Professional Documents
Culture Documents
CONTENTS
1. About This Manual ........................................................................................................................................ 3
2. Introduction ................................................................................................................................................... 3
2.1. Overview ............................................................................................................................................ 3
2.2. Technical Specifications.....................................................................................................................3
2.3. Standards ............................................................................................................................................ 5
3. Installation and Connections ......................................................................................................................... 6
3.1. Panel’s interior ....................................................................................................................................6
3.2. Internal wiring .................................................................................................................................... 7
3.3. Mounting the chassis to the wall ........................................................................................................ 8
3.4. Mains connection ............................................................................................................................... 9
3.5. Battery connection ............................................................................................................................10
3.6. Connection of the ZONE ..................................................................................................................10
3.7. Connection of the SOUNDER ......................................................................................................... 11
3.7.1. S.C.Out .................................................................................................................................. 11
3.7.2. 2ND SOUNDER ................................................................................................................... 11
3.8. Connection of the Fire OUT ............................................................................................................ 12
3.9. Connection of the EXTING ............................................................................................................. 12
3.10. Wiring of the monitor input ............................................................................................................12
3.11. Other I/O interfaces ........................................................................................................................ 13
4. Debugging and programming ......................................................................................................................13
4.1. Normal state ..................................................................................................................................... 13
4.2. Fire alarm status ............................................................................................................................... 14
4.3. The first stage of the deflation process ............................................................................................ 14
4.4. Compound fire alarm bleed ..............................................................................................................14
4.5. Manual deflation ...............................................................................................................................15
4.6. Silence .............................................................................................................................................. 15
4.7. Evacuate ........................................................................................................................................... 16
4.8. Reset ................................................................................................................................................. 16
4.9. FAULT ..............................................................................................................................................16
4.9.1. Comm. Fault ..........................................................................................................................17
4.9.2. Flooding Zone Fault .............................................................................................................. 17
4.9.3. System fault ...........................................................................................................................17
4.9.4. FAULT_IN Monitoring ......................................................................................................... 18
4.10. Buzzer .............................................................................................................................................19
4.10.1. 5V buzzer ............................................................................................................................ 19
4.10.2. 24V buzzer .......................................................................................................................... 19
4.11. Hold ................................................................................................................................................ 19
4.12. Pressure Feedback .......................................................................................................................... 19
4.13. PROG.IN (Programmable input) ................................................................................................... 20
4.14. Modify the control mode ................................................................................................................20
4.15. DISABLE ....................................................................................................................................... 21
4.15.1. ZONE1/2 DISABLE ........................................................................................................... 21
Page 1 of 27
Version:V1.1
Page 2 of 27
ECP1000 Gas Extinguishing Control Panel
2.Introduction
2.1. Overview
The ECP1000 control panel is designed in accordance with European standards EN54-2 and
EN54-4 Fire Detection and Fire Alarm systems - Control and Indicating Equipment and EN12094-
1 Fixed firefighting systems - Components for gas extinguishing systems - Part 1: Requirements
and test methods for electrical automatic control and delay devices.
The control equipment is a combined fire alarm control panel and extinguishing system and has
two detection zones, any or all of which are capable of contributing to the extinguishing release
decision.
The ECP1000 Control panel have an integral, mains powered battery charger and power supply designed in
accordance with the requirements of EN54-4.
2.2.Technical Specifications
Power supply
Mains supply 110V/230V AC (-15%, +10%), 10A, 50Hz/60Hz
Mains fuse 3A 250V
Operating voltage 21 ~ 30V DC
Recommended mains cable Standard/black mains cable, cable size 0.75mm2
Power rating Imin=0.1A; Imax.a=3.2A; Imax.b=3.8A
Max. battery supply current 8A (when the Mains is disconnected)
Max. charging current 1A
Battery capacity, type and
NP7-12 for 7Ah VRLA(Yuasa)
recommended model
Page 3 of 27
ECP1000 Gas Extinguishing Control Panel
Page 4 of 27
ECP1000 Gas Extinguishing Control Panel
2.3. Standards
ECP1000 Gas Extinguishing Control Panel and power supply equipment conform to the essential
requirements of the Construction Products Directive 305/2011/EU:
0370-CPR-XXXX
EN54-2:1997 +A1:2006
Control and indicating equipment for fire detection and fire alarm systems for
buildings
Provided options:
- Outputs to Fire Alarm Devices
-Delays to outputs
EN54-4:1997 +A1:2002 +A2:2006
Power supply equipment for fire detection and fire alarm
systems for buildings
Page 5 of 27
ECP1000 Gas Extinguishing Control Panel
EN 12094-1:2003
Electrical automatic control and delay devices for for gas extinguishing systems
Environmental Class A. 1 Flooding Zone.
