The manual describes the control, protection, measurement and supervision functions with the
information of relevant hardware for PCS-902S Line Distance Relay.

Copyright © 2021 NR. All rights reserved.

NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd. No NR
trademarks may be used without written permission. NR products appearing in this document may be
covered by P.R. China and foreign patents. NR Electric Co., Ltd. reserves all rights and benefits afforded
under P.R. China and international copyright and patent laws in its products, including but not limited to
software, firmware and documentation. NR Engineering Co., Ltd. is licensed to use this document as
well as all intellectual property rights owned or held by NR Electric Co., Ltd, including but not limited to
copyright, rights in inventions, patents, know-how, trade secrets, trademarks and trade names, service
marks, design rights, database rights and rights in data, utility models, domain names and all similar
rights.

The information in this document is provided for informational use only and does not constitute a legal
contract between NR and any person or entity unless otherwise specified. Information in this document
is subject to change without prior notice.

To the extent required the products described herein meet applicable IEC and IEEE standards, but no
such assurance is given with respect to local codes and ordinances because they vary greatly.

Although every reasonable effort is made to present current and accurate information, this document
does not purport to cover all details or variations in equipment nor provide for every possible contingency
to be met in connection with installation, operation, or maintenance. Should further information be
desired or should particular problems arise which are not covered sufficiently for your purposes, please
do not hesitate to contact us.

PCS-902S Line Distance Relay 1


Document Revision History
Document Revision History
PN: ZL_PCS-902S_X_DataSheet_EN_Overseas General_X

Current version: R1.20

Corresponding Version
Release Date Description of change
Document Software

R1.00 R1.00 2019-04-19 ⚫ Form the original manual.

⚫ Modify the technical data of binary input

⚫ Modify the technical data of protection class for front side

⚫ Modify the description about remote control mode

⚫ Add the description about digital substation application

⚫ Update functional overview diagram and function lists

⚫ Add synchrophasor measurement function

⚫ Add the description about digital interface

R1.12 2020-01-07 ⚫ Add typical application of single circuit breaker (double

busbars)

⚫ Add out-of-step protection

R1.10 ⚫ Add stub differential protection

⚫ Modify the description about switchgear control

⚫ Modify the technical data of device′s power consumption

⚫ Modify the technical data of binary input

⚫ Delete the technical data of BNC connector

⚫ Update the back cover


2020-04-17
⚫ Modify the technical standard of power supply

⚫ Update the diagrams of typical applications


R1.20
⚫ Modify the section "Functions Overview"
2020-07-07
⚫ Modify the section "Features"

⚫ Update functional overview of PCS-902S

2 PCS-902S Line Distance Relay


Document Revision History
⚫ Add thermal overload protection

⚫ Add travelling-wave fault location

⚫ Delete stage 5 and stage 6 of overfrequency protection,

underfrequency protection and frequency rate-of-change

protection

⚫ Update voltage selection

⚫ Modify VT circuit supervision

⚫ Modify the introduction of front and rear panel

⚫ Modify the technical standard of power supply

⚫ Modify the technical data of communication port

⚫ Revise measurement scope and accuracy

⚫ Update the section "Functions Overview"

⚫ Add the technical data of clock synchronization for BNC port

R1.20 R1.40 2021-02-25 ⚫ Add the technical data of binary input

⚫ Modify the technical data of power supply

⚫ Modify the technical data of Ethernet port and optical fibre

port

PCS-902S Line Distance Relay 3


Overview
Overview

PCS-902S is a high-speed transmission line distance relay featuring single-pole and three-pole tripping
and reclosing with synchronism check, which can protect overhead and underground lines, feeders and
cables on all voltage levels with highest selectivity possible. The availability of various protection and
automation functions permits its utilization in all domains of line protection. The devices contain control,
measurement and monitoring functions. The large number of communication interfaces and
communication protocols satisfies the requirements of communication-based selective protection and of
automated operation. Their modular structure permits line protection devices always to be adapted
flexibly to the individual requirements.

PCS-902S is widely adopted not only for conventional substations, but also for digital substations. It
supports IEC 61850 Editions 1 and 2 and provides GOOSE and SV network interfaces with high
real-time performance. The process level network supports peer-to-peer (P2P) mode and networking
mode, including single network mode and dual network mode. The station level network could also
receive and send MMS messages (such as interlocking signals) or process level GOOSE messages
(such as circuit breakers or disconnectors positions and trip signals).

4 PCS-902S Line Distance Relay


Highlights
Highlights
⚫ Unified software and hardware platform, comprehensive power grid solutions of protection, control,
measurement and monitoring, easy to use and maintain.

⚫ High reliability and redundancy design for drive systems of the sampling circuit and the output circuit
ensure that the overall reliability of the device is high. Real-time sampling based on dual AD can
mutually check and detect the potential abnormality in the sampling circuit in time. The control power
supply of the output relay is independent with the control circuit of trigger signals, which can prevent
from undesired operation caused by the abnormality of drive circuit of output relays.

⚫ Various function modules can satisfy various situations according to the different requirements of
users. Flexible and universal logic programming, user-defined configuration of BI/BOs, buttons and
LEDs and powerful analog programming are supported.

⚫ Modularized hardware design makes the device be easily upgraded or repaired by a qualified service
person. It can be mixed with different I/O modules, with online self-check and monitoring function,
and the device can be restored from abnormal operation only need to replace a single abnormal
module.

⚫ Support memory check and error correction function, ensure high reliability and safety.

⚫ Support the internet communication protocol of native PRP/HSR and RSTP.

⚫ Fully compatible with IEC 61850 edition 1 & edition 2, support MMS service, IEC 62351
communication service, GOOSE communication in station level & process level, SV communication
with multi-sampling rate.

⚫ Fully complies with cyber security standards, including IEC62443, IEC62351, IEEE1686, NERC-CIP,
support role based access control (RBAC), security audit, security encryption communication and
security tool, improve the cyber security capability of devices.

⚫ Powerful COMTRADE fault and disturbance recording function is supported. The whole recording
time is automatically configurable by the fault duration, which is convenient to fault analysis and
replay. The recording sample rate is up to 9.6kHz.

⚫ Settable secondary rated current (1A/5A) and settable voltage threshold of binary input

⚫ Support small size and large size LCD, control and multifunction button

⚫ Support flush mounting, semi-flush mounting, surface mounting, wall mounting and other mounting
methods.

⚫ Cross screw IO, CT/VT terminals can support AWG12 specification connector and 4mm2 lead

⚫ Multiple variants with case size 1/1 or 1/2 × 19"

⚫ Protection class of front side is up to IP54 (valid for surface mounting mode of 6U, 1/2 × 19'' case
with sealing strip)

PCS-902S Line Distance Relay 5


Highlights
⚫ PCS-Studio is the configuration tool providing all the related functionality for PCS S series devices. It
ranges from device configuration to full substation design of bay integration.

⚫ Support IEEE 1588, IRIG-B clock synchronization

⚫ Support actual system phase sequence, either ABC or ACB, incorrect connection of actual phase
sequence can automatically be verified and relevant protection functions can be blocked.

⚫ Equipped with high-speed large capacity output relay, its operation speed is less than 1ms and its
break capacity is up to 10A. The real-time supervision for output drive circuit can detect the
abnormality in advance.

⚫ Support setup up to 40 users and allow each user to own different password and access authority.

6 PCS-902S Line Distance Relay


Features
Features
⚫ Two-terminal transmission line application, including overhead line and cable

⚫ Distance Protection

 Distance protection adopts the half-wave algorithm, and its typical operation time is 12-15ms.

 6 zones distance protection, independent zero-sequence compensation factor for each zone,
the phase-to-ground and phase-to-phase characteristics of distance protection can be set
independently.

 The unique power swing blocking releasing logic can properly supervise distance protection
during power swing, which ensures distance protection to operate correctly for internal faults
during power swing, and prevents distance protection from mal-operation during power swing.

⚫ The unique phase selector has the same protection zone as operation element. The phase selection

Line
is automatically resulted according to the reliability of phase selector, so that to avoid probable

Transmission
mistaken multi-phase selection by adopting overreaching phase selector.

⚫ The overcurrent protection is combined with harmonic blocking and cold load starting logic, which
can prevent from mal-operation affected by impulse current while the transformer is initiated on
no-load.

⚫ Selectable IEC, ANSI inverse-time characteristics curves, also the curve can be defined by users and
the inverse-time drop-off curve selection is supported.

⚫ Support single-ended impedance-based fault location, mutual compensation for parallel lines
arrangement is also available.

⚫ Support single-ended & double-ended travelling-wave-based fault location, locate faults to the
nearest tower.

⚫ Both dedicated fiber channel and multiplexing fiber channel are supported, and single mode and
multi-mode channel combination operation mode is enabled. Communication rate supports 64kbit/s
and 2Mbit/s, and communication protocol supports C37.94 and G.703.

