SF6 Gas-insulated Switchgear (GIS)

Routine Test Report

Equipment Model:ZF28-252
Day/Month/Year:2022-09-27

Sieyuan Electric Co., LTD.


SF6 Gas-insulated Metal-enclosed Switchgear (GIS)

Routine Test Report


Report No 20220926 Rated Voltage 252kV
Project Name SHF22064NS Rated Power Frequency Withstand Voltage 460kV

Customer Name CEME1 Solar 480MWp PV Project Partial Discharge Measuring Voltage 175kV

"Owner:CEME 1 SpA;
Substation Name Contractor:Powerchina Ltd. Rated Frequency 50Hz
Agencia en Chile"
Bay No D01-D04 Rated Short-time Withstand Current 50kA
Rated Gas
0.62MPa Rated Duration of Short Circuit 3s
Pressure (20℃)
Standard Code IEC62271-203 Rated Peak Withstand Current 125kA
IEC62271-1
IEC61869-2
No Bay Name Component Name Component Identification Number Report No

1 Circuit breaker CB SHF22064NSCB011 SHF22064NSCT30011 2022092601

2 Disconnecting switch DS1 SHF22064NSDS011 SHF22064NSCJ30011 2022092601

3 Disconnecting switch DS2 SHF22064NSDS012 SHF22064NSCJ30012 2022092601

4 SHF22064NSTA011 2022092601

BAY
5 Current transformer TA SHF22064NSTA012 2022092601
(D01)

6 SHF22064NSTA013 2022092601

7 SHF22064NSTA014 2022092601

8 Current transformer TA SHF22064NSTA015 2022092601

9 SHF22064NSTA016 2022092601

10 Circuit breaker CB SHF22064NSCB021 SHF22064NSCT30021 2022092602

Three-position disconnecting/earthing
11 SHF22064NSDES021 SHF22064NSCJ30021 2022092602
switch DES

12 Disconnecting switch DS2 SHF22064NSDS021 SHF22064NSCJ30022 2022092602


BAY
(D02)
13 SHF22064NSTA021 2022092602

14 Current transformer TA SHF22064NSTA022 2022092602

15 SHF22064NSTA023 2022092602
16 SHF22064NSTA024 2022092602

BAY
17 Current transformer TA SHF22064NSTA025 2022092602
(D02)

18 SHF22064NSTA026 2022092602

19 Circuit breaker CB SHF22064NSCB031 SHF22064NSCT30031 2022092603

20 Disconnecting switch DS1 SHF22064NSDS031 SHF22064NSCJ30031 2022092603

21 Disconnecting switch DS2 SHF22064NSDS032 SHF22064NSCJ30032 2022092603

22 SHF22064NSTA031 2022092603

BAY
23 Current transformer TA SHF22064NSTA032 2022092603
(D03)

24 SHF22064NSTA033 2022092603

25 SHF22064NSTA034 2022092603

26 Current transformer TA SHF22064NSTA035 2022092603

27 SHF22064NSTA036 2022092603

28 Circuit breaker CB SHF22064NSCB041 SHF22064NSCT30041 2022092604

29 Disconnecting switch DS1 SHF22064NSDS041 SHF22064NSCJ30041 2022092604

30 Disconnecting switch DS2 SHF22064NSDS042 SHF22064NSCJ30042 2022092604

31 SHF22064NSTA041 2022092604
BAY
32 Current transformer TA SHF22064NSTA042 2022092604
(D04)
33 SHF22064NSTA043 2022092604

34 SHF22064NSTA044 2022092604

35 Current transformer TA SHF22064NSTA045 2022092604

36 SHF22064NSTA046 2022092604
Bay F01 Test Report
F01
Report No. 2022092601 Rated Voltage 252kV
Bay No D01 Rated Power Frequency Withstand Voltage 460kV
Project No. SHF22064NS Partial Discharge Measuring Voltage 175kV

CEME1 Solar 480MWp


User Name Rated Frequency 50Hz
PV Project

"Owner :CEME 1 SpA;


Substation Name Contractor :Powerchina Ltd. Rated Short-time Withstand Current 50kA
Agencia en Chile"
Rated Gas Gauge
0.62MPa Rated Duration of Short Circuit 3s
Pressure(20℃)
Alarm Gas Gauge
0.58MPa Rated Peak Withstand Current 125kA
Pressure(20℃)
I. Appearance Inspection
No Inspection Item Result
Nameplate and sign are free from corrosion, characters and symbols are clear, and nameplate position
1 Qualified
should be apparent

2 Earthing identification is clear and in correct position. Qualified

The appearance is in good condition and free from defects such as color difference, damage, scratch,
3 Qualified
rust and paint falling off.

LCP control cabinet door and circuit breaker mechanism case door can be opened and closed flexibly,
4 Qualified
and the case is not deformed.

5 Electrical control circuit wiring is neat and beautiful.Check the wire cross section area Qualified

6 Check the wire conductor type and insulation (stranded copper, flexible copper) Qualified

7 Check the wire color and (------) label Qualified

8 No more than one control wire at each terminal lug Qualified

Ambient Relative
II. Resistance Measurement of Main Circuit 21℃ 50% RH
Temperature Humidity
Measured
No. Measure Point Phase Requirement (μΩ)
Value (μ
1 R 27.2-54.4 Ω)
48.21
2 A1-A2 S 27.2-54.4 49.47
3 T 27.2-54.4 48.35
Ambient Relative
III.Dielectric Test of the main circuit 21℃ 50% RH
Temperature Humidity
1. Power Frequency Withstand Voltage Test of Main Circuit (Gas gauge pressure of Gas chamber is blocking
pressure)
No. Test Item Applied Voltage Unit Test Result
断路器、三工位开关隔离侧依
1 CB 460kV kV/1min Qualified
次分开,其余非被试断口关
合;断口间工频耐压试验
1 A 460kV kV/1min Qualified
断路器、三工位开关隔离侧合
闸,所有接地开关分闸;相间
2 B 460kV kV/1min Qualified
及对地工频耐压试验和接地断
口工频耐压试验
3 C 460kV kV/1min Qualified

2. Partial Discharge Measurement Test of Main Circuit (Gas gauge pressure of Gas chamber is blocking pressure)

Technical
No. Test Item Measuring Voltage Test Result
Requirement
断路器、三工位开关隔离侧合
1 CB 175kV ≤5 2.85
闸,所有接地开关分闸;断口
1 A 175kV ≤5 2.71
断路器、三工位开关隔离侧依
次分开,其余非被试断口关
2 B 175kV ≤5 2.85
合;相间及对地局部放电试验
和接地断口局部放电测量试验
3 C 175kV ≤5 2.82

IV. Insulation Test of Auxiliary And Control Circuit


No Test Item Test Result
1 Power frequency withstand voltage test of Auxiliary And control circuit AC 2,000V/1min Qualified
V. Interlocking Test of Control Circuit
No. Test Item Test Result
1 Q0cannot be closed during the action of Q1 mechanism; Qualified
2 Q0cannot be closed during the action of Q2 mechanism; Qualified
3 When Q0 is closed, Q1、Q2 cannot be closed or open; Qualified
VI.Gas Tightness Test
No. Gas Chamber Name Technical Requirement Unit Test Result
1 CB ≤0.1 %/year Qualified
2 DES1 ≤0.1 %/year Qualified
3 DES2 ≤0.1 %/year Qualified
Bay F01 Test Report
F01
Report No. 20220926001 Rated Voltage 252kV
Rated Power Frequency
Bay No D01 460kV
Withstand Voltage
Project No. SHF22064NS Partial Discharge Measuring Voltage 175kV

CEME1 Solar 480MWp


User Name Rated Frequency 50Hz
PV Project

"Owner :CEME 1 SpA;


Substation Name Contractor :Powerchina Ltd. Rated Short-time Withstand Current 50kA
Agencia en Chile"

Rated Gas Gauge Pressure (20.62MPa


℃) Rated Duration of Short Circuit 3s
Alarm Gas Gauge Pressure (2 0.58MPa
℃) Rated Peak Withstand Current 125kA
I. Appearance Inspection
No Inspection Item Result
Nameplate and sign are free from corrosion, characters and symbols are clear, and nameplate
1 Qualified
position should be apparent

2 Earthing identification is clear and in correct position. Qualified

The appearance is in good condition and free from defects such as color difference, damage,
3 Qualified
scratch, rust and paint falling off.
LCP control cabinet door and circuit breaker mechanism case door can be opened and closed
4 Qualified
flexibly, and the case is not deformed.

