SMA2 Spring Mount (Deflection : 50mm)

■Features
As an open-spring mount, it is usually used together with the inertia
base. It is easy to install and has a static deflection that is visible to
the naked eye, which facilitates inspection after installation. It has the
same components as SMA type, but has a static deflection of 50 mm,
and therefore, it is used when operation of equipment needs to be
quieter, such as when air conditioners and fans and are installed on
the ground level within the building. The top cap is made of SS400
steel plate, and it can be welded to the bottom structure, when it is
made of steel, like the H-bean, without making an extra hole for
installation. There is a CR-type pad attached on the base plate for a
slip-resistant and high-frequency isolation.

■Usage
◆F or standing pipes
◆F or high-efficient vibration control of ventilators (ground level)
◆F or high-efficient vibration control of air conditioning units
(ground level)
◆F or high-efficient vibration control of equipment that needs to be
kept quiet

■Specification
No. Name of Components Material Standard
1 Non Skid Pad CR KS M 6617
2 Lower Housing SS400 KS D 3503
SUP9 KS B 2402
3 Coil Spring
HSW3 KS B 2403
4 Upper Spring Cap SS400 KS D 3503
5 Level Bolt SS400 KS B 1002
6 Cap Screw SS400 KS B 1002

■Dimension & Selection Guide


Spring Dimension(mm)
Type Capacity Constant Weight Color
(kgf) (kg) A B C D H Level Blot Cap Screw
(kgf/mm)
SMA2-A-100 100 2.0 2.00 Blue
SMA2-A-150 150 3.0 2.00 Brown
SMA2-A-200 200 4.0 2.04 White
SMA2-A-300 300 6.0 2.18 Orange
SMA2-A-400 400 8.0 2.46 Pink 150 123 106 14 172 M20x90 M12x25
SMA2-A-500 500 10.0 2.78 Green
SMA2-A-600 600 12.0 3.34 Blue
SMA2-A-750 750 15.0 3.08 Black
SMA2-A-1000 1000 20.0 3.38 Yellow
SMA2-B-1200 1200 24.0 7.60 Red
SMA2-B-1500 1500 30.0 7.62 Black
SMA2-B-1800 1800 36.0 7.12 Blue 190 170 138 14 254 M20x90 M12x25
SMA2-B-2000 2000 40.0 8.90 Yellow
SMA2-B-2500 2500 50.0 11.6 Brown
SMA2-C-3000 3000 60.0 12.6 White
SMA2-C-3500 3500 70.0 13.4 Black 214 184 162 14 289 M24x110 M12x40
SMA2-C-4000 4000 80.0 13.4 Orange
(NOTE) The mentioned size and scale can be altered to improve the quality performance and capacity of the product without any notice.

72
Pump Performance:According to ISO9906-2012,Grade 2B

Pump Performance Datasheet


Customer Quote number
Customer Reference Pump size LS125-100-381F
Item number Tai Wo CHWP Stages 1
Service Based on curve number 1
Quantity of pumps Data last saved 2023-10-9
Operating Conditions Liquid
Flow 58.88 l/s Liquid type Water
Head(requested) 30 m Additional liquid description
Head(actual) 30 m Solids diameter,max 0 mm
Suction pressure,rated/max Temperature 20 C
NPSH available,rated Ample m Fluid density,rated/max 1000.00 kg/m3
Frequency 50 HZ Viscosity,rated 1.0 cst
Performance Material
Pump speed,rated 1475 rpm Casing Material CI
Impeller diameter,rated 318.4 mm Impeller Material SS
Impeller diameter,maximum 381.0 mm Pressure Data
Impeller diameter,minimum 241.3 mm Flange Rating PN16
Efficiency 75.82 % Maximum working pressure 0.35 MPa
NPSH 5.2 m Maximum allowable working requested 1.60 MPa
- - Maximum allowable suction pressure limit 1.25 MPa
MCSF 28.49 l/s Casing hydrostatic test pressure 2.40 MPa
Head Maximum,rated diameter 35.6 m
Driver&Power Data
Head rise to shut off 85.23 %
Driver sizing specification 200L
Flow,best eff.Point(BEP) 55.83 l/s Margin over specification 1.31
Flow ratio(rated/BEP) 105.47 % Service factor
Head ratio(rated/Max Diameter) 63.15 % Power,hydraulic 17.31 kW
Diameter ratio(ratio/max) 83.56 % Power,rated 22.83 kW
Viscous coefficients(CQ/CH/CE) 1.0/1.0/1.0 Power,maximum 25.93 kW
Selection status Acceptable Min recommended driver 30.00 kW

P(kW)
35

28

21

14

7
0
0 12 24 36 48 60 72 84 96 108 120

H(m) Eff(%)
60 100

54

48 80

42

36 381.00mm 60

30

24 40
318.36mm
18

12 20
241.30mm
6

0 0
0 12 24 36 48 60 72 84 96 108 120

NPSH(m) Q(l/s)
12.5
10.0
7.5
5.0
2.5
0.0
0 12 24 36 48 60 72 84 96 108 120

Printed from Grundfos Selector [V3.0.2019-12-31] Motor Sizing Method:ISO 5199


1/2
Printed from Grundfos Selector [V3.0.2019-12-31]
2/2
Note:

