You are on page 1of 37

VRF

Technical
Data Book
DVM S2
(R410A, 50/60Hz, HP)

Model : Energy efficiency / Standard Type


AM***AXVANH*EA
2. Specification
Standard - 50/60Hz
Model Name AM080AXVANH/EA AM100AXVANH/EA AM120AXVANH/EA
Outdoor unit module 1 - - -
Outdoor unit module 2 - - -
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Power Supply Ø, #, V, Hz 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60
Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 8 10 12
Performance Cooling kW 22.4 28.0 33.6
Capacity
Heating kW 25.2 31.5 37.8
Maximum number of connectable indoor units EA 14 18 21

Total capacity of the connected Min. kW 11.2 14.0 16.8


Indoor Units Max. kW 29.1 36.4 43.7
Cooling kW 4.84 6.29 8.77
Power Input
Heating kW 4.80 6.30 8.90
Cooling A 7.60 9.90 13.80
Power Current Input
Heating A 7.50 9.90 14.10
MCA A 19.0 23.0 26.0
Current
MFA A 25 32 32
EER Cooling W/W 4.63 4.45 3.83
Efficiency
COP Heating W/W 5.25 5.00 4.25
Body - GI Steel Plate GI Steel Plate GI Steel Plate
Casing Material
Base - GI Steel Plate GI Steel Plate GI Steel Plate
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Type - Inverter Scroll x 1 Inverter Scroll x 1 Inverter Scroll x 1
Output kW x n 4.60 x 1 6.67 x 1 6.67 x 1

Model Name - DS2GR7046FV* x 1 DS4GR7066FV* x 1 DS4GR7066FV* x 1


Compressor
Type - PVE PVE PVE
Oil
Initial charge cc x n 900 x 1 1,100 x 1 1,100 x 1

Type - Propeller Propeller Propeller


Discharge direction - Top Top Top
Quantity EA 1 1 1
Fan ㎥/min 174 188 205
Air Flow Rate
l/s 2,906 3,138 3,425

External Static mmAq 11 11 8


Max.
Pressure Pa 110 110 80
Type - BLDC Motor BLDC Motor BLDC Motor
Fan Motor
Output Wxn 630 x 1 630 x 1 630 x 1
2. Specification
Standard - 50/60Hz
Model Name AM080AXVANH/EA AM100AXVANH/EA AM120AXVANH/EA
Outdoor unit module 1 - - -
Outdoor unit module 2 - - -
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Type Braze connection Braze connection Braze connection
Liquid Pipe
Φ, ㎜ (inch) 9.52 (3/8) 9.52 (3/8) 12.70 (1/2)
Type Braze connection Braze connection Braze connection
Gas Pipe
Φ, ㎜ (inch) 19.05 (3/4) 22.22 (7/8) 28.58 (1-1/8)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length Max. [Equiv.] m 200[220] 200[220] 200[220]
(ODU-IDU)

Piping Piping length Max. m 90 90 90


(1st Branch-IDU)
Connections
Total piping
Max. m 1,000 1,000 1,000
length (System)
Level difference
(ODU in highest Max. m 110 110 110
position)

Level difference Max. m 110 110 110


(IDU in highest position)

Level difference Max. m 50 50 50


(IDU-IDU)

Transmission Min. ㎟ 0.75 0.75 0.75


Wiring Cable Remark - F1, F2 F1, F2 F1, F2
connections
Both indoor and Both indoor and Both indoor and
Power supply intake -
outdoor unit outdoor unit outdoor unit
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 5.5 5.5 6.2
Sound Pressure (Cooling) dB(A) 55 56 60
Sound
Sound Power (Cooling) dB(A) 75 78 81
Net Weight kg 171 183 187
Shipping Weight kg 185 197 201
External
Dimension Net Dimensions (WxHxD) ㎜ 930 x 1,695 x 765 930 x 1,695 x 765 930 x 1,695 x 765

Shipping Dimensions (WxHxD) ㎜ 998 x 1,887 x 829 998 x 1,887 x 829 998 x 1,887 x 829

