A single-line diagram (also known as an SLD or one-
line diagram) is a simplified representation of an electrical system and Grid Station Scheme. Symbols and lines are used to represent the nodes and connections in the system. A single-line diagram is used to visualize the power distribution system to improve planning and troubleshooting, ensure redundancy, and reduce potential outages. High Impedance Differential Protection (87Z) Engr. Irshad Gul Electrical Power System and its Protection Engineer High Impedance Differential Protection (87Z)
As the name signifies, differential protection (87)
works on the principle of difference of current that develops during abnormalities, unbalance governed by or according to KCL. Differential Protection is Unit Protection; its boundaries CTs location defined, type is either low impedance or high impedance. High Impedance Differential Protection (87Z)
In high impedance differential protection (87Z)
high resistance (Rs) is intentionally included for stabilization and security reasons; against current errors and CT saturation. R-stabilizing (Rs) be of CT class on part of thermal rating, robust enough. 87Z can be set more sensitive than 87 low impedance one. CTs Class PX of proper Vk. Protection 87Z is applied to transformer windings, generator winding, Busbars (BB). High Impedance Differential Protection (87Z)
When used for Phase to Ground faults, 87Z is
called Restricted Earth Fault (REF) Protection; used for star winding, auto transformer. It can be applied to delta winding as well. In Y or auto transformer winding, 87Z can be used for inter-phase faults as well, working on circulating current principle; also called High Impedance Circulating Current Differential Protection. High Impedance Differential Protection (87Z) As 87Z is sensitive and high impedance is involved in the differential circuit, high accuracy CTs required like PX class; in order to have minimum Id development during heavy loads and external faults; CT saturation issue something else. Due to high impedance in the differential circuit, high voltage spikes up to 8-10KV are expected in the secondary system during internal fault. Thus proper surge arresting devices are installed; Metrosils; basically Voltage Dependent Resistors (VDR), to avoid insulation breakdown in the wiring & P&C devices. High Impedance Differential Protection (87Z) First setting requirement is current pickup setting that is the initial Id. In transformers the viable setting band is 5-25% of the winding current rating, blind zone be minimum possible. In 87Z BBP current pickup sensitivity not an issue; security is preferred. The Id can be set just above the heaviest circuit load of the zone; purpose is to safeguard against a CT open circuiting but it entails requirement of CT supervision and subsequent CTs shorting arrangement. High Impedance Differential Protection (87Z) CT Supervision setting is of voltage, usually very low say 15-25 volts but well above the voltage impressed on the relay during heavy system loading and current mis-matches. Time delay (TD) usually set 3-5s to initiate alarm and short circuit the CTs. It saves the 87Z system, also taking it out of service but it may not save the CT in trouble, depending upon the CT opening location. All the CTs are identical; no intermediate/matching CTs allowed. High Impedance Differential Protection (87Z) In 87Z the effective pickup is somewhat higher than the relay Id pickup for some current spills will be there in circuits of the scheme parallel to the relay. These spills are due to I-exciting absorbed by CTs of the group, CTs ratio errors and I-Metrosil that is hardly 2-20mA at Vs of the relay. Vs setting not excessive & always well below 0.5Vk of the CTs; a bit speed issue. It is neither set too low to endanger selectivity nor too high to speed down the relay; also causing somewhat decrease in sensitivity due to increase in current spills. High Impedance Differential Protection (87Z) I-Metrosil drastically goes up during in-zone fault, also called internal fault, because the net differential current does not find low impedance path and instantly all CTs undergoing saturation, partial or full. The saturated CT generated voltages are like