You are on page 1of 6

2019 3rd International Conference on Recent Developments in Control, Automation & Power Engineering (RDCAPE)

Impact of Solar Photovoltaic Penetration


In Distribution Network
Authors : Ram Singh1, Pushkar Tripathi2, Kuwar Yatendra3
Electrical Engineering Department, Institute of Engineering and Technology, Lucknow, India

Abstract: - The integration of Renewable Energy However, since the present distribution network is
Generation to the grid steadily being growing due to radial network designed for unidirectional power flow, a
environmental awareness, green energy evolution and high penetration of PV may cause of several power
incentives from the government. Most of the RES quality issues to the system such as voltage rise, voltage
integrated to the distribution system in the form of fluctuation and reverse power flow. The integration of
distributed Photovoltaic(PV). As seen from the last few
solar PV can cause of bidirectional power flow which
years the integration of PV at residential distribution
network increases rapidly and it is expected to further make the distribution system an active network [5][6].
increase in the penetration level with growth of RES, The existing distribution network was designed without
causing some undesirable impact on the distribution consideration of distributed PV integration. There are
system such as over voltage, voltage fluctuations and different technical concerns from utility regarding
reverse power flow to the grid. power quality and general impact of high penetration of
A IEEE 13bus test case by EPRI has taken for the PV on low voltage distribution network [7].
distribution system impact analysis in terms of voltage The voltage is an important parameter for the electrical
performance and system losses. The distribution system is distribution system, utility needs to regulate the voltage
modelled in the OpenDSS (Open Distribution System
within the ANSI range that the appliances and machines
Simulator) and interfacing has done with MATLAB to
investigate the effect of PV penetration at the distribution connected to the system can operate well [8]. The power
system. A comparative study of with and without PV is output of the PV system directly dependent to the solar
shown and several PV integration scenarios are discussed irradiance coming from the sun, which is an uncertain
with different penetration level. Further mitigation and varies with time, also depends on the cloud
methods are proposed to overcome the power quality. movement.
Most of the PV impact studies are of deterministic or
Keyword - Solar Photovoltaic, Distributed Generation, probabilistic type, several case studies have been
Open Distribution system simulator (OpenDSS), performed on different distribution network to identify
the potential impact of PV penetration in distribution
I. INTRODUCTION system [9][10]–[12]. In [2][6] the potential impacts of
The growth of the solar PV integration in distribution solar PV generation on the climate change issues are
system is continuously being increasing. In recent years introduced and growth of solar rooftop PV installation
the number of solar Photovoltaic (PV) integration in and its future challenges to the distribution system are
distribution system has steadily being increased and it is discussed [5]. Many distribution system studies have
expected to increase continuously with the growth of been carried-out to better investigate the impact of high
renewable energy due to green energy evolution, penetration of distributed solar PV. Research work [9],
environmental awareness and incentives from the [13], [14] presented a deterministic approach carried out
government and increased energy prices [1]. Solar PV to analyse the impact of high penetration of PV in
generation is a better option of electricity generation distribution system. A detailed simulation model has
because it is a sustainable source of energy and produce been developed by [15] for the impact analysis of high
pollution free electricity [2]. Distributed PV generation penetration of grid interacted PV system. In [14] the
is well known for its positive contribution Technically, impact assessment of high penetration of PV on medium
environmentally and economically. It can provide voltage distribution network has been discussed.
various advantages to the electrical distribution system
such as improved power quality and grid reliability,
reduction in Transmission and Distribution losses etc. II. SIMULATION TOOLS AND
[3]. Due to continuous growth of distributed PV METHODOLOGY
generation and its penetration in the medium voltage This section describes the methodology and simulation
(MV) and low voltage (LV) distribution network, the tools used to carried out the research work. The
system is negatively affected [4]. distribution system simulation tool OpenDSS (Open

