Professional Documents
Culture Documents
net/publication/305417550
CITATIONS READS
17 4,189
4 authors:
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Surya Santoso on 31 January 2017.
2169-3536 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/ACCESS.2016.2589545, IEEE Access
can accommodate without creating protection problems. In to accept PV interconnection requests. For PV integration, the
this work, an analytical approach is presented to determine penetration level is limited to 15% of the maximum feeder
a distribution feeder’s accommodation limits of integrating load on a line section to avoid any adverse impacts [19].
large-scale PV and ESS based on relay insensitivity and Alternatively, system studies need to be performed with all
sympathetic tripping as impact criteria considering LVRT. The possible combinations of fault types, fault locations, PV size
analysis presented in this work is validated against simulation and locations which is time consuming posing scalability
studies on a distribution circuit model in OpenDSS developed challenges and resulting in circuit specific outcomes. In this
using actual circuit data from a utility. The results match context, the main contribution of this work is development of
within 7% of theoretical predictions, thus validate the analysis. a scalable analysis-based method to conservatively estimate
This paper is organized into six sections. The problem large-scale PV and ESS accommodation limits of a distribution
statement and the motivation of this work are detailed in feeder without causing relay insensitivity and sympathetic
Section II. An overview of distribution feeder overcurrent tripping problems. The objective is to simplify the estimation
protection is provided in Section III. The relay insensitivity process with reasonable approximations under conservative
and sympathetic tripping problems are also described in this settings. The other contribution is providing insights into
section. In Section IV, the analysis of relay insensitivity and overcurrent relay settings when large-scale PV and ESS are
sympathetic tripping protection problems in the presence of present. The analysis for assessing the impact of ESS installed
large-scale PV and ESS is presented and key parameters in- either individually or in conjunction with PV on the protection
fluencing these problems are discussed. Section V presents the relay response and its application to assess accommodation
simulation results using a detailed distribution circuit model limits of a utility distribution feeder is not reported in litera-
that validate the analysis. The conclusions and discussion are ture.
provided in Section VI. In recent years, there are several changes to the regulations
for grid interconnection of DG. While previous regulations
mandated disconnection of DG during abnormal system con-
II. P ROBLEM S TATMENT AND M OTIVATION
ditions, many new regulations require the DG to remain
Protection studies, similar to other impact studies, for connected during the faults, referred to as ‘low voltage ride
deployment of PV systems require development of detailed through’ (LVRT) or ‘fault ride through’ (FRT). Similar to DG,
distribution system models using distribution system sim- as part of grid support functions, the ESS also offers LVRT
ulation tools [21]. Then the developed model is validated functionality [24]. Since protection studies are performed con-
using suitable methods such as comparing power flow results sidering the worst case situation, it is reasonable to consider
with actual field measurements. Once the validated model that the large-scale PV and ESS remain connected in the
is available, simulation studies are performed to assess the system during the fault conditions and assess the impact of
impact of PV integration on protection schemes with large their steady state current injection into the distribution network
number of scenarios. However, this process requires consider- [20]. Thus, in this work, analysis is provided considering
able time and effort [22]. Furthermore, in this particular case LVRT requirements of PV and ESS.
of determining feeder accommodation limits of integrating PV
using circuit simulations, the approach presented in [19] is III. OVERVIEW OF D ISTRIBUTION F EEDER OVERCURRENT
useful to study only small test systems with few nodes. Such a P ROTECTION AND I MPACTS OF PV AND ESS
simulation based approach when applied to actual distribution
Majority of the conventional distribution systems are radial
feeders having thousands of buses poses several complications
in nature as the radial systems are least expensive, simpler in
of scalability. Some of the reported scalability challenges are
planning, design and operation compared to other alternatives
power flow solution convergence problems, complexity of
[25]. In radial systems, the primary substation is the only
analysis and visualization of results considering large number
source feeding the distribution load and there exists only
of fuses, huge time requirement to study all possible combina-
a single path between each customer and the substation.
tions of PV sizes, and fault locations [20]. These complexities
Typically, overcurrent protection is the main feeder protec-
can be handled to some extent by using network reduction
tion in radial systems. Overcurrent relays, circuit breakers,
technique [23] and some reasonable approximations such as
reclosers, sectionalizers and fuses are the main protection
modeling only few main protection devices such as reclosers,
devices in overcurrent protection schemes. The role of these
simulating only few representative scenarios of selected PV
protection devices and the overcurrent protection coordination
locations [20]. However, the accommodation limits obtained
are briefly explained in this section. Then relay insensitivity
as outcome pertains only to that particular circuit and is valid
and sympathetic tripping problems that may arise due to the
only for a particular set of protection device settings. As such,
presence of large-scale PV and ESS are described.
