Professional Documents
Culture Documents
DIFFERENTIAL PROTECTION 87
TEAM NO. 4
MEMBERS:
• SALVADOR GUTIERREZ CRUZ
• RODRIGO GÓMEZ DÍAZ
NOVEMBER 2022
CONTENTS:
INTRODUCTION.
CONSIDERATIONSIN THE IMPLEMENTATION OF
THE PROTECTION 87 BARS.
ADVANTAGES OF DIFFERENTIAL PROTECTION 87 IN
BARS.
TYPES OF PROTECTION
PROTECTION CHARACTERISTIC CURVE 87.
CONCLUSIONS.
BIBLIOGRAPHY.
INTRODUCTION
A bar or bus is an element of the electrical power system, it is the point at which various circuits such as
transmission, generation or loads converge.
The effect of a fault in a bus arrangement results in disturbances of large magnitudes due to the large amounts
of currents that are handled. That is why busbar protection is required to be very high speed, to limit effects
that could harm equipment connected to the busbar and thus maintain the stability of the electrical service.
Under normal system conditions, the power entering a bus is identical to the
power leaving it; a fault within the differential circuit unbalances the system and
thus currents flow in the operating coil of the relay which then results in the
tripping of all breakers associated with that bus.
NOTE: High impedance relays predominate due to better performance.
Most busbar failures involve a grounded phase and are due to various causes such as lightning
strikes or switchgear insulation defects, with the highest proportion of busbar failures resulting
from human error.
The main reason substation bus differential
protection is used is to ensure that it de-
energizes the bus only when necessary,
thus justifying the large extra cost of a high-
speed bus differential relay.
Another problem is that when the secondary circuit of the CT is open, no current
flows to the differential relay, so the absence of the contribution of any of the
phases can cause the undesirable operation of the relay by causing an imbalance of
the input currents. and out.
types of protection:
Voltage differential protection
Where:
IR: is the current in the relay and in the linear
couplers.
ZR: is the relay impedance
Bus differential protection with
restriction or variable percentage
relays
An improvement in selectivity is
provided by relays with a "variable
percentage" characteristic, ensuring that
very high internal fault currents will not
cause sufficient holding to prevent
tripping. This protection equipment has
operating times of the order of 3 to 6
cycles (based on 60 Hertz), however
there are relays that work with shorter
trip times, making them high-speed
equipment. The use of the retention
characteristic, so called for having coils
that retain "false" or external fault
currents, makes the relay insensitive to
the effects of CT error.
High impedance bus differential protection.
The high impedance arrangement tends to force a differential current flowing through the CT
instead of through the relay operating coil, thus avoiding misoperation due to external fault
or overload conditions when the secondary current of all the CT's is not the same, due to
differences in magnetization characteristics. When you have several circuits connected in
parallel on a bus, it is necessary to use connections of a number of current transformer
secondary in parallel
se of common bus for each
phase
In conventional schemes, the
secondary terminals of the CTs
found in each of the phases are
connected to a common bar or
comparison bar so that through it the
outputs of the differential relays of
each phase are connected as shown.
shows in the picture
PROTECTION CHARACTERISTIC CURVE
87 The operating current Iop corresponds to the sum
of the absolute value of the supply currents which
arrive at the bus.