1. Project Information
Date 2022-8-5
Project name
Project address
Country China
State
City GUANGZHOU
Client name
Client address
Designed by
Reference
Revision
Altitude(m) 8
Indoor DB temperature in cooling(℃) 26
Indoor WB temperature in cooling(℃) 19
Outdoor DB temperature in cooling(℃) 34.4
Outdoor WB temperature in cooling(℃) 27.4
Indoor DB temperature in heating(℃) 21
Indoor WB temperature in heating(℃) 14
Outdoor DB temperature in heating(℃) 7.6
Outdoor WB temperature in heating(℃) 6.9
2.1Equipment List
MSSP 3.1002 1
Φ6.35 3 m Copper pipe
Φ9.53 60 m Copper pipe
Φ12.7 12 m Copper pipe
Φ15.9 60 m Copper pipe
Φ19.1 9 m Copper pipe
Φ22.2 9 m Copper pipe
Φ28.6 21 m Copper pipe
Φ31.8 6 m Copper pipe
Insulation casing for piping All refrigerant piping and branch joints should be completely insulated.
Recommended insulation casing thickness:
Thickness
Piping size Humidity<80%RH Humidity≥80%RH
Φ6.35~Φ38.1mm ≥15mm ≥20mm
Φ41.3~Φ38.1mm ≥20mm ≥25mm
MSSP 3.1002 2
4. System1
IDU Model
Tmp-
RTC(kW) ATC(kW) RSC(kW) ASC(kW)
PI- Tmp-
RHC(kW) AHC(kW)
PI-
Name C(℃) C(W) H(℃) H(W)
MDV-
IDU1 D140T2/VN1- 26,0/19,0 14 11,5 352 21 15,03 352
BA5(B)
MDV-
IDU1 D71T2/VN1- 26,0/19,0 7,1 5,9 125 21 7,76 125
DA5(B)
MDV-
IDU2 D71T2/VN1- 26,0/19,0 7,1 5,9 125 21 7,76 125
DA5(B)
MDV-
IDU3 D112T2/VN1- 26,0/19,0 11,16 9,17 378 21 12,12 378
BA5(B)
MI-71G/DHN1-
IDU4 26,0/19,0 7,04 4,46 55 21 7,76 55
M
MI-71G/DHN1-
IDU4 26,0/19,0 7,04 4,46 55 21 7,76 55
M
MSSP 3.1002 3
IDU Name Model Airflow(m^3/h) Sound-Pr dB(A) ESP(Pa)
IDU1 MDV-D140T2/VN1-BA5(B) 1745(100pa)[1] 48[H] 40(10~100)
IDU1 MDV-D71T2/VN1-DA5(B) 1127(30pa)[1] 41[H] 10(10~30)
IDU2 MDV-D71T2/VN1-DA5(B) 1127(30pa)[1] 41[H] 10(10~30)
IDU3 MDV-D112T2/VN1-BA5(B) 1851(80pa)[1] 48[H] 40(10~80)
IDU4 MI-71G/DHN1-M 1195[H] 44[H] 0
IDU4 MI-71G/DHN1-M 1195[H] 44[H] 0
Model MVC-560WV2WN1
MSSP 3.1002 4
Module MVC-560WV2WN1
Tmp-C ℃ 34.4
RTC kW
ATC kW 53,59
PI-C kW 14,53
EER 3,69
Tmp-H ℃/℃ 7,6/6,9
RHC kW
AHC kW 0
PI-H kW -0,00
COP
CR 95,7
Airflow m^3/h 12200
Sound-Pr 63
Sound-Po
Bas-Refr kg 13,00
Ex-Refr kg 2,60
TCO2 eq. 32,58
MCA A 86
MFA A 100
Power supply V/ph/Hz 220V-3ph-60Hz
Dimension (WxHxD) mm 1250*1615*765
Weight kg 296
MSSP 3.1002 5
4.4.1 Piping Limitations
MSSP 3.1002 6
4.5 Piping Diagrams (System1)
MSSP 3.1002 7
4.6 Wiring Diagrams (System1)
MSSP 3.1002 8
5. System2
MSSP 3.1002 9
IDU Name Model Weight(kg) Dimension(WxHxD)(mm) Power supply MCA(A) MFA(A)
IDU1 MDV-D71T2/VN1-DA5(B) 27.5 1220*210*500 220-240V-60Hz 0,31 15
IDU1 MDV-D71T2/VN1-DA5(B) 27.5 1220*210*500 220-240V-60Hz 0,31 15
IDU1 MDV-D71T2/VN1-DA5(B) 27.5 1220*210*500 220-240V-60Hz 0,31 15
IDU1 MDV-D71T2/VN1-DA5(B) 27.5 1220*210*500 220-240V-60Hz 0,31 15
IDU1 MDV-D71T2/VN1-DA5(B) 27.5 1220*210*500 220-240V-60Hz 0,31 15
IDU1 MDV-D71T2/VN1-DA5(B) 27.5 1220*210*500 220-240V-60Hz 0,31 15
IDU2 MDV-D90T2/VN1-BA5(B) 37.5 1230*270*775 220-240V-60Hz 0,36 15
IDU2 MDV-D90T2/VN1-BA5(B) 37.5 1230*270*775 220-240V-60Hz 0,36 15