Provided options:
- Delay of extinguishing signal
- Monitoring of the status of components
- Emergency hold device
- Manual only mode
- Triggering of equipment outside the system
- Activation of alarm devices with different signals
3.1.Panel’s interior
The front door panel of the controller can be opened by the matching key to access the inside of the
controller.
4 Mounting
1 2 3 hole
8
7 Mounting
hole
Page 6 of 27
ECP1000 Gas Extinguishing Control Panel
2. The right internal section contains the DZ-Board, the Communication Board for networking, the P.S.E
(power supply equipment), the Buzzer, the battery compartment, the mounting holes and cable knock-outs.
PS-A2810B
The PS-A2810B is an integrated unit that provides power both for the panel and the backup rechargeable
battery. And it is capable of monitoring the mains and battery states.
A-Board
It is the main processor of system. The B-Board responsible for display.
ECP1000_B
It provides connections for the main processor A-Board, the KEY-Board, the LCD and the IO Board;
terminals of RS-485 bus for the communication between internal circuit boards.
ECP1000_KEY
The ECP1000_KEY Board responsible for Buttons and LEDs.
Presure 2ND
PROG.IN Feedback FAULT_IN S.C.OUT SOUNDER F.A.OUT1 F.A.OUT2 EXTING. 24VK 24VK
SEC1000_COM(Communication Board )
This board is optional for external communication with other panels. Specifically, up to 20 panels can be
networked with each other through the terminal pair of CANH and CANL on the communication board;
3.2.Internal wiring
Page 7 of 27
ECP1000 Gas Extinguishing Control Panel
1 2
4
5
+ - + -
8 8
Page 8 of 27
ECP1000 Gas Extinguishing Control Panel
270
365
(Unit: mm)
3.4.Mains connection
To connect the panel to the main power source, use a three-core cable with good quality cable glands fitted,
and connect it to the P.S.E as the figure shows below.
Page 9 of 27
ECP1000 Gas Extinguishing Control Panel
BLACK
RED
RED BLACK
+ - + -
8 8
3.5.Battery connection
For this single loop system, 2×12V/7Ah sealed lead acid batteries are used as per the calculation of battery
capacity in section 6. The batteries should be connected in series first using the link wire supplied and be
located within the panel enclosure. Then connect the battery wire leads to the P.S.E terminal connections.
RED BLACK
+ - + -
8 8
Page 10 of 27
ECP1000 Gas Extinguishing Control Panel
circuit to monitor its line for open or short faults. The detection area supports the access of the traditional
current type detector and the switching type detector. The switching type detector requires a built-in or
external contact resistor. The typical connection is shown in the following figure:
+
4.7K
Detector Detector End‐of‐line resistor
+ 1K
Trigger resistor
4.7K
Detector End‐of‐line resistor
or
‐ Call point
3.7.1. S.C.Out
Abbreviation for acousto-optic output, which outputs a 24V DC power supply to drive conventional
acousto-optic equipment in the event of a fire. A 10 K termination resistor (supplied) needs to be connected
at the end of the circuit to monitor its line for open or short faults. A typical connection is shown in the
following figure:
+ Diode Diode
10K
+ + End‐of‐line resistor
Sounder Sounder
‐ ‐ ‐
Page 11 of 27
ECP1000 Gas Extinguishing Control Panel
+ Diode Diode
10K
+ + End‐of‐line resistor
Sounder Sounder
‐ ‐ ‐
+ Diode Diode
10K
+ Fire + Fire End‐of‐line resistor
‐
Monitoring Monitoring
‐ ‐
EXTING : The bleed output interface can provide an output of up to 3A for 10 minutes to drive the
solenoid valve. The resistance of the solenoid must be greater than 10 ohms to ensure that the maximum
amperage rating of the bleed output is not exceeded. The solenoid valve shall be equipped with a
freewheeling diode to prevent the electromotive force (EMF) generated by the solenoid valve when
de-energized from interfering with the operation of the controller. One 10 K termination resistor
(supplied)It needs to be connected at the end of the circuit to monitor the open or short circuit fault of its
wiring. In addition, in order to prevent the misoperation of the solenoid valve, the circuit needs to be
connected in series with a diode in the forward direction. The typical connection is shown in the figure
below:
+ Diode
Solenoid
10K Diode Valve
‐
End‐of‐line resistor
The monitoring inputs (HOLD, PROG. IN, Pressure Feedback, FAULT _ IN) require a 10 K termination
resistor (supplied) to be connected at the end of the circuit to monitor its wiring for open or short faults. A
trigger resistor with a typical value of 10 K is also required.
