DESCRIPTION
These packaged cooling/heating air conditioners are designed
for outdoor installation. Only utility and duct connections are
required at the point of installation.
FEATURES
• Operating Efficiency - All PCG6 model gas units provide a
minimum AFUE of 81.0% in heating and 16.0 SEER, 12.0
EER rating for cooling operation. All models meet California
TECHNICAL GUIDE Low-Nox requirements of 40 ng/joule emission level for Air
Quality Management Districts. All PCG6 models utilize a
SINGLE PACKAGE multi-stage compressor for maximum comfort and efficiency.
AIR CONDITIONER / GAS HEAT • On Site Flexibility - All model sizes use a compact design
16 SEER – R-410A – 208/230V - 3 PHASE cabinet. Field convertible duct connections from side flow to
downflow allows the installer to have greater flexibility with
3 THRU 5 NOMINAL TONS
less inventory.
65 - 125 MBH HEAT INPUT
• Lower Installation Cost - Installation time and costs are
MODELS: PCG6*36 THRU 60 reduced by easy power and control wiring connections. The
small base dimension means less space is required on the
ground or roof. All units are completely wired, charged with
R-410A and tested prior to shipment. Test stations using a
state-of-the-art computerized process system are used to
ensure product quality. Refrigerant charge and component
part numbers are verified via computers during assembly.
Vital run test statistics such as system pressure, motor cur-
rents, air velocity and temperature, unit vibration, and gas
system safeties are monitored and recorded by the system to
ensure unit performance. Equal size side supply and return
duct connections allow easy connection of ducts to match
low crawl spaces without transition pieces.
• Utility Connections Made Easy - Gas and electric utility
access provided through the bottom or the side of the unit.
Utility connections can be made quickly and with a minimum
amount of field labor. A field supplied and field installed elec-
trical disconnect switch must be installed.
® • Convertible Airflow Design - The bottom duct openings are
covered when they leave the factory, ready to be used for a
side supply/side return application. If a bottom supply/bottom
return application is desired, simply remove the two panels
from the bottom of the unit and place them in the side supply/
side return duct openings. No panel cutting is required and
no accessory panel is necessary. Convertible airflow design
Due to continuous product improvement, specifications allows maximum field flexibility and minimum inventory.
are subject to change without notice. • Condensate Pan - A corrosion-resistant, long-lasting, water-
tight pan is positioned below the evaporator coil to collect
Visit us on the web at
www.upgnet.com and www.york.com and drain all condensate, preventing build-up of stagnant
condensate. The condensate pan conforms to ASHRAE 62-
Additional rating information can be found at:
89 standards (Ventilation for Acceptable Indoor Air Quality).
www.ahridirectory.org • Condensate Drain - The 3/4 inch NPT female connection is
rigidly mounted to assure proper fit and leak tight seal.
WARRANTY SUMMARY* • Durable Finish - The cabinet is made of G90 galvanized
Standard 1-Year limited parts warranty. steel with a powder paint coating for appearance and protec-
Standard 5-Years limited compressor warranty. tion. The pre-treated galvanized steel provides a better paint-
10-Year gas heat exchanger warranty. to-steel bond, which resists corrosion and rust creep. Pow-
*See limited warranty certificate in User’s Information Manual for details der paint finish ensure less fading when exposed to sunlight,
and provides superior corrosion resistance (1000 hour salt
spray tested).
Continued on next page.
• Full Perimeter Base Rails - The easily removable base rails accomplished by the simultaneous operation of scroll bypass
provide a solid foundation for the entire unit and protects the and a temperature sensor which protect the compressor if
unit during shipment. The rails provide fork lift access from undesirable operating conditions occur.
all sides, and rigging holes are also provided so that an over- • Pressure Switches - A high pressure switch is standard in
head crane can be used to place the units on a roof. On all units. It is an automatic reset switch. When discharge
applications where the unit is placed on a pad, the base will pressure reaches 650 psi, the compressor de-energizes until
keep the unit off the pad to deter corrosion. On applications pressure reaches 450 psi.
where height is limited, the base rails may be removed by
• Exclusive Coil Design - Grooved copper tubes and
removing 2 screws in each corner.
enhanced aluminum fin construction improves heat transfer
• More Attractive Appearance - A single-piece top cover for maximum efficiency and durability for long-lasting durabil-
containing a top-discharge outdoor fan arrangement requires ity and efficient operation. Indoor coils use tin-coated copper
less square footage on installation and provides a wider vari- tubing with aluminum fins for effective heat transfer.
ety of installations. The one-piece design adds greater water
• Heat Exchangers - Gas heat exchangers use corrosion-
integrity. Rounded corners with water drip edges add to the
resistant, stainless-steel tubular construction to provide long-
attractive appearance.
life, trouble-free operation. Gas heat exchangers are offered
• Top Discharge - The top-discharge outdoor fan does not with lifetime warranties as standard with registration.
disrupt neighboring areas or dry out vegetation surrounding
• Post Purge Induced Draft Combustion - Exhausts com-
the unit. The warm air from the top mounted fan is blown up
bustion products from the heat exchanger upon completion
and away from the structure and any landscaping. This
of the heating cycle to prolong the heat exchanger life.
allows compact location on multi-unit applications.