Operating Cooling ℃ -5 ~ 50 -5 ~ 50 -5 ~ 50
Temp. Range Heating ℃ -25 ~ 24 -25 ~ 24 -25 ~ 24

NOTE
• Specification may be subject to change without prior notice.
1) Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°CDB, 19°CWB, Outdoor temperature 35°CDB, 24°CWB
- Heating : Indoor temperature 20°CDB, 15°CWB, Outdoor temperature 7°CDB, 6°CWB
- Equivalent refrigerant pipe length 5m, Level differences 0m
2) Performance of Multiple Module Outdoor unit is weighted average of Single Module outdoor units.
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
2. Specification
Standard - 50/60Hz
Model Name AM140AXVANH/EA AM160AXVANH/EA AM180AXVANH/EA
Outdoor unit module 1 - - -
Outdoor unit module 2 - - -
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Power Supply Ø, #, V, Hz 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60
Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 14 16 18
Performance Cooling kW 40.0 45.0 50.4
Capacity
Heating kW 45.0 50.4 56.7
Maximum number of connectable indoor units EA 26 29 32

Total capacity of the connected Min. kW 20.0 22.5 25.2


Indoor Units Max. kW 52.0 58.5 65.5
Cooling kW 10.68 11.50 13.94
Power Input
Heating kW 11.08 11.58 13.50
Cooling A 16.80 18.00 21.70
Power Current Input
Heating A 16.90 18.20 21.20
MCA A 29.0 34.0 39.2
Current
MFA A 32 40 50
EER Cooling W/W 3.75 3.91 3.62
Efficiency
COP Heating W/W 4.06 4.35 4.20
Body - GI Steel Plate GI Steel Plate GI Steel Plate
Casing Material
Base - GI Steel Plate GI Steel Plate GI Steel Plate
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Type - Inverter Scroll x 1 Inverter Scroll x 1 Inverter Scroll x 1
Output kW x n 6.67 x 1 8.93 x 1 8.93 x 1

Model Name - DS4GR7066FV* x 1 DS4GM7090FV* x 1 DS4GM7090FV* x 1


Compressor
Type - PVE PVE PVE
Oil
Initial charge cc x n 1,100 x 1 1,400 x 1 1,400 x 1

Type - Propeller Propeller Propeller


Discharge direction - Top Top Top
Quantity EA 1 2 2
Fan ㎥/min 201 293 313
Air Flow Rate
l/s 3,346 4,880 5,217

External Static mmAq 8 11 11


Max.
Pressure Pa 80 110 110
Type - BLDC Motor BLDC Motor BLDC Motor
Fan Motor
Output Wxn 630 x 1 620 x 2 620 x 2
2. Specification
Standard - 50/60Hz
Model Name AM140AXVANH/EA AM160AXVANH/EA AM180AXVANH/EA
Outdoor unit module 1 - - -
Outdoor unit module 2 - - -
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Type Braze connection Braze connection Braze connection
Liquid Pipe
Φ, ㎜ (inch) 12.70 (1/2) 12.70 (1/2) 15.88 (5/8)
Type Braze connection Braze connection Braze connection
Gas Pipe
Φ, ㎜ (inch) 28.58 (1-1/8) 28.58 (1-1/8) 28.58 (1-1/8)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length Max. [Equiv.] m 200[220] 200[220] 200[220]
(ODU-IDU)

Piping Piping length Max. m 90 90 90


(1st Branch-IDU)
Connections
Total piping
Max. m 1,000 1,000 1,000
length (System)
Level difference
(ODU in highest Max. m 110 110 110
position)

Level difference Max. m 110 110 110


(IDU in highest position)

Level difference Max. m 50 50 50


(IDU-IDU)

Transmission Min. ㎟ 0.75 0.75 0.75


Wiring Cable Remark - F1, F2 F1, F2 F1, F2
connections
Both indoor and Both indoor and Both indoor and
Power supply intake -
outdoor unit outdoor unit outdoor unit
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 7.0 8.0 8.0
Sound Pressure (Cooling) dB(A) 63 59 59
Sound
Sound Power (Cooling) dB(A) 85 81 81
Net Weight kg 200 234 234
Shipping Weight kg 214 251 251
External
Dimension Net Dimensions (WxHxD) ㎜ 930 x 1,695 x 765 1,295 x 1,695 x 765 1,295 x 1,695 x 765