the conclusions may not necessarily be applicable to other
circuits or even to the same circuit with different protection
device settings as the results are highly dependent on the A. Overcurrent Protection Devices
circuit characteristics. 1) Circuit Breakers: Circuit breakers are used to protect the
In the absence of insights into the relationship among distribution networks by interrupting the fault currents during
various system parameters, the utility planners are usually faulty circuit conditions. Overcurrent relays control the circuit
forced to apply conservative rules of thumb penetration levels breaker operations. While isolating the faulted line section,
2169-3536 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/ACCESS.2016.2589545, IEEE Access
due to the interruption of inductive current, electric arc forms total clearing curve is a plot of the longest melting time versus
between the circuit breaker contacts. To quench the electric the current required to melt the fuse link. When a fuse melts,
arc, circuit breakers use different types of arc-extinguishing the fault current and its associated time would lie between the
media such as air, oil, vacuum or SF6 gas. two curves.
2) Overcurrent relays: Overcurrent relays are the fault
sensing devices that detect faults in the distribution system 1000
and open the circuit breaker. They can function as phase
overcurrent or ground overcurrent relays depending on the 100
current being monitored. Phase overcurrent relays detect the
fault currents flowing in the lines. When the line currents are 10
Time [seconds]
above the phase overcurrent relay pickup setting, the relay
Total Clearing
trips the circuit breaker. The trip time depends upon the time-
dial setting of the relay. For detecting the unbalanced faults, 1
2169-3536 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/ACCESS.2016.2589545, IEEE Access
Recloser slow curve multiplied by accomplish the recloser-recloser coordination by selecting dif-
safety factor
C’ ferent types of reclosers. If same type of reclosers are chosen,
C
Fuse TCC curves
the coordination can be done by selection of different current
ratings or different operating sequences of the reclosers.
4) Relay Coordination with Reclosers and Sectionalizers:
A Fig. 3 shows the typical arrangement of circuit breakers,
Time, S
CB – Circuit Breaker
R – Recloser
A S – Sectionalizer
Time, S
CB
S F
Isc max at recloser CB R
Current, A
(b) S F
F
Fig. 2. Fuse-recloser coordination (a) when fuse is at the source side (b)
when fuse is at the load side.
Fig. 3. Typical arrangement of protective devices in a distribution system.
2169-3536 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/ACCESS.2016.2589545, IEEE Access
Reduction of relay reach is illustrated in Fig. 4 where a large- actual utility distribution circuit model and protection device
scale PV system is planned to be connected to a bus in the settings reported in [20] indicates that sympathetic tripping
middle of the feeder. The fault current contribution by the PV is one of the major issues utility planners face due to the
for a fault downstream of the PV reduces the reach of the integration of IIDG. Solutions for preventing the protection
relay upstream. problems under study are reported in [37]–[39]. However,
implementing these over many distribution networks can be
a costly decision [20]. Therefore, there is a strong motivation
Vsg
Fault to perform comprehensive analysis into relay insensitivity and
R sympathetic tripping problems.
3) Protection Coordination Issues: The bi-directional cur-
IR
rent flows due to fault current injections from PV and ESS in-
PV terfere with the coordination of overcurrent protective devices
and could lead to misoperations. The exact impact typically
depends upon the size of the PV, relative locations of PV, ESS
Fig. 4. Illustration of reduction of relay reach.
and protective devices, protection settings and the distribution
Fault analysis to calculate reduction of relay reach consider- system feeder impedance.
ing RBDG is presented in [19], [28]. Unlike the RBDG, which 4) Reverse Power Flow: At higher PV penetration levels
acts as a voltage behind a reactance during the faults, IIDG and minimum loading condition in the feeder, the power flow
acts as a current source due to the current controllers present direction reverses at the substation when the PV generation
in the IIDG controlling their power output [12]. Therefore, the is more than the power consumption in the feeder. The
fault analysis of RBDG is not applicable to IIDG. Considering reverse power flow could possibly operate the reverse power
this fact, analysis for the impact of IIDG on relay reach with relays installed at the head of the feeder causing outage of
IIDG acting as a current source is reported in [29]–[31]. A the feeder significantly affecting the system reliability [40].
real-world example of a potential relay insensitivity problem in The power reversal could also cause incorrect operation of
a distribution feeder due to the integration of a large-scale PV voltage regulators and capacitor controls as these controls
system is reported in [3], indicating the necessity of studying are not designed for reverse power flow. This increases the
relay insensitivity problem. number of operations and related equipment wear in addition
to power quality problems to the customers. The operational
2) Sympathetic Tripping: Sympathetic tripping occurs
problems due to reverse power flow include over voltages on
when the fault current from the PV causes relays on the healthy
the distribution feeder and increased short-circuit levels.