• Spark To Burner Ignition - No pilot assembly required,
• Outdoor Coil Grille - All models utilize a stamped slotted
which provides more consistent ignition in gas heating mode.
design which provides superior impact protection against
This ignition is highly reliable, durable and eliminates nui-
small objects during transit and after installation.
sance lockouts.
• Low Operating Sound Level - The upward air flow carries
• Multi Port In-shot Burners - No field adjustment is required
the normal operating noise up and away from the living area.
to mix the air and gas for natural gas or propane use. These
The rigid top panel effectively isolates noise. Isolator
burners are constructed of high-grade corrosion-resistant,
mounted compressor and the rippled fins of the outdoor coil
aluminized steel.
muffle the normal fan motor and compressor operating
sounds. The uniquely formed base pan also aids in sound • Low Maintenance - Long life, permanently lubricated out-
attenuation with its structural design. This design strategi- door and evaporator fan motor bearings need no annual
cally places embossments in the pan for optimum strength maintenance, adding greater reliability to the unit. Slide-out
and rigidity. blower assembly can be easily removed for cleaning.
• Fan System - All models operate over a wide range of • Easy Service Access - Individual access panels covering
design conditions with an enhanced ECM indoor fan motor. the electrical and gas controls makes servicing easy. Remov-
These units easily match all types of applications and pro- ing this panel will allow easy removal of the blower assembly
vide greater on-site flexibility to match comfort requirements. for maintenance and ease of troubleshooting.
The cooling speed is factory-set and can be field-adjusted to • Replacement Parts - The installer requires no special train-
a second speed. The heating speed is factory set to maintain ing to replace any of the components of these units and the
mid point rise at the units heating input, but can be field number of new components have been reduced to minimize
adjusted. This allows maximum comfort conditions. the inventory of unique parts.
• Simple Control Circuit - A low voltage gas heat printed cir- • Loss of Charge Switch - All models include a loss of charge
cuit board contains a status/diagnostic indicator light. Field switch to provide safe shutdown of compressor.
thermostat wiring connects to color coded leads using twist • Filter Frame Kit - All 3 phase units include a filter frame kit
on wire connections. Cooling controls use contactor and which is shipped inside the unit from production. Field instal-
relays for simple application and troubleshooting. Mate-n- lation is required.
lock plug connectors are used. The electrical control box is
not located in the compressor compartment. The controls are • Filters - All 3 phase units include an applicable number of 1"
mounted to allow the separate access panel to be removed washable filters, which are shipped inside the unit from pro-
for trouble shooting and maintenance without affecting the duction. Field installation is required. Three filters are
normal system operating pressures. All wiring internal to the required for the B base units.
unit is color/number coded.
• Protected Compressor - The compressor is internally pro-
tected against high pressure and temperature. This is
NOMENCLATURE
PCG 4 A 24 50 2 X 1 A
1 2 3 4 5 6 7 8 9
1. Model Family 5. Gas Heating Input BTU/Hr x 1000
PCG - packaged A/C with gas heat, 050 = 50,000 BTU/Hr. input, blank = electric heat
PHG - packaged heat pump with gas heat,
6. Voltage-Phase-Frequency
PCE - packaged A/C with electric heat,
2 = 208/230-1-60, 3=208/230-3-60, 4 = 460-3-60
PHE - packaged heat pump with electric heat
2. Nominal Cooling Efficiency 7. NOx Approval
4 = 14 SEER, 6 = 16 SEER, etc. X = low-NOx, blank = not low-Nox
3. Cabinet Size 8. Generation Level
A = small 35 x 51, B = large 45 x 51 1 = first generation
4. Nominal Air Conditioning Cooling Capacity BTUx1000 9. Revision Level
24 = 24,000 BTU, etc. A = original release, B = second release
Examples:
PHG4B421002X1A is a dual fuel, 14 SEER, 3-1/2 ton, large cabinet, single-stage heat, 100,000 BTU gas heat, 230 volt, single phase, low-NOx
model (first generation, first release)
COMPONENT LOCATION
FAN MOTOR OUTDOOR FAN
OUTDOOR COIL
(Behind Panel)
CONTROL BOARD
BLOWER MOTOR TRANSFORMER
HIGH VOLTAGE
CONTACTOR
TXV
PRESSURE SWITCH
INDOOR COIL
DRAFT INDUCER BLOWER
INDOOR BLOWER
GAS VALVE
COMPRESSOR GAS HEAT
EXCHANGER
REMOVABLE BURNER
BASE RAILS ASSEMBLY
A0297-001
UNIT LIMITATIONS
Unit Limitations
Model Unit Voltage Applied Voltage Outdoor DB Temp
Min Max Max (°F)
All Models 208/230-3-60 187 252 125
• Economizer for Horizontal Applications • Roof Curbs (S1-1RC0503, S1-1RC0501) - NRCA approved
(S1-2EE04710224, S1-2EE04710324) - Modulating inte- curbs provide proper fit to base unit for rooftop installations.
