1. Features:

 DC 12V;

 The communication interface supports RS485 serial port;

 Communication baud rate: 9600(Default);

 Communication control: use the provided instructions to control;

 Relay channels: 2 ;

 With relay status indicator and power indicator;

 With Momentary function, you can use the command to operate the relay to open

for a period of time and automatically close.

2. product function

 2-Channels relay control;

 RS485 serial port input control;

 MODBUS instruction supports 03 06 16 function codes

 The maximum delay under MODBUS instruction is 255 seconds;

 In MODBUS command mode, it can support up to 64 devices to be used in

parallel;
 Support the manual control of the upper computer software (the upper computer

software is not provided);

 Can read status on/off of the relay;

 "open" "close" "Momentary" "Self-locking" "Interlock" "Delay" 6 Commands;

 Support self-locking mode (reverse the relay status, if the relay NO is engaged

with COM, send this command to disconnect NO from COM, and vice versa);

 Support jog mode (pull in relay NO and COM, then disconnect after 0.6S);

 Support interlock mode (pull in the corresponding relay with others

disconnected);

 Support delay mode (pull in relay NO with COM, and disconnected after nS), n

can be set;

 Support to control single relay on/off operation

 Support simultaneous control of multiple relay on/off operations;

 The default baud rate is 9600BPS, and the baud rate can be selected to 1200

2400 4800 19200 BPS by changing the baud rate command .

3. The main parameters

Relay 10A/250VAC,10A/125AC,10A/30VDC,10A28VDC

specifications
Data interface RS485

Rated voltage DC 12V

Power 1 channel red LED indication

indication

Output 2-Channels red LED indication

indication

size 60*35*19mm

weight 32g

Baud rate 9600, No parity, 8 data bits, 1 stop bit

4. interface description

1. Interface distribution of the whole machine:

2. Relay wiring:
3. RS485 connection:

4. Power wiring:
5. Instructions for instruction

Example: Connect to PC via USB to RS485 module, open the serial port
debugging assistant, select the corresponding port, select the baud rate
9600, no parity, 8 data bits, 1 stop bit, as shown in the figure.
If you want to open all the relays, send the command 01 06 00 70 00
FF C8 51, 01 is the device address, 06 is the function code, 0070 is the
register address, 00FF means to open all the relays, the effect of sending
the command is as follows.
The serial port returns 01 06 00 70 00 FF C8 51. The return is the
same as sending, indicating that it is received correctly, and all relays
have been turned on. At this time, it can be observed that all the relay
indicators on the main board are on and the relays are all turned on.

For more instructions, please refer to the "N428E02 2-channel RS485


relay command" file.