spikes, and can go up to the tune of 8-10KV in absence of Metrosils. Metrosils are commonly of 450V and 900V classes; very rarely used 1100V class. High Impedance Differential Protection (87Z) 87Z is highly secure protection if properly set. Its operating time has to be less than 25ms if it has to escape adverse effect of CT saturation; otherwise, very likely leading to failure to operate during in-zone severe fault or at least phenomenal delays, offset dc current decay dependent. The delay can be of many cycles and the decay speed is L/R or X/R ratio dependent. Time Delay (intentional) in 87Z not desirable rather detrimental and risky during internal fault; always be instantaneous. High Impedance Differential Protection (87Z) If Rs is not applied; simply low impedance 87, stability issue will be there due to some reasons viz current errors, varying CT distances, during transient through fault situation differential currents more pronounced, leading to spurious tripping. CT saturation issue major and on the top. Low impedance differential protection has to be biased with restraining elements otherwise security issue rather, one can say, no security. High Impedance Differential Protection (87Z) In 87Z protection Rs is applied and thus it is converted to voltage build-up based differential protection, current setting with wide range. In 87Z a viable compromise is made among setting of current, Rs and protection and power system requirement on part of sensitivity and security. For 87Z, proper PX Class CTs required; a matter of high precision. Examples of High Impedance Differential Protection
Example-1: 87Z BBP
• Let’s say the BB has 10 circuits. All the identical CTs are of PX Class, ratio 3000/1, Rct = 10Ω at 20 , Vk=1600 V, Ie=30mA at Vk • CT cable 6 sq mm of copper • Cable length of the farthest bay from BBP location: 300m • Bay CTs secondary wiring leading to the BBP location (RP) can be 4 wire or 6 wire system; opted for the latter one. • CT secondary wiring earthing shall be on one side only, also called single point earthing; its confirmation part of SAT. Examples of High Impedance Differential Protection
• CTs shorted out if earthing on both sides mistakenly done;
rendering protection out. • To be on the safe side, CT winding and cable resistances will be referred to 75 for setting calculation, avoiding chance of trimming down of the safety margin. • For BBP (87Z), highly sensitive current setting is not required; no issue of any blind region. Rather for stability and security purpose high current setting is required, following the highest circuit load say 1000A here. • To avoid setting revisions due to increases in fault levels due to multiple reasons, switchgear breaking capacity say 40KA is taken as maximum fault reference for setting calculations. Examples of High Impedance Differential Protection
• Stabilizing resistor is essentially required due to CT ratio errors
and particularly mismatch developed due to CT saturation during a through fault. • During the worst situation of full saturation, the magnetizing impedance of the CT renders zero and only secondary winding resistance is left behind, in series with 2x300m cable. • During a 40KA through fault if the farthest CT saturates, the voltage developed across the relay shall be worked out with a safety factor of 1.5 or 2.0 here the former one opted for. Examples of High Impedance Differential Protection
Is = 1000/3000= 0.333A (Relay setting)
If = 40KA Primary so If Sec = 40000/3000 = 13.333A Rct at 20 = 10Ω Rct at 75 =10(1+0.00393(75-20)) = 12.1615Ω R cable at 20 = xL/A where Ωmm2/m Length (L) =2x300=600m, A = 6 mm2 R cable at 20 = 0.0175x600/6 = 1.75Ω (actually Cable loop resistance) R cable at 75 = 1.75(1+0.00393(75-20)) = 2.1283Ω Vs (voltage set) = 1.5xIf(Rct + R-cable loop) =1.5x13.333(12.1615+2.1283) = 285.789V Rs (R-stabilizing) = 285.789/0.3333 = 857.453Ω (relay internal resistance hardly 0.1Ω thus negligible) Examples of High Impedance Differential Protection
• At Relay pickup threshold voltage (Vs=285.795V), 0.333A will