grated economizer provides simultaneous operation Curbs are designed to be assembled through hinge pins in
between the mechanical cooling and economizer operation. each corner. Kit also provides seal strip to assure an air tight
Independent blade design ensures proper control and less seal. These are 8 inch high roof curbs.
than 1% leak rate. Includes hood and mesh bird screen filter • Roof Curbs (S1-1RC0504, S1-1RC0502) - NRCA approved
integrated into the hood, dry bulb sensor and relief damper. curbs provide proper fit to base unit for rooftop installations.
Separate field accessories of single enthalpy and dual Curbs are designed to be assembled through hinge pins in
enthalpy are also available. each corner. Kit also provides seal strip to assure an air tight
• Single/Dual Enthalpy Sensor (S1-HE-6863-0N00WS) - seal. These are 14 inch high roof curbs.
Sensor replaces dry bulb sensor standard in economizer kit. • Transition Curb Kits (S1-1TC01*) - Adapter kits to allow
Provides improved economizer operation by sensing the dry field use of pre-existing installed roof curbs to match PCG6*
bulb temperature from outdoors plus the enthalpy content of footprint to Affinity roof curbs, Carrier, Trane, or Goodman
the outdoor air. curb footprints. Curb adapters are optional for current gener-
• Duct/Unit Mount CO2 Kit (S1-2AQ04700924) - Sensor kit ation Carrier replacements but are recommended for previ-
detects CO2 levels automatically and overrides the econo- ous generation applications. Refer to the PCG6* price pages
mizer when CO2 levels rise above the preset limits. for more details.
• Wall Mount CO2 Kit (S1-2AQ04701024) - Sensor kit • Manual Outdoor Damper (S1-1FA0502, S1-1FA0501) -
detects CO2 levels automatically and overrides the econo- Provides 0% through 50% outdoor air capability (field adjust-
mizer when CO2 levels rise above the preset limits. able). Designed for duct mounted side supply/return
applications. Includes hood and screen assembly.
• Supply Air Temperature Sensor Kit (S1-TE-63616E-2D) -
Outdoor supply air temperature sensor kit used with econo- • Thermostat (S1-THXU280*) - Compatible thermostat con-
mizers. trols are available through accessory sourcing. For optimum
performance, these outdoor units are fully compatible with
• Filter/Frame Kit (Kit provided) the York Hx™ Touchscreen Thermostat (S1-THXU280*)
(S1-1FF0602, S1-1FF0601) - Kit contains the necessary available through Source1. For more information, see the
hardware to field install return air filters into the base unit. thermostat section of the Product Equipment Catalog.
The filter rack is suitable for either 1" or 2" filters.
• Wall Thermostat - The units are designed to operate with
• Filter (S1-02647812000) - Washable 1” filter. Three filters standard, 24-volt electronic and electro-mechanical thermo-
are required for the B base units. Washable filters are stats. All units can operate with a single stage heat thermo-
included inside shipped units for field installation. stat, but requires a multistage thermostat for cooling.
• Motorized Fresh Air Damper
• Loss of Charge Switch (S1-2LC00024) - Kit provides Loss
(S1-2MD04705224, S1-2MD04705124) - Designed for duct
mounted side supply/return and unit mounted down supply/ of Charge Switch and wiring to provide safe shutdown of
return applications. Damper capable of providing 0% through compressor.
50% of outdoor air (field supplied). Closes on power loss, • Low Ambient Kit (S1-2LA04701024) - Kit provides neces-
includes hood and screen assembly. sary hardware to convert unit to operate in cooling cycle
down to 0º F. Standard unit operation 45º F.
• Base Rail Hole Cover Kit (S1-1HC0101) - Kit provides nec-
essary hardware to close off openings in base rails to block
off openings, i.e. prevent animal entrance.