A typical connection is shown in the following figure:
+ Detector 10K
End‐of‐line resistor
‐
10K
Trigger resistor
4.1.Normal state
Under normal conditions, only the Power lamp and AUTOMANUAL lamp or MANUAL ONLY lamp on
the panel are normally on. The system is divided into three levels. The user is only allowed to view the
main interface information and perform some security operations at level 1 (without password). The user
needs to log in at level 2 with a password. At level 2, the user can operate all the keys on the panel, view
and modify some configurations; Level 3 also requires a password to log in. Under Level 3, all operations
and configurations can be performed.
Prompt: Level 2 menu operation authority is shown in the following table:
Parent menu Submenu Permissions
Basic Read and write
System You can modify the configuration of Level 2
User Setup
user
Page 13 of 27
ECP1000 Gas Extinguishing Control Panel
A) The fire alarm information will be displayed at the main interface of the screen, and the gas
extinguishment related information will display the alarm information of the corresponding detector
equipment type;
B) The 2ND SOUNDER relay will operate in 1 Hz intermittent mode;
C) 2ND STAGE relay will output;
D) The Activated light on the front panel will be on constantly;
E) The Release Imminent light of the remote status panel is normally on;
F) The countdown control pops up on the main interface of the screen to display the remaining time before
the extinguishing agent is released;
G) The remote status panel provides an LED display to show the countdown time;
H) Extinguishing agent (EXTING. Relays) will be output at the end of the configured delay time. If the
Released signal is configured as "None", the Extinguishant Released lights on the front panel and the
Page 14 of 27
ECP1000 Gas Extinguishing Control Panel
remote status panel will be displayed in the EXTING.. Always on after output;
I) The 2ND SOUNDER relay will output continuously;
J) EXTING. The relay stops outputting after the configured duration is reached;
Prompt: Auto Delay and EXTING. Continuous output time of the relay (Exting. Duration time) can be
modified by entering the gas extinguishment configuration interface at level 3.
Notice:
The controller will not respond to the reset operation until the deflation is completed when the
deflation process of the gas extinction zone has been started and the start condition has been reached
(i.e., when the Released Imminent light is on or when the screen interface displays a countdown).
The deflated Activated and Released messages are indicated only by the indicator light, and the
interface does not display messages about Activated and Released.
4.5.Manual deflation
When the front panel-mounted Extinguishant Released button, the Monitored Manual Air Bleed input
(PROG. IN type set to "manual release" "), or the Remote Status Dial mounted Extinguishant Released
button are operated, The controller will respond in this order.
What is different from the above response is the pre-deflation delay time, which needs to be modified at
level 3 by the Manual Delay in the gas extinguishment configuration.
4.6.Silence
Silence button is used to control the start and stop of audible and visual alarm. When the sound-light
control is in the enabled state, the sound-light control state will automatically switch to the disabled state
after the site sound-light alarm starts or resounds due to certain conditions.
: Silence disabled,Turn on all audible and visual alarms that are turned off.
: Silence enabled,Turn off all audible and visual alarms that are turned on.
Page 15 of 27
ECP1000 Gas Extinguishing Control Panel
Note: The 2ND SOUNDER can be stopped by the Silence button, but cannot be restarted by the Silence
button.
4.7.Evacuate
The Evacuate button responds as follows:
Activate all audible and visual alarms connected to the controller, such as the S. C. OUT relay (except
the 2ND SOUNDER relay).
The Evacuate light on the front panel stays on.
Tip: The Evacuate light will be turned off after the Silence function is enabled or reset.
4.8.Reset
Operating the Reset button in level 2 or 3 resets the system in the following ways:
The gas extinction zone is not in the bleeding process, or the gas extinction zone has entered the
bleeding process but the system has a system fault:
After pressing the Reset button, all the States of the system will be reset. The reset time is about 10 seconds,
and a prompt box will pop up on the screen interface.
4.9.FAULT
Page 16 of 27
ECP1000 Gas Extinguishing Control Panel
If the system detects a fault event, the corresponding fault message will be displayed at the fault message of
the main interface of the screen, the fault lamp of the panel and the fault lamp of the remote status panel
corresponding to the fault in the gas extinguishment area will be normally on, and the fault relay FAUlT _
OUT1/2 in the gas extinguishment area will output.