978-1-7281-2068-3/19/$31.00 ©2019 IEEE 551

Authorized licensed use limited to: University of Wollongong. Downloaded on May 31,2020 at 02:20:58 UTC from IEEE Xplore. Restrictions apply.
2019 3rd International Conference on Recent Developments in Control, Automation & Power Engineering (RDCAPE)

Distribution System Simulator) and well-known used for the impact analysis of high penetration of PV in
software MATLAB have been used for the analysis of the distribution network.
PV penetration in the distribution system. A 13-bus
A detailed diagram of the distribution feeder is shown
IEEE test distribution feeder is taken for the study and
in Figure 2.
different integration scenarios has discussed with
different penetration level.
Grid
115kV
A. Distribution System Simulator-OpenDSS
Sourcebus
Distribution
It is an electrical distribution system simulation tool Transformer
that supports all frequency domain analysis performed (115/4.16kV)
650.1.2.3
for the analysis and planning distribution system. The
software provides in-built simulation models of 1-Ǿ Regulation
Transformers
Distributed Generators (DGs) such as photovoltaic Rg60.1.2.3
generator, wind generator with their control blocks, that
632.1.2.3 Transformer
can be used for the smart grid analysis and future studies (4.16/0.48kV)
[16]. 646.3.2
645.3.2
Scripts 633.1.2.3 634.1.2.3
671.1.2.3
684.1.3

COM- Main Simulation Engine


Interface
611.3 692.1.2.3
User-Written DLLs 670.1.2.3

652.1 680.1.2.3
Scripts,
Results Figure 2: IEEE 13 bus Test System [17]

The test system has the following distribution


components-
Figure 1. OpenDSS Structure [15] ¾ Two transformers, one is connected between
Sourcebus and bus-650 to transform the
A basic nominal block diagram is shown in Figure 1. voltage level from 115kV to 4.16kV and
OpenDSS is capable to be run as a stand-alone second is connected between bus 633 and 634
executable program and also can be executed by the to transform the voltage level from 4.16kV to
various available software platforms as a COM 0.48kV.
(Component Object Model) server DLL. The COM ¾ The unbalanced 1-Φ and 3-Φ loads are
interfacing provides the ability to the researcher to connected to 9 nodes and two capacitors are
control the solution modes and variables in the DSS also connected at bus 675 and 611.
from the existing software. MATLAB, Python, C# and ¾ Three 1-Φ voltage regulators are incorporated
other languages are used to drive the DSS [17]. between bus 650 and rg60 to maintain the
The OpenDSS can used to perform power flow system voltage within range.
solution for the medium and low voltage distribution
network because it is designed to run as a distribution There are five objects class of distribution components
system power flow solver. The in-built models of DGs in OpenDSS which can be categories as follows-
facilitate the simulation capability for the smart grid ¾ Power Conversion Elements
analysis and the impact analysis of DG integration in ¾ Power Delivery Elements
distribution system. In this study, MATLAB is used to ¾ Control Element
drive the OpenDSS through COM server DLL to ¾ Meters and
investigate the impact of high penetration of PV in ¾ General
distribution system [16].
The above listed may be single phase or multi-phase
B. Test System used for Study according to the requirements for system designed.
All the impact studies have been performed on a 13- C. OpenDSS PV System Model
bus IEEE test case made available by EPRI [18]. The
system includes all electrical power system component In OpenDSS, an in-built simulation model is available
for solar PV system and it has the capability of

552

Authorized licensed use limited to: University of Wollongong. Downloaded on May 31,2020 at 02:20:58 UTC from IEEE Xplore. Restrictions apply.
2019 3rd International Conference on Recent Developments in Control, Automation & Power Engineering (RDCAPE)

simulation studies for 1 sec time step and greater. The


in-built OpenDSS model of PV system combines the
Photovoltaic(PV) array and DC/AC inverter into
convenient model [16]. It is considered that the
maximum power point tracking (MPPT) algorithm
performing well to extract the maximum power from the
PV array. It can be used for Distribution System impact
studies for snap mode, daily mode and duty mode. The
PV system is modelled as a power conversion element
that produce electrical AC output power according to a
production function. A schematic diagram of PV System
Bus names based on Distance from Substation
model is shown in Figure 2.
(a)
Inverter
Effi
PV Array
P(kW)
Pmpp
@1kW/m2
Temperature(T) I
Irradiance DC
P AC P*Effi V
Irradiance Yearly
Loadshape{ Daily Inverter
Curve Duty (One-Line) Delta-Wye
or
Pmpp 1-ph
kV Conn kVAr PF