GUIDE SPECIFICATIONS Indoor Blower Assembly - Fan shall be direct drive design.
GENERAL Fan wheel shall be double-inlet type with forward-curved
Units shall be manufactured by Unitary Products in an ISO blades, dynamically balanced to operate smoothly throughout
9001 certified facility. Package units give you the flexibility and the entire range of operation. Airflow design shall be constant
choices you need in today’s market. These packaged cooling/ air volume. Bearings shall be sealed and permanently
heating air conditioners are designed for outdoor installation. lubricated for longer life and no maintenance. Fan assembly
Only utility and duct connections are required at the point of shall be a slide-out design for easy removal and cleaning.
installation. The single-stage gas fired heaters have stainless Indoor blower motors shall be equipped with a standard high
steel tubular heat exchangers and spark to burner ignition. efficiency brushless DC motor (constant torque) also known as
They are available in natural gas with field conversion to a standard ECM motor.
propane. Outdoor Fan Assembly - The outdoor fan shall be of the
DESCRIPTION direct-driven propeller type, discharge air vertically, have
Units shall be factory-assembled, single packaged, Electric aluminum blades riveted to corrosion resistant steel spider
Cooling/Gas Heating units, designed for outdoor installation. bracket and shall be statically balanced for smooth operation.
For SEER ratings, refer to technical literature. They shall have The outdoor fan motor shall be totally enclosed with
built in, equal size, field convertible duct connections for supply/ permanently lubricated bearings and internally protected
return or horizontal supply/return. The units shall be factory against overload conditions.
wired, piped, charged with R-410A Refrigerant and factory REFRIGERANT COMPONENTS
tested prior to shipment. All unit wiring shall be both numbered Compressors:
and color coded. All models shall be rated in accordance with a. Shall be fully hermetic type, direct drive, internally pro-
DOE and AHRI test procedures for both heating and cooling tected with internal high-pressure relief and over tempera-
operation. Units shall be CSA listed and classified to ANSI ture protection. The hermetic motor shall be suction gas
Z21.47/CAN/ CSA 2.3 standards and UL 1995/CAN/CSA No. cooled and have a voltage range of +/- 10% of the unit
236-M90 standards. nameplate voltage.
UNIT CABINET b. Shall have internal isolation and sound muffling to mini-
Unit cabinet shall be constructed of G-90 galvanized, powder- mize vibration and noise, and be externally isolated on a
painted steel, certified at 1000 hours salt spray test per ASTM- dedicated, independent mounting.
B117 standards. The unit top shall be a single piece design, Coils:
with drip edges and no-seam corners to provide optimum water a. Indoor coils shall have aluminum plate fins mechanically
integrity. Unit shall have a rigidly mounted outdoor coil guard to bonded to seamless internally enhanced tin-coated cop-
provide protection from objects and personnel after installation. per tubes with all joints brazed.
Indoor blower section shall be insulated with foil-faced or foam b. Indoor coil shall be of the direct expansion, draw through
insulation, fastened to prevent insulation from entering the air design.
stream. Cabinet panels shall be separate, easily removable for c. Outdoor coils shall have aluminum plate fins mechanically
servicing and maintenance. Unit shall be built on a formed, bonded to seamless internally enhanced copper tubes
design base pan, with embossments at critical points to add with all joints brazed.
strength and rigidity and to aid in minimizing sound. Full d. Outdoor coil shall be draw through design.
perimeter base rails shall be provided to assure reliable transit Refrigerant Circuit and Refrigerant Safety Components
of equipment, overhead rigging, for truck access and proper shall include:
sealing on roof curb applications. Base rails shall be easily
a. Thermal expansion devices (TXVs) shall be factory
removable, when required to lower unit height. Filters shall be
mounted and provided.
field installed, furnished and be accessible through a removable
b. Filter/strainer to eliminate any foreign matter.
access door, sealed airtight. Units vertical discharge and return
duct configuration shall be designed to fit between standard 24”
O.C. beams without modification to building structure, duct work
and base unit. Condensate pan shall be internally sloped and
conform to ASHRAE 62-89 self-draining standards, with 3/4”
NPT female ridged mount connection.
GAS HEATING SECTION (If Equipped) Heating section shall be provided with the following minimum
Heat exchanger and exhaust system shall be constructed of protection:
corrosion-resistant materials and shall be designed with a. Primary high-temperature limit switch.
induced draft combustion with post purge logic and redundant b. Induced draft pressure switch.
main gas valve. The heat exchanger shall be of the tubular c. Flame roll out switch(es) (manual reset).
type, constructed of stainless steel for corrosion resistance and d. Flame proving controls.
allowing minimum mixed air entering temperature of 40 ºF. All gas heat models will meet the California requirement for
Burners shall be of the in-shot type, constructed of emissions of less than 40 nanograms per Joule (California
aluminumized steel. All gas piping shall enter the unit cabinet at requirement on single phase models only).
a single location through either the side or bottom, without any
field modifications. An integrated control board shall provide
timed control of indoor fan functioning and burner ignition.
