You are on page 1of 29

place picture here

Shakeel Ahmed Batliwale


Senior Products Specialist (Enclosure & Din-Rail Products)

Product Group Distribution Enclosures


place picture here

Product Group Distribution Enclosures


System pro E comfort, plastic consumer units
System pro E control
Gemini
Specifications:
§ IP66
§ 6 dimensions (max 1005x840x360 mm)
§ Thermoplastic material with co-injection
technology
§ In up to 400 A
§ Class of protection: II
§ With blind or transparent (smoky) doors
§ Shock resistance: IK10
§ Standards:
§ IEC 60670, CEI EN 60439-1, IEC 61439-1-2

§ Modular panels for DIN Rail or mounting


plates available
§ Inner door available
§ Color: grey RAL 7035
§ 100% recyclable

© ABB
July 22, 2018 | 3
Produced at ITECS
System pro E control
Gemini
External Dimensions:
Size External dimensions in mm
(H) (W) (D)
1 400 335 210
2 550 460 260
3 700 460 260
4 700 580 260
5 855 585 360
6 1005 840 360

Internal Dimensions & Modules:

© ABB
July 22, 2018 | 4
System pro E comfort, plastic
MISTRAL41W (global range)

Specifications:
§ IP41 Wall
§ Class of protection: II
§ In up to 63 A
§ 2 to 72 DIN modules
§ Shock resistance IK08
§ Available with opaque or transparent (blue
petrol) door or without door
§ In compliance with IEC 60670 and EN61439-3
Standards
§ Thermoplastic, GWT 650°C (Halogen Free)
§ Colors: white RAL 9016

© ABB
July 22, 2018 | 5
Produced at ITECS
System pro E comfort, plastic
MISTRAL41W (global range)

Sizes with Rows (GWT 650 & 750)

Ø 1Row

• 2M, 4M, 8M, 12M & 18M


Ø 2Row

§ 24M & 36M


Ø 3Row

§ 36M & 54M


Ø 4Row

§ 48M & 72M

© ABB
July 22, 2018 | 6
Produced at ITECS
System pro E comfort, plastic
MISTRAL41F (global range)

Specifications:
§ IP41 Flush
§ Class of protection: II
§ In up to 125 A (bigger sizes)
§ 4 to 72 DIN modules
§ Extractable DIN rail frame
§ Shock resistance up to 10 joules (IK09)
§ Available with opaque or transparent (blue
petrol) door
§ In compliance with IEC 60670 and EN61439-3
Standards
§ IMQ mark approval
§ Thermoplastic, GWT 650°C (Halogen Free)
and 850°C (Hollow wall version)
§ Colors: white RAL 9016

© ABB
July 22, 2018 | 7
Produced at ITECS
System pro E comfort, plastic
MISTRAL41F (global range)

Sizes with Rows (GWT 650 & 850)

Ø 1Row

• 4M, 6M, 8M, 12M & 18M


Ø 2Row

§ 24M & 36M


Ø 3Row

§ 36M & 54M


Ø 4Row

§ 48M & 72M

© ABB
July 22, 2018 | 8
Produced at ITECS
System pro E comfort, plastic
MISTRAL65 (global range)

Specifications:
§ IP65 Wall
§ Class of protection: II
§ In up to 125 A (bigger sizes)
§ 4 to 72 DIN modules
§ Extractable DIN rail frame
§ Shock resistance up to 10 joules (IK09)
§ Available with opaque or transparent (blue
petrol) door
§ In compliance with IEC 60670 and EN61439-3
Standards
§ IMQ mark approval
§ Thermoplastic, GWT 650°C (Halogen Free)
and 750°C
§ Colors: grey RAL 7035

© ABB
July 22, 2018 | 9
Produced at ITECS
System pro E comfort, plastic
MISTRAL65 (global range)

Sizes with Rows (GWT 650 & 750)

Ø 1Row

• 4M, 8M, 12M & 18M


Ø 2Row

§ 24M & 36M


Ø 3Row

§ 36M & 54M


Ø 4Row

§ 48M & 72M

© ABB
July 22, 2018 | 10
Produced at ITECS
place picture here

Product Group Distribution Enclosures


System pro E energy, Sub Distribution
Mirage
System pro E energy
Enclosures – Sub-distribution
Wall and Floor-standing cabinets – Mirage
Grounded cabinets
§ IP42 and IP54
§ Rated current (In): 250 A up to 630 A
Available in both
Specifications:
Panel board &
Pan Assembly
§ XT-max: XT1 & XT3 outgoing
§ Formula A1 & A2 outgoing
§ Rated operational voltage 690 V ac
§ Rated short-time withstand current up to 50 kA
§ Outgoing groups 4 up to 16 way, 3 pole only
§ Standards: IEC BS EN 61439-1&2
§ Enclosures and doors are made of cold rolled sheet steel
§ Colour: grey, RAL 7035, powder coated
§ Complete with earth and neutral bars
System pro E energy
Mirage 250