5 Electrical control circuit wiring is neat and beautiful.Check the wire cross section area Qualified

6 Check the wire conductor type and insulation (stranded copper, flexible copper) Qualified

7 Check the wire color and (------) label Qualified

8 No more than one control wire at each terminal lug Qualified

Ambient Relative
II. Resistance Measurement of Main Circuit 21℃ 48% RH
Temperature Humidity
Measured
No. Measure Point Phase Requirement (μΩ)
Value(μ
1 R 10.2-15.2 Ω)
13.98
2 A1-A2 S 10.2-15.2 12.17
3 T 10.2-15.2 13.16
Ambient Relative
III.Dielectric Test of the main circuit 21℃ 48 %RH
Temperature Humidity
1. Power Frequency Withstand Voltage Test of Main Circuit (Gas gauge pressure of Gas chamber is blocking
pressure)
No. Test Item Applied Voltage Unit Test
Result
1 断路器、三工位开关隔离侧依 DES1 460kV kV/1min Qualified
次分开,其余非被试断口关
2 合;断口间工频耐压试验 DES2 460kV kV/1min Qualified

1 A 460kV kV/1min Qualified


断路器、三工位开关隔离侧合
闸,所有接地开关分闸;相间
2 B 460kV kV/1min Qualified
及对地工频耐压试验和接地断
口工频耐压试验
3 C 460kV kV/1min Qualified

2. Partial Discharge Measurement Test of Main Circuit (Gas gauge pressure of Gas chamber is blocking pressure)
Technical Test
No. Test Item Measuring Voltage
Requireme Result
nt
1 断路器、三工位开关隔离侧合 DES1 368kV ≤5 2.33
闸,所有接地开关分闸;断口
2 间局部放电测量试验 DES2 368kV ≤5 2.36

1 A 368kV ≤5 2.19
断路器、三工位开关隔离侧依
次分开,其余非被试断口关
2 B 368kV ≤5 2.32
合;相间及对地局部放电试验
和接地断口局部放电测量试验
3 C 368kV ≤5 2.49

IV. Insulation Test of Auxiliary And Control Circuit


No Test Item Test
1 Power frequency withstand voltage test of Auxiliary And control circuit AC 2,000V/1min Result
Qualified
V. Interlocking Test of Control Circuit
No. Test Item Test
1 The interlocking relationship between mechanisms shall comply with the five prevention design Result
Qualified
VI.Gas Tightness Test principles
No. Gas Chamber Name Technical Requirement Unit Test
1 DES1 ≤0.1 %/year Result
Qualified
2 DES2 ≤0.1 %/year Qualified
Circuit Breaker Component Test Report

Report No 2022092601 Rated Voltage 252kV

Rated Power Frequency Withstand


Component Model SSCB01/SSCT33 460kV
Voltage
Partial Discharge Measuring
Bay D01 175kV
Voltage
CB Identification
SHF22064NSCB011 Rated Frequency 50Hz
Number

Mechanism Rated Short-time Withstand


SHF22064NSCT30011 50kA
Identification Number Current

CEME1 Solar 480MWp


User Name Rated Duration of Short Circuit 3s
PV Project

"Owner:CEME 1 SpA;
Substation Name Contractor:Powerchina Ltd. Rated Peak Withstand Current 125kA
Agencia en Chile"
Rated Control Voltage DC110V

Rated Voltage of Motor AC220V

No. Test Item Test Result


1 Inspection of Circuit Breaker Mechanism Case Wiring Correctness √ Qualified
2 Withstand Voltage Test of Auxiliary And Control Circuit 2kV/1min √ Qualified
3 Function Inspection of Auxiliary Contact and Position Indicating Equipment √ Qualified
Mechanical running-in test of Circuit Breaker(the Gas chamber pressure is rated pressure)
No. Operating Condition Number of Test Result
1 The operation of the joint gate with fixed voltage Operations
50 Qualified
Mechanical Operation Test of Circuit Breaker
No. Operating Condition Number of Test Result
1 Manual Mechnical operation and trip free test by operation handle Operations
5 Qualified
2 Conduct opening operation at 65% of rated opening voltage 5 Qualified
3 Conduct closing operation at 85% of rated closing voltage 5 Qualified
4 Conduct opening operation at 110% of rated opening voltage 5 Qualified
5 Conduct closing operation at 110% of rated closing voltage 5 Qualified
6 Conduct continuous operation at 30% of rated operating voltage not operated 3 Qualified
Mechanical Characteristics Test of Circuit Breaker (the Gas chamber pressure is rated pressure)
No. Name Unit
Technical Requirem Measured Value Test Result
1 Contact travel mm 162.0-168.0 A:165.06/B:165.93/C:166.10 Qualified
2 Over-travel ms 43.0-53.0 A:49.48/B:48.18/C:45.98 Qualified
3 Overshoot of closing+ Over-travel ms 0.0-68.0 A:65.30/B:65.06/C:61.16 Qualified
4 Coil 1 average opening speed ms 4.8-6.0 A:5.53/B:5.73/C:5.79 Qualified
5 Coil 1 rated opening time ms 24.0-30.0 A:28.8/B:28.0/C:27.1 Qualified
6 Coil 2 average opening speed mm 4.8-6.0 A:5.47/B:5.78/C:5.80 Qualified
7 Coil 2 rated opening time mm 24.0-30.0 A:28.8/B:28.2/C:27.2 Qualified
8 Average closing speed Ω 3.5-4.3 A:3.88/B:3.95/C:3.94 Qualified
9 Rated closing time s 49.0-65.0 A:60.0/B:59.7/C:59.2 Qualified
10 Closing asynchronism ms 0.0-5.0 0.8 Qualified
11 Coil 1 opening asynchronism ms 0.0-3.0 1.7 Qualified
12 Coil 2 opening asynchronism ms 0.0-3.0 1.6 Qualified
13 Time of closing-opening ms 0.0-60.0 A:51.1/B:51.0/C:52.4 Qualified
Opening and Closing Coil and Energy Storage Motor Test
No. Test Item Technical Requireme Unit Test Result
A:63.2
1 DC resistance of closing coil (20℃) 57.34-64.66 ms B:63.3
C:63.5

A:61.4
2 DC resistance of the first opening coil (20℃) 55.65-62.75 Ω B:61.0
C:62.1

A:61.0
3 DC resistance of the second opening coil (20℃) 55.65-62.75 Ω B:62.3
C:61.1
4 Spring energy storage time of mechanism at 100% of rated voltage of mo 0.0-15.0 Ω 9
Closing travel characteristic curve

Opening travel characteristic curve


Disconnecting Switch (DS) Component Test Report
Report No. 2022092601 Rated Voltage 252 kV
Component Model SSDS01 Rated Power Frequency Withstand
460 kV
Bay No. D01 Voltage
DS Identification SHF22064NSDS011 Partial Discharge Measuring 175 kV
Number
Mechanism SHF22064NSCJ30011 Voltage
Rated Frequency 50 Hz
Identification Number
CEME1 Solar 480MWp
User Name Rated Short-time Withstand Current 50 kA
PV Project

"Owner:CEME 1 SpA;
Substation Name Contractor:Powerchina Ltd. Rated Duration of Short Circuit 1s
Agencia en Chile"
Rated Control Voltage DC 110V Rated Peak Withstand Current 125 kA
Rated Voltage of Motor AC 220V / / /
Test
No. Test Item
Result
1 Inspection of Disconnecting Switch (DS)Mechanism Case Wiring Correctness √ Qualified
2 Withstand Voltage Test of auxiliary and Control Circuit 2kV/1min √ Qualified
3 Function Inspection of Auxiliary Contact and Position Indicating Equipment √ Qualified
Mechanical running-in test of Disconnecting Switch (DS)(the Gas chamber pressure is rated pressure)

Number of Test
No. Operating Condition
Operations Result

1 Close and open at the rated voltage 200 Qualified


Mechanical Operation Test of Disconnecting Switch (DS)

Number of Test
No. Operating Condition
Operations Result

1 Conduct opening and closing operation locally through operating handle 5 Qualified
2 Conduct opening and closing operation at 85% of rated opening and closing 10 Qualified
3 Conduct opening and closing operating
operation voltage
at 110% of rated opening and closing 10 Qualified
operating
I. Mechanical Characteristics Test of Disconnecting voltage
Switch (DS)
Technical Measured Value Test
No. Name Unit Requireme Phase A Phase B Phase C Result
1 Disconnecting-side mm 142~nt 148 144.69 Qualified
2 (DS) contact travel
Disconnecting-side mm 45~56 48.46 Qualified
3 (DS) contacting travel
Disconnecting-side ms ≤40 5.0 Qualified
4 opening synchronism
Disconnecting-side ms ≤40 2.5 Qualified
5 closing synchronism
Disconnecting-side ms ≤2000 513.2 516.5 518.2 Qualified
6 (DS) opening time
Disconnecting-side ms ≤2000 760.3 760.8 762.8 Qualified
(DS) closing time
Motor Current Test
Test
No. Test Item Unit
Result
1 Closing persistent motor current of disconnecting switch (DS) 3.35 A
2 Opening persistent motor current of disconnecting switch (DS) 3.48 A
Closing travel characteristic curve

Opening travel characteristic curve


Disconnecting Switch (DS) Component Test Report
Report No. 2022092601 Rated Voltage 252 kV
Component Model SSDS01 Rated Power Frequency
460 kV
Bay No. D01 Withstand Voltage
DS Identification SHF22064NSDS012 Partial Discharge Measuring 175 kV
Number
Mechanism SHF22064NSCJ30012 Voltage
Rated Frequency 50 Hz
Identification Number
CEME1 Solar 480MWp Rated Short-time Withstand
User Name 50 kA
PV Project Current