flow in the relay circuit and some current spills will be in all the parallel loops viz 10 CTs, and Metrosil (VDR or MOV C900 class; C450 class Metrosil only applicable up to Vs=125V) • Iect total at Vs=10x30x285.789/1600= 53.585 mA • I Metrosil at Vs = 0.52(285.789xsqr2/900)1/.25 = 21.11mA • Thus, effective pickup current will be sum of Is and all the current spills. • I effective= 333.33+53.585+21.11= 408.025 mA • On primary side the effective pickup = 3000x0.408025 = 1224.075A (against 1000A equivalent setting on the relay) Examples of High Impedance Differential Protection
• Note: For stability and security Safety Factor of 1.5 has
been selected but actually it is more than that because fault level will be phenomenally less than 40KA; the switchgear rating. • Metrosil of C900 Class, for in-zone fault of 40KA that is 13.333A secondary differential current will restrict the Vpeak to 2000V thus safe for secondary system. Irms = 0.52(Vrms√2/C)1/β Vpeak = 1.09C(Irms)β Examples of High Impedance Differential Protection
Example-2: 87Z REF Protection of Y Winding
• The power transformer is 132/11KV, Dyn11, 40MVA rated, Impedance 12% at Sb = 40 MVA. All the four CTs are of PX Class, ratio 3000/1, Rct=10Ω at 20 , Vk=800 V, Ie = 30mA at Vk; identical in all respects. • CT cable 6 sq mm of copper • Cable length of the longest one is 200m • CT secondary wiring earthing shall be on one side only, also called single point earthing; its confirmation part of the SATs otherwise protection will be absolutely failed or say out. • CTs shorted out if earthing on both sides mistakenly done. To be on the safe side, CT winding and cable resistances will be referred to 75 for setting calculation, minimizing rather avoiding chance of trimming down of the safety margin. Examples of High Impedance Differential Protection
• Sensitive current setting is required to keep the blind region minimum
in the neutral area. Generally, for the differential current setting the viable setting band is 5-25% of the transformer rating. In the wake of a compromise between sensitivity and security (stability), 10% is selected. • For stability, maximum through fault is the criterion; for safety margin, a factor of 1.5-2.0 further applied, here in example 1.5 selected. • Stabilizing resistor is essentially required due to CT ratio errors and particularly mismatch developed due to CT saturation during a through fault. During the worst situation of full saturation, the magnetizing impedance of the CT renders zero and only secondary winding resistance is left behind, in series with 2x200m cable. Examples of High Impedance Differential Protection
During a maximum through fault if the longest loop CT
saturates, the voltage developed across the relay shall be worked out, also applying a safety factor of 1.5. IFLC: 40000/(√3x11) = 2099.456A I-through fault maximum = 2099.456Ax100/12 = 17,495.4627 10% of IFLC = 209.9456 A Examples of High Impedance Differential Protection
Thus, Is of relay = 209.9456/3000 = 0.06998 say 70 mA
If = 17495.4627A Primary so If Sec = 17495.4627/3000 = 5.8318A Rct at 20 = 10Ω Rct at 75 =10(1+0.00393(75-20)) = 12.1615Ω Resistance (R) at 20 = ρxL/A where ρ is 0.0175Ωmm2/m Length (L) =2x200=400m, A = 6 mm2 R cable loop at 20 = 0.0175x400/6 = 1.1667Ω R cable at 75 = 1.1667(1+0.00393(75-20)) = 1.4189 Ω Vs (voltage set) = 1.5xIf(Rct + R-cable loop) =1.5x5.8318 (12.1615+1.4189) = 118.797V Rs (R-stabilizing) = 118.797/0.070 = 1697.1Ω (relay internal resistance hardly 0.1Ω thus negligible) Examples of High Impedance Differential Protection
At Relay pickup threshold voltage (Vs=118.797V) 0.070A will flow
in the relay circuit and some current spills will be in all the parallel loops viz 4 CTs, and Metrosil (VDR or MOV; C450 class Metrosil applicable up to Vs=125V) Iect total at Vs=4x30x118.797/800= 17.820 mA I Metrosil at Vs = 0.52(118.797xsqr2/450)1/.25 = 10.1mA Thus, effective pickup current will be sum of Is and all the current spills: I effective= 70+17.82+10.1= 97.92 mA On primary side the effective pickup = 3000x0.09792 = 293.76A (against 210A equivalent setting on the relay) Examples of High Impedance Differential Protection
Metrosil of C450 Class, for in-zone fault of 2x17495A that is
2x5.831A secondary differential current will restrict the Vpeak to 1000V thus safe for secondary system; 2 incorporated for two transformers in parallel. Irms = 0.52(Vrms√2/C)1/β Vpeak = 1.09C(Irms)β 31