Shipping Dimensions (WxHxD) ㎜ 998 x 1,887 x 829 1,363 x 1,887 x 829 1,363 x 1,887 x 829

Operating Cooling ℃ -5 ~ 50 -5 ~ 50 -5 ~ 50
Temp. Range Heating ℃ -25 ~ 24 -25 ~ 24 -25 ~ 24

NOTE
• Specification may be subject to change without prior notice.
1) Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°CDB, 19°CWB, Outdoor temperature 35°CDB, 24°CWB
- Heating : Indoor temperature 20°CDB, 15°CWB, Outdoor temperature 7°CDB, 6°CWB
- Equivalent refrigerant pipe length 5m, Level differences 0m
2) Performance of Multiple Module Outdoor unit is weighted average of Single Module outdoor units.
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
2. Specification
Standard - 50/60Hz
Model Name AM200AXVANH/EA AM220AXVANH/EA AM240AXVANH/EA
Outdoor unit module 1 - - -
Outdoor unit module 2 - - -
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Power Supply Ø, #, V, Hz 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60
Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 20 22 24
Performance Cooling kW 56.0 61.6 67.2
Capacity
Heating kW 63.0 69.3 75.6
Maximum number of connectable indoor units EA 36 40 43

Total capacity of the connected Min. kW 28.0 30.8 33.6


Indoor Units Max. kW 72.8 80.1 87.4
Cooling kW 12.18 16.20 16.80
Power Input
Heating kW 13.55 15.06 16.61
Cooling A 19.60 26.20 26.40
Power Current Input
Heating A 21.30 23.70 26.10
MCA A 43.0 44.6 55.0
Current
MFA A 50 50 63
EER Cooling W/W 4.60 3.80 4.00
Efficiency
COP Heating W/W 4.65 4.60 4.55
Body - GI Steel Plate GI Steel Plate GI Steel Plate
Casing Material
Base - GI Steel Plate GI Steel Plate GI Steel Plate
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Type - Inverter Scroll x 1 Inverter Scroll x 2 Inverter Scroll x 2
Output kW x n 8.93 x 1 6.67 x 2 6.67 x 2

Model Name - DS4GM7090FV* x 1 DS4GR7066FV* x 2 DS4GR7066FV* x 2


Compressor
Type - PVE PVE PVE
Oil
Initial charge cc x n 1,400 x 1 1,100 x 2 1,100 x 2

Type - Propeller Propeller Propeller


Discharge direction - Top Top Top
Quantity EA 2 2 2
Fan ㎥/min 330 330 344
Air Flow Rate
l/s 5,504 5,504 5,741

External Static mmAq 11 11 8


Max.
Pressure Pa 110 110 80
Type - BLDC Motor BLDC Motor BLDC Motor
Fan Motor
Output Wxn 620 x 2 620 x 2 620 x 2
2. Specification
Standard - 50/60Hz
Model Name AM200AXVANH/EA AM220AXVANH/EA AM240AXVANH/EA
Outdoor unit module 1 - - -
Outdoor unit module 2 - - -
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Type Braze connection Braze connection Braze connection
Liquid Pipe
Φ, ㎜ (inch) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
Type Braze connection Braze connection Braze connection
Gas Pipe
Φ, ㎜ (inch) 28.58 (1-1/8) 28.58 (1-1/8) 34.92 (1-3/8)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length Max. [Equiv.] m 200[220] 200[220] 200[220]
(ODU-IDU)

Piping Piping length Max. m 90 90 90


(1st Branch-IDU)
Connections
Total piping
Max. m 1,000 1,000 1,000
length (System)
Level difference
(ODU in highest Max. m 110 110 110
position)

Level difference Max. m 110 110 110


(IDU in highest position)