feeder to pick up for faults on the adjacent feeders and results
5) Fuse Saving and Fuse Tripping: Majority of the faults
in unnecessary outage of the healthy feeder [5], [6]. This is
in the distribution systems are temporary in nature. They
illustrated in Fig. 5 where a large-scale PV system is connected
occur momentarily for various reasons and are cleared by
in Feeder 1 and a fault occurs on adjacent Feeder 2. During
themselves. Isolation of such faults by blowing the fuses cre-
the fault, if the PV system remains in the circuit as per LVRT
ates unnecessary long duration service outages. To minimize
requirements, it feeds the fault back through the relay ‘R’ at
the service outages for temporary faults, utilities use ‘fuse
the substation. When the large-scale PV is of considerable size,
saving practice for coordination of breaker or recloser with
the fault current from the PV can go above the pickup setting
the downstream fuses. In this practice, the breaker or recloser
of the overcurrent relay at the substation causing unwanted
operates on fast curve before the fuse gets affected as was
tripping of the Feeder 1 [32]–[34].
shown in Fig. 2(b). This saves the fuse in case of temporary
faults. For permanent faults, the fuse blows when the breaker
or recloser operates on slow curve after preset number of fast
PV operations. The faster curve of breaker or recloser can also
Vsg Feeder 1 be replaced with instantaneous overcurrent elements. In that
IfPV case, the instantaneous overcurrent element trips the breaker
R
or recloser before the fuse melts and is blocked temporarily.
If the fault is permanent, the fuse blows as the breaker or
Ifgrid
recloser operation is delayed based on their slow curve. The
Fault
fuse saving practice leads to increased number of momentary
service interruptions as the breaker or recloser trips the entire
Feeder 2 line downstream for all faults. As such, the utilities follow fuse
tripping practice wherein the fuse is allowed to blow for all
Fig. 5. Illustration of sympathetic tripping. faults. The fuse blowing practice produces fewer momentary
interruptions but more sustained interruptions.
While sympathetic tripping may not be likely a problem The DG installations could affect the timing coordination
in case of small-scale PV with low penetration levels, it is between breaker/recloser and the fuse due to the additional
a potential problem with high penetration of PV or large- fault current contribution from the DG. As a result, the fuse
scale PV [35], [36]. The IIDG impact study results using an could blow first or both the fuse and breaker/recloser could
2169-3536 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/ACCESS.2016.2589545, IEEE Access
(b)
Vsg
Zeq Fault
Fig. 7. Equivalent circuit of the distribution system a) without PV and b)
R ZLine1 ZLine2
with PV.
IR,no PV Rf
PV substation. The location of PV alters the fault current distri-
bution. During faults, the PV systems behave like constant
power sources and the PV inverters try to push the same
Fig. 6. Distribution system with fault.
power even at the low terminal voltages by injecting higher
1) Analysis for symmetrical faults: Consider the fault in currents [31]. As such, a PV system located close to the fault
Fig. 6 is a three-phase fault. Fig. 7(a) shows the equivalent can inject a higher current due to its lower terminal voltage
circuit of the system when the PV is not connected. Using compared to the PV system located far away from the fault
Kirchoff’s voltage law (KVL), the fault current seen by the which has higher terminal voltage during the same fault for
relay is given by: a given PV power output. Conservatively, this current can be
considered as 2 times the inverter rated current [31]. When
Vsg the PV fault current contribution is fixed at this value, the
IR,noP V = (1)
(Zeq + ZLine1 + ZLine2 + Rf ) PV can be placed close to the substation with the fault at
where Vsg and IR,noP V are the line-to-ground pre-fault volt- the end of the feeder as per (2) so that ZLine2 is maximum
age at the substation bus and fault current through the relay causing more reduction in the fault current seen by the relay
without PV, repectively. at the substation. In such a scenario, when the three-phase
When the large-scale PV system is connected injecting a fault resistance is sufficiently high, the fault current seen
fault current IPf V during the three-phase fault, the equivalent by the relay goes below its phase overcurrent pickup value,
circuit of the distribution system is shown in Fig. 7(b). making the relay insensitive to the fault. Under this situation,
Then the fault current through the relay with the large-scale any additional fault current contribution from the PV would
PV connected can be obtained by applying superposition in further reduce the fault current seen by the relay and make it
Fig. 7(b) as insensitive to the faults with lesser fault resistance. In other
words, the large-scale PV reduces the reach of the overcurrent
(ZLine2 + Rf )
IR,P V = IR,noP V − If relay.