"Owner:CEME 1 SpA;
Substation Name Contractor:Powerchina Ltd. Rated Duration of Short Circuit 1s
Agencia en Chile"
Rated Control Voltage DC 110V Rated Peak Withstand Current 125 kA
Rated Voltage of Motor AC 220V / / /
Test
No. Test Item
Result
1 Inspection of Disconnecting Switch (DS)Mechanism Case Wiring Correctness √ Qualified
2 Withstand Voltage Test of auxiliary and Control Circuit 2kV/1min √ Qualified
3 Function Inspection of Auxiliary Contact and Position Indicating Equipment √ Qualified
Mechanical running-in test of Disconnecting Switch (DS)(the Gas chamber pressure is rated pressure)
Number
of Test
No. Operating Condition
Operation Result
s
1 Close and open at the rated voltage 200 Qualified
Mechanical Operation Test of Disconnecting Switch (DS)
Number
of Test
No. Operating Condition
Operation Result
s
1 Conduct opening and closing operation locally through operating handle 5 Qualified
2 Conduct opening and closing operation at 85% of rated opening and closing 10 Qualified
3 Conduct opening and closing operating
operation voltage
at 110% of rated opening and closing 10 Qualified
operating
I. Mechanical Characteristics Test of Disconnecting voltage
Switch (DS)
Technical Measured Value Test
No. Name Unit Requireme Phase A Phase B Phase C Result
1 Disconnecting-side mm 142~nt 148 144.51 Qualified
2 (DS) contact travel
Disconnecting-side mm 45~56 47.59 Qualified
3 (DS) contacting travel
Disconnecting-side ms ≤40 3.6 Qualified
4 opening synchronism
Disconnecting-side ms ≤40 5.5 Qualified
5 closing synchronism
Disconnecting-side ms ≤2000 521.3 517.7 520.5 Qualified
6 (DS) opening time
Disconnecting-side ms ≤2000 766.5 771.2 772.0 Qualified
(DS) closing time
Motor Current Test
Test
No. Test Item Unit
Result
1 Closing persistent motor current of disconnecting switch (DS) 3.65 A
2 Opening persistent motor current of disconnecting switch (DS) 3.44 A
Closing travel characteristic curve

Opening travel characteristic curve


Current Transformer Test Report
Report No. 2022092601 Rated Voltage 252 kV

SHF22064NSTA011
Rated Power Frequency Withstand
Identification Number SHF22064NSTA012 460 kV
Voltage
SHF22064NSTA013

Bay Model BAY(D01) Partial Discharge Measuring Voltage 175 kV

Bay No. D01 Rated Frequency 50 Hz

Project No. SHF22064NS Rated Short-time Withstand Current 50 kA

CEME1 Solar 480MWp PV


User Name Rated Duration of Short Circuit 3s
Project

"Owner:CEME 1 SpA;
Substation Name Contractor:Powerchina Ltd. Rated Peak Withstand Current 125 kA
Agencia en Chile"

Primary current of current


Ambient Temperature 25℃ 1600/2000 A
transformer

Secondary current of current


Relative Humidity 35% RH 1A
transformer

/ / Rated Power Factor 0.8

/ / Rated Load 5/15 VA


Current Transformer Test Report
Report No. 2022092601 Rated Voltage 252 kV

SHF22064NSTA014
Rated Power Frequency Withstand
Identification Number SHF22064NSTA015 460 kV
Voltage
SHF22064NSTA016

Bay Model BAY(D01) Partial Discharge Measuring Voltage 175 kV

Bay No. D01 Rated Frequency 50 Hz

Project No. SHF22064NS Rated Short-time Withstand Current 50 kA

CEME1 Solar 480MWp PV


User Name Rated Duration of Short Circuit 3s
Project

"Owner:CEME 1 SpA;
Substation Name Contractor:Powerchina Ltd. Rated Peak Withstand Current 125 kA
Agencia en Chile"

Primary current of current


Ambient Temperature 25℃ 1600/2000 A
transformer

Secondary current of current


Relative Humidity 35% RH 1A
transformer

/ / Rated Power Factor 0.8

/ / Rated Load 5/15 VA


Bay F01 Test Report
F01
Report No. 2022092602 Rated Voltage 252kV
Rated Power Frequency
Bay No D02 460kV
Withstand Voltage
Project No. SHF22064NS Partial Discharge Measuring 175kV
Voltage
CEME1 Solar 480MWp
User Name Rated Frequency 50Hz
PV Project

"Owner:CEME 1 SpA;
Rated Short-time Withstand
Substation Name Contractor:Powerchina Ltd. 50kA
Current
Agencia en Chile"
Rated Gas Gauge Pressure (20℃)0.62MPa Rated Duration of Short Circuit 3s
Alarm Gas Gauge Pressure (20℃)0.58MPa Rated Peak Withstand Current 125kA
I. Appearance Inspection
No Inspection Item Result
Nameplate and sign are free from corrosion, characters and symbols are clear, and nameplate
1 Qualified
position should be apparent

2 Earthing identification is clear and in correct position. Qualified

The appearance is in good condition and free from defects such as color difference, damage,
3 Qualified
scratch, rust and paint falling off.
LCP control cabinet door and circuit breaker mechanism case door can be opened and closed
4 Qualified
flexibly, and the case is not deformed.

5 Electrical control circuit wiring is neat and beautiful.Check the wire cross section area Qualified

6 Check the wire conductor type and insulation (stranded copper, flexible copper) Qualified

7 Check the wire color and (------) label Qualified

8 No more than one control wire at each terminal lug Qualified

Ambient Relative
II. Resistance Measurement of Main Circuit 21℃ 48 %RH
Temperature Humidity
Measured
No. Measure Point Phase Requirement(μΩ)
Value(μΩ)
1 R 27.2-54.4 47.21
2 A1-A2 S 27.2-54.4 47.88
3 T 27.2-54.4 47.73
Ambient Relative
III.Dielectric Test of the main circuit 21℃ 48 %RH
Temperature Humidity
1. Power Frequency Withstand Voltage Test of Main Circuit (Gas gauge pressure of Gas chamber is blocking
pressure)
No. Test Item Applied Voltage Unit Test Result

1 DES1 460kV kV/1min Qualified


断路器、三工位开关隔离侧依次分
2 开,其余非被试断口关合;断口间 DES2 460kV kV/1min Qualified
工频耐压试验
3 DS 460kV kV/1min Qualified

1 A 460kV kV/1min Qualified


断路器、三工位开关隔离侧合闸,
所有接地开关分闸;相间及对地工
2 B 460kV kV/1min Qualified
频耐压试验和接地断口工频耐压试

3 C 460kV kV/1min Qualified

2. Partial Discharge Measurement Test of Main Circuit (Gas gauge pressure of Gas chamber is blocking pressure)
Technical
No. Test Item Measuring Voltage Test Result
Requireme
nt
1 DES1 175kV ≤5 2.08
断路器、三工位开关隔离侧合闸,
2 所有接地开关分闸;断口间局部放 DES2 175kV ≤5 2.08
电测量试验
3 DS 175kV ≤5 2.08

1 A 175kV ≤5 2.14
断路器、三工位开关隔离侧依次分
开,其余非被试断口关合;相间及
2 B 175kV ≤5 2.26
对地局部放电试验和接地断口局部
放电测量试验
3 C 175kV ≤5 2.24
IV. Insulation Test of Auxiliary And Control Circuit
No Test Item Test Result
1 Power frequency withstand voltage test of Auxiliary And control circuit AC 2,000V/1min Qualified
V. Interlocking Test of Control Circuit
No. Test Item Test Result
1 Q0cannot be closed during the action of Q1 mechanism; Qualified
2 Q0cannot be closed during the action of Q2 mechanism; Qualified
3 When Q0 is closed, Q1、Q2 cannot be closed or open; Qualified
4 When Q1 is closed, Q51 cannot be closed or open; Qualified
5 When Q51 is closed, Q1 cannot be closed or open; Qualified
VI.Gas Tightness Test
No. Gas Chamber Name Technical Unit Test Result
1 CB Requirement
≤0.1 %/year Qualified
2 DES1 ≤0.1 %/year Qualified
3 DES2 ≤0.1 %/year Qualified
Circuit Breaker Component Test Report

Report No 2022092602 Rated Voltage 252kV

Rated Power Frequency


Component Model SSCB01/SSCT33 460kV
Withstand Voltage
Partial Discharge Measuring
Bay D02 175kV
Voltage
CB Identification
SHF22064NSCB021 Rated Frequency 50Hz
Number

Mechanism Rated Short-time Withstand


SHF22064NSCT30021 50kA
Identification Number Current

CEME1 Solar 480MWp


User Name Rated Duration of Short Circuit 3s
PV Project

"Owner:CEME 1 SpA;
Substation Name Contractor:Powerchina Ltd. Rated Peak Withstand Current 125kA
Agencia en Chile"