Level difference Max. m 50 50 50


(IDU-IDU)

Transmission Min. ㎟ 0.75 0.75 0.75


Wiring Cable Remark - F1, F2 F1, F2 F1, F2
connections
Both indoor and Both indoor and Both indoor and
Power supply intake -
outdoor unit outdoor unit outdoor unit
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 10.5 10.5 14.0
Sound Pressure (Cooling) dB(A) 61 64 65
Sound
Sound Power (Cooling) dB(A) 84 86 87
Net Weight kg 259 292 317
Shipping Weight kg 276 309 334
External
Dimension Net Dimensions (WxHxD) ㎜ 1,295 x 1,695 x 765 1,295 x 1,695 x 765 1,295 x 1,695 x 765

Shipping Dimensions (WxHxD) ㎜ 1,363 x 1,887 x 829 1,363 x 1,887 x 829 1,363 x 1,887 x 829

Operating Cooling ℃ -5 ~ 50 -5 ~ 50 -5 ~ 50
Temp. Range Heating ℃ -25 ~ 24 -25 ~ 24 -25 ~ 24

NOTE
• Specification may be subject to change without prior notice.
1) Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°CDB, 19°CWB, Outdoor temperature 35°CDB, 24°CWB
- Heating : Indoor temperature 20°CDB, 15°CWB, Outdoor temperature 7°CDB, 6°CWB
- Equivalent refrigerant pipe length 5m, Level differences 0m
2) Performance of Multiple Module Outdoor unit is weighted average of Single Module outdoor units.
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
2. Specification
Standard - 50/60Hz
Model Name AM260AXVANH/EA AM280AXVANH/EA AM300AXVANH/EA
Outdoor unit module 1 - - -
Outdoor unit module 2 - - -
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Power Supply Ø, #, V, Hz 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60
Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 26 28 30
Performance Cooling kW 72.8 78.6 84.0
Capacity
Heating kW 78.4 78.4 94.5
Maximum number of connectable indoor units EA 47 51 54

Total capacity of the connected Min. kW 36.4 39.3 42.0


Indoor Units Max. kW 94.6 102.2 109.2
Cooling kW 18.86 23.93 22.70
Power Input
Heating kW 17.19 17.61 20.54
Cooling A 30.00 38.00 35.50
Power Current Input
Heating A 27.00 27.70 32.30
MCA A 60.0 61.0 65.0
Current
MFA A 75 75 75
EER Cooling W/W 3.86 3.28 3.70
Efficiency
COP Heating W/W 4.56 4.45 4.60
Body - GI Steel Plate GI Steel Plate GI Steel Plate
Casing Material
Base - GI Steel Plate GI Steel Plate GI Steel Plate
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Type - Inverter Scroll x 2 Inverter Scroll x 2 Inverter Scroll x 2
Output kW x n 6.67 x 2 6.67 x 2 8.93 x 2

Model Name - DS4GR7066FV* x 2 DS4GR7066FV* x 2 DS4GM7090FV* x 2


Compressor
Type - PVE PVE PVE
Oil
Initial charge cc x n 1,100 x 2 1,100 x 2 1,400 x 2

Type - Propeller Propeller Propeller


Discharge direction - Top Top Top
Quantity EA 2 2 2
Fan ㎥/min 353 353 412
Air Flow Rate
l/s 5,882 5,882 6,860

External Static mmAq 8 8 8


Max.
Pressure Pa 80 80 80
Type - BLDC Motor BLDC Motor BLDC Motor
Fan Motor
Output Wxn 620 x 2 620 x 2 630 x 2
2. Specification
Standard - 50/60Hz
Model Name AM260AXVANH/EA AM280AXVANH/EA AM300AXVANH/EA
Outdoor unit module 1 - - -
Outdoor unit module 2 - - -
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Type Braze connection Braze connection Braze connection
Liquid Pipe
Φ, ㎜ (inch) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
Type Braze connection Braze connection Braze connection
Gas Pipe
Φ, ㎜ (inch) 34.92 (1-3/8) 34.92 (1-3/8) 34.92 (1-3/8)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length Max. [Equiv.] m 200[220] 200[220] 200[220]
(ODU-IDU)

