You are on page 1of 1

IS Entity Calculation

Associated Apparatus Cable 1 Cable 2 Certified Apparatus


Make Typical Make other
Make Pepperl + Fuchs Type Instrument Cable Type Make Rosemount
Model KFD2-ST4-EX2 Dcable 1 5000 m Dcable 2 0 m Model 644H Temp Transmitter
Ccable 1 11 nF/100m Ccable 2 0 nF/100m
Lcable 1 0.8 mH/100m Lcable 2 mH/100m
Certificate Number IECEx BAS 04.0015 Rcable 1 0.014 Ω/100m Rcable 2 Ω/100m Certificate Number BAS 00 ATEX 1033X
Protection ia L/Rcable 1 56 µH/Ω L/Rcable 2 µH/Ω Protection ia
Gas Group IIA Gas Group IIA
60 °CAmb CTot c1 0.550 µF CTot c2 0.00 µF T Rating T4 @ 80 °CAmb
LTot c1 40.00 mH LTot c2 0.00 mH/m
RTot c1 0.70 Ω RTot c3 0.00 Ω
Safety Pararmeters Safety Pararmeters
Uo 25.20 Vdc Ui 30.00 Vdc
Io 93.00 mA Dcable Tot 5000.00 m Ii 200.00 mA
Po 585.00 W Ccable Tot 0.55 µF Pi 1.00 W
Co 2.89 µF Lcable Tot 40.00 mH Ci 0.01 µF
Lo 305.00 mH Rcable Tot 0.70 Ω Li 0.000 mH
L/R 60.00 µH/Ω CTot 0.56 µF
LTot 40.00 mH

RESULTS
U i > Uo PASS
When a Pepperl + Fuchs KFD2-ST4-EX2 is connected to Rosemount 644H Temp
and Ii > Io PASS
and Ci + Ccable < Co PASS
Transmitter , using a maximum of 5000 metres of Typical Instrument Cable cable and 0
and either Li + Lcable < Lo PASS metres of other cable, the circuit is verified as Ex ia IIA T4 @ 80 °CAmb
or L/Rcable < L/R. PASS
TRUE
TRUE
Revision Date Issued Author Issued By Acc By
Drwg Number Number
ISEC0003 1 16/06/2006 SvB SvB

Cable data not supplied.


Typical cable data used as per AS2381.7 cl:A4