© ABB
July 22, 2018 | 13
Produced at EGARC
System pro E energy
Mirage 250

Mirage – XT I/C & Formula O/G


Incoming XT3-250A, Outgoing A1-125A

Mirage – Formula I/C & O/G


Incoming A2-250A, Outgoing A1-125A

Mirage – XT I/C & O/G


Incoming XT3-250A, Outgoing XT1-160A

© ABB
July 22, 2018 | 14
System pro E energy
Mirage 400

© ABB
July 22, 2018 | 15
System pro E energy
Mirage 400

Mirage – Tmax I/C & Formula O/G


Incoming T5-400A, Outgoing A1-125A
Incoming T5-400A, Outgoing A2-250A
Incoming T5-400A, Mixed outgoing A1-125A; A2-250A

Mirage – Tmax I/C & XT O/G


Incoming T5-400A, Outgoing XT1-160A
Incoming T5-400A, Outgoing XT3-250A
Incoming T5-400A, Mixed outgoing XT1-160A; XT3-250A

© ABB
July 22, 2018 | 16
System pro E energy
Mirage 630

© ABB
July 22, 2018 | 17
System pro E energy
Mirage 630
Mirage – Tmax I/C & Formula O/G
Incoming T5-630A, Outgoing A1-125A
Incoming T5-630A, Outgoing A2-250A
Incoming T5-630A, Mixed outgoing A1-125A; A2-250A

Mirage – Tmax I/C & XT O/G


Incoming T5-630A, Outgoing XT1-160A
Incoming T5-630A, Outgoing XT3-250A
Incoming T5-630A, Mixed outgoing XT1-160A; XT3-250A

© ABB
July 22, 2018 | 18
place picture here

Product Group Distribution Enclosures


System pro E energy, Final Distribution
Minicenter
System pro E energy
Mini Center (local range, Saudi Arabia)

Specifications:
§ Standard :Complying with IEC 439-3, BS EN 61439 -2
§ Busbar Rating :160A and 250 A
§ Operation Voltage :220-440VAC, 50/60Hz
§ Rated Short Circuit :17kA @415V
§ Mounting type :Flush- and Surface mounting
§ Degree of Protection :IP 43, Form2A
§ Enclosure material :Galvanized sheet steel
§ Steel Thickness :Overall body 1mm / Pan assembly 1.5mm
§ Color :RAL 7035, grey
§ Ambient temperature :50/55 deg. C
§ Incoming option : MCB, MCCB, RCCB, Direct connection
§ No. of TP(SP) ways :4(12), 6(18), 8(24), 10(30), 12(36), 16(48),
20(60) & 24(72)
(also Row type available)

© ABB
July 22, 2018 | 20
Types of Mini Center.

Isolator Incomer MCB Incomer


S200
E200

MCCB Incomer
Formula & XT

RCCB Incomer Direct Cable


F200
System pro E control SR Basic
Low voltage small and medium-sized enclosures
for automation and distribution
System Pro E ® control

SR Basic

Technical specifications and features:


• SR Basic is the latest range of multipurpose enclosures
suitable for industrial and commercial applications,
with high degree of protection in accordance to standard.
• Conformity with standard IEC 62208
• Degree of protection IP 65 for single door (IEC 60529)
• Degree of protection IP 54 for double door (IEC 60529)
• Degree of mechanical strength IK 10 (IEC 62262)
System Pro E ® control

SR Basic

Technical specifications and features:


• Fixing method Floor standing / wall mounting
• Color RAL 7035
• Type of material
15/10 Galvanized gland plates
15/10 Sheet Steel for enclosure
20/10 Galvanized mounting plate
• Suitable for residential and commercial applications
System Pro E ® control

SR Basic Range

The range is divided into 30 different dimensions:


H=300mm to 1800mm W=200mm to 1200mm D=150mm to 400mm.

1000 1200 800 600 500 400 300 200

1800
1600
1400
1800 1200
1600 1000
1400 800
1200 700
1000
600
500
400
300

300 400 400 300 200 150


System Pro E ® control

SR Basic

Features:

Internal polyurethane foam


Removable gland gasket, laid using a
plates plates as continuous casting process
standard supplied on
the top and the
bottom Door can be
hinged on the
right or left side

full length stiffener for


door stability

Mounting plate wide angle opening


System Pro E ® control

SR Basic

Features:

Double Door
Internal polyurethane foam
gasket, laid using a
continuous casting process

Full size
Mounting plate full length stiffener for
door stability

Removable gland plates


standard supplied on the
bottom
wide angle opening
SR Basic
Technical information

Details of technical information are


available on technical catalogue
§ Overall dimensions etc.

© ABB Group
July 22, 2018 | Slide 28
© ABB
July 22, 2018 | 29

You might also like