Rated Control Voltage DC110V

Rated Voltage of Motor AC220V

No. Test Item Test Result


1 Inspection of Circuit Breaker Mechanism Case Wiring Correctness √ Qualified
2 Withstand Voltage Test of Auxiliary And Control Circuit 2kV/1min √ Qualified
3 Function Inspection of Auxiliary Contact and Position Indicating Equipment √ Qualified
Mechanical running-in test of Circuit Breaker(the Gas chamber pressure is rated pressure)
No. Operating Condition Number of Test Result
1 The operation of the joint gate with fixed voltage Operations
50 Qualified
Mechanical Operation Test of Circuit Breaker
No. Operating Condition Number of Test Result
1 Manual Mechnical operation and trip free test by operation handle Operations
5 Qualified
2 Conduct opening operation at 65% of rated opening voltage 5 Qualified
3 Conduct closing operation at 85% of rated closing voltage 5 Qualified
4 Conduct opening operation at 110% of rated opening voltage 5 Qualified
5 Conduct closing operation at 110% of rated closing voltage 5 Qualified
6 Conduct continuous operation at 30% of rated operating voltage not operated 3 Qualified
Mechanical Characteristics Test of Circuit Breaker (the Gas chamber pressure is rated pressure)
No. Name Unit
Technical Requirem Measured Value Test Result
1 Contact travel mm 162.0-168.0 A:163.10/B:165.70/C:165.87 Qualified
2 Over-travel ms 43.0-53.0 A:50.12/B:46.95/C:44.08 Qualified
3 Overshoot of closing+ Over-travel ms 0.0-68.0 A:66.54/B:61.80/C:59.50 Qualified
4 Coil 1 average opening speed ms 4.8-6.0 A:5.25/B:5.58/C:5.49 Qualified
5 Coil 1 rated opening time ms 24.0-30.0 A:28.2/B:27.8/C:28.6 Qualified
6 Coil 2 average opening speed mm 4.8-6.0 A:5.34/B:5.53/C:5.53 Qualified
7 Coil 2 rated opening time mm 24.0-30.0 A:28.4/B:27.8/C:28.5 Qualified
8 Average closing speed Ω 3.5-4.3 A:3.89/B:3.95/C:3.87 Qualified
9 Rated closing time s 49.0-65.0 A:59.1/B:59.7/C:61.1 Qualified
10 Closing asynchronism ms 0.0-5.0 2.00 Qualified
11 Coil 1 opening asynchronism ms 0.0-3.0 0.80 Qualified
12 Coil 2 opening asynchronism ms 0.0-3.0 0.70 Qualified
13 Time of closing-opening ms 0.0-60.0 A:52.2/B:48.4/C:50.4 Qualified
Opening and Closing Coil and Energy Storage Motor Test
No. Test Item Technical Requirem Unit Test Result

A:63.2 B:61.9
1 DC resistance of closing coil (20℃) 57.34-64.66 ms
C:62.5

A:61.7 B:61.5
2 DC resistance of the first opening coil (20℃) 55.65-62.75 Ω
C:61.1

A:61.9 B:61.3
3 DC resistance of the second opening coil (20℃) 55.65-62.75 Ω
C:61.3

4 Spring energy storage time of mechanism at 100% of rated voltage of mo 0.0-15.0 Ω 9


Closing travel characteristic curve

Opening travel characteristic curve


Three-position Disconnecting and Earthing Switch
Report No. 2022092602 Rated Voltage 252 kV
Component Model SSDES01 Rated Power Frequency Withstand
460 kV
Bay D02 Voltage
DES Identification SHF22064NSDES021 Partial Discharge Measuring 175 kV
Number
Mechanism SHF22064NSCJ30021 Voltage
Rated Frequency 50 Hz
Identification
CEME1 Solar 480MWp
User Name Rated Short-time Withstand Current 50 kA
PV Project
"Owner:CEME 1 SpA;
Substation Name Contractor:Powerchina Ltd. Rated Duration of Short Circuit 1s
Agencia en Chile"
Rated Control DC110V Rated Peak Withstand Current 125 kA
Voltage
Rated Voltage of AC220V / / /
Motor Test
No. Test Item
Result
1 Inspection of Three-position Disconnecting and Earthing Switch (DES) √ Qualified
2 MechanismVoltage
Withstand Case Wiring
Test ofCorrectness
auxiliary and Control Circuit 2kV/1min √ Qualified
3 Function Inspection of Auxiliary Contact and Position Indicating Equipment √ Qualified
Mechanical running-in test of Three-position Disconnecting and Earthing Switch(the Gas chamber pressure is rated
pressure)
Number of Test
No. Operating Condition
Operations Result

1 Close and open at the rated voltage 200 Qualified


Mechanical Operation Test of Three-position Disconnecting and Earthing Switch (DES)

Number of Test
No. Operating Condition
Operations Result

1 Conduct opening and closing operation locally through operating handle 5 Qualified
2 Conduct opening and closing operation at 85% of rated opening and closing 10 Qualified
3 Conduct opening and closing operating
operation voltage
at 110% of rated opening and closing 10 Qualified
operating
Mechanical Characteristics Test of Three-position voltage
Disconnecting and Earthing Switch (DES)
Technical Measured Value Test
No. Name Unit Requireme Phase A Phase B Phase C Result
1 Disconnecting-side mm nt 148
142~ 144.20 Qualified
2 (DS) contact travel
Disconnecting-side mm 30~40 36.89 Qualified
3 (DS) contacting
Disconnecting-side ms ≤40 11.2 Qualified
4 opening
Disconnecting-side ms ≤40 0.4 Qualified
5 closing synchronism
Disconnecting-side ms ≤2000 492.5 498.5 503.7 Qualified
6 (DS) opening time
Disconnecting-side ms ≤2000 893.1 893.5 893.4 Qualified
7 (DS) closing time
Earthing-side (ES) mm 142~148 145.96 Qualified
8 contact travel
Earthing-side (ES) mm 32~42 38.05 Qualified
9 contacting travel
Earthing-side ms ≤40 8.5 Qualified
10 opening
Earthing-side ms ≤40 15.1 Qualified
11 closing synchronism
Earthing-side (ES) ms ≤2000 501.6 493.1 501.0 Qualified
12 opening time
Earthing-side (ES) ms ≤ 2000 837.1 852.2 847.4 Qualified
closing
Motor Current Test time
Test
No. Test Item Unit
Result
1 Closing persistent motor current of disconnecting switch (DS) 3.94 A
2 Opening persistent motor current of disconnecting switch (DS) 4.34 A
3 Closing persistent motor current of earthing switch (ES) 4.17 A
4 Opening persistent motor current of earthing switch (ES) 4.34 A
Closing travel characteristic curve

Opening travel characteristic curv


Disconnecting Switch (DS) Component Test Report
Report No. 2022092602 Rated Voltage 252 kV
Component Model SSDS01 Rated Power Frequency Withstand
460 kV
Bay No. D02 Voltage
DS Identification SHF22064NSDS021 Partial Discharge Measuring 175 kV
Number
Mechanism SHF22064NSCJ30021 Voltage
Rated Frequency 50 Hz
Identification Number
CEME1 Solar 480MWp
User Name Rated Short-time Withstand Current 50 kA
PV Project

"Owner:CEME 1 SpA;
Substation Name Contractor:Powerchina Ltd. Rated Duration of Short Circuit 1s
Agencia en Chile"
Rated Control Voltage DC 110V Rated Peak Withstand Current 125 kA
Rated Voltage of Motor AC 220V / / /
Test
No. Test Item
Result
1 Inspection of Disconnecting Switch (DS)Mechanism Case Wiring Correctness √ Qualified
2 Withstand Voltage Test of auxiliary and Control Circuit 2kV/1min √ Qualified
3 Function Inspection of Auxiliary Contact and Position Indicating Equipment √ Qualified
Mechanical running-in test of Disconnecting Switch (DS)(the Gas chamber pressure is rated pressure)

Number of Test
No. Operating Condition
Operations Result

1 Close and open at the rated voltage 200 Qualified


Mechanical Operation Test of Disconnecting Switch (DS)

Number of Test
No. Operating Condition
Operations Result

1 Conduct opening and closing operation locally through operating handle 5 Qualified
2 Conduct opening and closing operation at 85% of rated opening and closing 10 Qualified
3 Conduct opening and closing operating
operation voltage
at 110% of rated opening and closing 10 Qualified
operating
I. Mechanical Characteristics Test of Disconnecting voltage
Switch (DS)
Technical Measured Value Test
No. Name Unit Requireme Phase A Phase B Phase C Result
1 Disconnecting-side mm nt 148
142~ 144.49 Qualified
2 (DS) contact travel
Disconnecting-side mm 45~56 48.15 Qualified
3 (DS) contacting travel
Disconnecting-side ms ≤40 1.2 Qualified
4 opening synchronism
Disconnecting-side ms ≤40 5.8 Qualified
5 closing synchronism
Disconnecting-side ms ≤ 2000 518.5 518.6 519.7 Qualified
6 (DS) opening time
Disconnecting-side ms ≤ 2000 773.6 778.6 779.4 Qualified
(DS)
Motor Current Test closing time
Test
No. Test Item Unit
Result
1 Closing persistent motor current of disconnecting switch (DS) 3.38 A
2 Opening persistent motor current of disconnecting switch (DS) 3.33 A
Closing travel characteristic curve

Opening travel characteristic curve


Current Transformer Test Report
Report No. 2022092602 Rated Voltage 252 kV

SHF22064NSTA021
Rated Power Frequency Withstand
Identification Number SHF22064NSTA022 460 kV
Voltage
SHF22064NSTA023

Bay Model BAY(D02) Partial Discharge Measuring Voltage 175 kV

Bay No. D02 Rated Frequency 50 Hz

Project No. SHF22064NS Rated Short-time Withstand Current 50 kA

CEME1 Solar 480MWp PV


User Name Rated Duration of Short Circuit 3s
Project

"Owner:CEME 1 SpA;
Substation Name Contractor:Powerchina Ltd. Rated Peak Withstand Current 125 kA
Agencia en Chile"

Primary current of current


Ambient Temperature 25℃ 1600/2000 A
transformer

Secondary current of current


Relative Humidity 35% RH 1A
transformer

/ / Rated Power Factor 0.8

/ / Rated Load 5/15 VA


Current Transformer Test Report
Report No. 2022092602 Rated Voltage 252 kV

SHF22064NSTA024
Rated Power Frequency Withstand
Identification Number SHF22064NSTA025 460 kV
Voltage
SHF22064NSTA026