(Zeq + ZLine1 + ZLine2 + Rf ) P V Considering the bus voltage phasor where the large-scale
(2)
PV/ESS is connected as reference and the steady-state fault
Equation (2) shows that the fault current through the relay current contribution from the large-scale PV is twice the PV
is reduced due to the fault current contribution from the PV rated current in phase with the bus voltage [9], [10], [20], the
during a three-phase fault. This current seen by the relay is fault current through the phase overcurrent relay from (2) can
also influenced by the available short-circuit capacity at the be expressed in terms of the PV size as (3). Taking the PV/ESS
2169-3536 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/ACCESS.2016.2589545, IEEE Access
2169-3536 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/ACCESS.2016.2589545, IEEE Access
3Vsg IP V 0
IRN,P V = − [2ZLine2 + ZLine2 + 3Rf
ZT S ZT S
f
I PVc I PVc − 3(ZLine1 + Zeq )]
For the worst case scenario, the maximum unbalance is When the ESS is also present, analysis can be done along
considered in the large-scale PV fault current injections i.e., it the same lines and the ground fault current seen by the
is assumed that the PV is injecting 2 times the rated current upstream relay can be obtained from (8) as
(IP V ) in the faulted phase and rated currents in the healthy
phases as shown in Fig. 9. IRN,P V +ESS = IRN,noP V − Z (IP V + IESS ) (10)
The sequence components of fault currents injected by the
PV for maximum unbalance is given by: For conservative estimation, (10) considers that both ESS
⎡ ⎤ ⎡ ⎤ and PV fault currents are in phase with each other. Then, the
2IP V a IP V ∠0◦
1
[IPf V ]012 = [A]−1 ⎣ IP V b ⎦ = ⎣4IP V ∠0◦ ⎦ (6) PV rating in (9) includes both PV and ESS ratings.
3
IP V c IP V ∠0◦
Sometimes the phase overcurrent relays alone are used for
From (5) and (6), the zero sequence current through the protection against all types of faults [43]. As such, we are
relay for maximum unbalance is given by: also interested in determining the reduction of fault current
Vsg IP V 0
seen by the phase overcurrent relay installed at the substation
IR0,P V = − [2ZLine2 + ZLine2 + 3Rf due to the ground fault current injections by the PV and ESS
ZT S 3ZT S (7)
− 3(ZLine1 + Zeq )] during remote end SLG fault. The fault current seen by phase
overcurrent relay in the presence of large-scale PV can be
The ground fault current seen by the relay is three times computed by applying superposition in Fig. 8(b) for each
the zero sequence current: source Vsg , IPf V 1 , IPf V 2 , IPf V 0 and by adding the resulting
currents to determine the current flowing through the relay
IRN,P V = 3IR0,P V in each sequence network IR1,P V , IR2,P V , IR0,P V . Then the
2169-3536 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/ACCESS.2016.2589545, IEEE Access
1 0 0
= IR,noP V − (−ZLine1 + 2ZLine2 + ZLine1 + ZLine2 Vsg Feeder 1
IfPV
ZT S Zeq
0 R
−Zeq + Zeq + 3Rf )(IPf V 1 + IPf V 2 ) + (2ZLine1 + 2ZLine2
Ifgrid
0 0 0
−2ZLine1 + ZLine2 + 2Zeq − 2Zeq + 3Rf )IPf V 0 Fault
(11)
Feeder 2
Rf
When the maximum unbalance is considered, from (6) and
(11) we can determine the maximum reduction in this fault
current as:
(a)
IR,P V = IR,noP V − Z × IP V (12)
Zeq
1
where Z = 0
[4ZLine2 ++ZLine1 0
2ZLine2 0
+Zeq +6Rf − R
ZT S
(ZLine1 + Zeq )]
Ifau lt,3φ IR=-IfPV
Ifgrid
The above equation indicates that the ground fault current
contribution of the large-scale PV during the SLG fault Rf IfPV
downstream causes reduction in the fault current seen by the Vsg
upstream phase overcurrent relay also. The above analysis can
be extended to include the impact of ESS also as
IR,P V +ESS = IR,noP V − Z (IP V + IESS ) (13) (b)
In (13), fault current injection of ESS is considered as Fig. 10. Distribution system with three-phase fault a) without PV and b) with
in phase with the PV fault current injection for maximum PV.
reduction. In terms of the PV and ESS ratings, (13) can be
expressed as
study. Considering the PV and ESS fault current contributions
(PV + ESS) rating are in phase for conservative estimation, the fault current seen
|IR,P V +ESS | = IR,noP V − Z × √
3 × PV bus voltage by relay becomes |IR | = |IPf V + IESS
f
| and the PV rating in
(14) (15) includes ESS rating also.
