You are on page 1of 3

Project: HIEX AVLABARI

Calculation Title: Staircase Pressurization Reference


Project No.: Calculation Sheet No.: Rev. 1
Calculated By: Date: Check By: Date: Pressure Difference
17/12/2020 10 Pa
STAIRCASE PRESSURIZATION Velocity through an open door
Staircase Reference Staircase 01 1 m/s
Pressurization Fan Reference SPF-01 Number of open doors
Location Block A 2
1. Pressurization as per NFPA Relief Pressure
Number of Landings
2. No pressurised lobbies associated with staircase landings 7
3. Fan closed by motorized smoke damper.
4. (1m/s) through open doors at one successive floor and the discharge floor. The stair pressure differential
maintained at 10Pa.
Type of Stair Shaft
Floors served
Number of Landing 7
Pressurization Air Volume
Air Leakage Through Landing Doors
Landing Door width (m) 1.00
Landing Door height (m) 2.10
Open door area (m2) 2.10
Crack Length (m) 8.90
Quantity of Landing Doors (Nos.) 7
Leakage area(m2) per single leaf door 0.02
Total Leakage Area (m2)
Total Leakage Area (m2) 0.14
Calculated supply air volume to achieve pressurization to 10 Pa
Formula QE=0.827XAExPE1/2
Leakage Rate (m3/s) 0.37
10 Pa min pressure ventilation rate at 2 open door (m3/s) 10.98
(1m/s) air velocity through the opened door (2 doors open)
4.20
Total airflow for staircase pressurization (m3/s) 11.35
Area of Pressure Relief (m²) 13.23

Calculated Fan Capacity = 40860 m3/h


Selected Fan Capacity = 41000 m3/h
Project: HIEX AVLABARI
Calculation Title: Staircase Pressurization Reference
Project No.: Calculation Sheet No.: Rev. 1
Calculated By: Date: Check By: Date: Pressure Difference
17/12/2020 10 Pa
STAIRCASE PRESSURIZATION Velocity through an open door
Staircase Reference Staircase 02 1 m/s
Pressurization Fan Reference SPF-02 Number of open doors
Location Block B 2
1. Pressurization as per NFPA Relief Pressure
Number of Landings
2. No pressurised lobbies associated with staircase landings 6
3. Fan closed by motorized smoke damper.
4. (1m/s) through open doors at one successive floor and the discharge floor. The stair pressure differential
maintained at 10Pa.
Type of Stair Shaft
Floors served
Number of Landing 6
Pressurization Air Volume
Air Leakage Through Landing Doors
Landing Door width (m) 1.00
Landing Door height (m) 2.10
Open door area (m2) 2.10
Crack Length (m) 6.60
Quantity of Landing Doors (Nos.) 6
Leakage area(m2) per single leaf door 0.02
Total Leakage Area (m2)
Total Leakage Area (m2) 0.12
Calculated supply air volume to achieve pressurization to 10 Pa
Formula QE=0.827XAExPE1/2
Leakage Rate (m3/s) 0.31
10 Pa min pressure ventilation rate at 2 open door (m3/s) 10.98
(1m/s) air velocity through the opened door (2 doors
open) 4.20
Total airflow for staircase pressurization (m3/s) 11.30
Area of Pressure Relief (m²) 13.23

Calculated Fan Capacity = 40672 m3/h


Selected Fan Capacity = 41000 m3/h
Project: HIEX AVLABARI
Calculation Title: Staircase Pressurization Reference
Project No.: Calculation Sheet No.: Rev. 1
Calculated By: Date: Check By: Date: Pressure Difference
17/12/2020 10 Pa
STAIRCASE PRESSURIZATION Velocity through an open door
Staircase Reference Staircase 03 1 m/s
Pressurization Fan Reference SPF-03 Number of open doors
Location Block B 2
1. Pressurization as per NFPA Relief Pressure
Number of Landings
2. No pressurised lobbies associated with staircase landings 7
3. Fan closed by motorized smoke damper.
4. (1m/s) through open doors at one successive floor and the discharge floor. The stair pressure differential
maintained at 10Pa.
Type of Stair Shaft
Floors served
Number of Landing 7
Pressurization Air Volume
Air Leakage Through Landing Doors
Landing Door width (m) 1.00
Landing Door height (m) 2.10
Open door area (m2) 2.10
Crack Length (m) 7.40
Quantity of Landing Doors (Nos.) 7
Leakage area(m2) per double leaf door 0.02
Total Leakage Area (m2)
Total Leakage Area (m2) 0.14
Calculated supply air volume to achieve pressurization to 10 Pa
Formula QE=0.827XAExPE1/2
Leakage Rate (m3/s) 0.37
10 Pa min pressure ventilation rate at 2 open door (m3/s) 10.98
(1m/s) air velocity through the opened door (2 doors
open) 4.20
Total airflow for staircase pressurization (m3/s) 11.35
Area of Pressure Relief (m²) 13.23

Calculated Fan Capacity = 40860 m3/h


Selected Fan Capacity = 41000 m3/h