1. Project Informa on
Date 2024-4-4
Project name
Project address
Country China
State
City GUANGZHOU
Client name
Client address
Designed by
Reference
Revision
Al tude(m) 8
Indoor DB temperature in cooling(℃) 26
Indoor WB temperature in cooling(℃) 19
Outdoor DB temperature in cooling(℃) 34.4
Outdoor WB temperature in cooling(℃) 27.4
Indoor DB temperature in hea ng(℃) 21
Indoor WB temperature in hea ng(℃) 14
Outdoor DB temperature in hea ng(℃) 7.6
Outdoor WB temperature in hea ng(℃) 6.9
1
Power supply cable Select based on MCA of each unit According to the actual system design
Communica on cable 0.75mm2 3-core shielded According to the actual system design
Notes:
1. MCA: Minimum Circuit Amps. MCA is used to select wire size.The value in above table is for one unit.
2. MFA: Maximum Fuse Amps. MFA is used to select overcurrent circuit breakers and residual-current circuit breakers.The value in above
table is for one unit.
4. System2
4.1 BOM List (System2)
Model Quan ty Unit Descrip on
38VR016H119018-E 1 Super YS-E (380-415V EU series)
42VD048H115003016 1 Medium Sta c Pressure Duct(EU series)
42VD036H115003016 1 Medium Sta c Pressure Duct(EU series)
42VD020H115003016 1 Medium Sta c Pressure Duct(EU series)
42VD012H115003016 4 Medium Sta c Pressure Duct(EU series)
BJF-224-CM(i) 4 Branch joint
BJF-330-CM(i) 1 Branch joint
BJF-710-CM(i) 1 Branch joint
R410A 2.24 kg Extra Refrigerant Added
Φ1/4 21 m Copper pipe
Φ3/8 20 m Copper pipe
Φ1/2 25 m Copper pipe
Φ5/8 10 m Copper pipe
Φ3/4 8 m Copper pipe
Φ7/8 2 m Copper pipe
Φ1-1/8 4 m Copper pipe
IDU Name Model Tmp-C(℃) RTC(kW) ATC(kW) RSC(kW) ASC(kW) PI-C(W) Tmp-H(℃) RHC(kW) AHC(kW) PI-H(W)
IDU1 42VD012H115003016 26,0/19,0 3,6 2,6 45 21 3,84 45
IDU1 42VD012H115003016 26,0/19,0 3,6 2,6 45 21 3,84 45
IDU2 42VD036H115003016 26,0/19,0 11,2 7,8 200 21 12,02 200
IDU1 42VD012H115003016 26,0/19,0 3,59 2,59 45 21 3,84 45
IDU1 42VD012H115003016 26,0/19,0 3,6 2,6 45 21 3,84 45
IDU3 42VD048H115003016 26,0/19,0 14 9,8 250 21 14,9 250
IDU4 42VD020H115003016 26,0/19,0 5,58 3,69 92 21 6,05 92
2
IDU Name Model Airflow(m^3/h) Sound-Pr dB(A) ESP(Pa)
IDU1 42VD012H115003016 580[SSH] 33[SSH] 10(0~50)
IDU1 42VD012H115003016 580[SSH] 33[SSH] 10(0~50)
IDU2 42VD036H115003016 1500[SSH] 39[SSH] 20(10~100)
IDU1 42VD012H115003016 580[SSH] 33[SSH] 10(0~50)
IDU1 42VD012H115003016 580[SSH] 33[SSH] 10(0~50)
IDU3 42VD048H115003016 1960[SSH] 41[SSH] 40(30~150)
IDU4 42VD020H115003016 830[SSH] 36[SSH] 10(0~50)
3
Power supply V/ph/Hz 380-415V-3ph-50Hz
Dimension (WxHxD) mm 1250*1760*580
Weight kg 208
4
(13) 6,00 Φ1/2/Φ1/4
5
5. Centralized Control Solu on
5.1 Centralized Controller List
The centralized control system of this project is full output regardless of whether the system is selected.