⚫ Optional synchrophasor measurement

PCS-902S Line Distance Relay 7


Functions Overview
Functions Overview
Busbar

3VT

52

85 21 67P 67G 67Q 32R 49P 50DZ 46BC 62P D 50BF 37 PMU 59P
3CT
*

21D 50/51P 50/51G 50/51Q FR 59Q

78 FL

Data transmit/Rec eiv e


SOTF 59G

81O 27P

81U 81R

87STB (Only for one and a half breakers arrangement)


1VT
25 79

Line

Protection

ANSI Protection functions Remark

⚫ Independent pilot zone (forward direction and reverse

direction, mho or quadrilateral characteristics)

⚫ PUTT, POTT, Blocking, Unblocking, Zone Extension


Pilot distance protection
⚫ Current reversal logic

⚫ Weak infeed echo or echo&trip

85 ⚫ Open breaker echo

⚫ Directional zero-sequence comparison element for pilot

scheme

Pilot directional earth-fault protection ⚫ PTT, Blocking and Unblocking

⚫ Current reversal logic

⚫ Open breaker echo

21L Distance protection ⚫ Up to 6 zones

8 PCS-902S Line Distance Relay


Functions Overview
⚫ 3 independent phase-to-ground distance elements for

each zone

⚫ 3 independent phase-to-phase distance elements for each

zone

⚫ Selectable quadrilateral characteristics or mho

characteristics

⚫ Independent impedance settings and time delays for each

zone

⚫ Zero-sequence current compensation for phase-to-ground

distance element

⚫ Selectable forward direction, reverse direction or non

direction (except zone 1 that is fixed as forward direction)

⚫ Load encroachment for each zone

⚫ Power swing blocking and releasing for each zone

⚫ Faulty phase selection for each zone

⚫ Fixed forward direction

21D DPFC distance protection ⚫ High-speed operation

⚫ Supplementary for zone 1 of distance protection

78 Out-of-step protection ⚫ Easy to set and independent of system parameters

⚫ Up to 6 stages with independent logic

⚫ Voltage control element for each stage

⚫ Optional direction element for each stage, including

67P forward direction, reverse direction or non direction


Phase overcurrent protection
50/51P ⚫ Optional definite-time characteristics and inverse-time

characteristics for each stage

⚫ Trip purpose or alarm purpose for each stage

⚫ Harmonic control element for each stage

67G ⚫ Up to 6 stages with independent logic


Earth fault protection
50/51G ⚫ Optional direction element for each stage, including

PCS-902S Line Distance Relay 9


Functions Overview
forward direction, reverse direction or non direction

⚫ Optional definite-time characteristics and inverse-time

characteristics for each stage

⚫ Selectable trip purpose or alarm purpose for each stage

⚫ Harmonic control element for each stage

⚫ Up to 2 stages with independent logic

⚫ Optional direction element for each stage, including


67Q Negative-sequence overcurrent
forward direction, reverse direction or non direction
50/51Q protection
⚫ Optional definite-time characteristics and inverse-time

characteristics for each stage

⚫ Via distance measurement elements

SOTF Switch onto fault ⚫ Via dedicated earth fault element

⚫ Via phase overcurrent element

⚫ Up to 2 stages with independent logic


49P Thermal overload protection
⚫ Selectable trip purpose or alarm purpose for each stage

⚫ Up to 2 stages with independent logic

⚫ Optional definite-time characteristics and inverse-time

characteristics for each stage


59P Phase overvoltage protection
⚫ Optional phase voltage or phase-to-phase voltage

⚫ Optional “1-out-of-3” logic or “3-out-of-3” logic

⚫ Selectable trip purpose or alarm purpose for each stage

⚫ Up to 2 stages with independent logic

⚫ Optional definite-time characteristics and inverse-time

characteristics for each stage

⚫ Optional phase voltage or phase-to-phase voltage


27P Phase undervoltage protection
⚫ Optional “1-out-of-3” logic or “3-out-of-3” logic

⚫ Blocked by instantaneous VT circuit failure

⚫ Selectable trip purpose or alarm purpose for each stage

⚫ Optional auxiliary criterion, including CB position check

10 PCS-902S Line Distance Relay


Functions Overview
and current check

Negative-sequence overvoltage ⚫ Up to 2 stages with independent logic


59Q
protection ⚫ Selectable trip purpose or alarm purpose for each stage

⚫ Up to 2 stages with independent logic


59G Residual overvoltage protection
⚫ Selectable trip purpose or alarm purpose for each stage

⚫ Up to 4 stages with independent logic


81O Overfrequency protection
⚫ Voltage control element

⚫ Up to 4 stages with independent logic


81U Underfrequency protection
⚫ Voltage control element

⚫ Up to 4 stages with independent logic


81R Rate of change of frequency protection
⚫ Voltage control element

⚫ Up to 2 stages with independent logic


32R Reverse power protection
⚫ Selectable trip purpose or alarm purpose for each stage

⚫ Optional auxiliary criterion, including CB position check

37 Undercurrent protection and current check

⚫ Selectable trip purpose or alarm purpose for each stage

⚫ Phase-segregated re-trip and three-phases re-trip

⚫ Optional current criterion (phase overcurrent element,

zero-sequence overcurrent element, negative-sequence


50BF Breaker failure protection
overcurrent element)

⚫ Optional circuit breaker position check

⚫ Two time delays

⚫ Protect the T-zone in one-and-a-half breaker and ring


87STB Stub differential protection
breaker arrangements

⚫ Clear the dead zone faults between CT and the circuit


50DZ Dead zone protection
breaker

⚫ Adopt the ratio of negative-sequence current to

46BC Broken conductor protection positive-sequence current (Ι2/Ι1) to detect the broken

conductor.

PCS-902S Line Distance Relay 11


Functions Overview
⚫ Initiated by three auxiliary contacts of phase-segregate

circuit breaker
62PD Pole discrepancy protection
⚫ Optional auxiliary criterion (zero-sequence current element

or negative-sequence current element)

25 Synchronism check ⚫ Independent logic for auto-reclosing and manually closing

⚫ One shot or multi-shot

⚫ 1-pole AR, 3-pole AR or 1/3-pole AR

79 Auto-reclosing ⚫ Optional trigger mode, including protection operating and

external binary input

⚫ Support synchro-check and voltage check

⚫ Compatible with IEEE C37.118-2005, IEEE

PMU Phasor measurement unit C37.118.1-2011, IEEE C37.118.2-2011 and IEEE

C37.118.1a-2014.

⚫ Single-ended impedance-based method

FL Fault location ⚫ Zero-sequence mutual coupling compensation for parallel

lines

DPFC is the abbreviation of deviation of power frequency component.

Control

⚫ Circuit breaker & disconnector control (Remote/local)

⚫ Synchronism check for auto-reclosing and manual closing

⚫ Voltage selection

Synchrophasor Measurement

⚫ Synchronize with the GPS time by IRIG-B time source

⚫ Calculate synchronized phasors, including: Ua, Ub, Uc, U1, U2, U0, Ia, Ib, Ic, I1, I2, I0

⚫ Calculate analog values, including: active power (P), reactive power (Q), frequency, ROCOF
(df/dt)

12 PCS-902S Line Distance Relay


Functions Overview
⚫ Transmit binary status of the IED to PDC (Phasor Data Concentrator) according to IEEE
C37.118 standard

⚫ Realize high accurate measurement of the phasors and analogs according to the IEEE
C37.118.1-2011 and IEEE C37.118.1a-2014 standard.

⚫ Communicate with PDC according to IEEE C37.118-2005 and IEEE C37.118.2-2011

⚫ Supporting P Class or M Class measurement (user selectable)

⚫ Measurement of up to 32 binary status (user configurable)

⚫ Output of synchrophasor with timestamp, support of multiple protocols (TCP, TCP-UDP, UDP)
and multiple data rates (2f0, f0, f0/2) for maximum 4 clients (PDC)

Measurement

⚫ Current and voltage measurement at a 2.4KHz sampling rate

⚫ Current and voltage measurement at a 9.6KHz sampling rate

⚫ Energy metering (active and reactive energy are calculated in import respectively export
direction)

⚫ Power (Apparent/Real/Reactive)

⚫ Power factor

⚫ Frequency

Recording

⚫ Event Recorder including 1024 disturbance records, 1024 binary events, 1024 supervision
events, 256 control logs and 1024 device logs.

⚫ 64 disturbance waveforms records (The file format of disturbance recorder is compatible with
international COMTRADE file.)

⚫ 64 high-frequency waveforms records (The file format of disturbance recorder is compatible


with international COMTRADE file.)