Notice:
When the active relay output (F. A. OUT/1, S. C. OUT, EXTING.) startup condition is reached in
some cases, if the active output is in the fault state at this time, the active relay output will not act for
safety. The output state of the active relay remains unchanged even after changing from the fault state
to the normal state, except for the new condition trigger.
Due to the circuit design of the terminal board itself, when one of the active relays of the F. A. OUT1
or the F. A. OUT2 has a fault, the relays of the F. A. OUT1 and the F. A. OUT2 will not operate.
4.9.1.Comm. Fault
Comm. Fault is the abbreviation of communication fault, which represents the communication failure
between a device and the host. The communication failure message shown in the figure below represents
that the remote status panel 1 (RSU1000 is the model of the remote status panel) has a communication
failure with the host.
4.9.3.System fault
Page 17 of 27
ECP1000 Gas Extinguishing Control Panel
When the system has a system fault, in addition to responding to the actions described in 5.8, the System
Fault light on the front panel will also be on, the buzzer will output continuously, and the terminal board
will enter the safety mode. If the system fault is not caused by the main control board, the UI interface will
display the system fault event which is different from the normal fault event. The two system fault
messages as shown in the figure below represent that the power supply of the controller and the
communication between the terminal board and the main control board are faulty respectively. It is only
allowed to be removed by manually pressing the reset button on the front panel after login.
Safe mode: fault relay and 24VK relay output, other relays stop output, and input monitoring of terminal
board is closed.
4.9.4.FAULT_IN Monitoring
FAULT _ IN of the terminal board is an additional fault monitoring input terminal provided to the user,
which can be connected to fault monitoring equipment. If the FAULT _ IN terminal detects the input, the
corresponding fault message will be displayed at the fault information of the UI interface, the fault lamp of
the front panel and the remote status panel corresponding to the gas extinguishment area will be on, and the
fault relay corresponding to the gas extinguishment area will output.
Page 18 of 27
ECP1000 Gas Extinguishing Control Panel
4.10.Buzzer
Two buzzers are provided on the controller, one is a 5V buzzer and the other is a 24V buzzer.
4.10.1. 5V buzzer
There is a small 5V buzzer on the controller, which is used to indicate the tone when the key is pressed.
Priority: Fire alarm tone = deflated tone > fault tone = hold press tone
Note: In case of system failure, the buzzer shall output continuously and shall not be silenced.
4.11.Hold
When the system detects that there is an input at the HOLD terminal or there is a short-circuit fault at the
HOLD input terminal, the Hold Activated light on the front panel and the remote status panel will remain
on, and the buzzer of the controller and the remote status panel will sound at the same frequency as the
normal fault. If a deflation countdown is in progress in the deflation zone, the countdown will be
interrupted and the predeflation remaining time will return to the initial value.When the HOLD is released
and there are no HOLD-related faults, the Hold Activated light on the front panel and remote status panel
will go off and the countdown to predeflation will continue.
4.12.Pressure Feedback
The pressure feedback input is connected to the fire extinguisher. When the fire extinguisher is released, the
controller will detect the input signal and the Extinguishant Released light will remain on. If the fire
extinguisher is released by abnormal means and the Pressure Feedback terminal of the controller detects the
input, the Activated light on the front panel will remain on, 1ST/2ND STAGE relay output and 2ND
SOUNDER continuous output.
Note: If the "Released Signal" is set to "None" in the gas extinguishment configuration, the Extinguishant
Released lamp will remain on when the fire extinguisher is released by the compound fire alarm or manual
deflation, regardless of whether the pressure feedback signal is received.
Page 19 of 27
ECP1000 Gas Extinguishing Control Panel
Page 20 of 27
ECP1000 Gas Extinguishing Control Panel
4.15.DISABLE
It is possible to disable certain functions, inputs or outputs of the gas extinction zone. If the system is
shielded, the shielding message on the UI main interface will display specific shielding information, and
the Disabled light on the front panel and the Disabled light on the remote status panel corresponding to the
gas extinguishment area will be on.
Note: When certain conditions reach the relay response condition, the relay will not respond if the relay is
in the shielding state at this time. Without resetting, the output state of the relay remains unchanged, except
for the new condition trigger, even after changing from the shield state to the normal state.
4.15.1.ZONE1/2 DISABLE
Input, fault of ZONE 1/2 on shield terminal block.
Note: If the existing fire alarm is shielded, the fire alarm message on the interface will not be eliminated
and will take effect only after reset; if the shielding is cancelled, the status of ZONE1/2 will be detected
again and reported. (The same applies to faults)
4.15.2.S.C.OUT DISABLE
For S. C. OUT output and fault on the shield terminal board, the Sounder Disabled/Fault lamp on the shield
rear panel will be yellow in addition to the Disabled lamp.
