team3 comments

13 March 2024

TB1/PB1 TB1/PB1 TB1/PB1 TB1/PB1 TB1/PB1

F1 F1 F1 F1 F1 F1

BOUNDARY WALL PLAN

The given difference


is not constant throughout
the site, as confirmed. SADHAK'S ROOM LAYOUT (FOR
To be considered as per MEDITATION ROOM GUY)
worst case scenario,
as per site.

13 March 2024

Due to level difference between school site level


and adjacent Lord Ayappa temple's site level, there might be chances of dampness NNC DESIGN INTERNATIONAL
towards the temple side (between tie beam and plinth beam lvl). CONSULTING STRUCTURAL ENGINEERS

Pls confirm whether weep holes to be provided for the same, or thickness of wall
to be increased for avoiding dampness through the wall. Pls review and proceed accordingly.