B. Sympathetic Tripping 2) Analysis for unsymmetrical faults: In case of SLG faults,
the ground overcurrent relay of the feeder shall detect the
To analyze the sympathetic tripping, consider the system
ground fault current and trip. The ground fault current or
shown in Fig. 10(a) where a large-scale PV system is installed
residual current through the relay is the sum of the fault
in Feeder 1 and a three-phase fault is assumed on adjacent
currents being injected by the PV system in all the three phases
Feeder 2. Its equivalent circuit is shown in Fig. 10(b). During
and can be expressed as:
the fault, the PV system feeds the fault back through the relay
‘R’ at the substation. IRN,P V = −(IPf V a + IPf V b + IPf V c ) = −3IPf V 0 (16)
1) Analysis for symmetrical faults: From Fig. 10(b), the From (6) and (16), the current seen by the ground overcur-
fault current through the relay in Feeder 1 is rent relay under maximum unbalance condition is |IRN,P V | =
IR = −IPf V |IP V |. In terms of PV rating, this can be expressed as
PV rating
It indicates that the current through the relay solely depends |IRN,P V | = |IP V | = √ (17)
on the fault current from the large-scale PV system and flows 3 × PV bus voltage
in the reverse direction. Therefore, as the PV size increases, When the ESS is also present, the total ground fault current
its fault current contribution also increases and eventually trips through the relay would be vectorial sum of both the ground
the relay when the fault current contribution from the PV goes fault currents from the PV and the ESS which is given by
above the phase overcurrent relay pickup current setting.
IRN,P V +ESS = − (IPf V a + IPf V b + IPf V c )
Considering that IPf V is twice the IP V for the conservative
f f f
study, the magnitude of fault current flowing through the relay − (IESSa + IESSb + IESSc ) (18)
can be expressed in terms of the PV rating as: =− 3(IPf V 0 + f
IESS0 )
2 × PV rating
|IR | = |IPf V | = √ where IPf V 0 and IESS0
f
(15) are the zero sequence current injec-
3 × PV bus voltage tions from PV and ESS respectively.
If the ESS is also present in the system, we need to consider For conservative estimation, the ESS fault current injection
its fault current contribution also for the sympathetic tripping would be in phase with PV fault current. Then the PV rating
2169-3536 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/ACCESS.2016.2589545, IEEE Access
10
TABLE I
S EQUENCE IMPEDANCES OF DIFFERENT S ECTIONS OF THE UTILITY Vsg Bus 1 Bus 2 Bus 3
DISTRIBUTION FEEDER Zeq, Z0eq ZLine 1, Z0Line 1 ZLine 2, Z0Line 2
Fault
R
Feeder Section Sequence Impedance (Ω) IR,PV+ESS Rf
IfPV IfESS
Zeq = 0.1016∠72.4◦
Substation
0 = 0.312∠74.1◦
Zeq PV
PV ESS
PV
ZLine1 = 1.389∠55.4◦
Upstream of PV & ESS
0
ZLine1 = 2.193∠55.56◦
Fig. 11. Single-line diagram of utility distribution feeder with fault.
ZLine2 = 0.538∠59.45◦
Downstream of PV & ESS
0
ZLine2 = 1.678∠60.97◦
3 times the maximum steady-state load current is used [46].
In this study, pickup current of 1500 A is used for the phase
overcurrent relay which is 2.05 p.u. of maximum steady-state
in (17) gives combined PV and ESS rating.
load current in the circuit (730 A). For ground overcurrent
relays, pickup current need to be above the maximum expected
V. VALIDATION OF R ELAY R EACH AND S YMPATHETIC
unbalance current in the circuit. For most feeders, the ground
T RIPPING USING U TILITY D ISTRIBUTION F EEDER M ODEL
relays are set with a pickup range from 25% to 50% of the
The analysis presented in the previous section is validated phase relay pickup [46]. In this study, 750 A is chosen as
through the simulation studies on a utility distribution feeder pickup current setting for the ground overcurrent relay which
model in OpenDSS. The generator and storage objects avail- is 0.5 p.u. of the phase relay pickup setting.
able in the OpenDSS model library are used for simulating PV b) The PV and ESS are connected to a bus approximately 0.83
and ESS respectively. A common approach to model inverters mi away from the substation (Bus 2) and the fault is simulated
for a fault study is to assume inverters behave like synchronous at the remote bus (Bus 3) as shown in Fig. 11.
generators during faults. The transient reactance Xd then c) Although loading condition does not have much impact
can be adjusted to obtain desired fault current output like a on short-circuit studies, more current from PV fault current
PV inverter [44]. The generator model (model 7) available injection is available when the load is minimum. Therefore,
in OpenDSS is useful for this purpose to approximate the minimum loading condition is considered for conservative
nominal behavior of the inverter based DG systems [45]. study.