Notice:
When the existing S. C. OUT fault is masked, the fault message on the interface will not be eliminated
and will take effect only after reset; if the mask is cancelled, the status of the S. C. OUT will be
detected again and reported.
Masking or unmasking does not update the expected output state of the S. C. OUT and requires a reset
to take effect.
4.15.3.FAULT_OUT DISABLE
Page 21 of 27
ECP1000 Gas Extinguishing Control Panel
4.15.4.Extinguishant DISABLE
Block the Exting uishant function. When the Extinguishant is masked, the system does not enter the bleed
process.
Notice:
After the Extinguishant is shielded, it will not enter the deflation process through the two fire alarm
composite automatic deflation or manual deflation, but the Activated light on the front panel will be on,
the 2ND SOUNDER relay will continue to output, and the 1ST/2ND STAGE relay will output.
After masking the Exting uishant, for an existing EXTING. Fault, the fault message on the interface
will not be eliminated, and will take effect only after reset; unmasking will re-detect and report
EXTING. The status of the terminal.
If the system performs composite fire alarm deflation or manual deflation in the Extinguishant
shielding state, it will not enter the deflation process. After the Extinguishant shielding state is
cancelled, the deflation process can be reestablished only by resetting.
4.15.6.Stage_1 DISABLE
Shield the output of the 1ST STAGE terminal.
Note:masking or unmasking does not update the expected output status of the 1ST STAGE and requires a
reset to take effect.
4.15.7.Stage_2 DISABLE
Shield the output of the 2ND STAGE terminal.
Note:masking or unmasking does not update the expected output state of the 2ND STAGE and requires a
reset to take effect.
Page 22 of 27
ECP1000 Gas Extinguishing Control Panel
In which,
The multiplier 1.25 is present to account for loss of capacity over the life of the battery.
IFq = 0.15A, which is the quiescent current of the fire alarm control panel in the event of the loss of the
mains supply;
ILq is the quiescent current of the loop load, which is determined by the number of loads. The quiescent
current of a smoke detector, a heat detector, or a manual call point is typically 0.0002A (or 200μA), while
that of a module/sounder strobe is 0.002A (or 2mA);
IFmax = 0.16A, which is the alarm current of the fire alarm control panel;
ILmax is the maximum loop current. The alarm current of a smoke detector, a heat detector, or a manual call
point is typically 0.001A (or 1mA), while that of a input/output modules or Intelligent Sounder Beacon is
0.008A (or 8mA) ;
IRout is the alarm output current of the panel’s three relays, which is determined by the number of loads they
connect;
T1 is the amount of standby hours required (most commonly being 24 hours);
T2 is the amount of alarm hours required (most commonly being half an hour).
Take the system of 120 points as an example: there are 104 addressable detectors, 8 input/output modules, 8
intelligent Sounder Beacon, 8 loop isolators and 3 full loaded relay output.
Thus,
ILq = 0.0002 x 104 + 0.002 x 16 = 0.0528A,
ILmax = 0.001 x 104+0.008 x 16 = 0.232A,
IRout = 1 x 1.1 = 1.1A,
Battery capacity = 1.25 x (24 x (0.15+0.0528) + 0.5 x (0.16+0.232+1.1) )
= 1.25 x (4.8672 + 0.746)
= 7.0165Ah
6.1.Maintenance
Periodic maintenance should be carried out on the system as prescribed in the local design, maintenance
and installation regulations.
The key to the panel shall be kept by specially assigned maintenance personnel.
The standby batteries should be periodically checked for integrity of the connections. And a period of 5
years is recommended to replace the correct type of battery.
6.2.Troubleshooting
Solution of all suspected faults MUST only be carried out by suitably qualified technical engineers.
Problem: apply power to the panel but the LCD display is off and panel does not work.
Possible reason and solution: check whether the cable is properly connected between the CB-Board and
the MB-Board; Check if the POWER indicator on the front panel is on, otherwise something is wrong with
the P.S.E that the manufacturer should be informed.
Page 23 of 27
ECP1000 Gas Extinguishing Control Panel
Page 24 of 27
ECP1000 Gas Extinguishing Control Panel
Page 25 of 27
ECP1000 Gas Extinguishing Control Panel
Page 26 of 27
ECP1000 Gas Extinguishing Control Panel
Page 27 of 27
ECP1000 Gas Extinguishing Control Panel
28