Supervision

⚫ VT circuit supervision

⚫ CT circuit supervision

⚫ Trip/Close coil supervision

⚫ Self diagnostic

⚫ Pilot communication channel supervision

PCS-902S Line Distance Relay 13


Functions Overview
⚫ DC power supply supervision

⚫ Channel status statistic

⚫ System frequency supervision

Pilot Channel Scheme

⚫ Optional single- or dual- pilot channels (fiber optic)

⚫ Support G.703 and C37.94

Communication Interface

⚫ 2 or 4 100Base-TX copper Ethernet ports for SCADA communication

⚫ 2 or 4 100Base-FX optical Ethernet ports for SCADA communication

⚫ 2 RS-485 serial ports for SCADA communication

⚫ 1 RS-485 serial port for clock synchronization

⚫ 1 TTL serial port for clock synchronization

⚫ 1 BNC port for clock synchronization

⚫ 1 front RJ-45 port for debugging

⚫ 1 rear RJ-45 port for debugging

Communication Protocol

⚫ IEC 61850 Editions 1 and 2

⚫ IEC 60870-5-103

⚫ DNP3.0

⚫ Modbus

⚫ IEC 62439 Parallel Redundancy Protocol (PRP)

⚫ IEC 62439 High-availability Seamless Redundancy (HSR)

⚫ IEEE 802.1w Rapid Spanning Tree Protocol (RSTP)

Digital Application

⚫ IEC 61850 MMS Server

⚫ IEC 61850-8-1 GOOSE

⚫ IEC 61850-9-2LE SV

14 PCS-902S Line Distance Relay


Functions Overview
⚫ 4 100Base-TX electrical or 100Base-FX optical Ethernet port (station level)

⚫ Extendable 100Base-FX optical Ethernet port (process level)

Clock Synchronization

⚫ IRIG-B: IRIG-B via RS-485 differential level, TTL level or BNC

⚫ PPS: Pulse per second (PPS) via RS-485 differential level, binary input or BNC

⚫ IEEE 1588: Clock message based on IEEE 1588 via Ethernet network

⚫ SNTP: Unicast (point-to-point) & broadcast SNTP mode via Ethernet network

⚫ Clock messages: IEC 60870-5-103 protocol, Modbus protocol and DNP3.0 protocol

Cyber Security

⚫ NERC CIP

⚫ IEC 62351

⚫ IEC 62443

⚫ IEEE 1686

User Interface

⚫ Friendly HMI interface with LCD, easy-to-use keypad aids simple navigation and set-point
adjustment

⚫ Push buttons for open/close, switch for selection between local and remote control, and user's
login and logout authority management

⚫ 4 Programmable operator push-buttons with user-configurable labels

⚫ Up to 18 programmable target LEDs with user-configurable labels

⚫ 1 RS-232 rear ports for printer

⚫ Language switchover—English + selected language

⚫ Configuration tool—PCS-Studio

Miscellaneous

⚫ User programmable logic

⚫ Fault phase selection

⚫ Switching system phase sequences function (ABC or ACB)

PCS-902S Line Distance Relay 15


Typical Application
Typical Application
PCS-902S protect overhead and underground lines, feeders and cables on all voltage levels with
highest selectivity possible.

3CT 3CT

52 * * 52

3VT 3VT

CH1 CH1
PCS-902S Optical fibre channel or PLC channel PCS-902S
CH2 CH2

1VT 1VT
Communication channel via direct dedicated fibre, MUX or PLC

Figure 1 Typical application of single circuit breaker (single busbar)

3CT 3CT

52
* * 52

1VT 1VT

CH1 CH1
PCS-902S Optical fibre channel or PLC channel PCS-902S
CH2 CH2

3VT 3VT

Communication channel via direct dedicated fibre, MUX or PLC


3VT 3VT

Figure 2 Typical application of single circuit breaker (double busbars)

52 52
1VT 1VT

3CT 3CT
*
*

3VT 3VT

CH1 CH1
52 52
PCS-902S Optical fibre channel or PLC channel PCS-902S
CH2 CH2
3CT 3CT
*
*

1VT Communication channel via direct dedicated fibre, MUX or PLC 1VT

1VT 1VT
52 52

Figure 3 Typical application of double circuit breakers

16 PCS-902S Line Distance Relay


Protection Functions
Protection Functions

Circuit Breaker Position Supervision

In order to prevent that incorrect status of CB position is input into the device via binary input, the
appropriate monitor method is used to check the rationality of the binary input. When the binary input of
CB open position is detected, the status of CB position will be thought as incorrect and an alarm
[Alm_52b] will be issued if there is current detected in the line.

Together with the status of circuit breaker and the information of external circuit, this function can be
used to supervise control circuit of circuit breaker.

Fault Detector (FD)

Fault detector is responsible to determine the fault appearance on the protected power system. The
device will switch to protection calculation after the fault detector picks up, for example the calculation of
distance protection, and to determine the operating logic. If the fault is within the protected zone, the
device will issue tripping command. The fault detector continuously detects the change of
phase-to-phase power frequency current and the calculated zero-sequence and negative-sequence
currents. The fault detector includes:

1. Fault detector based on DPFC current: DPFC current is greater than the setting value

2. Fault detector based on residual current: Zero-sequence current is greater than the setting value

3. Fault detector based on negative-sequence current: Negative-sequence current is greater than the
setting value

Optical Pilot Channel (FO)

The devices can transmit Boolean quantities such as blocking signal, permissive signal and transfer trip
signal to the remote end via optical fibre channel. Up to 2 optical fibre channels are supported, which can
be dedicated optical fibre channel or multiplex channel, the channel mode could be selected as
single-mode or multi-mode. The communication rate can be 64kbits/s or 2048kbits/s, and G.703 or
C37.94 are optional for communication protocol. 8 digital bits are integrated in each frame of
transmission message for various applications, and 8 binary signals are configurable. Each received
message frame via fibre optical channel will pass through security check to ensure the integrity of the
message consistently.

Pilot Distance Protection (85)

Pilot distance protection requires communication channel to exchange protection information at both
ends. The channel may be dedicated or multiplexed channel through optical fiber or any other
communication media. Pilot distance protection has schemes of permissive underreaching transfer trip
(PUTT), permissive overreaching transfer trip (POTT) and blocking. The device provides dual pilot

PCS-902S Line Distance Relay 17


Protection Functions
distance protections. The communication media and mode can be independent each other.

Pilot distance protection determines whether it will send the signal to the remote end according to the
discrimination result of the distance element or direction element. Pilot distance protection can be
divided into permissive scheme and blocking scheme according to whether the signal sent is used to
permit tripping or block tripping. For permissive scheme, it can be divided into overreaching mode or
underreaching mode according to the setting of distance element and scheme selected, furthermore, it
will provide the unblocking scheme as auxiliary function. For overreaching mode, current reversal logic
and weak infeed logic are available for parallel line operation and weak power source situation
respectively.

Pilot Directional Earth-fault Protection (85)

Pilot directional earth-fault protection can be used independently, for example, no distance protection is
equipped with the device but fast operation is required for the whole line, or it is used as backup
protection of pilot distance protection to enhance the sensitivity for an earth fault with high fault
resistance.

Pilot directional earth-fault protection comprises permissive scheme and blocking scheme. It can share
pilot channel 1 with pilot distance protection, or uses independent pilot channel 2. For underreach mode,
pilot directional earth-fault always adopts independent pilot channel 2. Sending permissive signal (or
terminating sending signal) to the opposite end is controlled by forward direction element. Current
reversal logic is available for parallel line operation and CB echo logic is provided once pilot directional
earth fault protection is enabled. Current reversal logic is only used for permissive scheme. For blocking
scheme, current reversal need not be considered because there is a settable time delay in pilot
directional earth-fault protection.

Distance Protection (21L)

Distance protection includes three independent phase-to-phase measuring loops as well as three
independent phase-to-ground measuring loops. Both mho and quadrilateral characteristics are available
for different application. In addition, load encroachment, power swing blocking and releasing, and faulty
phase selection functions are also provided.

Up to 8 zones distance protection are supplied, including 1 zone distance protection with fixed forward
direction, 5 zones distance protection with settable direction, 1 zone pilot distance protection with fixed
forward direction and 1 zone pilot distance protection with fixed reverse direction. Each zone includes
three independent phase-to-phase measuring loops as well as three independent phase-to-ground
measuring loops. Phase-to-ground distance element should be compensated by zero-sequence current
of local line. Zone 2~6 can select forward direction, reverse direction and non-direction.

Load encroachment can distinguish effectively between heavily loaded line and faulty line, and the risk of
encroachment of the load impedance into the tripping characteristics of the distance protection can be
excluded.

Power swing blocking and releasing can prevent distance protection from undesired operation during
power swing, even if measured impedance reaches into operation area of distance protection. Moreover,

18 PCS-902S Line Distance Relay


Protection Functions
distance protection can operate reliably when a fault occurs during power swing.