For simulating PV fault current behavior two times its rated
current, the ‘xdp’ parameter of the generator model (model 7) B. Reduction of Relay Reach
is adjusted to 0.5.
The utility distribution feeder model is simulated initially
with a bolted three-phase fault at bus 3 without the large-scale
A. System Description PV and ESS in the system. The fault resistance is increased
For simulation studies, a detailed distribution circuit model and the phase-A current through the relay at the substation
has been developed in OpenDSS using the data obtained is monitored. Next, a large-scale PV system is connected to
from a utility. The data comprises of transformer, line data, bus 2 and the study is repeated. The fault current profiles seen
load profiles, capacitors, regulator data etc. The system has by the phase overcurrent relay for varied fault resistance as
a 24 MVA transformer at the substation. The three-phase the PV size is increased from 1 MW to 8 MW are shown in
and single-phase short-circuit MVA of transmission system Fig. 12. It is observed that when the PV is not connected, the
upstream of the substation transformer are 562 MVA and 93 relay at the substation is insensitive to the three-phase faults
MVA respectively. A 1.6 mi long 12.47 kV level primary with Rf > 3.8 Ω. In other words, the phase overcurrent relay
distribution feeder is supplied by this transformer. Maximum cannot detect the three-phase remote end faults having fault
loading in the feeder is 15.77 MW and the corresponding load resistance higher than 3.8 Ω. The relay is blind to the fact that
current is 730 A. Minimum loading is 6 MW. This detailed a fault is present in the system. As the PV size is increased, the
distribution model is used for simulations. corresponding PV fault current contribution IPf V is increased
Fig. 11 shows the single-line diagram of the distribu- resulting in relay insensitivity at lower fault resistances. For
tion system used for theoretical calculations. The sequence the large-scale PV size of 8 MW, the phase overcurrent relay is
impedances of the system are obtained from the short-circuit insensitive to the remote end three-phase fault with resistance
study which are given in the Table I. above 2.5 Ω. This means, if the relay at the substation is set
Following are the circuit conditions considered for this to detect a 3.8 Ω fault resistance considering no PV in the
study: system, the relay fails to perform its intended operation due
a) The breaker installed at the feeder head is controlled by to the presence of PV.
both phase and ground overcurrent relays. The pickup current The simulation results can be compared with theoretical
setting for the phase overcurrent relay should be above the relay currents predicted using (2) to validate the analysis.
maximum cold load pickup current in the feeder and below The pre-fault voltage of bus 3 is obtained from the load
the minimum fault current. Typically, a pickup value of 1.5 to flow program as Vsg = 7279∠ − 33.7◦ V. Using the system
2169-3536 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/ACCESS.2016.2589545, IEEE Access
11
3000
No PV
No PV
PV = 1 MW PV = 1 MW &
PV = 1 MW
2000 ESS = 3 MW
Ip = 1500 A
Ip = 1500 A
1000 IfPV = 63 A
Rf = 2.5 Ω Rf = 3.8 Ω Rf = 3.1 Ω Rf = 3.6 Ω IfESS = 179.6 A
PV = 8 MW
0
0 2 4 6 8 10
Fault resistance Rf (Ω)
Fig. 12. Fault current seen by phase overcurrent relay with large-scale PV
and varied remote end three-phase fault resistance using circuit simulations.
Fig. 14. Fault current seen by phase overcurrent relay installed at the
substation for various PV ratings and three-phase fault resistance.
2169-3536 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/ACCESS.2016.2589545, IEEE Access
12
500 Rf = 7 Ω
0 0 1 2 3 4 5 6 7 8 9 10
Fault resistance Rf (Ω)
Fig. 15. Comparison of predicted ground fault current seen by relay using
(8) and simulated values without PV and with 8 MW PV for varied Rf .
Fig. 17. Locational impact of large-scale PV systems.
Phase-A fault current seen by relay (A)
PV
3000
Vsg
Zeq IfPV
2500 No PV R
IfESS
2000 1 MW PV, No ESS
ESS
PV
1500 I = 1500 A
p
1000
1 MW PV, 3 MW ESS
500 Fault
0
0 1 2 3 4 5 6 7 8 9 10 Adjacent feeder
Fault resistance Rf (Ω)
2169-3536 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/ACCESS.2016.2589545, IEEE Access
13
Fig. 20. Fault current seen by ground overcurrent relay as the PV size is
Fig. 19. Fault current seen by phase overcurrent relay without and with ESS increased.
as the PV size is increased.