0 100℃
Figure 3: Block Diagram of OpenDSS PV System Model
Bus names based on Distance from Substation
The output active power (P) from the PV array is a (b)
function of irradiance coming from the sun, temperature
of PV array and rated maximum power (Pmpp) at an
irradiance of 1.0kW/m2 and at a selected temperature
(~27℃) [15].

III. RESULTS AND DISCUSSION


The impact analysis of PV integration in distribution
system has discussed in this section. A 13bus system has
taken into consideration for the analysis of PV impact
on the conventional distribution network. The PV has
integrated to each load bus except Sourcebus, 650 and
rg60. The bus voltages have been plotted for different Bus names based on Distance from Substation
penetration level of PV shown below. (c)
A. Impact on the Bus Voltages Figure 4: Per Unit Bus Voltages with 1000kW PV Capacity
a) Phase-1, b) Phase-2, c) Phase-3
A 13bus system (Figure-2) is taken for the analysis and
PV is integrated to each load bus and buses are arranged Figure 4: shows the Per Unit voltage of all 3-phases at
in order of increasing distance from substation. Y axis with respect to the buses at X axis. It can be seen
Sourcebus (Substation Bus) is infinite bus. It has been that as the PV penetration increases from 0 to 1.1 pu in
considered that the substation bus is directly connected the distribution system the voltage of the buses increases
to the grid that can supply and absorb a large amount of respectively. If the irradiance from the sun varies over a
power without voltage deviation. day, it will cause of voltage fluctuations on the buses.
Case-1 Pmpp=1000kW: - In this case 1000kW Case-2 Pmpp =2000kW: - In this case 2000kW
capacity has installed and the irradiance value has Capacity has installed at each bus and the irradiance
increased from 0 to 1.1 pu. The per unit voltage has value has increased from 0 to 1.1 pu.
shown on Y axis with respect to the buses X axis. The
voltage plot has shown for increasing irradiance with
fixed installed.

553

Authorized licensed use limited to: University of Wollongong. Downloaded on May 31,2020 at 02:20:58 UTC from IEEE Xplore. Restrictions apply.
2019 3rd International Conference on Recent Developments in Control, Automation & Power Engineering (RDCAPE)

bus-650 and bus-rg60 and the impact of high PV


penetration has identified for different irradiance
level. The PV capacity Pmpp=2000kW has integrated
to each load bus of the distribution system.

Bus Names

Bus names based on Distance from Substation


(a)

Bus names based on Distance from Substation


(a)

Bus names based on Distance from Substation


(b)

Bus names based on Distance from Substation


(b)

Bus names based on Distance from Substation


(c)
Figure 5: Per Unit Bus Voltages with 2000kW PV Capacity
a) Phase-1, b) Phase-2, c) Phase-3

From figure 5: it can be observed that the voltage has


further increased with increase of PV penetration and Bus names based on Distance from Substation
also identified that the voltage limits get violated for (c)
phase-2 at bus-645, 646 and for phase-3 at bus- Figure 5: Per Unit Bus Voltages with 2000kW PV with OLTC
684,611. The above figures show that voltage a) Phase-1, b) Phase-2, c) Phase-3
fluctuation is less at the bus near the substation and
the voltage fluctuated more at the bus far away from Figures 5. shows that as the PV penetration level
the substation. increases the Taps of the load Tap Changer (OLTC)
decreased to maintain the system voltage within the
B. Impact on Legacy Devices (OLTC) ANSI limits [17]. Hence it can be observed that the total
number of Tap operations increases with variation of the
In this case auto control of voltage regulation irradiance.
transformer i.e. the On-line Load Tap Changer
(OLTC) is enabled which is incorporated between