Piping Piping length Max. m 90 90 90


(1st Branch-IDU)
Connections
Total piping
Max. m 1,000 1,000 1,000
length (System)
Level difference
(ODU in highest Max. m 110 110 110
position)

Level difference Max. m 110 110 110


(IDU in highest position)

Level difference Max. m 50 50 50


(IDU-IDU)

Transmission Min. ㎟ 0.75 0.75 0.75


Wiring Cable Remark - F1, F2 F1, F2 F1, F2
connections
Both indoor and Both indoor and Both indoor and
Power supply intake -
outdoor unit outdoor unit outdoor unit
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 14.0 14.0 15.5
Sound Pressure (Cooling) dB(A) 65 65 65
Sound
Sound Power (Cooling) dB(A) 87 87 87
Net Weight kg 317 317 390
Shipping Weight kg 334 334 416
External
Dimension Net Dimensions (WxHxD) ㎜ 1,295 x 1,695 x 765 1,295 x 1,695 x 765 1,860 x 1,695 x 765

Shipping Dimensions (WxHxD) ㎜ 1,363 x 1,887 x 829 1,363 x 1,887 x 829 1,928 x 1,887 x 829

Operating Cooling ℃ -5 ~ 50 -5 ~ 50 -5 ~ 50
Temp. Range Heating -25 ~ 24 -25 ~ 24 -25 ~ 24

NOTE
• Specification may be subject to change without prior notice.
1) Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°CDB, 19°CWB, Outdoor temperature 35°CDB, 24°CWB
- Heating : Indoor temperature 20°CDB, 15°CWB, Outdoor temperature 7°CDB, 6°CWB
- Equivalent refrigerant pipe length 5m, Level differences 0m
2) Performance of Multiple Module Outdoor unit is weighted average of Single Module outdoor units.
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
2. Specification
Standard - 50/60Hz
Model Name AM320AXVANH/EA AM340AXVANH/EA AM360AXVANH/EA
Outdoor unit module 1 - - AM120AXVANH/EA
Outdoor unit module 2 - - AM240AXVANH/EA
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Power Supply Ø, #, V, Hz 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60
Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 32 34 36
Performance Cooling kW 89.6 95.2 100.8
Capacity
Heating kW 95.2 95.2 113.4
Maximum number of connectable indoor units EA 58 61 63

Total capacity of the connected Min. kW 44.8 47.6 50.4


Indoor Units Max. kW 116.5 123.8 131.0
Cooling kW 27.57 31.73 25.57
Power Input
Heating kW 21.15 21.63 25.51
Cooling A 43.40 49.90 40.20
Power Current Input
Heating A 33.30 34.00 40.20
MCA A 68.6 73.0 81.0
Current
MFA A 75 80 90
EER Cooling W/W 3.25 3.00 3.94
Efficiency
COP Heating W/W 4.50 4.40 4.45
Body - GI Steel Plate GI Steel Plate GI Steel Plate
Casing Material
Base - GI Steel Plate GI Steel Plate GI Steel Plate
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Type - Inverter Scroll x 2 Inverter Scroll x 2 Inverter Scroll x 3
Output kW x n 8.93 x 2 8.93 x 2 (6.67 x 1) x 1 + (6.67 x 2) x 1
(DS4GR7066FV* x 1) x 1 +
Model Name - DS4GM7090FV* x 2 DS4GM7090FV* x 2
Compressor (DS4GR7066FV* x 2) x 1
Type - PVE PVE PVE
Oil (1,100 x 1) x 1 +
Initial charge cc x n 1,400 x 2 1,400 x 2
(1,100 x 2) x 1
Type - Propeller Propeller Propeller
Discharge direction - Top Top Top
Quantity EA 2 2 3
Fan ㎥/min 412 412 205 x 1 + 344 x 1
Air Flow Rate
l/s 6,860 6,860 3,425 x 1 + 5,741 x 1