2169-3536 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/ACCESS.2016.2589545, IEEE Access
14
Normally, in addition to the breaker at the substation, [11] T. Sidhu and D. Bejmert, “Short-circuit current contribution from large
the distribution circuits can have few reclosers placed along scale PV power plant in the context of distribution power system protec-
tion performance,” in IET Conference on Renewable Power Generation,
the feeder. In such cases, the expected fault current can Sept 2011, pp. 1–6.
be computed at each recloser using the proposed method. [12] M. E. Baran and I. El-Markaby, “Fault analysis on distribution feeders
Once we have the expected fault currents with large-scale with distributed generators,” IEEE Transactions on Power Systems,
vol. 20, no. 4, pp. 1757–1764, Nov 2005.
PV and ESS, the possibility of relay/recloser insensitivity can [13] S. Essakiappan et al., “A utility scale battery energy storage system
be checked quickly by comparing with the pickup current for intermittency mitigation in multilevel medium voltage photovoltaic
setting. Based on the expected fault currents and pickup system,” in Energy Conversion Congress and Exposition (ECCE), 2015
IEEE, Sept 2015, pp. 54–61.
current settings of the breaker and the reclosers, the possibility
[14] A. Barnes, J. Balda, A. Escobar-Mejia, and S. Geurin, “Placement of
of miscoordination problems can also be studied. Note that energy storage coordinated with smart PV inverters,” in IEEE Innovative
protection device miscoordination is not in the scope of this Smart Grid Technologies, Jan 2012, pp. 1–7.
study. [15] G. Huff, “DOE global energy storage database.” Sandia National Labora-
tories (SNL-NM), Albuquerque, NM (United States), Tech. Rep., 2015.
In case of sympathetic tripping, the reclosers play a limited [16] I. Gyuk et al., “Grid energy storage,” U.S. Department of Energy, Tech.
role as faults beyond the reclosers do not create sympathetic Rep., 2013.
tripping. When the faults are beyond the reclosers, usually [17] W. S. Moon, J. N. Won, J. S. Huh, and J. C. Kim, “A study on
the application of a superconducting fault current limiter for energy
the reclosers perform reclosing operations when the fault is storage protection in a power distribution system,” IEEE Transactions
detected in their protected zone creating momentary outages on Applied Superconductivity, vol. 23, no. 3, p. 5603404, June 2013.
or nuisance tripping. Relay in the faulted feeder clears the [18] A. Dubey, S. Santoso, and A. Maitra, “Understanding photovoltaic
hosting capacity of distribution circuits,” in IEEE Power Energy Society
fault before these reclosing operations finish and sympathetic General Meeting, July 2015, pp. 1–5.
tripping happen. Sympathetic tripping is a severe problem [19] D. V. Tu, S. Chaitusaney, and A. Yokoyama, “Maximum-allowable
compared to nuisance tripping or momentary outages as it distributed generation considering fault ride-through requirement and
results in permanent outage of a complete feeder. reach reduction of utility relay,” IEEE Transactions on Power Delivery,
vol. 29, no. 2, pp. 534–541, April 2014.
[20] J. Seuss, M. J. Reno, R. J. Broderick, and S. Grijalva, “Maximum PV
size limited by the impact to distribution protection,” in IEEE 42nd
ACKNOWLEDGMENT Photovoltaic Specialist Conference, 2015, pp. 1–6.
[21] B. Mather et al., “Southern California Edison high-penetration photo-
The work was supported in part by Electric Power Research voltaic project–year 1,” Tech. Rep., 2011.
Institute, the National Science Foundation Industry/University [22] A. Hoke, R. B. J. Hambrick, and B. Kroposki, “Maximum photovoltaic
Cooperative Research Center on Next Generation Photo- penetration levels on typical distribution feeders,” Tech. Rep., 2012.
[Online]. Available: http://www.nrel.gov/docs/fy12osti/55094.pdf
voltaics (IIP−1134849 and IIP−1540028), and the Colombian [23] M. J. Reno, K. Coogan, R. Broderick, and S. Grijalva, “Reduction of
Department of Science, Technology and Innovation (Colcien- distribution feeders for simplified PV impact studies,” in IEEE 39th
cias) in cooperation with Universidad de los Andes. Photovoltaic Specialists Conference, June 2013, pp. 2337–2342.
[24] V. Scaini, “Whitepaper: Grid support stability for reliable, renewable
power,” Eaton Corporation, 2012.
[25] H. L. Willis, Power distribution planning reference book. CRC press,
R EFERENCES 2004.
[26] T. Gonen, Electric Power Distribution Engineering. CRC press, 2014.