Bay Model BAY(D02) Partial Discharge Measuring Voltage 175 kV

Bay No. D02 Rated Frequency 50 Hz

Project No. SHF22064NS Rated Short-time Withstand Current 50 kA

CEME1 Solar 480MWp PV


User Name Rated Duration of Short Circuit 3s
Project

"Owner:CEME 1 SpA;
Substation Name Contractor:Powerchina Ltd. Rated Peak Withstand Current 125 kA
Agencia en Chile"

Primary current of current


Ambient Temperature 25℃ 1600/2000 A
transformer

Secondary current of current


Relative Humidity 35% RH 1A
transformer

/ / Rated Power Factor 0.8

/ / Rated Load 5/15 VA


Bay F01 Test Report
F01
Report No. 2022092603 Rated Voltage 252kV
Bay No D03 Rated Power Frequency Withstand Voltage 460kV
Project No. SHF22064NS Partial Discharge Measuring Voltage 175kV

CEME1 Solar 480MWp


User Name Rated Frequency 50Hz
PV Project

"Owner:CEME 1 SpA;
Contractor:Powerchina
Substation Name Rated Short-time Withstand Current 50kA
Ltd.
Agencia en Chile"

Rated Gas Gauge Pressure (20℃)0.62MPa Rated Duration of Short Circuit 3s


Alarm Gas Gauge Pressure (20℃)0.58MPa Rated Peak Withstand Current 125kA
I. Appearance Inspection
No Inspection Item Result
Nameplate and sign are free from corrosion, characters and symbols are clear, and nameplate
1 Qualified
position should be apparent

2 Earthing identification is clear and in correct position. Qualified

The appearance is in good condition and free from defects such as color difference, damage, scratch,
3 Qualified
rust and paint falling off.

LCP control cabinet door and circuit breaker mechanism case door can be opened and closed
4 Qualified
flexibly, and the case is not deformed.

5 Electrical control circuit wiring is neat and beautiful.Check the wire cross section area Qualified

6 Check the wire conductor type and insulation (stranded copper, flexible copper) Qualified

7 Check the wire color and (------) label Qualified

8 No more than one control wire at each terminal lug Qualified

Ambient Relative
II. Resistance Measurement of Main Circuit 21℃ 48 %RH
Temperature Humidity
Measured
No. Measure Point Phase Requirement(μΩ)
Value(μΩ)
1 R 27.2-54.4 48.38
2 A1-A2 S 27.2-54.4 49.21
3 T 27.2-54.4 48.44
Ambient Relative
III.Dielectric Test of the main circuit 21℃ 48% RH
Temperature Humidity
1. Power Frequency Withstand Voltage Test of Main Circuit (Gas gauge pressure of Gas chamber is blocking
pressure)
No. Test Item Applied Voltage Unit Test Result
断路器、三工位开关隔离侧依次分
1 CB 460kV kV/1min Qualified
开,其余非被试断口关合;断口间
工频耐压试验
1 A 460kV kV/1min Qualified
断路器、三工位开关隔离侧合闸,
所有接地开关分闸;相间及对地工
2 B 460kV kV/1min Qualified
频耐压试验和接地断口工频耐压试

3 C 460kV kV/1min Qualified

2. Partial Discharge Measurement Test of Main Circuit (Gas gauge pressure of Gas chamber is blocking pressure)
Technical
No. Test Item Measuring Voltage Test Result
Requiremen
断路器、三工位开关隔离侧合闸, t
1 CB 175kV ≤5 2.25
所有接地开关分闸;断口间局部放
1 A 175kV ≤5 2.19
断路器、三工位开关隔离侧依次分
开,其余非被试断口关合;相间及
2 B 175kV ≤5 2.32
对地局部放电试验和接地断口局部
放电测量试验
3 C 175kV ≤5 2.49

IV. Insulation Test of Auxiliary And Control Circuit


No Test Item Test Result
1 Power frequency withstand voltage test of Auxiliary And control circuit AC 2,000V/1min Qualified
V. Interlocking Test of Control Circuit
No. Test Item Test Result
1 Q0cannot be closed during the action of Q1 mechanism; Qualified
2 Q0cannot be closed during the action of Q2 mechanism; Qualified
3 When Q0 is closed, Q1、Q2 cannot be closed or open; Qualified
VI.Gas Tightness Test
No. Gas Chamber Name Technical Requirement Unit Test Result
1 CB ≤0.1 %/year Qualified
2 DES1 ≤0.1 %/year Qualified
3 DES2 ≤0.1 %/year Qualified
Bay F01 Test Report
F01
Report No. 2022092603 Rated Voltage 252kV
Rated Power Frequency
Bay No D03 460kV
Withstand Voltage
Project No. SHF22064NS Partial Discharge 175kV
Measuring Voltage
CEME1 Solar 480MWp
User Name Rated Frequency 50Hz
PV Project

"Owner:CEME 1 SpA;
Contractor:Powerchina Rated Short-time
Substation Name 50kA
Ltd. Withstand Current
Agencia en Chile"

Rated Gas Gauge Pressure (20℃) 0.62MPa Rated Duration of Short 3s


Alarm Gas Gauge Pressure (20℃) 0.58MPa Circuit 125kA
Rated Peak Withstand
I. Appearance Inspection Current
No Inspection Item Result
Nameplate and sign are free from corrosion, characters and symbols are clear, and nameplate position
1 Qualified
should be apparent

2 Earthing identification is clear and in correct position. Qualified

The appearance is in good condition and free from defects such as color difference, damage, scratch,
3 Qualified
rust and paint falling off.
LCP control cabinet door and circuit breaker mechanism case door can be opened and closed flexibly,
4 Qualified
and the case is not deformed.

5 Electrical control circuit wiring is neat and beautiful.Check the wire cross section area Qualified

6 Check the wire conductor type and insulation (stranded copper, flexible copper) Qualified

7 Check the wire color and (------) label Qualified

8 No more than one control wire at each terminal lug Qualified

Ambient
II. Resistance Measurement of Main Circuit 21℃ 48 %RH
Temperat Relative
Measured
No. Measure Point Phase Requirement(μΩ)
Value(μ
1 R 7.1-17.1 Ω)11.24
2 A1-A2 S 7.1-17.1 10.88
3 T 7.1-17.1 10.94
Ambient
III.Dielectric Test of the main circuit 21℃ 48% RH
Temperat Relative
1. Power Frequency Withstand Voltage Test of Main Circuit (Gas gauge pressure of Gas chamber is blocking
pressure)
No. Test Item Applied Voltage Unit Test Result

1 断路器、三工位开关隔离侧依次分 DES1 460kV kV/1min Qualified


开,其余非被试断口关合;断口间工
2 频耐压试验 DES2 460kV kV/1min Qualified

1 A 460kV kV/1min Qualified


断路器、三工位开关隔离侧合闸,所
2 有接地开关分闸;相间及对地工频耐 B 460kV kV/1min Qualified
压试验和接地断口工频耐压试验
3 C 460kV kV/1min Qualified

2. Partial Discharge Measurement Test of Main Circuit (Gas gauge pressure of Gas chamber is blocking pressure)
Measuring
No. Test Item Test Result
Voltage Technic
al
1 断路器、三工位开关隔离侧合闸,所 DES1 175kV ≤5 2.08
有接地开关分闸;断口间局部放电测
2 量试验 DES2 175kV ≤5 2.23

1 A 175kV ≤5 2.14
断路器、三工位开关隔离侧依次分
开,其余非被试断口关合;相间及对
2 B 175kV ≤5 2.26
地局部放电试验和接地断口局部放电
测量试验
3 C 175kV ≤5 2.24

IV. Insulation Test of Auxiliary And Control Circuit


No Test Item Test Result
1 Power frequency withstand voltage test of Auxiliary And control circuit AC 2,000V/1min Qualified
V. Interlocking Test of Control Circuit
No. Test Item Test Result
1 The interlocking relationship between mechanisms shall comply with the five prevention design Qualified
VI.Gas Tightness Test principles
No. Gas Chamber Name Technical Unit Test Result
1 DES1 Requirement
≤0.1 %/year Qualified
2 DES2 ≤0.1 %/year Qualified
Circuit Breaker Component Test Report

Report No 2022092603 Rated Voltage 252kV

Rated Power Frequency Withstand


Component Model SSCB01/SSCT33 460kV
Voltage
Partial Discharge Measuring
Bay D03 175kV
Voltage
CB Identification
SHF22064NSCB031 Rated Frequency 50Hz
Number

Mechanism Rated Short-time Withstand


SHF22064NSCT30031 50kA
Identification Number Current

CEME1 Solar 480MWp


User Name Rated Duration of Short Circuit 3s
PV Project

"Owner:CEME 1 SpA;
User Name Contractor:Powerchina Ltd. Rated Duration of Short Circuit 4s
Agencia en Chile"
Rated Control Voltage DC110V