Based on distance protection characteristics, faulty phase can be identified correctly. It is beneficial for
the faulty phase selection which is important to the line which uses phase-segregated circuit breaker and
provides valid information for 1-pole AR and fault location.

DPFC Distance Protection (21D)

As an independent fast protection, DPFC distance protection is mainly used to clear close up fault of
long line quickly, its protected range can set as 60%~70% of the whole line. Since DPFC distance
protection only reflects the fault component and is not influenced by current change due to load variation
and power swing, power swing blocking (PSB) function is not required. Moreover, there is no transient
overreaching due to infeed current from the remote power supply because it is not influenced by load
current.

Out-of-Step Protection (78)

For the power grid of loss synchronous, the voltage of each node in the tie line that synchronous or
asynchronous oscillation happens to will oscillate periodically, and where the voltage oscillation is the
most violent in each tie line is the center of synchronous or asynchronous oscillation. In general, the
voltage oscillation is more violent more close to the oscillation center. Out-of-step center is the point
where the lowest voltage appears in the tie line of asynchronous oscillation in the process of out-of-step
oscillation, i.e., the oscillation center of the tie line of asynchronous oscillation. The phase angle of bus
voltage difference on either side of out-of-step center will change within 0°~180°~360° periodically.
Therefore, the oscillation center voltage can be used to discriminate among out-of-step oscillation,
short-circuit fault and synchronous oscillation.

Considering the selectivity, the separation should be performed within 2~3 out-of-step period or the
corresponding time delay after the system is out of step, otherwise the out-of-step oscillation among
multiple generators may is developed, further expanding the accident, so as to cause system separation
even collapse accident. So when the out-of-step operation time or oscillation times is greater than
specified value, out-of-step protection should operate to separate.

Distance SOTF Protection (21SOTF)

Distance SOTF (switch onto fault) protection shares pickup signal as initiation condition with distance
protection. It is selectable among zone 2, 3 or 4 of distance protection which is accelerated to trip by
manual closing or auto-reclosing, and they can enable or disable be controlled by power swing blocking.
Distance SOTF protection equips with independent time delay. Zone 2 of distance protection is fixedly
accelerated to trip by 1-pole AR. Zone 2 of distance protection is also accelerated to trip by pole
discrepancy condition. For single-phase fault, distance SOTF protection will accelerate to operate if
another fault happens to the healthy phase before auto-reclosing.

Phase Overcurrent Protection (50/51P)

The device can provide six stages of phase overcurrent protection with independent logic. Each stage

PCS-902S Line Distance Relay 19


Protection Functions
can be independently set as definite-time characteristics or inverse-time characteristics. The dropout
characteristics can be set as instantaneous dropout, definite-time dropout or inverse-time dropout. It can
be chosen whether it is blocked by voltage control element or harmonic control element. The direction
control element can be set as no direction, forward direction and reverse direction. Phase overcurrent
protection picks up when the current exceeds the setting, and operates after a certain time delay. Once
the fault disappears, phase overcurrent protection will dropout. Phase overcurrent protection can
operate to trip or alarm.

Phase Current SOTF Protection (50PSOTF)

Phase current SOTF protection will operate to trip three-phase circuit breaker with a time delay when
manual closing or auto-reclosing. For in-line transformer application, large inrush current generated
during manual closing and auto-reclosing will lead to an undesired operation of phase current SOTF
protection. Second harmonic blocking can be selected to prevent maloperation due to inrush current.

Earth Fault Protection (50/51G)

The device can provide six stages of earth fault protection with independent logic. Each stage can be
independently set as definite-time characteristics or inverse-time characteristics. It can be chosen
whether it is blocked by harmonic control element. The direction control element can be set as no
direction, forward direction and reverse direction. The zero-sequence current used by earth fault
protection always adopts calculated zero-sequence current. Earth fault protection can operate to trip or
alarm.

Residual Current SOTF Protection (50GSOTF)

Residual current SOTF protection will operate to trip three-phase circuit breaker with a time delay via
1-pole auto-reclosing, manual closing or 3-pole auto-reclosing. For in-line transformer application, large
inrush current generated during manual closing and auto-reclosing will lead to an undesired operation of
residual current SOTF protection. Second harmonic blocking can be selected to prevent maloperation
due to inrush current.

Negative-sequence Overcurrent Protection (50/51Q)

The device can provide two stages of negative-sequence overcurrent protection with independent logic.
Each stage can be independently set as definite-time characteristics or inverse-time characteristics. For
parallel lines or a ring network line, the flow direction of negative-sequence current may be different.
Considering the selectivity of negative-sequence overcurrent protection, the direction control element
can be set as no direction, forward direction and reverse direction. Negative-sequence overcurrent
protection can operate to trip or alarm.

Phase Overvoltage Protection (59P)

The device can provide two stages of phase overvoltage protection with independent logic. When a high

20 PCS-902S Line Distance Relay


Protection Functions
voltage occurs in the system, phase overvoltage protection will operate to isolate the fault from the
system after a time delay if the voltage is greater than the setting. In addition, phase overvoltage
protection also provides the alarm function to notify that there is the overvoltage in the system and find
the cause timely to prevent from further deterioration of the fault.

Each stage of phase overvoltage protection can be independently set as definite-time characteristics or
inverse-time characteristics. The dropout characteristics can be set as instantaneous dropout and
definite-time dropout.

Phase voltage or phase-to-phase voltage can be selected to be used by the protection calculation.
“1-out-of-3” or “3-out-of-3” logic can be selected for the protection criterion. (1-out-of-3 means any of
three phase voltages, 3-out-of-3 means all three phase voltages).

Residual Overvoltage Protection (59G)

The device can provide two stages of residual overvoltage protection with independent logic. When the
residual voltage is greater than the setting, residual overvoltage protection will operate to isolate the fault
from the system after a time delay. In addition, residual overvoltage protection also provides the alarm
function to notify that there is an earth fault leading to residual voltage generation, and find the cause
timely to prevent from further deterioration of the fault. Residual overvoltage protection supports
definite-time characteristics. The dropout characteristics can be set as instantaneous dropout and
definite-time dropout.

Negative-sequence Overvoltage Protection (59Q)

The device provides two stages of negative-sequence overvoltage protection. If negative-sequence


voltage is greater than the setting, negative-sequence overvoltage protection will operate.
Negative-sequence overvoltage protection is with independent definite-time characteristics and
definite-time or instantaneous dropout characteristics.

Phase Undervoltage Protection (27P)

The device can provide two stages of phase undervoltage protection with independent logic. When the
voltage drops in the system and it is lower than the setting, phase undervoltage protection will operate to
isolate the fault from the system after a time delay. In addition, phase undervoltage protection also
provides the alarm function to notify that there is the undervoltage in the system and find the cause
timely to prevent from further deterioration of the fault.

Each stage of phase undervoltage protection can be independently set as definite-time characteristics or
inverse-time characteristics. The dropout characteristics can be set as instantaneous dropout and
definite-time dropout.

Phase voltage or phase-to-phase voltage can be selected to be used. “1-out-of-3” or “3-out-of-3” logic
can be selected for the protection criterion. (1-out-of-3 means any of three phase voltages, 3-out-of-3
means all three phase voltages). The circuit breaker position with/without the current condition can be as
an auxiliary criterion for phase undervoltage protection.

PCS-902S Line Distance Relay 21


Protection Functions
Overfrequency Protection (81O)

The device can provide four stages of overfrequency protection. If the system frequency is greater than
the setting, overfrequency protection will operate to remove some part of active power supplies from the
system. Overfrequency protection is with independent definite-time characteristics and with
instantaneous dropout characteristics.

Underfrequency Protection (81U)

The device can provide four stages of underfrequency protection. If the system frequency is less than
the setting, underfrequency protection will operate to shedding some part of loads from the system.
Underfrequency protection is with independent definite-time characteristics and with instantaneous
dropout characteristics.

Frequency Rate-of-change Protection (81R)

The device can provide four stages of frequency rate-of-change protection. If the system frequency
rate-of-change is greater than the setting, frequency rate-of-change protection will operate. Frequency
rate-of-change protection is with independent definite-time characteristics and with instantaneous
dropout characteristics.

Reverse Power Protection (32R)

The device can provide two stages of reverse power protection. If the reverse power is detected and it is
greater than the setting, reverse power protection will operate. Reverse power protection is with
independent operating definite-time characteristics and with instantaneous dropout characteristics.
Reverse power protection can be enabled or disabled by the settings and the signals. For some specific
applications, reverse power protection needs to be blocked by the external signal, so the device provides
an input signal to be used to block reverse power protection.

Thermal Overload Protection (49P)

The device provides two methods to fulfill thermal overload protection, one is to calculate thermal
accumulation according the actual measured current, and the other is to calculate the protected
component's temperature according to the environmental medium temperature plus the temperature
difference.