[1] D. Feldman, G. L. Barbose, R. Margolis, and T. James, “Photovoltaic
(PV) pricing trends: Historical, recent, and near-term projections,” [27] “Distribution system feeder overcurrent protection.” [Online]. Available:
National Renewable Energy Laboratory, Tech. Rep., November 2012. http://www.geindustrial.com/publibrary
[2] B. Tsuchida, S. Sergici, B. Mudge, W. Gorman, P. Fox-Penner, [28] M. H. Bollen and F. Hassan, Integration of distributed generation in the
and J. Schoene, “Comparative generation costs of utility-scale and power system. John wiley & sons, 2011, vol. 80.
residential-scale PV in Xcel Energy Colorado’s service area,” Tech. Rep., [29] R. Jafari, M. Naderi, G. Gharehpetian, and N. Moaddabi, “Compensation
2015. of DGs impact on overcurrent protection system of smart micro-grids,”
[3] J. Bank, B. Mather, J. Keller, and M. Coddington, “High penetration in 22nd Int. Conf. and Exhibition on Electricity Distribution, June 2013.
photovoltaic case study report,” National Renewable Energy Laboratory, [30] M. Baran, H. Hooshyar, Z. Shen, and A. Huang, “Accommodating high
Tech. Rep., November 2013. PV penetration on distribution feeders,” IEEE Transactions on Smart
[4] P. Chiradeja and R. Ramakumar, “An approach to quantify the tech- Grid, vol. 3, no. 2, pp. 1039–1046, June 2012.
nical benefits of distributed generation,” IEEE Transactions on Energy [31] H. Hooshyar, M. Baran, and L. Vanfretti, “Coordination assessment of
Conversion, vol. 19, no. 4, pp. 764–773, Dec 2004. overcurrent relays in distribution feeders with high penetration of PV
[5] R. A. R. Walling, R. Saint, S. Member, R. C. Dugan, J. Burke, and L. A. systems,” in IEEE PowerTech, June 2013, pp. 1–6.
Kojovic, “Summary of distributed resources impact on power delivery [32] V. A. Papaspiliotopoulos, V. A. Kleftakis, P. C. Kotsampopoulos, G. N.
systems,” vol. 23, no. 3, pp. 1636–1644, 2008. Korres, and N. D. Hatziargyriou, “Hardware-in-the-loop simulation of
[6] “IEEE guide for conducting distribution impact studies for distributed protection blinding and sympathetic tripping phenomena in modern
resource interconnection,” IEEE Std 1547.7-2013, pp. 1–137, Feb 2014. distribution grids,” ENERGY, vol. 2012, pp. 1–1.
[7] H. Yazdanpanahi, W. Xu, and Y. W. Li, “A novel fault current control [33] G. Bernardi and J. de Carvalho Filho, “High-resistance neutral grounding
scheme to reduce synchronous DG’s impact on protection coordination,” in industrial systems and the ground fault protection,” in 2013 Brazilian
IEEE Trans. on Power Delivery, vol. 29, no. 2, pp. 542–551, April 2014. Power Electronics Conference, Oct 2013, pp. 1276–1282.
[8] H. Yazdanpanahi and W. Xu, “Contribution of induction-machine [34] H. Ravindra, M. Faruque, P. McLaren, K. Schoder, M. Steurer, and
distributed generators to fault current and assessing their impact on R. Meeker, “Impact of PV on distribution protection system,” in North
overcurrent protection,” in 26th Annual IEEE Canadian Conference on American Power Symposium, Sept 2012, pp. 1–6.
Electrical and Computer Engineering, May 2013, pp. 1–4. [35] M. McGranaghan, T. Ortmeyer, D. Crudele, T. Key, J. Smith, and
[9] S. Bhattacharya, T. Saha, and M. J. Hossain, “Fault current contribution P. Barker, “Renewable systems interconnection study: Advanced grid
from photovoltaic systems in residential power networks,” in IEEE planning and operations,” Sandia National Laboratories, 2008.
Australasian Universities Power Engg Conf., 2013, pp. 1–6. [36] R. Meeker et al., “High penetration solar PV deployment Sunshine
[10] J. Keller and B. Kroposki, “Understanding fault characteristics of state solar grid initiative (SUNGRIN),” Florida State University, Tech.
inverter-based distributed energy resources,” National Renewable Energy Rep., May 2015. [Online]. Available: http://www.caps.fsu.edu/pdfs/
Laboratory, Tech. Rep., January 2010. Final Report SUNGRIN 20160104.pdf
2169-3536 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/ACCESS.2016.2589545, IEEE Access
15
2169-3536 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
View publication stats http://www.ieee.org/publications_standards/publications/rights/index.html for more information.