External Static mmAq 8 8 8


Max.
Pressure Pa 80 80 80
Type - BLDC Motor BLDC Motor BLDC Motor
Fan Motor (630 x 1) x 1 +
Output Wxn 630 x 2 630 x 2
(620 x 2) x 1
2. Specification
Standard - 50/60Hz
Model Name AM320AXVANH/EA AM340AXVANH/EA AM360AXVANH/EA
Outdoor unit module 1 - - AM120AXVANH/EA
Outdoor unit module 2 - - AM240AXVANH/EA
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Type Braze connection Braze connection Braze connection
Liquid Pipe
Φ, ㎜ (inch) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
Type Braze connection Braze connection Braze connection
Gas Pipe
Φ, ㎜ (inch) 34.92 (1-3/8) 34.92 (1-3/8) 41.28 (1-5/8)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length Max. [Equiv.] m 200[220] 200[220] 200[220]
(ODU-IDU)

Piping Piping length Max. m 90 90 90


(1st Branch-IDU)
Connections
Total piping
Max. m 1,000 1,000 1,000
length (System)
Level difference
(ODU in highest Max. m 110 110 110
position)

Level difference Max. m 110 110 110


(IDU in highest position)

Level difference Max. m 50 50 50


(IDU-IDU)

Transmission Min. ㎟ 0.75 0.75 0.75


Wiring Cable Remark - F1, F2 F1, F2 F1, F2
connections
Both indoor and Both indoor and Both indoor and
Power supply intake -
outdoor unit outdoor unit outdoor unit
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 15.5 15.5 6.2 x 1 + 14.0 x 1
Sound Pressure (Cooling) dB(A) 65 66 66
Sound
Sound Power (Cooling) dB(A) 87 88 88
Net Weight kg 390 390 187 x 1 + 317 x 1
Shipping Weight kg 416 416 201 x 1 + 334 x 1
External (930 x 1,695 x 765) x 1 +
Dimension Net Dimensions (WxHxD) ㎜ 1,860 x 1,695 x 765 1,860 x 1,695 x 765
(1,295 x 1,695 x 765) x 1
(998 x 1,887 x 829) x 1 +
Shipping Dimensions (WxHxD) ㎜ 1,928 x 1,887 x 829 1,928 x 1,887 x 829
(1,363 x 1,887 x 829) x 1

Operating Cooling ℃ -5 ~ 50 -5 ~ 50 -5 ~ 50
Temp. Range Heating ℃ -25 ~ 24 -25 ~ 24 -25 ~ 24

NOTE
• Specification may be subject to change without prior notice.
1) Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°CDB, 19°CWB, Outdoor temperature 35°CDB, 24°CWB
- Heating : Indoor temperature 20°CDB, 15°CWB, Outdoor temperature 7°CDB, 6°CWB
- Equivalent refrigerant pipe length 5m, Level differences 0m
2) Performance of Multiple Module Outdoor unit is weighted average of Single Module outdoor units.
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
2. Specification
Standard - 50/60Hz
Model Name AM380AXVANH/EA AM400AXVANH/EA AM420AXVANH/EA
Outdoor unit module 1 AM140AXVANH/EA AM140AXVANH/EA AM140AXVANH/EA
Outdoor unit module 2 AM240AXVANH/EA AM260AXVANH/EA AM280AXVANH/EA
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Power Supply Ø, #, V, Hz 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60
Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 38 40 42
Performance Cooling kW 107.2 112.8 118.6
Capacity
Heating kW 120.6 123.4 123.4
Maximum number of connectable indoor units EA 64 64 64