1.The pump may be exposed to forces and moments:


(the pipeline connection is tension-free)
Fx=Fy=Fz=1300N Mx=My=Mz=550Nm
Other forces and torque are inadmissible
2.Pump parameter Weight
Pump:267kg Motor:255kg
Water:/kg Baseplate:72kg
YY X HZ HS HD HE HA CP LM W HM HR HP n
3.Pump rotational inertia:
Without water:.38kgm2 357 357 508 319 319 355 415 622 833 254 824 70 150 4 Pump model LS125-100-381F(CW)
With water:/kgm2 M HL HB d3 HF h Motor series MMG-W(Low voltage)
4.Foundation static load M16x400 920 1300 80 420 12 Motor brand MMG IE3
Pump unit:5.8kN Ds D1 K1 T1 n1 d1 Dd D2 K2 T2 n2 d2 Speed(rpm) 1475
5.Direction of rotation:Clockwise Power(kW) 30
125 279.4 210 35 8 19 100 254 180 32 8 19
(Pump direction of rotation as seen from motor end) Flange rating PN16
6.Packaging:Complete package for motor and pump. Total weight(kg) 594
7.All units are in [mm] unless others are stated.
Disclaimer:Figure only for reference,main dimensions data table will prevail.

2023-10-9
LEGEND ACOUSTICS ENGINEERING LTD.
UNIT 12, 4/F., BLOCK A, WAH TAT IND. CENTRE, 8-10 WAH SING ST., KWAI CHUNG, N.T. Selection Guideline: Selection Criteria
TEL : (852) 2815 0928, 2815 0899 FAX : (852) 2854 0123 As the end suction water pump <30kW and width <6m, the minimum static deflection should be >19mm (By ASHRAE handbook & NSV handbook) Minimum static deflection > 19mm
The requirement of Isolation Efficiency is > 95% E > 95%
By equation E=(1-TR)x100%, Transimssion Rate TR should be < 0.05 TR < 0.05
By equation TR=1/-(1-η2), Frequency Ratio η should be > 4.58 η > 4.58
CLIENT : ATAL By equation η=fd/fn, fn should be < fd/4.58
As given by manufacturer, the lowest fd is 738 RPM. By fn < 738/4.58, fn should be < 161RPM
fn < 161RPM
PROJECT : Tai Wo As given by manufacturer, the highest fd is 1475 RPM. By fn < 1475/4.58, fn should be < 322RPM
Under such circumstance, the 161 RPM is used as the criteria for fn
TITLE : Summary Table for Vibration Isolator - Water Pump By equation fn=1/2(3.14)Sqrt((9800/ds))*60, static deflection ds should be > 34.5mm to achieve 95% isolation efficiency
Minimum static deflection > 34.5mm
Also required by the specification, minimum 50% deflection should be achieved. Minimum static deflection should be > 12.5mm
DATE : 2024/1/15 (Rev.1) By equation K=W/ds, Spring Constant K should be less than Point Load/34.5 for each point K < (Point Load/34.5)
Total weight is divided into 4 points. Point load = Total Weight/4

Selection Criteria Point Load = Total Load/4 34.5 < ds < 50 Spring > 19mm > Point Load 4 fn < 161 Given fd (by manufacturer) K < (Point Load/34.5) η > 4.58 TR < 0.05 E > 95%
Isolation Isolation
Lowest Highest Frequency Frequency
No. of Total load (Inertia Block + Deflection of Rate Rate No. of Natural Spring constant Spring TR TR Efficiency Efficiency
Point Selection of Operating Operating Ratio η Ratio η
Item Designation Water Point Pump + Motor + Fittings + Point Load Deflection Capacity Spring frequency K criteria constant K (Lowest (Highest % %
Load (kg) Spring model Frequency Frequency (Lowest (Highest
Pump Water) (kg) (mm) (mm) (kg) Isolator fn (RPM) (kg/mm) (kg/mm) fd) fd) (Lowest (Highest
fd (RPM) fd (RPM) fd) fd)
fd) fd)
1 CHWP-4 1 4 4460 1115 46.5 SMA2-B-1200 50 1200 4 139 738 1475 < 32.3 24.0 5.32 10.64 0.037 0.009 96.33 99.11

Vibration Isolation Efficiency E = (1-TR) x 100%


Transmission Rate TR = 1/-(1- η2)
Frequency Ratio η = fd/fn
Natural Frequency fn = 1/2(3.14)Sqrt((Ks*9800/W))*60
Spring Coefficient Ks = Rate Capcity/Rate Deflection
Weight W = Point Load
Operating Frequency fd

Point Load = Operatuion Weight/No. of Point Load


Deflection of Point Load = Point Load /Rate Capacity * Rate Deflection
No. of Spring Isolator = No. of Equipment * No. of Point Load

You might also like