IDU3 MI-36G/DHN1-M 11.4 990*315*223 220-240V-60Hz 0,45 15
IDU4 MDV-D140DL/N1-C 54 1670*680*244 220-240V-60Hz 0,83 15
IDU Name Model Tmp-C(℃) RTC(kW) ATC(kW) RSC(kW) ASC(kW) PI-C(W) Tmp-H(℃) RHC(kW) AHC(kW) PI-H(W)
IDU1 MDV-D71T2/VN1-DA5(B) 26,0/19,0 6,98 5,8 125 21 7,76 125
IDU1 MDV-D71T2/VN1-DA5(B) 26,0/19,0 6,98 5,8 125 21 7,76 125
IDU1 MDV-D71T2/VN1-DA5(B) 26,0/19,0 6,98 5,8 125 21 7,76 125
IDU1 MDV-D71T2/VN1-DA5(B) 26,0/19,0 6,95 5,78 125 21 7,76 125
IDU1 MDV-D71T2/VN1-DA5(B) 26,0/19,0 6,92 5,75 125 21 7,76 125
IDU1 MDV-D71T2/VN1-DA5(B) 26,0/19,0 6,88 5,72 125 21 7,76 125
IDU2 MDV-D90T2/VN1-BA5(B) 26,0/19,0 8,68 7,13 134 21 9,7 134
IDU2 MDV-D90T2/VN1-BA5(B) 26,0/19,0 8,63 7,1 134 21 9,7 134
IDU3 MI-36G/DHN1-M 26,0/19,0 3,43 2,29 30 21 3,88 30
IDU4 MDV-D140DL/N1-C 26,0/19,0 13,36 8,59 245 21 15 245
MSSP 3.1002 10
IDU1 MDV-D71T2/VN1-DA5(B) 1127(30pa)[1] 41[H] 10(10~30)
IDU1 MDV-D71T2/VN1-DA5(B) 1127(30pa)[1] 41[H] 10(10~30)
IDU1 MDV-D71T2/VN1-DA5(B) 1127(30pa)[1] 41[H] 10(10~30)
IDU1 MDV-D71T2/VN1-DA5(B) 1127(30pa)[1] 41[H] 10(10~30)
IDU2 MDV-D90T2/VN1-BA5(B) 1388(50pa)[1] 45[H] 20(10~50)
IDU2 MDV-D90T2/VN1-BA5(B) 1388(50pa)[1] 45[H] 20(10~50)
IDU3 MI-36G/DHN1-M 656[H] 33[H] 0
IDU4 MDV-D140DL/N1-C 1980[H] 47[H] 0
MSSP 3.1002 11
RSC Required sensible cooling capacity
ASC Available sensible cooling capacity
Tmp-H Indoor temperature in heating (Dry bulb temp.)
RHC Required heating capacity
AHC Available heating capacity
Tdis-H Indoor unit discharge air temperature in heating
Airflow Indoor unit airflow (High/Medium/Low)
ESP External static pressure
Sound-Pr Sound pressure level (High/Medium/Low)
Sound-Po Sound power level (High/Medium/Low)
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
PI-C Power input in cooling
PI-H Power input in heating
Power supply Power supply
Dimension(WxHxD) Net Dimension (WxHxD) mm
Weight Weight
Model MVC-785WV2WN1
Module MVC-785WV2WN1
Tmp-C ℃ 34.4
RTC kW
ATC kW 76,83
PI-C kW 23,10
EER 3,33
Tmp-H ℃/℃ 7,6/6,9
MSSP 3.1002 12
RHC kW
AHC kW 0
PI-H kW -0,00
COP
CR 99,6
Airflow m^3/h 20600
Sound-Pr 64
Sound-Po
Bas-Refr kg 19,00
Ex-Refr kg 6,38
TCO2 eq. 52,99
MCA A 92
MFA A 100
Power supply V/ph/Hz 220V-3ph-60Hz
Dimension (WxHxD) mm 1585*1615*765
Weight kg 352
MSSP 3.1002 13
CR Combination ratio
Airflow Outdoor unit airflow
Sound-Pr Sound pressure level
Sound-Po Sound power level
Bas-Refr Standard factory refrigerant charge
Ex-Refr Extra refrigerant charge
TCO2 eq. Tonnes of CO2 equivalent
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
Power supply Power supply
Dimension (WxHxD) Net Dimension (WxHxD) mm
Weight Weight
MSSP 3.1002 14
5.4.2 Correction Factors
MSSP 3.1002 15
(19) 3,00 Φ15.9/Φ9.53
MSSP 3.1002 16
5.5 Piping Diagrams (System2)
MSSP 3.1002 17
5.6 Wiring Diagrams (System2)
MSSP 3.1002 18
6. Centralized Control Solution
The centralized control system of this project is full output regardless of whether the system is selected.
MSSP 3.1002 19