The main electricity consumption of LOT1 includes office area, resident area, indoor &
outdoor lighting. The power of the main electrical equipment is shown in the following table.

Total Final Total


Power
No. Area Equipment Qty. Power KX KT Power
(W)
(W) (W)

1 Laptop 34 65 2210 0.9 0.9 1790.1

Water
2 6 300 1800 0.7 0.7 882
dispenser

Office
3 Printer 2 500 1000 0.8 0.5 400

area
4 Projector 1 200 200 0.5 0.5 50

5 Air conditioner 9 1200 10800 0.9 0.9 8748

6 Network 1 500 500 0.9 0.8 360

7 Thermal kettle 35 1500 52500 0.7 0.5 18375

8 Water heater 30 1500 45000 0.7 0.5 15750

9 Air conditioner 32 1200 38400 0.9 0.9 31104

10 Living Electric cooker 2 600 1200 0.5 0.8 480

11 area Electric grill 2 1300 2600 0.5 0.8 1040

12 Fridge 2 300 600 0.9 0.9 486

13 Kitchen hood 2 200 400 0.5 0.8 160

14 Gas stove 2 4000 8000 0.5 0.8 3200


15 Outdoor 98 50 4900 0.8 0.9 3528
Lighting
16 Indoor 4 500 2000 1 1 2000

Total 172.11KW 88.33KW

Power statistics table of major electrical equipment

Total load calculation:

P=1.05(KXKT×∑P1+KXKT×∑P2+KXKT×∑P3+KXKT×∑P4)

式中:P—Total power supply of equipment requirements (KW)

P1—Rated power of office area (KW)

P2—Rated power of living area (KW)

P3—Indoor lighting capacity (KW)

P4—Outdoor lighting capacity (KW)

KX—Demand factor

KT—Synchronization factor

Total power for electrical equipment in office area: ΣKXKTP1 =12.23KW

Total power for electrical equipment in Living area: ΣKXKTP2 =70.6KW

Total power for outdoor lighting: ΣKXKTP3=3.5KW

Total power for indoor lighting: ΣKXKTP4=2KW

Total power consumption during the peak period is: P=1.05 ×

(12.23+70.6+3.5+2)=92.75KW.