Thermal overload protection calculates the overtemperature from the phase currents based on a thermal
model of the protected component (I2t characteristics) with the settable time constants according to the
IEC60255-8 standard. Two stages overload protection are available, each stage can operate for alarm
purpose and for trip purpose.

Based on the calculated protected component's temperature, the user can compare it with user-defined
temperature threshold value to trip or alarm with/without the time delay by PCS-Studio.

22 PCS-902S Line Distance Relay


Protection Functions
Undercurrent Protection (37)

The device can provide one stage of undercurrent protection for tripping purpose or alarm purpose. For
different protected equipment, single-phase criterion or three-phase criterion can be selected. The circuit
breaker position and the load current also can be taken as the enabling conditions of undercurrent
protection. Undercurrent protection is with definite-time operating characteristics and instantaneous
dropout characteristics.

Breaker Failure Protection (50BF)

According to the tripping information from the device and the auxiliary information (the current and the
position) of target circuit breaker, breaker failure protection constitutes the criterion to discriminate
whether the target circuit fails to open. If the criterion is confirmed, breaker failure protection will operate
to trip the target circuit breaker with the re-tripping time delay, trip it again with the first time delay and trip
the adjacent circuit breakers with the second time delay. As a special backup protection, breaker failure
protection can quickly isolate the fault, reduce the affected range by the fault, keep system stability and
prevent generators, transformers and other primary equipment from seriously damaged. For breaker
failure protection, phase-segregated re-trip, three-phases re-trip and two time delays are available.

Stub Differential Protection (87STB)

Stub differential protection is mainly designed for one and a half breakers arrangement. When line
disconnector is open and transmission line is put into maintenance, line VT is no voltage. Distance
protection is disabled, and stub differential protection is enabled. It is used to protect stub section among
two circuit breakers and line disconnector. Usually, stub differential protection is enabled automatically
by normally closed auxiliary contact of line disconnector.

Dead Zone Protection (50DZ)

For some wiring arrangement (for example, circuit breaker is located between CT and the line), if fault
occurs between CT and circuit breaker, line protection can operate to trip circuit breaker quickly, but the
fault have not been cleared since local circuit breaker is tripped. Here dead zone protection is needed in
order to trip relevant circuit breaker.

Broken Conductor Protection (46BC)

Broken-conductor fault mainly is single-phase broken or two-phases broken, so broken conductor


protection based on the ratio of negative-sequence current to positive sequence current can detect the
broken-conductor fault. According to the ratio of negative-sequence current to positive-sequence current
(I2/I1), it is used to judge whether there is an broken-conductor fault. Negative-sequence current under
normal operating condition (i.e. unbalance current) is due to CT error and unbalance load, so the ratio of
negative-sequence current to positive-sequence current (amplitude) is relative steady. The value with
margin can then be used as the setting of broken conductor protection. It is mainly used to detect
broken-conductor fault and CT circuit failure as well.

PCS-902S Line Distance Relay 23


Protection Functions
Pole Discrepancy Protection (62PD)

The pole discrepancy of circuit breaker may occur during operation of a breaker with segregated
operating gears for the three phases. Pole discrepancy protection determines three-phase breaker pole
discrepancy condition by its phase segregated CB auxiliary contacts. In order to improve the reliability of
pole discrepancy protection, zero-sequence current element or negative-sequence current element can
be selected as auxiliary criterion.

Transfer Trip (TT)

The device provides phase-segregated transfer trip and three-phases transfer trip, which can be
controlled by local fault detector. In addition, the input signals of phase-segregated transfer trip and
three-phases transfer trip are always supervised, and the device will issue an alarm and block transfer
trip once the binary input is energized for longer than the setting value. Both phase-segregated transfer
trip and three-phase transfer can be selected to operate to block AR.

Trip Logic (TRP)

Trip logic gathers signals from phase selection and protection tripping elements and then converts the
operation signal from protection tripping elements to appropriate tripping signals. The device can
implement phase-segregated tripping or three-phase tripping, and may output the contact of blocking AR
and the contact of initiating breaker failure protection.

Automatic Reclosure (79)

AR can be used with either integrated device or external device. When AR is used with integrated device,
the internal protection logic can initiate AR, moreover, a tripping contact from external device can be
connected to the device via input signal to initiate integrated AR.

When AR is used as an independent device, it can be initiated by the protections′ operating signal. The
device can output some configurable output signals (such as, contact signals or digital signal, for
example, GOOSE signal) to initiate external AR or block external AR. The contact signals includes
phase-segregated tripping signal, single-phase tripping signal, three-phase tripping signal, blocking AR
signal and protection operating signal, etc., According to requirement, these contacts can be selectively
connected to external AR.

According to the requirement, the device can be set as one-shot or multi-shot AR. When adopting
multi-shot AR, the AR mode of first time reclosing can be set as 1-pole AR, 3-pole AR or 1/3-pole AR.
The rest AR mode is only 3-pole AR.

Impedance-Based Fault Location (FL)

The device provides single-end fault location. Fault location picks up after the device operates to trip
when there is a fault in the line. If the pickup time is greater than 25ms, fault location is calculated with a
time delay of 10ms after the device operates to trip. If the pickup time is smaller than 25ms, fault location

24 PCS-902S Line Distance Relay


Protection Functions
is calculated with a time delay of 20ms after the device operates to trip.

When the faulty phase detected there is a protection tripping and the calculation of the fault impedance
is initiated. According to the fault impedance to locate the fault point, two calculation results are provided,
which is the length of the fault point distance from the end of the device and its percentage of lines
length.

For parallel lines, there is a mutual coupling between each phase, and also a mutual coupling between
parallel lines. The coupling strength between parallel lines associated with the transposition way. For
parallel lines with fully transposition, positive-sequence and negative-sequence mutual coupling is very
small, and usually can be ignored. But zero-sequence mutual coupling has a greater influence on the
line, so the measured impedance must consider the effect.

Travelling-Wave Fault Location (TWFL)

The device provides single-ended TW-based method and double-ended TW-based method. The TWFL
is not affected by the line distributed capacitance and faulty resistance, and is an accurate and
dependable fault location method. The TWFL module of the device on both ends of the line only needs to
capture the first travelling wave, so the double-ended TW-based method has higher precision than the
single-ended TW-based method, and almost no blind region of fault location.

PCS-902S Line Distance Relay 25


Control Functions
Control Functions

Switchgear Control

A control command can realize various control signals such as the CB/DS/ES opening/closing. In order
to ensure the reliability of the control output, a locking circuit is added to each control object. The
operation is strictly in accordance with the selection, check and execution steps, to ensure that the
control operation can be safely and reliably implemented. In addition, the device has a hardware
self-checking and blocking function to prevent hardware damage from maloperation output.

When the device is in the remote control mode, the control command may be sent via communication
protocol; when it is in the local control mode, the local operation may be performed on the device LCD or
panel handle.

A complete control process is:

1. Protocol module sends a selection command;

2. Control module responds the success or failure result of selection;

3. If the selection is successful, the protocol module sends an execution command, otherwise it sends
a cancel command;

4. Control module responds the success or failure result of execution;

5. The control operation may be open/close or up/down/stop.

When the device is in the maintenance status, it can still respond to local control commands.

The switchgear control function can cooperate with functions such as synchronism check and
interlocking criteria calculation to complete the output of the corresponding operation command. It can
realize the normal control output in one bay and the interlocking and programmable logic configuration
between bays. This device supports the following functional control module:

Module Description

CSWI Control of circuit breaker (CB), disconnector switch (DS) or earthing switch (ES)

RMTLOC Remote or local control mode

XCBR Synthesis of CB position, three-phase or phase separated

XSWI Synthesis of DS/ES position

SXCBR/SCSWI Trip counter of CB/DS/ES

RSYN Synchronism check for CB closing

CILO Interlocking logic for CB/DS/ES control

MCSWI Manual control of CB/DS/ES

26 PCS-902S Line Distance Relay


Control Functions
Module Description

CHKPOS Position verification for switchgear control

The initiation of a control command may be sent to the device by the SCADA or the NCC through
communication protocol. It may also be the operation of the device LCD or the manual triggering through
configured signal. The command is sent by the CPU to the control module for processing, and a control
record is made on the CPU module according to the control result.

Synchronism Check (25)

The synchronism check includes synchro-check and dead charge check. By comparing between the
reference voltage and the synchronization voltage, the synchro-check is satisfied if the voltage
difference, frequency difference, slip frequency difference and phase angle difference are all within their
setting ranges. The dead charge check mode checks only the synchro-check voltage. Several dead
charge check modes are supported, including dead synchronism voltage & dead reference voltage
check, live synchronism voltage is & dead reference voltage, synchronism voltage is dead & live
reference voltage, dead reference voltage, dead synchronism voltage, live synchronism voltage & dead
reference voltage or dead synchronism voltage & live reference voltage, dead synchronism voltage or
reference voltage.