PHYSICAL DATA
MODELS
NOMINAL TONNAGE PCG6B36 PCG6B42 PCG6B48 PCG6B60
3.0 3.5 4.0 5.0
AHRI Cooling Performance
Gross Capacity @ AHRI A point (MBH) 36.5 43.3 49.1 60.0
AHRI net capacity (MBH) 36.0 42.5 45.5 58.0
EER 12.5 12.5 12.0 12.0
SEER 16.0 16.0 16.0 16.0
Nominal CFM 1200 1400 1600 2000
System power (KW) 3.0 3.4 3.6 4.6
Refrigerant type R410A R410A R410A R410A
Refrigerant charge (lb-oz) 11-8 11-4 13-8 14-0
AHRI Gas Heat Performance
Heating model 65 100 65 100 65 100 125 65 100 125
Heat input - High Fire (KBtu) 65 100 65 100 65 100 125 65 100 125
Heat output - High Fire (KBtu) 52 81 52 81 52 81 101 52 81 101
Heat input - Low Fire (KBtu) 43 65 43 65 43 65 82 43 65 82
Heat output - Low Fire (KBtu) 34 53 34 53 34 53 66 34 53 66
AFUE % 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0
No. burners 2 3 2 3 2 3 4 2 3 4
No. stages 2 2 2 2 2 2 2 2 2 2
Temperature Rise Range - High Fire (°F) 40-70 40-70 40-70 40-70
Temperature Rise Range - Low Fire (°F) 25-55 25-55 25-55 25-55
Max. Static Pressure w.c. 0.5 0.5 0.5 0.5
Max. Outlet Air Temp. (°F) 180 180 180 180
Gas piping connection (in.) 1/2 1/2 1/2 1/2
Dimensions (inches)
Length 51-1/4 51-1/4 51-1/4 51-1/4
Width 45-3/4 45-3/4 45-3/4 45-3/4
Height 49 49 53 55
Compressor
Type Scroll Scroll Scroll Scroll
Stages 2 2 2 2
Outdoor Coil Data
Face area (Sq. Ft.) 19.5 19.5 23.8 25.9
Rows 2 2 2 2
Fins per inch 22 22 22 22
Tube diameter 3/8 3/8 3/8 3/8
Circuitry Type Interlaced Interlaced Interlaced Interlaced
Continued on next page.
COOLING PERFORMANCE DATA - 3.5 TON (LOW SPEED) - MODEL NO. PCG6B42
CONDENSER ID CFM 800 1000 1200
ENTERING AIR IDDB 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
TEMPERATURE IDWB 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 30.2 33.8 24.4 36.3 39.4 33.3 36.0 26.3 37.9 40.4 36.4 38.2 28.1 39.5 41.3
55 / 45 S.C. 29.7 26.3 23.9 21.8 18.2 32.0 29.6 25.8 23.8 19.3 34.4 32.8 27.6 25.9 20.4
K.W. 0.97 0.96 0.93 0.98 0.98 0.97 0.97 0.94 1.00 1.00 0.97 0.97 0.94 1.01 1.01
T.C. 27.7 32.0 23.2 34.8 37.3 30.3 34.0 25.4 36.6 38.9 32.8 36.0 27.6 38.4 40.6
65 / 55 S.C. 27.3 25.4 22.6 21.3 17.5 29.5 28.7 24.7 23.6 19.0 31.7 31.9 26.8 25.9 20.5
K.W. 1.13 1.11 1.09 1.14 1.10 1.13 1.12 1.09 1.15 1.11 1.12 1.13 1.09 1.15 1.13
T.C. 25.2 30.1 22.1 33.3 35.1 27.2 32.0 24.6 35.3 37.5 29.2 33.9 27.1 37.3 40.0
75 / 63 S.C. 25.0 24.5 21.2 20.9 16.9 27.0 27.8 23.6 23.5 18.7 29.0 31.1 26.0 26.0 20.5
K.W. 1.29 1.26 1.25 1.29 1.22 1.28 1.27 1.24 1.30 1.23 1.27 1.28 1.24 1.30 1.25
T.C. 22.4 27.0 21.1 31.1 34.4 24.1 29.0 23.5 33.0 35.8 25.9 31.0 26.0 34.9 37.2