Rated Voltage of Motor AC220V

No. Test Item Test Result


1 Inspection of Circuit Breaker Mechanism Case Wiring Correctness √ Qualified
2 Withstand Voltage Test of Auxiliary And Control Circuit 2kV/1min √ Qualified
3 Function Inspection of Auxiliary Contact and Position Indicating Equipment √ Qualified
Mechanical running-in test of Circuit Breaker(the Gas chamber pressure is rated pressure)
No. Operating Condition Number of Test Result
1 The operation of the joint gate with fixed voltage Operations
50 Qualified
Mechanical Operation Test of Circuit Breaker
No. Operating Condition Number of Test Result
1 Manual Mechnical operation and trip free test by operation handle Operations
5 Qualified
2 Conduct opening operation at 65% of rated opening voltage 5 Qualified
3 Conduct closing operation at 85% of rated closing voltage 5 Qualified
4 Conduct opening operation at 110% of rated opening voltage 5 Qualified
5 Conduct closing operation at 110% of rated closing voltage 5 Qualified
6 Conduct continuous operation at 30% of rated operating voltage not operated 3 Qualified
Mechanical Characteristics Test of Circuit Breaker (the Gas chamber pressure is rated pressure)
No. Name Unit
Technical Requirem Measured Value Test Result
1 Contact travel mm 162.0-168.0 A:165.43/B:164.53/C:166.83 Qualified
2 Over-travel ms 43.0-53.0 A:48.01/B:44.61/C:48.52 Qualified
3 Overshoot of closing+ Over-travel ms 0.0-68.0 A:64.69/B:59.89/C:63.84 Qualified
4 Coil 1 average opening speed ms 4.8-6.0 A:5.71/B:5.45/C:5.69 Qualified
5 Coil 1 rated opening time ms 24.0-30.0 A:28.6/B:28.2/C:28.6 Qualified
6 Coil 2 average opening speed mm 4.8-6.0 A:5.65/B:5.42/C:5.64 Qualified
7 Coil 2 rated opening time mm 24.0-30.0 A:28.8/B:28.2/C:28.8 Qualified
8 Average closing speed Ω 3.5-4.3 A:3.95/B:3.75/C:3.87 Qualified
9 Rated closing time s 49.0-65.0 A:60.7/B:61.7/C:61.9 Qualified
10 Closing asynchronism ms 0.0-5.0 1.20 Qualified
11 Coil 1 opening asynchronism ms 0.0-3.0 0.40 Qualified
12 Coil 2 opening asynchronism ms 0.0-3.0 0.60 Qualified
13 Time of closing-opening ms 0.0-60.0 A:56.0/B:53.2/C:53.5 Qualified
Opening and Closing Coil and Energy Storage Motor Test
No. Test Item Technical Requireme Unit Test Result
A:62.8
1 DC resistance of closing coil (20℃) 57.34-64.66 ms B:63.2
C:63.8
A:61.7
2 DC resistance of the first opening coil (20℃) 55.65-62.75 Ω B:61.3
C:61.3
A:61.3
3 DC resistance of the second opening coil (20℃) 55.65-62.75 Ω B:61.1
C:61.4
4 Spring energy storage time of mechanism at 100% of rated voltage of mo 0.0-15.0 Ω 9
Closing travel characteristic curve

Opening travel characteristic curve


Disconnecting Switch (DS) Component Test Report
Report No. 2022092603 Rated Voltage 252 kV
Component Model SSDS01 Rated Power Frequency Withstand
460 kV
Bay No. D03 Voltage
DS Identification SHF22064NSDS031 Partial Discharge Measuring 175 kV
Number
Mechanism SHF22064NSCJ30031 Voltage
Rated Frequency 50 Hz
Identification Number
CEME1 Solar 480MWp
User Name Rated Short-time Withstand Current 50 kA
PV Project

"Owner:CEME 1 SpA;
Substation Name Contractor:Powerchina Ltd. Rated Duration of Short Circuit 1s
Agencia en Chile"

Rated Control Voltage DC 110V Rated Peak Withstand Current 125 kA


Rated Voltage of AC 220V / / /
Motor Test
No. Test Item
Result
1 Inspection of Disconnecting Switch (DS)Mechanism Case Wiring Correctness √ Qualified
2 Withstand Voltage Test of auxiliary and Control Circuit 2kV/1min √ Qualified
3 Function Inspection of Auxiliary Contact and Position Indicating Equipment √ Qualified
Mechanical running-in test of Disconnecting Switch (DS)(the Gas chamber pressure is rated pressure)

Number of Test
No. Operating Condition
Operations Result

1 Close and open at the rated voltage 200 Qualified


Mechanical Operation Test of Disconnecting Switch (DS)

Number of Test
No. Operating Condition
Operations Result

1 Conduct opening and closing operation locally through operating handle 5 Qualified
2 Conduct opening and closing operation at 85% of rated opening and closing 10 Qualified
3 Conduct opening and closing operating
operation voltage
at 110% of rated opening and closing 10 Qualified
operating
I. Mechanical Characteristics Test of Disconnecting voltage
Switch (DS)
Technical Measured Value Test
No. Name Unit Requireme Phase A Phase B Phase C Result
1 Disconnecting-side mm 142~nt 148 144.57 Qualified
2 (DS) contact travel
Disconnecting-side mm 45~56 46.60 Qualified
3 (DS) contacting travel
Disconnecting-side ms ≤40 1.2 Qualified
4 opening synchronism
Disconnecting-side ms ≤40 8.2 Qualified
5 closing synchronism
Disconnecting-side ms ≤2000 505.3 506.5 506.5 Qualified
6 (DS) opening time
Disconnecting-side ms ≤2000 747.7 750.5 755.9 Qualified
(DS) closing time
Motor Current Test
Test
No. Test Item Unit
Result
1 Closing persistent motor current of disconnecting switch (DS) 3.71 A
2 Opening persistent motor current of disconnecting switch (DS) 3.44 A
Closing travel characteristic curve

Opening travel characteristic curve


Disconnecting Switch (DS) Component Test Report
Report No. 2022092603 Rated Voltage 252 kV
Component Model SSDS01 Rated Power Frequency Withstand
460 kV
Bay No. D03 Voltage
DS Identification SHF22064NSDS032 Partial Discharge Measuring 175 kV
Number
Mechanism SHF22064NSCJ30032 Voltage
Rated Frequency 50 Hz
Identification Number
CEME1 Solar 480MWp
User Name Rated Short-time Withstand Current 50 kA
PV Project

"Owner:CEME 1 SpA;
Substation Name Contractor:Powerchina Ltd. Rated Duration of Short Circuit 1s
Agencia en Chile"
Rated Control Voltage DC 110V Rated Peak Withstand Current 125 kA
Rated Voltage of Motor AC 220V / / /
Test
No. Test Item
Result
1 Inspection of Disconnecting Switch (DS)Mechanism Case Wiring Correctness √ Qualified
2 Withstand Voltage Test of auxiliary and Control Circuit 2kV/1min √ Qualified
3 Function Inspection of Auxiliary Contact and Position Indicating Equipment √ Qualified
Mechanical running-in test of Disconnecting Switch (DS)(the Gas chamber pressure is rated pressure)

Number of Test
No. Operating Condition
Operations Result

1 Close and open at the rated voltage 200 Qualified


Mechanical Operation Test of Disconnecting Switch (DS)

Number of Test
No. Operating Condition
Operations Result

1 Conduct opening and closing operation locally through operating handle 5 Qualified
2 Conduct opening and closing operation at 85% of rated opening and closing 10 Qualified
3 Conduct opening and closing operating
operation voltage
at 110% of rated opening and closing 10 Qualified
operating
I. Mechanical Characteristics Test of Disconnecting voltage
Switch (DS)
Technical Measured Value Test
No. Name Unit Requireme Phase A Phase B Phase C Result
1 Disconnecting-side mm 142~nt 148 144.03 Qualified
2 (DS) contact travel
Disconnecting-side mm 45~56 46.60 Qualified
3 (DS) contacting travel
Disconnecting-side ms ≤40 6.3 Qualified
4 opening synchronism
Disconnecting-side ms ≤40 5.0 Qualified
5 closing synchronism
Disconnecting-side ms ≤2000 468.5 474.8 474.1 Qualified
6 (DS) opening time
Disconnecting-side ms ≤2000 758.1 753.1 757.0 Qualified
(DS) closing time
Motor Current Test
Test
No. Test Item Unit
Result
1 Closing persistent motor current of disconnecting switch (DS) 3.69 A
2 Opening persistent motor current of disconnecting switch (DS) 3.64 A
Closing travel characteristic curve

Opening travel characteristic curve


Current Transformer Test Report
Report No. 2022092603 Rated Voltage 252 kV

SHF22064NSTA031
Rated Power Frequency Withstand
Identification Number SHF22064NSTA032 460 kV
Voltage
SHF22064NSTA033

Bay Model BAY(D03) Partial Discharge Measuring Voltage 175 kV

Bay No. D03 Rated Frequency 50 Hz

Project No. SHF22064NS Rated Short-time Withstand Current 50 kA

CEME1 Solar 480MWp PV


User Name Rated Duration of Short Circuit 3s
Project

"Owner:CEME 1 SpA;
Substation Name Contractor:Powerchina Ltd. Rated Peak Withstand Current 125 kA
Agencia en Chile"

Primary current of current


Ambient Temperature 25℃ 1600/2000 A
transformer

Secondary current of current


Relative Humidity 35% RH 1A
transformer

/ / Rated Power Factor 0.8

/ / Rated Load 5/15 VA


Current Transformer Test Report
Report No. 2022092603 Rated Voltage 252 kV

SHF22064NSTA034
Rated Power Frequency Withstand
Identification Number SHF22064NSTA035 460 kV
Voltage
SHF22064NSTA036

Bay Model BAY(D03) Partial Discharge Measuring Voltage 175 kV

Bay No. D03 Rated Frequency 50 Hz

Project No. SHF22064NS Rated Short-time Withstand Current 50 kA

CEME1 Solar 480MWp PV


User Name Rated Duration of Short Circuit 3s
Project

"Owner:CEME 1 SpA;
Substation Name Contractor:Powerchina Ltd. Rated Peak Withstand Current 125 kA
Agencia en Chile"