Voltage Selection

The voltage selection function can be used to switch the reference and synchronization voltages of
synchronism check in double busbars and one-and-half circuit breakers, or to switch three-phases
voltage between double busbars used by protection calculations or measurements.

By default, the device adopts the principle of proximity in built-in voltage selection logic. Moreover, it
supports customized selection logic. The default voltage selection logic is automatically disabled if the
customized voltage selection logic is correctly configured. The customized selection result may be
derived from any source binary signals, such as binary inputs, isolators status and programmable logic
output signals.

1. Double busbars arrangement

⚫ Three-phases voltages from Bus1 VT and Bus2 VT via switching is used for protection
calculations or measurements and meanwhile used as reference side of synchronism check.
Single-phase voltage from line VT is used as synchronizing side of synchronism check.

PCS-902S Line Distance Relay 27


Control Functions
Bus2

Bus1

DS1 DS2
Ua

UB1 Ub
Uc
Ua

UB2 Ub
Uc
CB
DS1.DPS

DS2.DPS

UL1
Line

⚫ The voltage from Bus 1 VT and Bus 2 VT via switching is used as synchronizing side of
synchronism check. The voltage from Line VT is used as reference side of synchronism check.

Bus2

Bus1

DS1 DS2
UB1

UB2

DS1.DPS

CB

DS2.DPS

Ua

UL1 Ub
Line
Uc

2. One-and-half circuit breakers

⚫ For bus-side CB, the voltage from Line1 VT, Line2 VT and Bus VT of the other sie via switching
is used as synchronizing side of synchronism check. The voltage from Bus VT of local side is
used as reference side of synchronism check.

⚫ For tie CB, the voltages from Line1 VT & Bus1 VT and Line2 VT & Bus2 VT via switching are
used as synchronizing side and reference side of synchronism check respectively.

28 PCS-902S Line Distance Relay


Control Functions
Bus1

UB1

Bus1_CB.DPS Bus1_CB
Line 1

Ua
UL1 Ub
Uc DS1

DS1.DPS

Tie_CB.DPS Tie_CB
Line 2

UL2

DS2.DPS

DS2

Bus2_CB.DPS Bus2_CB

UB2

Bus2

3. For a customized voltage selection logic, the inputs "in_bus1_sel", "in_bus2_sel", "in_line1_sel" and
"in_line2_sel" are derived from binary signals, such as switchgear positions, binary inputs,
programmable logic outputs, etc. The inputted value "1" means "Channel selected" while the
inputted value "0" means "Channel not selected". Make sure that all these customized voltage
selection inputs and measurement channels are correctly configured before put the logic into
service.

PCS-902S Line Distance Relay 29


Monitoring Functions
Monitoring Functions

VT Circuit Supervision (VTS)

VT circuit supervision can detect failure of single-phase, two-phase and three-phase on protection VT.
Under normal condition, the device continuously supervises input voltage from VT, VT circuit failure
signal will be activated if residual voltage exceeds the threshold value, or negative-sequence voltage
exceeds the threshold value or positive-sequence voltage is lower than the threshold value. If the device
is under pickup state due to system fault or other abnormality, VT circuit supervision will be disabled.

VT (secondary circuit) MCB auxiliary contact as a binary input can be connected to the binary input
circuit of the device. If MCB is open, the device will consider the VT circuit is in open state and issues an
alarm without a time delay. If the auxiliary contact is not connected to the device, VT circuit supervision
will be issued with time delay as mentioned in previous paragraph.

CT Circuit Supervision (CTS)

Under normal conditions, CT secondary signal is continuously supervised by detecting the residual
current and voltage. If residual current is larger than the setting whereas residual voltage is less than the
setting, and any phase current is less than 0.04In, CT circuit failure is considered.

30 PCS-902S Line Distance Relay


Hardware
Hardware

Front Panel

7 7

6 1 3 6 1 3

2 4 2 4

5 5
8 8

1. Front-panel status indication and control of switches

2. Easy-to-use keypad aids simple navigation and set-point adjustment

3. Push buttons for open/close, switch for selection between local and remote control, and user's login
and logout authority management

4. Programmable operator push-buttons with user-configurable labels

5. Front RJ45 debugging port

6. 18 programmable target LEDs with user-configurable labels

7. 2 fixed LEDs for device running status indication

8. Push button for target reset

PCS-902S Line Distance Relay 31


Hardware
Rear Panel

5 5

1 1
2 3 4 2 3 4

6 6

7 7

5 5

1 1
2 3 4 2 3 4

6 6

7 7

1. Current and voltage analog inputs

2. Binary inputs

3. Binary outputs

4. Power supply and binary I/O

5. Copper or fiber-optic Ethernet port

6. RS-485 or RS-232 serial port, TTL level

7. Rear RJ45 debugging port

32 PCS-902S Line Distance Relay


Hardware
Typical Wiring

0201
0202

0204
0205

0207
0208

0210

0216

0219

0222
0203

0206

0209

0211
0212

0215

0217
0218

0220
0221

0223
0224
0213
0214
Ia1 Ib1 Ic1 Ia2 Ib2 Ic2 UB2 UL1 UB1 Ua Ub Uc

BI_01 + 0501
Ethernet (RJ 45 and LC-
Connector)

BI_02 + 0502

To SCADA


BI_16 + 0516

0517 -
0518 -

BI_17 + 0519

BI_18 + 0520

BI_32 … + 0534
1A 0101
COM

1B 0102 0535 -
SGND 0103 0536 -
cable with single point earthing

BI_01 + P101
To the screen of other coaxial

2A 0104
COM

2B 0105 P102 -
SGND 0106
BI_02 + P103
SYN+ 0107
Clock SYN

SYN- 0108 P104 -


SGND 0109 P105 -
TTL 0110 BI_03 + P106

Console
BI_04 + P107
0601
BO_01

0602
0603
BO_02 BI_09 + P112
0604

P113
0617 BO_01
BO_09 P114
0618
P115
0619 BO_02 P116
BO_10

0620
P121
0621 BO_05
BO_11 P122
0622
P123

0631 BO_Fail P124


0632 BO_16 P125 PWR+
BO_16 Power External DC power
0633
Supply P126 supply
0634 PWR-

0635 BO_17

0636 BO_17
Grounding Bus

Figure 2 Typical wiring with pin ferrule

PCS-902S Line Distance Relay 33


Hardware

0201
0202

0204
0205

0207
0208

0210

0216

0219

0222
0203

0206

0209

0211
0212

0215

0217
0218

0220
0221

0223
0224
0213
0214
Ia1 Ib1 Ic1 Ia2 Ib2 Ic2 UB2 UL1 UB1 Ua Ub Uc

BI_01 + 0501

Ethernet (RJ 45 and LC-


Connector)
BI_02 + 0502

To SCADA


BI_25 + 0525

0526 -

BI_01 + P101

P102 -

BI_02 + P103

P104 -
P105 -

1A 0101 BI_03 + P106


COM

1B 0102
SGND 0103 BI_04 + P107
cable with single point earthing
To the screen of other coaxial

2A 0104
COM

2B 0105
SGND 0106 BI_09 + P112

SYN+ 0107 P113


Clock SYN

SYN- 0108 BO_01 P114


SGND 0109 P115
TTL 0110 BO_02 P116

Console P121
BO_05 P122
0601 P123
0602 BO_01 BO_Fail P124
0603
0604 BO_02 P125 PWR+
Power External DC power

0625 Supply P126 supply


PWR-
0626 BO_13

Grounding Bus

Figure 3 Typical wiring with ring ferrule

34 PCS-902S Line Distance Relay


Installation
Installation

Dimensions

The device includes two kinds of case sizes

Case size (mm) H1 H2 D1 D2 W1 W2

6U, 1/2 × 19'' 265.9 253 243 233.5 219.4 208.4

6U, 1/1 × 19'' 265.9 253 243 233.5 453 442

Note: The dimensions of device depth include the dimension of terminal connector without wire harness 22mm.

Certain mounting method needs special mounting accessory for support.

PCS-902S Line Distance Relay 35


Installation
Flush Mounting

36 PCS-902S Line Distance Relay


Installation

Case size (mm) H3 H4 D3 W3 W4 W5

6U, 1/2 × 19'' 190.5 259 9.5 229.4 263.4 246.4

6U, 1/1 × 19'' 190.5 259 9.5 463 497 480

Semi-flush Mounting

PCS-902S Line Distance Relay 37


Installation

Case size (mm) H3 H4 D4 D5 W3 W4 W5

6U, 1/2 × 19'' 190.5 259 82.5 160.5 229.4 263.4 246.4

38 PCS-902S Line Distance Relay


Installation
Surface mounting

Case size (mm) H5 D6 D7 W6

6U, 1/2 × 19'' 254.5 4~10 243—D6 212.4

PCS-902S Line Distance Relay 39


Installation
Wall Mounting

Note: The wall mounting method needs special mounting accessory for wall support.