85 / 69 S.C. 22.2 22.4 20.2 19.6 16.0 23.9 25.8 22.5 22.2 17.6 25.7 29.1 24.8 24.8 19.3
K.W. 1.48 1.47 1.45 1.49 1.43 1.48 1.48 1.45 1.49 1.44 1.48 1.49 1.45 1.50 1.45
T.C. 19.6 23.9 20.1 28.9 33.8 21.0 26.0 22.5 30.7 34.1 22.5 28.2 24.8 32.5 34.4
95 / 75 S.C. 19.4 20.3 19.2 18.3 15.0 20.9 23.7 21.4 21.0 16.5 22.3 27.1 23.6 23.7 18.0
K.W. 1.67 1.68 1.66 1.68 1.63 1.69 1.69 1.66 1.69 1.64 1.70 1.70 1.66 1.70 1.65
T.C. 17.0 20.4 18.8 25.0 29.8 18.6 22.2 21.1 27.0 31.3 20.2 23.9 23.4 29.0 32.9
105 / 83 S.C. 16.8 18.0 17.9 17.6 13.4 18.4 20.6 20.0 20.2 14.9 20.0 23.2 22.1 22.7 16.3
K.W. 1.94 1.94 1.92 1.94 1.90 1.95 1.95 1.92 1.95 1.91 1.96 1.96 1.93 1.95 1.92
T.C. 14.5 17.0 17.5 21.2 25.8 16.2 18.4 19.8 23.4 28.7 18.0 19.8 22.0 25.6 31.5
115 / 89 S.C. 14.4 15.8 16.6 17.0 11.9 16.1 17.6 18.6 19.3 13.3 17.8 19.4 20.7 21.7 14.7
K.W. 2.19 2.20 2.17 2.19 2.16 2.20 2.20 2.18 2.20 2.17 2.21 2.21 2.19 2.20 2.18
T.C. 12.0 13.6 16.2 17.4 21.9 13.9 14.7 18.5 19.8 26.0 15.8 15.8 20.7 22.1 30.1
125 / 95 S.C. 11.9 13.5 15.3 16.3 10.3 13.7 14.6 17.3 18.5 11.7 15.6 15.6 19.3 20.8 13.1
K.W. 2.45 2.45 2.42 2.44 2.42 2.46 2.46 2.44 2.45 2.43 2.47 2.47 2.46 2.45 2.44
COOLING PERFORMANCE DATA - HIGH - 3.5 TON (HIGH SPEED) - MODEL NO. PCG6B42
CONDENSER ID CFM 1120 1320 1520
ENTERING AIR IDDB 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
TEMPERATURE IDWB 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 43.6 47.7 30.8 50.0 55.0 45.8 49.6 31.8 51.4 55.8 48.1 51.4 32.8 52.8 56.7
55 / 45 S.C. 41.7 36.8 29.9 30.0 23.2 43.7 39.6 30.9 31.2 23.8 45.8 42.4 31.9 32.3 24.5
K.W. 2.19 2.22 2.17 2.16 2.16 2.29 2.30 2.26 2.22 2.21 2.39 2.39 2.36 2.27 2.26
T.C. 39.9 45.2 31.1 49.1 53.4 41.9 47.2 32.4 50.5 55.0 44.0 49.3 33.6 51.8 56.7
65 / 55 S.C. 38.6 35.7 29.9 29.6 23.2 40.5 38.8 31.2 31.1 24.3 42.5 41.8 32.4 32.6 25.4
K.W. 2.44 2.46 2.43 2.42 2.46 2.54 2.56 2.53 2.48 2.54 2.64 2.65 2.64 2.54 2.61
T.C. 36.1 42.7 31.4 48.3 51.8 38.0 44.9 33.0 49.6 54.2 39.9 47.1 34.5 50.8 56.6
75 / 63 S.C. 35.5 34.6 29.9 29.2 23.2 37.3 37.9 31.4 31.1 24.8 39.2 41.2 33.0 32.9 26.4
K.W. 2.68 2.71 2.69 2.67 2.77 2.79 2.81 2.80 2.74 2.86 2.90 2.91 2.91 2.80 2.95
T.C. 33.3 39.4 30.5 45.2 49.9 35.2 41.2 32.4 46.2 52.0 37.0 42.9 34.3 47.3 54.0
85 / 69 S.C. 32.8 33.0 29.0 27.8 22.0 34.5 35.3 30.8 30.0 23.4 36.3 37.6 32.7 32.2 24.8
K.W. 3.02 3.03 3.05 3.04 3.09 3.12 3.13 3.16 3.12 3.18 3.22 3.22 3.26 3.20 3.28
T.C. 30.5 36.0 29.7 42.0 48.0 32.3 37.4 31.9 42.9 49.7 34.1 38.8 34.1 43.8 51.4