Primary current of current


Ambient Temperature 25℃ 1600/2000 A
transformer

Secondary current of current


Relative Humidity 35% RH 1A
transformer

/ / Rated Power Factor 0.8

/ / Rated Load 5/15 VA


Bay F01 Test Report
F01
Report No. 2022092604 Rated Voltage 252kV
Bay No D04 Rated Power Frequency Withstand Voltage 460kV
Project No. SHF22064NS Partial Discharge Measuring Voltage 175kV

CEME1 Solar 480MWp


User Name Rated Frequency 50Hz
PV Project

"Owner:CEME 1 SpA;
Substation Name Contractor :Powerchina Rated Short-time Withstand Current 50kA
Ltd. Agencia en Chile"

Rated Gas Gauge Pressure (20℃)0.62MPa Rated Duration of Short Circuit 3s


Alarm Gas Gauge Pressure (20℃)0.58MPa Rated Peak Withstand Current 125kA
I. Appearance Inspection
No Inspection Item Result
Nameplate and sign are free from corrosion, characters and symbols are clear, and nameplate
1 Qualified
position should be apparent

2 Earthing identification is clear and in correct position. Qualified

The appearance is in good condition and free from defects such as color difference, damage,
3 Qualified
scratch, rust and paint falling off.
LCP control cabinet door and circuit breaker mechanism case door can be opened and closed
4 Qualified
flexibly, and the case is not deformed.

5 Electrical control circuit wiring is neat and beautiful.Check the wire cross section area Qualified

6 Check the wire conductor type and insulation (stranded copper, flexible copper) Qualified

7 Check the wire color and (------) label Qualified

8 No more than one control wire at each terminal lug Qualified

Ambient Relative
II. Resistance Measurement of Main Circuit 21℃ 48% RH
Temperatur Humidity
Measured
No. Measure Point Phase Requirement(μΩ)
Value (μ
1 R 27.2-54.4 Ω)
47.21
2 A1-A2 S 27.2-54.4 48.46
3 T 27.2-54.4 48.75
Ambient Relative
III.Dielectric Test of the main circuit 21℃ 48%RH
Temperatur Humidity
1. Power Frequency Withstand Voltage Test of Main Circuit (Gas gauge pressure of Gas chamber is blocking
pressure)
No. Test Item Applied Voltage Unit Test Result
断路器、三工位开关隔离侧依次分
1 CB 460kV kV/1min Qualified
开,其余非被试断口关合 ;断口间
工频耐压试验
1 A 460kV kV/1min Qualified
断路器、三工位开关隔离侧合闸 ,
所有接地开关分闸;相间及对地工
2 B 460kV kV/1min Qualified
频耐压试验和接地断口工频耐压试

3 C 460kV kV/1min Qualified

2. Partial Discharge Measurement Test of Main Circuit (Gas gauge pressure of Gas chamber is blocking
pressure)
Technical
No. Test Item Measuring Voltage Test Result
Requirement
断路器、三工位开关隔离侧合闸 ,
1 CB 175kV ≤5 2.05
所有接地开关分闸;断口间局部放
1 A 175kV ≤5 2.14
断路器、三工位开关隔离侧依次分
开,其余非被试断口关合 ;相间及
2 B 175kV ≤5 2.35
对地局部放电试验和接地断口局部
放电测量试验
3 C 175kV ≤5 2.22

IV. Insulation Test of Auxiliary And Control Circuit


No Test Item Test Result
1 Power frequency withstand voltage test of Auxiliary And control circuit AC 2,000V/1min Qualified
V. Interlocking Test of Control Circuit
No. Test Item Test Result
1 Q0cannot be closed during the action of Q1 mechanism; Qualified
2 Q0cannot be closed during the action of Q2 mechanism; Qualified
3 When Q0 is closed, Q1、Q2 cannot be closed or open; Qualified
VI.Gas Tightness Test
No. Gas Chamber Name Technical Requirement Unit Test Result
1 CB ≤0.1 %/year Qualified
2 DES1 ≤0.1 %/year Qualified
3 DES2 ≤0.1 %/year Qualified
Bay F01 Test Report
F01
Report No. 2022092604 Rated Voltage 252kV
Bay No D04 Rated Power Frequency Withstand Voltage 460kV
Project No. SHF22064NS Partial Discharge Measuring Voltage 175kV

CEME1 Solar 480MWp


User Name Rated Frequency 50Hz
PV Project

"Owner:CEME 1 SpA;
Substation Name Contractor:Powerchina Rated Short-time Withstand Current 50kA
Ltd. Agencia en Chile"

Rated Gas Gauge Pressure (20℃) 0.62MPa Rated Duration of Short Circuit 3s
Alarm Gas Gauge Pressure (20℃) 0.58MPa Rated Peak Withstand Current 125kA
I. Appearance Inspection
No Inspection Item Result
Nameplate and sign are free from corrosion, characters and symbols are clear, and nameplate position
1 Qualified
should be apparent

2 Earthing identification is clear and in correct position. Qualified

The appearance is in good condition and free from defects such as color difference, damage, scratch,
3 Qualified
rust and paint falling off.
LCP control cabinet door and circuit breaker mechanism case door can be opened and closed flexibly,
4 Qualified
and the case is not deformed.

5 Electrical control circuit wiring is neat and beautiful.Check the wire cross section area Qualified

6 Check the wire conductor type and insulation (stranded copper, flexible copper) Qualified

7 Check the wire color and (------) label Qualified

8 No more than one control wire at each terminal lug Qualified

Ambient Relative
II. Resistance Measurement of Main Circuit 21℃ 48 %RH
Temperatur Humidity
Measured
No. Measure Point Phase Requirement(μΩ)
Value(μΩ)
1 R 12.8-22.8 14.21
2 A1-A2 S 12.8-22.8 14.56
3 T 12.8-22.8 14.01
Ambient Relative
III.Dielectric Test of the main circuit 21℃ 48% RH
Temperatur Humidity
1. Power Frequency Withstand Voltage Test of Main Circuit (Gas gauge pressure of Gas chamber is blocking
pressure)
No. Test Item Applied Voltage Unit Test Result
断路器、三工位开关隔离侧依次分
1 DES1 460kV kV/1min Qualified
开,其余非被试断口关合;断口间工
频耐压试验
1 A 460kV kV/1min Qualified
断路器、三工位开关隔离侧合闸,所
2 有接地开关分闸;相间及对地工频耐 B 460kV kV/1min Qualified
压试验和接地断口工频耐压试验
3 C 460kV kV/1min Qualified

2. Partial Discharge Measurement Test of Main Circuit (Gas gauge pressure of Gas chamber is blocking pressure)
Technical
No. Test Item Measuring Voltage Test Result
Requirement
断路器、三工位开关隔离侧合闸,所
1 DES1 175kV ≤5 2.13
有接地开关分闸;断口间局部放电测
1 A 175kV ≤5 2.14
断路器、三工位开关隔离侧依次分
开,其余非被试断口关合;相间及对
2 B 175kV ≤5 2.35
地局部放电试验和接地断口局部放电
测量试验
3 C 175kV ≤5 2.22
IV. Insulation Test of Auxiliary And Control Circuit
No Test Item Test Result
1 Power frequency withstand voltage test of Auxiliary And control circuit AC 2,000V/1min Qualified
V. Interlocking Test of Control Circuit
No. Test Item Test Result
1 The interlocking relationship between mechanisms shall comply with the five prevention design Qualified
VI.Gas Tightness Test principles
No. Gas Chamber Name Technical Requirement Unit Test Result
1 DES2 ≤0.1 %/year Qualified
Circuit Breaker Component Test Report

Report No 2022092604 Rated Voltage 252kV

Rated Power Frequency


Component Model SSCB01/SSCT33 460kV
Withstand Voltage
Partial Discharge Measuring
Bay D04 175kV
Voltage
CB Identification
SHF22064NSCB041 Rated Frequency 50Hz
Number

Mechanism Rated Short-time Withstand


SHF22064NSCT30041 50kA
Identification Number Current

User Name CEME1 Solar 480MWp PV Project Rated Duration of Short Circuit 3s

"Owner:CEME 1 SpA;
Substation Name Contractor:Powerchina Ltd. Rated Peak Withstand Current 125kA
Agencia en Chile"