40 PCS-902S Line Distance Relay


Installation

Case size (mm) H6 H7 D8 W7 W8

6U, 1/2 × 19'' 320 280 292 280.4 248.4

Rack Mounting

⚫ Cut-out

PCS-902S Line Distance Relay 41


Installation

⚫ Single 6U, 1/1 × 19''

⚫ Single 6U, 1/2 × 19''

42 PCS-902S Line Distance Relay


Installation

⚫ Dual 6U, 1/2 × 19''

PCS-902S Line Distance Relay 43


Installation

44 PCS-902S Line Distance Relay


Technical Data
Technical Data

Electrical Specifications

AC Current Input

Phase rotation ABC or ACB

Nominal frequency (fn) 50Hz, 60Hz

Rated current (In) 1A/5A (settable)

Linear to 0.05In~40In

Thermal withstand

-continuously 4In

-for 10s 30In

-for 1s 100In

-for half a cycle 250In

Burden <0.05VA/phase @1A, <0.25VA/phase @5A

AC Voltage Input

Phase rotation ABC or ACB

Nominal frequency (fn) 50Hz, 60Hz

Rated voltage (Un) 100V~130V

Linear to 1V~300V

Thermal withstand Phase-to-ground Phase-to-phase

-continuously 300V 519V

-10s 600V 1038V

-1s 660V 1141V

Burden at rated <0.10VA/phase @100V

Power Supply

Rated voltage 24/30/48/60Vdc 110/125/220/250Vdc

PCS-902S Line Distance Relay 45


Technical Data
IEC 61000-4-11:2017

Permissible voltage range IEC 61000-4-29:2000

18~72Vdc 88~300Vdc

IEC 60255-26:2013
Permissible AC ripple voltage
≤15% of the nominal auxiliary voltage

Quiescent condition <15W (default hardware configuration)

Additional for each


0.25W~0.35W
energized SFP socket

Quiescent condition: <1W

0.004W @ 24Vdc

0.015W @ 48Vdc

Additional for each energized binary 0.080W @ 110Vdc

input (common negative supply) 0.106W @ 125Vdc

0.320W @ 220Vdc
Additional for each binary
Burden 0.410W @ 250Vdc
input (BI) module
0.014W @24Vdc

0.031W @48Vdc

Additional for each energized binary 0.096W @110Vdc

input (independent negative supply) 0.115W @125Vdc

0.270W @220Vdc

0.330W @250Vdc

Additional for each binary Quiescent condition: <0.1W

output (BO) module Additional for each energized relay: <0.44W

Additional module for SV


<7W
sampling

Power Supply

Rated voltage 100/110/115/120/127/220/230/240/250Vac

46 PCS-902S Line Distance Relay


Technical Data
IEC 61000-4-11:2017

Permissible voltage range IEC 61000-4-29:2000

80~275Vac

IEC 60255-26:2013
Permissible AC ripple voltage
≤15% of the nominal auxiliary voltage

Quiescent condition <15W (default hardware configuration)

Additional for each


0.25W~0.35W
energized SFP socket

Quiescent condition: <1W

0.004W @ 24Vdc

0.015W @ 48Vdc
Additional for each energized
0.080W @ 110Vdc
binary input (common negative
0.106W @ 125Vdc
supply)
0.320W @ 220Vdc
Additional for each binary
Burden 0.410W @ 250Vdc
input (BI) module
0.014W @24Vdc

0.031W @48Vdc
Additional for each energized
0.096W @110Vdc
binary input (independent negative
0.115W @125Vdc
supply)
0.270W @220Vdc

0.330W @250Vdc

Additional for each binary Quiescent condition: <0.1W

output (BO) module Additional for each energized relay: <0.44W

Additional module for SV


<7W
sampling

Settable pickup voltage and dropout voltage (common negative supply)

Rated voltage 110Vdc 125Vdc 220Vdc 250Vdc

PCS-902S Line Distance Relay 47


Technical Data
Rated current drain 0.73mA 0.83mA 1.47mA 1.67mA

On value (default set) 69.3~132Vdc 78.75~160Vdc 138.6~264Vdc 157.5~300Vdc

Off value (default set) <55Vdc <62.5Vdc <110Vdc <125Vdc

Maximum permissible voltage 300Vdc

Withstand voltage 2000Vac, 2800Vdc (1 min)

Settable pickup voltage and dropout voltage (common negative supply)

Rated voltage 110Vac 220Vac

On value (default set) 69.3~132Vac 138.6~264Vac

Off value (default set) <55Vac <110Vac

Maximum permissible voltage 300Vac

Withstand voltage 2000Vac, 2800Vdc (1 min)

Settable pickup voltage and dropout voltage (common negative supply)

Rated voltage 24Vdc 48Vdc

Rated current drain 0.16mA 0.32mA

On value (default set) 15.12~28.8Vdc 30.24~57.6Vdc

Off value (default set) <12Vdc <24Vdc

Maximum permissible voltage 300Vdc

Withstand voltage 2000Vac, 2800Vdc (1 min)

Settable pickup voltage and dropout voltage (independent negative supply)

Rated voltage 110Vdc 125Vdc 220Vdc 250Vdc

Rated current drain 0.86mA 0.92mA 1.23mA 1.33mA

On value (default set) 69.3~132Vdc 78.75~160Vdc 138.6~264Vdc 157.5~300Vdc

Off value (default set) <55Vdc <62.5Vdc <110Vdc <125Vdc

Maximum permissible voltage 300Vdc

Withstand voltage 2000Vac, 2800Vdc (1 min)

48 PCS-902S Line Distance Relay


Technical Data
Settable pickup voltage and dropout voltage (independent negative supply)

Rated voltage 110Vac 220Vac

On value (default set) 69.3~132Vac 138.6~264Vac

Off value (default set) <55Vac <110Vac

Maximum permissible voltage 300Vac

Withstand voltage 2000Vac, 2800Vdc (1 min)

Settable pickup voltage and dropout voltage (independent negative supply)

Rated voltage 24Vdc 48Vdc

Rated current drain 0.58mA 0.66mA

On value (default set) 15.12~28.8Vdc 30.24~57.6Vdc

Off value (default set) <12Vdc <24Vdc

Maximum permissible voltage 300Vdc

Withstand voltage 2000Vac, 2800Vdc (1 min)

Binary Output: Tripping/signaling contact

Output mode Potential free contact

Max. system voltage 250Vac, 300Vdc

Continuous carry 10A

Pickup time (Typical value) <5ms

Dropoff time (Resistive load) <6ms

0.5A@48Vdc

0.35A@110Vdc

Breaking capacity (L/R=40ms) 0.30A@125Vdc

0.20A@220Vdc

0.15A@250Vdc

0.5A@48Vdc
Cyclic capacity (2.5 cycle/second,
0.35A@110Vdc
L/R=40ms)
0.30A@125Vdc

PCS-902S Line Distance Relay 49


Technical Data
0.20A@220Vdc

0.15A@250Vdc

30A@3s
Short duration current
50A@1s

Durability (Loaded contact) 10000 operations

Binary Output: Heavy-capacity tripping contact

Output mode Potential free contact

MOV protection (maximum voltage) 350Vdc, 275Vac

Continuous carry 10A

Pickup time (Typical value) <1ms

Dropoff time (Resistive load) <10ms

10A@48V

10A@110V
Breaking capacity (L/R=40ms)
10A@125V

10A@250V

10A@48V L/R=40ms
Cyclic capacity (4cycles in 1 second,
10A@110V L/R=40ms
followed by 2 minutes idle for thermal
10A@125V L/R=40ms
dissipation)
10A@250V L/R=20ms

30A@3s
Short duration current
50A@1s

Durability (Loaded contact) 10000 operations

Mechanical Specifications

Chassis color Silver grey

Weight per device Approx. 8.66kg (6U, 1/2 × 19'')

Approx. 13.88kg (6U, 1/1 × 19'')

Chassis material Aluminum alloy

50 PCS-902S Line Distance Relay


Technical Data
Location of terminal Rear panel of the device

Device structure Plug-in modular type @ rear side, integrated frontplate

Protection Class

Standard IEC 60529-2013

Front side IP52

IP54 (valid for surface mounting mode of 6U, 1/2 × 19'' case with sealing strip)

Other sides IP50

Rear side, connection terminals IP20

Ambient Temperature and Humidity Range

Standard IEC 60255-1:2009

-40°C to +80°C (Readability of display may be impaired below -20°C and


Operating temperature
above 70℃ )