95 / 75 S.C. 30.0 31.4 28.1 26.4 20.9 31.7 32.7 30.2 29.0 22.1 33.5 34.0 32.4 31.6 23.3
K.W. 3.35 3.35 3.40 3.41 3.41 3.45 3.45 3.51 3.50 3.51 3.54 3.54 3.61 3.59 3.60
T.C. 27.9 32.6 28.2 38.0 44.3 29.5 33.5 30.4 38.7 45.5 31.0 34.4 32.5 39.4 46.8
105 / 83 S.C. 27.5 29.1 26.6 24.7 19.2 29.0 30.1 28.7 27.1 20.3 30.5 31.0 30.7 29.5 21.5
K.W. 3.81 3.81 3.87 3.82 3.86 3.90 3.90 3.97 3.90 3.96 4.00 4.00 4.07 3.97 4.05
T.C. 25.4 29.3 26.8 34.1 40.6 26.7 29.7 28.9 34.7 41.5 28.0 30.1 31.0 35.2 42.4
115 / 89 S.C. 25.0 26.9 25.1 23.0 17.6 26.3 27.6 27.2 25.2 18.6 27.5 28.2 29.2 27.4 19.7
K.W. 4.25 4.25 4.32 4.21 4.30 4.35 4.34 4.42 4.28 4.39 4.44 4.44 4.52 4.35 4.49
T.C. 22.9 25.9 25.4 30.3 37.0 24.0 25.9 27.4 30.6 37.5 25.1 25.8 29.5 30.9 37.9
125 / 95 S.C. 22.5 24.7 23.7 21.3 15.9 23.6 25.1 25.6 23.4 17.0 24.6 25.4 27.6 25.4 18.0
K.W. 4.69 4.69 4.78 4.61 4.74 4.79 4.78 4.87 4.67 4.83 4.89 4.88 4.97 4.73 4.93
COOLING PERFORMANCE DATA - HIGH - 4 TON (HIGH SPEED) - MODEL NO. PCG6B48
CONDENSER ID CFM 1400 1600 1800
ENTERING AIR IDDB 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
TEMPERATURE IDWB 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 46.5 54.3 55.5 56.6 59.6 47.9 54.3 55.6 56.8 59.9 49.2 54.3 55.6 56.9 60.1
55 / 45 S.C. 45.7 41.3 35.4 35.0 27.8 47.2 43.3 36.8 35.0 28.0 48.7 45.2 38.2 35.0 28.1
K.W. 2.66 2.72 2.72 2.93 2.75 2.76 2.80 2.80 2.92 2.82 2.86 2.88 2.87 2.90 2.89
T.C. 43.8 51.2 52.2 54.8 58.3 44.9 51.7 52.7 54.8 58.7 46.1 52.1 53.3 54.9 59.1
65 / 55 S.C. 43.3 40.2 34.1 33.8 27.0 44.3 35.9 37.0 34.7 31.7 45.3 31.7 40.0 35.5 36.5
K.W. 2.93 3.06 2.98 3.11 3.13 3.03 3.06 3.06 3.15 3.16 3.13 3.06 3.14 3.19 3.20
T.C. 41.1 48.2 48.8 52.9 56.9 42.0 49.1 49.9 52.9 57.5 43.0 49.9 51.0 52.8 58.1
75 / 63 S.C. 41.0 39.1 32.9 32.6 26.1 41.5 28.6 37.3 34.3 35.5 41.9 18.2 41.8 36.0 44.9
K.W. 3.19 3.39 3.24 3.29 3.51 3.29 3.32 3.33 3.38 3.51 3.39 3.25 3.41 3.47 3.50
T.C. 40.3 45.2 46.3 49.4 53.8 40.1 45.6 46.8 49.2 54.0 39.9 46.1 47.2 48.9 54.2
85 / 69 S.C. 39.8 37.3 31.1 31.2 24.6 39.4 33.1 34.1 32.8 29.8 39.1 28.9 37.2 34.4 34.9
K.W. 3.55 3.66 3.58 3.72 3.77 3.64 3.67 3.66 3.77 3.81 3.74 3.67 3.75 3.81 3.85
T.C. 39.4 42.2 43.8 45.9 50.7 38.1 42.2 43.6 45.5 50.5 36.8 42.3 43.4 45.1 50.3
95 / 75 S.C. 38.6 35.5 29.3 29.7 23.1 37.4 37.6 30.9 31.2 24.1 36.2 39.7 32.6 32.7 25.0
K.W. 3.91 3.93 3.92 4.15 4.03 4.00 4.01 4.00 4.15 4.11 4.09 4.09 4.08 4.15 4.19
T.C. 34.6 37.5 39.1 41.7 46.5 34.0 37.9 39.0 41.3 46.1 33.4 38.3 38.9 40.9 45.7
105 / 83 S.C. 34.0 33.1 27.4 27.8 21.2 33.4 34.8 26.2 29.3 22.0 32.9 36.5 25.1 30.9 22.9