Rated Control
DC110V
Voltage
Rated Voltage of
AC220V
Motor
No. Test Item Test Result
1 Inspection of Circuit Breaker Mechanism Case Wiring Correctness √ Qualified
2 Withstand Voltage Test of Auxiliary And Control Circuit 2kV/1min √ Qualified
3 Function Inspection of Auxiliary Contact and Position Indicating Equipment √ Qualified
Mechanical running-in test of Circuit Breaker(the Gas chamber pressure is rated pressure)
No. Operating Condition Number of Test Result
1 The operation of the joint gate with fixed voltage Operations
50 Qualified
Mechanical Operation Test of Circuit Breaker
No. Operating Condition Number of Test Result
1 Manual Mechnical operation and trip free test by operation handle Operations
5 Qualified
2 Conduct opening operation at 65% of rated opening voltage 5 Qualified
3 Conduct closing operation at 85% of rated closing voltage 5 Qualified
4 Conduct opening operation at 110% of rated opening voltage 5 Qualified
5 Conduct closing operation at 110% of rated closing voltage 5 Qualified
6 Conduct continuous operation at 30% of rated operating voltage not operated 3 Qualified
Mechanical Characteristics Test of Circuit Breaker (the Gas chamber pressure is rated pressure)
No. Name Unit Technical Requirem Measured Value Test Result
1 Contact travel mm 162.0-168.0 A:165.73/B:165.13/C:166.30 Qualified
2 Over-travel ms 43.0-53.0 A:49.12/B:46.75/C:48.11 Qualified
3 Overshoot of closing+ Over-travel ms 0.0-68.0 A:65.44/B:63.90/C:64.73 Qualified
4 Coil 1 average opening speed ms 4.8-6.0 A:5.50/B:5.49/C:5.54 Qualified
5 Coil 1 rated opening time ms 24.0-30.0 A:29.0/B:28.8/C:28.5 Qualified
6 Coil 2 average opening speed mm 4.8-6.0 A:5.50/B:5.38/C:5.47 Qualified
7 Coil 2 rated opening time mm 24.0-30.0 A:29.1/B:28.9/C:28.9 Qualified
8 Average closing speed Ω 3.5-4.3 A:3.96/B:3.82/C:3.79 Qualified
9 Rated closing time s 49.0-65.0 A:60.4/B:60.3/C:60.1 Qualified
10 Closing asynchronism ms 0.0-5.0 0.3 Qualified
11 Coil 1 opening asynchronism ms 0.0-3.0 0.5 Qualified
12 Coil 2 opening asynchronism ms 0.0-3.0 0.2 Qualified
13 Time of closing-opening ms 0.0-60.0 A:52.9/B:53.3/C:52.6 Qualified
Opening and Closing Coil and Energy Storage Motor Test
No. Test Item Technical Requirem Unit Test Result
A:63.5
1 DC resistance of closing coil (20℃) 57.34-64.66 ms B:63.7
C:62.6

A:61.6
2 DC resistance of the first opening coil (20℃) 55.65-62.75 Ω B:61.8
C:61.5

A:61.4
3 DC resistance of the second opening coil (20℃) 55.65-62.75 Ω B:61.0
C:61.0
4 Spring energy storage time of mechanism at 100% of rated voltage of mo 0.0-15.0 Ω 9
Closing travel characteristic curve

Opening travel characteristic curve


Disconnecting Switch (DS) Component Test Report
Report No. 2022092604 Rated Voltage 252 kV
Component Model SSDS01 Rated Power Frequency Withstand
460 kV
Bay No. D04 Voltage
DS Identification SHF22064NSDS041 Partial Discharge Measuring 175 kV
Number
Mechanism SHF22064NSCJ30041 Voltage
Rated Frequency 50 Hz
Identification Number
User Name CEME1 Solar 480MWp PV Project Rated Short-time Withstand Current 50 kA
"Owner:CEME 1 SpA;
Substation Name Contractor:Powerchina Ltd. Rated Duration of Short Circuit 1s
Agencia en Chile"
Rated Control DC 110V Rated Peak Withstand Current 125 kA
Voltage
Rated Voltage of AC 220V / / /
Motor Test
No. Test Item
Result
1 Inspection of Disconnecting Switch (DS)Mechanism Case Wiring Correctness √ Qualified
2 Withstand Voltage Test of auxiliary and Control Circuit 2kV/1min √ Qualified
3 Function Inspection of Auxiliary Contact and Position Indicating Equipment √ Qualified
Mechanical running-in test of Disconnecting Switch (DS)(the Gas chamber pressure is rated pressure)

Number of Test
No. Operating Condition
Operations Result

1 Close and open at the rated voltage 200 Qualified


Mechanical Operation Test of Disconnecting Switch (DS)

Number of Test
No. Operating Condition
Operations Result

1 Conduct opening and closing operation locally through operating handle 5 Qualified
2 Conduct opening and closing operation at 85% of rated opening and closing 10 Qualified
3 Conduct opening and closing operating
operation voltage
at 110% of rated opening and closing 10 Qualified
operating
I. Mechanical Characteristics Test of Disconnecting voltage
Switch (DS)
Technical Measured Value Test
No. Name Unit Requireme Phase A Phase B Phase C Result
1 Disconnecting-side mm nt 148
142~ 144.92 Qualified
2 (DS) contact travel
Disconnecting-side mm 45~56 47.28 Qualified
3 (DS) contacting travel
Disconnecting-side ms ≤40 3.0 Qualified
4 opening synchronism
Disconnecting-side ms ≤40 4.0 Qualified
5 closing synchronism
Disconnecting-side ms ≤2000 470.9 473.9 473.7 Qualified
6 (DS) opening time
Disconnecting-side ms ≤2000 755.7 754.6 758.6 Qualified
(DS) closing time
Motor Current Test
Test
No. Test Item Unit
Result
1 Closing persistent motor current of disconnecting switch (DS) 3.72 A
2 Opening persistent motor current of disconnecting switch (DS) 3.49 A
Closing travel characteristic curve

Opening travel characteristic curve


Disconnecting Switch (DS) Component Test Report
Report No. 2022092604 Rated Voltage 252 kV
Component Model SSDS01 Rated Power Frequency Withstand
460 kV
Bay No. D04 Voltage
DS Identification SHF22064NSDS042 Partial Discharge Measuring 175 kV
Number
Mechanism SHF22064NSCJ30042 Voltage
Rated Frequency 50 Hz
Identification
User Name CEME1 Solar 480MWp PV Project Rated Short-time Withstand Current 50 kA

"Owner:CEME 1 SpA;
Substation Name Contractor:Powerchina Ltd. Rated Duration of Short Circuit 1s
Agencia en Chile"
Rated Control DC 110V Rated Peak Withstand Current 125 kA
Voltage
Rated Voltage of AC 220V / / /
Motor Test
No. Test Item
Result
1 Inspection of Disconnecting Switch (DS)Mechanism Case Wiring Correctness √ Qualified
2 Withstand Voltage Test of auxiliary and Control Circuit 2kV/1min √ Qualified
3 Function Inspection of Auxiliary Contact and Position Indicating Equipment √ Qualified
Mechanical running-in test of Disconnecting Switch (DS)(the Gas chamber pressure is rated pressure)

Number of Test
No. Operating Condition
Operations Result

1 Close and open at the rated voltage 200 Qualified


Mechanical Operation Test of Disconnecting Switch (DS)

Number of Test
No. Operating Condition
Operations Result

1 Conduct opening and closing operation locally through operating handle 5 Qualified
2 Conduct opening and closing operation at 85% of rated opening and closing 10 Qualified
3 Conduct opening and closing operating
operation voltage
at 110% of rated opening and closing 10 Qualified
operating
I. Mechanical Characteristics Test of Disconnecting voltage
Switch (DS)
Technical Measured Value Test
No. Name Unit Requireme Phase A Phase B Phase C Result
1 Disconnecting- mm 142~nt 148 144.51 Qualified
2 side (DS) contact
Disconnecting- mm 45~56 48.44 Qualified
3 side (DS)
Disconnecting- ms ≤40 7.3 Qualified
4 side opening
Disconnecting- ms ≤40 0.9 Qualified
5 side closing
Disconnecting- ms ≤2000 496.3 501.1 503.6 Qualified
6 side (DS) opening
Disconnecting- ms ≤ 2000 748.1 748.4 749.0 Qualified
side
Motor Current Test (DS) closing
Test
No. Test Item Unit
Result
1 Closing persistent motor current of disconnecting switch (DS) 3.43 A
2 Opening persistent motor current of disconnecting switch (DS) 3.33 A
Closing travel characteristic curve

Opening travel characteristic curve


Current Transformer Test Report
Report No. 2022092604 Rated Voltage 252 kV

SHF22064NSTA041
Rated Power Frequency Withstand
Identification Number SHF22064NSTA042 460 kV
Voltage
SHF22064NSTA043

Bay Model BAY(D04) Partial Discharge Measuring Voltage 175 kV

Bay No. D04 Rated Frequency 50 Hz

Project No. SHF22064NS Rated Short-time Withstand Current 50 kA

CEME1 Solar 480MWp PV


User Name Rated Duration of Short Circuit 3s
Project

"Owner:CEME 1 SpA;
Substation Name Contractor:Powerchina Ltd. Rated Peak Withstand Current 125 kA
Agencia en Chile"

Primary current of current


Ambient Temperature 25℃ 1600/2000 A
transformer

Secondary current of current


Relative Humidity 35% RH 1A
transformer

/ / Rated Power Factor 0.8

/ / Rated Load 5/15 VA


Current Transformer Test Report
Report No. 2022092604 Rated Voltage 252 kV

SHF22064NSTA044
Rated Power Frequency Withstand
Identification Number SHF22064NSTA045 460 kV
Voltage
SHF22064NSTA046

Bay Model BAY(D04) Partial Discharge Measuring Voltage 175 kV

Bay No. D04 Rated Frequency 50 Hz

Project No. SHF22064NS Rated Short-time Withstand Current 50 kA

CEME1 Solar 480MWp PV


User Name Rated Duration of Short Circuit 3s
Project

"Owner:CEME 1 SpA;
Substation Name Contractor:Powerchina Ltd. Rated Peak Withstand Current 125 kA
Agencia en Chile"

Primary current of current


Ambient Temperature 25℃ 1600/2000 A
transformer

Secondary current of current


Relative Humidity 35% RH 1A
transformer

/ / Rated Power Factor 0.8

/ / Rated Load 5/15 VA