu, G. Andersson, A. Bose, C. Canizares,
importance factors except for pβ17−18 , which is the importance N. Hatziargyriou, D. Hill, A. Stankovic, C. Taylor, T. Van Cutsem,
and V. Vittal, “Definition and classification of power system stability
factor for the line connecting Bus 17 to Bus 18, are equal to ieee/cigre joint task force on stability terms and definitions,” IEEE
1.0. As the fault occurred in Bus 18, the line connecting Bus Transactions on Power Systems, vol. 19, no. 3, pp. 1387–1401, 2004.
17 and Bus 18 experiences a large power flow deviation, and [8] J. Deane, F. Gracceva, A. Chiodi, M. Gargiulo, and B. P. Gallachóir,
“Assessing power system security. a framework and a multi model
the effects of this deviation are emphasized by the pβ17−18 approach,” International Journal of Electrical Power & Energy Systems,
of 2.0. This results in a lower local health assessment for vol. 73, pp. 283–297, 2015.
ASR3 and, in turn, a lower global health than the case where [9] V. K. Singh, M. Govindarasu, and R. Nuqui, “Impact analysis of data
integrity attacks on facts-based wide-area voltage control system,” in
pβ17−18 is 1.0 in the first row. The fourth row represents the 2021 IEEE Power Energy Society Innovative Smart Grid Technologies
case where all importance factors except for pλ3 are equal to Conference (ISGT), pp. 1–5, 2021.
1.0. As no importance factors for the power flows or voltages [10] Trudnowski, Donnelly, and Lightner, “Power-system frequency and
stability control using decentralized intelligent loads,” in 2005/2006
were changed, the local health of ASR3, λ3 , was unchanged. IEEE/PES Transmission and Distribution Conference and Exhibition,
However, the deviation due to the fault occurring in ASR3, are pp. 1453–1459, 2006.

Authorized licensed use limited to: National Renewable Energy Laboratory. Downloaded on February 23,2022 at 01:50:43 UTC from IEEE Xplore. Restrictions apply.
6

[11] H. Mohammadi, G. Khademi, M. Dehghani, and D. Simon, “Voltage


stability assessment using multi-objective biogeography-based subset
selection,” International Journal of Electrical Power & Energy Systems,
vol. 103, pp. 525–536, 2018.
[12] Y. Xu, R. Zhang, J. Zhao, Z. Y. Dong, D. Wang, H. Yang, and K. P.
Wong, “Assessing short-term voltage stability of electric power systems
by a hierarchical intelligent system,” IEEE Transactions on Neural
Networks and Learning Systems, vol. 27, no. 8, pp. 1686–1696, 2016.
[13] T. Van Cutsem and R. Mailhot, “Validation of a fast voltage stability
analysis method on the hydro-quebec system,” IEEE Transactions on
Power Systems, vol. 12, no. 1, pp. 282–292, 1997.
[14] V. Kumar Singh, A. Ozen, and M. Govindarasu, “Stealthy cyber attacks
and impact analysis on wide-area protection of smart grid,” in 2016
North American Power Symposium (NAPS), pp. 1–6, 2016.
[15] V. K. Singh, E. Vaughan, and J. Rivera, “Sharp-net: Platform for self-
healing and attack resilient pmu networks,” in 2020 IEEE Power Energy
Society Innovative Smart Grid Technologies Conference (ISGT), pp. 1–5,
2020.
[16] J. A. Barnes, A. R. Chi, L. S. Cutler, D. J. Healey, D. B. Leeson, T. E.
McGunigal, J. A. Mullen, W. L. Smith, R. L. Sydnor, R. F. C. Vessot,
and G. M. R. Winkler, “Characterization of frequency stability,” IEEE
Transactions on Instrumentation and Measurement, vol. IM-20, no. 2,
pp. 105–120, 1971.
[17] B. S. Abdulraheem and C. K. Gan, “Power system frequency stability
and control: Survey,” International Journal of Applied Engineering
Research, vol. 11, no. 8, pp. 5688–5695, 2016.
[18] M. Haque, “Load flow solution of distribution systems with voltage
dependent load models,” Electric Power Systems Research, vol. 36, no. 3,
pp. 151 – 156, 1996.
[19] V. Ajjarapu, Computational techniques for voltage stability assessment
and control. Springer Science & Business Media, 2007.
[20] K. Morison and L. Wang, “Implementation of online security assess-
ment,” IEEE Power and Energy Magazine, vol. 4, no. 5, pp. 46–59,
2006.
[21] A. Ioaneş and R. Tı̂rnovan, “Power grid health assessment using
machine learning algorithms,” in 2019 11th International Symposium
on Advanced Topics in Electrical Engineering (ATEE), pp. 1–4, 2019.
[22] T. Phillips, T. McJunkin, C. Rieger, J. Gardner, and H. Mehrpouyan,
“A framework for evaluating the resilience contribution of solar pv and
battery storage on the grid,” in 2020 Resilience Week (RWS), pp. 133–
139, 2020.

Authorized licensed use limited to: National Renewable Energy Laboratory. Downloaded on February 23,2022 at 01:50:43 UTC from IEEE Xplore. Restrictions apply.

You might also like