K.W. 4.42 4.49 4.43 4.65 4.58 4.51 4.54 4.47 4.65 4.63 4.59 4.60 4.52 4.65 4.68
T.C. 29.9 33.0 34.6 37.7 42.4 30.0 33.8 34.5 37.2 41.8 30.1 34.5 34.5 36.8 41.2
115 / 89 S.C. 29.5 30.7 25.5 26.0 19.3 29.6 32.1 21.7 27.6 20.1 29.8 33.5 17.9 29.1 20.8
K.W. 4.91 5.03 4.92 5.14 5.12 5.00 5.06 4.94 5.13 5.14 5.09 5.09 4.95 5.13 5.17
T.C. 25.2 28.4 30.1 33.6 38.2 26.0 29.6 30.1 33.2 37.5 26.8 30.7 30.1 32.7 36.7
125 / 95 S.C. 25.0 28.4 23.6 24.2 17.5 25.8 29.4 17.1 25.8 18.1 26.6 30.4 10.6 27.3 18.8
K.W. 5.41 5.58 5.41 5.62 5.66 5.50 5.58 5.40 5.62 5.66 5.58 5.58 5.39 5.62 5.65
81,77233$1(/
&251(53267
,1'225&2,/
&2,/*8$5'
+,*+92/7$*(
23(1,1*´
&
+,*+92/7$*(
&20%867,21$,5,17$.(
23(1,1*´
+($7(;&+$1*(5$&&(663$1(/
&2035(6625
$&&(663$1(/
)/8((;+$867+22'
&21'(16$7( $
'5$,1 %
%/2:(5
$&&(66 &21752/+($7 /2:92/7$*(23(1,1*´
3$1(/ $&&(663$1(/ *$66833/<+2/(´:,7+
*5200(723(1,1*2)´ $
UNIT DIMENSIONS
Dimensions
Model
A B C
36 51-1/4 45-3/4 49
42 51-1/4 45-3/4 49
48 51-1/4 45-3/4 53
60 51-1/4 45-3/4 55
UNIT CLEARANCES1 2
Direction Distance (in.) Direction Distance (in.)
Top3 36 Power Entry (Right Side) 36
Side Opposite Ducts 36 Left Side 24
Duct Panel 0 Bottom4 1
NOTES:
1. A 1" clearance must be provided between any combustible material and the supply air duct work.
2. The products of combustion must not be allowed to accumulate within a confined space and recirculate.
3. Units must be installed outdoors. Over hanging structure or shrubs should not obstruct condenser air discharge outlet.
4. Units may be installed on combustible materials made from wood or class A, B or C roof covering materials only if factory base rails are left in place as shipped.
SOUND PERFORMANCE
Model Sound Rating1 Octave Band Centerline Frequency (Hz)
(Tons) dB (A) 125 250 500 1000 2000 4000 8000
36 74 58.5 61.8 65.4 66.5 60.7 54.8 49.8
42 74 63.5 63.9 62.3 65 64 54.1 46.6
48 74 63.5 63.9 62.3 65 64 54.1 46.6
60 76 72.3 65.0 63.9 64 60 55.5 49.0
NOTES:
1. Rated in accordance with AHRI Standard 270.
"D"
CENTER OF
GRAVITY
COMPRESSOR
"A" "C"
FRONT
OF UNIT
"B" Y
X
A0295-001-TG
6833/< 5(7851
$,5'8&7 $,5'8&7
$ % $
$
Model A B
36, 42, 48, 60 13.6 14
ROOF CURB
INSTALLATION ROOF CURB
REAR DUCT INSTALLATION
BOTTOM DUCT
SLAB ON
GROUND
INSTALLATION
A0324-001
TO POWER SUPPLY
RETURN
AIR DUCT
SUPPLY
AIR DUCT
FIELD-SUPPLIED
DISCONNECT
SWITCH
CONDENSATE
DRAIN
MANUAL GAS
SHUTOFF VAVLE CONTROL WIRING TO
TO GAS INDOOR THERMOSTAT
SUPPLY LINE A0325-001
ROOF
CONDENSATE
DRAIN
TO POWER SUPPLY
CONTROL WIRING TO
INDOOR THERMOSTAT
RETURN
AIR DUCT SUPPLY
AIR DUCT A0326-001