554

Authorized licensed use limited to: University of Wollongong. Downloaded on May 31,2020 at 02:20:58 UTC from IEEE Xplore. Restrictions apply.
2019 3rd International Conference on Recent Developments in Control, Automation & Power Engineering (RDCAPE)

C. Mitigation Methods overvoltage and under voltage problems. The OLTC can
mitigate the overvoltage but in case of instant voltage
Voltage is an important parameter of the electrical
fluctuation a short duration peak will be observed which
power system, the performance of the equipments
cannot be mitigated by OLTC because of its slow
connected to the system highly dependent to the
mechanical response. The smart inverter helps to
terminal voltage. Hence it is necessary that the voltage
mitigate the overvoltages by controlling the flow of
should be in the permissible range. The On-line Load
reactive power in the system. It can mitigate the short
Tap Changer (OLTC) and Smart Inverter has
duration peak due to fast response of power electronic
implemented to minimize the overvoltages.
devices used in the inverter, that is by it is called smart
inverter.

Without Control
With OLTC
With Smart
Inverter

PV OFF When PV ON PV OFF

Figure 6: Bus Voltages of Phase-1 with Smart Inverter Figure 9: Per Unit Voltages of the System with PV in
Daily Mode

Figure 9: shows the per unit voltage of the system over


a 24-hour time period without voltage control and with
voltage control. Three plots have shown in figure for
without voltage control, with OLTC and smart inverter
control at the daily irradiance level. The results show
that the smart inverter improves the under voltage
during PV OFF period by in supplying reactive power.
However, mitigate the overvoltage during PV ON
period by absorbing reactive power.

Figure 7: Bus Voltages of Phase-2 with Smart Inverter IV. CONCLUSION


From above analysis it has been observed that the
integration of solar photovoltaic (PV) in distribution
system has several impact on the low voltage
distribution network. The low level of PV integration
improves the system voltage profile also minimizes the
overall power losses in the system by reducing the total
power demand from the substation. But as the
integration of the PV exceeds the integration limits, the
voltage range set by ANSI gets violated and also the
system losses starts increased.
Hence it can be concluded that high penetration of PV
in distribution system causes several impacts on the
system parameters such as voltage rise, voltage
fluctuation and power losses. The above discussed
Figure 8: Bus Voltages of Phase-1 with Smart Inverter issues limits the integration of PV in distribution system.
The PV can be integrated upto a feasible limit,
Figure 6 to 8 show the voltage plot of all three-phases integration of PV above a certain limit causes the
with voltage control methods to mitigate the voltage voltage violation, increase in operation of Load Tap

555

Authorized licensed use limited to: University of Wollongong. Downloaded on May 31,2020 at 02:20:58 UTC from IEEE Xplore. Restrictions apply.
2019 3rd International Conference on Recent Developments in Control, Automation & Power Engineering (RDCAPE)