Transport and storage temperature


-40°C to +80°C
range

Permissible humidity 5%-95%, without condensation

Pollution degree Ⅱ

Altitude <3000m

Communication Port

EIA-485 Port

Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s

Protocol IEC 60870-5-103:1997 or Modbus

Max. capacity 32

Max. transmission distance 500m

Safety level Isolation to ELV level

Twisted pair Screened twisted pair cable

PCS-902S Line Distance Relay 51


Technical Data
Ethernet Port

Connector type RJ-45

Transmission standard 100Base-TX

Max. transmission distance 100m

Protocol IEC 60870-5-103:1997, DNP 3.0 or IEC 61850

Safety level Isolation to ELV level

Ethernet Port

Connector type LC

Characteristics Glass optical fiber

Fibre type Multi-mode

Wave length 1310nm

Transmission standard 100Base-FX

Max. transmission distance 2km

Min. transmission power 50μm: -24dBm 62.5μm: -20dBm

Min. receiving power -31dBm

Protocol IEC 60870-5-103:1997, DNP 3.0 or IEC 61850

Safety level Isolation to ELV level

Optical Fibre Port: For Process Level

Characteristics Glass optical fiber

Connector type LC

Fibre type Multi-mode

Transmission standard 100Base-FX

Max. transmission distance 2km

Wave length 1310nm/850nm

Min. transmission power -20dBm

Min. receiving power -31dBm

52 PCS-902S Line Distance Relay


Technical Data
Optical Fibre Port: For Pilot Communications

Characteristic Glass optical fiber

Connector type ST or FC

Fibre type Single mode Multi-mode

Wave length 1310nm 1550nm 850nm

Transmission power -11.0dBm~-7.0dBm 0dBm~5dBm 62.5μm: -20dBm~-12dBm

Min. receiving power -38dBm -36dBm 62.5μm: -32dBm

Max. transmission distance 60km 120km 62.5μm: 2km

Print Port

Type RS-232

Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s

Printer type EPSON® 300K printer

Safety level Isolation to ELV level

Clock Synchronization Port

Type Serial port

Input Demodulated IRIG-B or PPS

Nominal voltage 5Vdc±10%

Maximum voltage 5.5Vdc

Input impedance 2.5kΩ

Isolation 500Vdc

Clock Synchronization Port

Type BNC port (Female connector)

Input Demodulated IRIG-B or PPS

Nominal voltage 5Vdc±10%

Maximum voltage 5.5Vdc

Characteristic impedance 50Ω

PCS-902S Line Distance Relay 53


Technical Data
Isolation 500Vdc

Type Tests

Environmental Tests

Dry cold test IEC60068-2-1:2007

Dry heat test IEC60068-2-2:2007

Damp heat test, cyclic IEC60068-2-30:2005

Mechanical Tests

Vibration IEC 60255-21-1:1988 Class Ⅰ

Shock and bump IEC 60255-21-2:1988 Class Ⅰ

Electrical Tests

Standard IEC 60255-27:2013

Dielectric tests Test voltage 2kV, 50Hz, 1min

Impulse voltage tests Test voltage 5kV

Overvoltage category Ⅲ

Insulation resistance measurements Isolation resistance >100MΩ@500VDC

Electromagnetic Compatibility

IEC 60255-26:2013

1MHz burst disturbance test Common mode: class Ⅲ 2.5kV

Differential mode: class Ⅲ 1.0kV

IEC 61000-4-2-2008 class Ⅳ

Electrostatic discharge test For contact discharge: 8kV

For air discharge: 15kV

IEC 60255-26:2013 class Ⅲ

Radio frequency interference tests Frequency sweep

Radiated amplitude-modulated

54 PCS-902S Line Distance Relay


Technical Data
10V/m (rms), f=80~1000MHz, 1400~2700MHz

Spot frequency

Radiated amplitude-modulated

10V/m (rms), f=80MHz/160MHz/450MHz/900MHz

IEC 60255-26:2013

Fast transient disturbance tests Power supply, I/O, Earth: class Ⅳ, 4kV, 5kHz, 5/50ns

Communication terminals: class Ⅳ, 2kV, 5kHz, 5/50ns

IEC 60255-26:2013

Power supply, AC input, I/O port: class Ⅳ, 1.2/50μs


Surge immunity test
Common mode: 4kV

Differential mode: 2kV

IEC 60255-26:2013

Power supply, AC, I/O, Comm. Terminal: Class Ⅲ , 10V (rms), 150
Conducted RF electromagnetic
kHz~80MHz
disturbance
Spot frequency

10V (rms), f=27MHz/68MHz

Power frequency magnetic field IEC 61000-4-8: 2009

immunity class Ⅴ, 100A/m for 1min, 1000A/m for 3s

IEC 61000-4-9:2016
Pulse magnetic field immunity
class Ⅴ, 6.4/16μs, 1000A/m for 3s

Damped oscillatory magnetic field IEC 61000-4-10:2016

immunity class Ⅴ, 100kHz & 1MHz–100A/m

IEC 60255-26:2013

Conducted emission 0.15MHz~0.50MHz: 79dB (μV) quasi peak, 66dB (μV) average

0.50MHz~30MHz: 73dB (μV) quasi peak, 60dB (μV) average

IEC 60255-26:2013

30MHz~230MHz: 40dB (μV/m) quasi peak @10m, 50dB


Radiated emission
Below 1GHz (μV/m) quasi peak @3m

230MHz~1000MHz: 47dB (μV/m) quasi peak @10m, 57dB

PCS-902S Line Distance Relay 55


Technical Data
(μV/m) quasi peak @3m

1GHz~3GHz: 56dB (μV/m) average, 76dB (μV/m) peak

@3m
Above 1GHz
3GHz~6GHz: 60dB (μV/m) average, 80dB (μV/m) peak

@3m

IEC 60255-26:2013

Up to 200ms for dips to 40% of rated voltage without reset


Auxiliary power supply performance
50ms for interruption without rebooting without energy storage board (Typical
- Voltage dips
configuration)
-Voltage short interruptions
500ms for interruption without rebooting with energy storage board (Typical

configuration)

Liquid Crystal Display (LCD)

Type Resolution

Large size 320x240 pixels

Terminals

⚫ Ring Ferrule

Connection Type Wire Size Screw Type Torque

AC current Screw terminals, 1.5~4mm2 lead M4 1.6~1.8 N·m

AC voltage Screw terminals, 0.8~4mm2 lead M4 1.6~1.8 N·m

Power supply Screw terminals, 0.8~4mm2 lead M4 0.8~1.4 N·m

Contact I/O Screw terminals, 0.8~4mm2 lead M4 0.8~1.4 N·m

Grounding (Earthing) connection BVR type, 0.8~4mm2 lead M3 0.6~0.8 N·m

⚫ Pin Ferrule

Connection Type Wire Size Screw Type Torque

Power supply Screw terminals, 0.3~3.3mm2 lead M2.5 0.4~0.6 N·m

Contact I/O Screw terminals, 0.3~3.3mm2 lead M2.5 0.4~0.6 N·m

56 PCS-902S Line Distance Relay


Technical Data
Measurement Scope and Accuracy

Item Range Accuracy

±0.2° at 0.2×In<I<4.0×In
Phase range 0°~360°
±0.5° at 0.1×In<I<0.2×In

Frequency fn±5Hz Max. 0.002Hz

±0.2% of I at 0.2×In<I<4.0×In
Current 0.06~4.00In
±0.6% of I at 0.06×In<I<0.2×In

Voltage 5~300V 0.2% of U at 5V<U<300V

±0.5% of P, @Un, at 0.1×In<I<4.0×In


Active power (W) 0.06~4.00In
±1% of P, @Un, at 0.06×In<I<0.1×In

±0.5% of Q, @Un, at 0.1×In<I<4.0×In


Reactive power (VAr) 0.06~4.00In
±1% of Q, @Un, at 0.06×In<I<0.1×In

±0.5% of S, @Un, at 0.1×In<I<4.0×In


Apparent power (VA) 0.06~4.00In
±1% of S, @Un, at 0.06×In<I<0.1×In

±0.5% of Wh, @Un, at 0.1×In<I<4.0×In


Energy (Wh) 0.06~4.00In
±1% of Wh, @Un, at 0.06×In<I<0.1×In

±0.5% of VArh, @Un, at 0.1×In<I<4.0×In


Energy (VArh) 0.06~4.00In
±1% of VArh, @Un, at 0.06×In<I<0.1×In

Management Function

Control Performance

Control mode Local or remote

Response time of local control ≤1s

Response time of remote control ≤3s

Clock Performance

Real time clock accuracy ≤1s/day

Accuracy of GPS synchronization ≤1ms

PCS-902S Line Distance Relay 57


Technical Data
External time synchronization IRIG-B (200-98), PPS, IEEE 1588 or SNTP protocol

Fault and Disturbance Recording

Duration & Recording position Settable pre-disturbance, post-disturbance and maximum recorded duration

Sampling rate Up to 9.6kHz

Binary Input Signal

Resolution of binary input signal ≤1ms

Binary input mode Potential-free contact

58 PCS-902S Line Distance Relay


Technical Data