Changer (LTC) and extra power losses in the system. Carlo-based assessment of PV impacts on real UK
The PV integration limits can be decided on the behalf low voltage networks,” in IEEE Power and Energy
of the issues discussed in this work. To mitigate the Society General Meeting, 2013.
impact of high penetration of PV in low voltage [10] I. S. Machado, B. S. M. C. Borba, and R. S. Maciel,
“Modeling distributed PV market and its impacts
distribution network the voltage control devices can be
on distribution System: A Brazilian case study,”
installed such as smart inverter control method, OLTC IEEE Lat. Am. Trans., vol. 14, no. 11, pp. 4520–
and D-STATCOM can be employed. The hosting 4526, 2016.
capacity can also be increased with the voltage control [11] J. Tan, Y. Zhang, S. Veda, T. Elgindy, and Y. Liu,
devices. A 33-bus system was analyzed to determine the “Developing High PV Penetration Cases for
hosting capacity. It was observed that the PV hosting Frequency Response Study of U.S. Western
capacity increases with the voltage control devices such Interconnection,” in IEEE Green Technologies
as OLTC and smart inverter. Conference, 2017, pp. 304–311.
[12] J. Putra, M. I.-2015 2nd I. C. on, and undefined
2015, “Impact of high penetration of Photovoltaic
V. REFERENCES Generation on voltage fluctuation of transmission
and distribution systems,” ieeexplore.ieee.org.
[1] M. Goel, “Solar rooftop in India: Policies, [13] K. Kumar and G. B. Kumbhar, “The effect of solar
challenges and outlook,” Green Energy Environ., power injection on aging of a distribution
vol. 1, no. 2, pp. 129–137, 2016. transformer,” in 2017 6th International Conference
[2] A. Magal, T. Engelmeier, G. M.-A. review of on Computer Applications In Electrical
technical aspects, best practices and, and Engineering-Recent Advances (CERA), 2017, pp.
undefined 2014, “Grid Integration of Distributed 242–246.
Solar Photovoltaics (PV) in India.” [14] Y.-J. Liu, Y.-H. Tai, C.-Y. Huang, H.-J. Su, P.-H.
[3] M. E. Khodayar, M. R. Feizi, and A. Vafamehr, Lan, and M.-K. Hsieh, “Assessment of the PV
“Solar photovoltaic generation: Benefits and hosting capacity for the medium-voltage 11.4 kV
operation challenges in distribution networks,” distribution feeder,” in 2018 IEEE International
Electr. J., 2019. Conference on Applied System Invention (ICASI),
[4] C. Debruyne, J. Desmet, J. Vanalme, B. Verhelst, 2018, pp. 381–384.
G. Vanalme, and L. Vandevelde, “Maximum power [15] J. W. Smith, R. Dugan, and W. Sunderman,
injection acceptance in a residential area,” in “Distribution modeling and analysis of high
International Conference on Renewable Energies penetration PV,” in 2011 IEEE Power and Energy
and Power Quality (ICREPQ 2010), 2010. Society General Meeting, 2011, pp. 1–7.
[5] L. M. Cipcigan and P. C. Taylor, “Investigation of [16] A. Dubey, “Impacts of Voltage Control Methods on
the reverse power flow requirements of high Distribution Circuit’s Photovoltaic (PV) Integration
penetrations of small-scale embedded generation,” Limits,” Inventions, vol. 2, no. 4, p. 28, 2017.
IET Renew. Power Gener., vol. 1, no. 3, pp. 160– [17] W. E. Ibraheem, C. K. Gan, M. R. A. Ghani, W. E.
166, 2007. Ibraheem, C. K. Gan, and M. R. A. Ghani, “Impact
[6] F. Katiraei and J. R. Agüero, “Solar PV integration of Photovoltaic (PV) Systems on Distribution
challenges,” IEEE Power Energy Mag., 2011. Networks,” Int. Rev. Model. Simulations, vol. 7, no.
[7] M. Karimi, H. Mokhlis, K. Naidu, S. Uddin, and A. 2, pp. 298–310, Apr. 2014.
H. A. Bakar, “Photovoltaic penetration issues and [18] “Smart Grid Resource Center. Electric Power
impacts in distribution network - A review,” Research Institute. Available online:
Renewable and Sustainable Energy Reviews, vol. http://smartgrid.epri.com/SimulationTool.aspx.”
53. 2016.
[8] Y. Liu, J. Bebic, B. Kroposki, J. De Bedout, and W.
Ren, “Distribution system voltage performance
analysis for high-penetration PV,” in 2008 IEEE
Energy 2030 Conference, 2008, pp. 1–8.
[9] A. Navarro, L. F. Ochoa, and D. Randles, “Monte

556

Authorized licensed use limited to: University of Wollongong. Downloaded on May 31,2020 at 02:20:58 UTC from IEEE Xplore. Restrictions apply.

You might also like