Total capacity of the connected Min. kW 53.6 56.4 59.3


Indoor Units Max. kW 139.4 146.6 154.2
Cooling kW 27.48 29.54 34.61
Power Input
Heating kW 27.69 28.27 28.69
Cooling A 43.20 46.80 54.80
Power Current Input
Heating A 43.00 43.90 44.60
MCA A 84.0 89.0 90.0
Current
MFA A 100 100 100
EER Cooling W/W 3.90 3.82 3.43
Efficiency
COP Heating W/W 4.36 4.37 4.30
Body - GI Steel Plate GI Steel Plate GI Steel Plate
Casing Material
Base - GI Steel Plate GI Steel Plate GI Steel Plate
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Type - Inverter Scroll x 3 Inverter Scroll x 3 Inverter Scroll x 3
Output kW x n (6.67 x 1) x 1 + (6.67 x 2) x 1 (6.67 x 1) x 1 + (6.67 x 2) x 1 (6.67 x 1) x 1 + (6.67 x 2) x 1
(DS4GR7066FV* x 1) x 1 + (DS4GR7066FV* x 1) x 1 + (DS4GR7066FV* x 1) x 1 +
Model Name -
Compressor (DS4GR7066FV* x 2) x 1 (DS4GR7066FV* x 2) x 1 (DS4GR7066FV* x 2) x 1
Type - PVE PVE PVE
Oil (1,100 x 1) x 1 + (1,100 x 1) x 1 + (1,100 x 1) x 1 +
Initial charge cc x n
(1,100 x 2) x 1 (1,100 x 2) x 1 (1,100 x 2) x 1
Type - Propeller Propeller Propeller
Discharge direction - Top Top Top
Quantity EA 3 3 3
Fan ㎥/min 201 x 1 + 344 x 1 201 x 1 + 353 x 1 201 x 1 + 353 x 1
Air Flow Rate
l/s 3,346 x 1 + 5,741 x 1 3,346 x 1 + 5,882 x 1 3,346 x 1 + 5,882 x 1

External Static mmAq 8 8 8


Max.
Pressure Pa 80 80 80
Type - BLDC Motor BLDC Motor BLDC Motor
Fan Motor
Output Wxn (630 x 1) x 1 + (620 x 2) x 1 (630 x 1) x 1 + (620 x 2) x 1 (630 x 1) x 1 + (620 x 2) x 1
2. Specification
Standard - 50/60Hz
Model Name AM380AXVANH/EA AM400AXVANH/EA AM420AXVANH/EA
Outdoor unit module 1 AM140AXVANH/EA AM140AXVANH/EA AM140AXVANH/EA
Outdoor unit module 2 AM240AXVANH/EA AM260AXVANH/EA AM280AXVANH/EA
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Type Braze connection Braze connection Braze connection
Liquid Pipe
Φ, ㎜ (inch) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
Type Braze connection Braze connection Braze connection
Gas Pipe
Φ, ㎜ (inch) 41.28 (1-5/8) 41.28 (1-5/8) 41.28 (1-5/8)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length Max. [Equiv.] m 200[220] 200[220] 200[220]
(ODU-IDU)

Piping Piping length Max. m 90 90 90


(1st Branch-IDU)
Connections
Total piping
Max. m 1,000 1,000 1,000
length (System)
Level difference
(ODU in highest Max. m 110 110 110
position)

Level difference Max. m 110 110 110


(IDU in highest position)

Level difference Max. m 50 50 50


(IDU-IDU)

Transmission Min. ㎟ 0.75 0.75 0.75


Wiring Cable Remark - F1, F2 F1, F2 F1, F2
connections
Both indoor and Both indoor and Both indoor and
Power supply intake -
outdoor unit outdoor unit outdoor unit
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 7.0 x 1 + 14.0 x 1 7.0 x 1 + 14.0 x 1 7.0 x 1 + 14.0 x 1
Sound Pressure (Cooling) dB(A) 67 67 67
Sound
Sound Power (Cooling) dB(A) 89 89 89
Net Weight kg 200 x 1 + 317 x 1 200 x 1 + 317 x 1 200 x 1 + 317 x 1
Shipping Weight kg 214 x 1 + 334 x 1 214 x 1 + 334 x 1 214 x 1 + 334 x 1
External (930 x 1,695 x 765) x 1 + (930 x 1,695 x 765) x 1 + (930 x 1,695 x 765) x 1 +
Dimension Net Dimensions (WxHxD) ㎜ (1,295 x 1,695 x 765) x 1 (1,295 x 1,695 x 765) x 1 (1,295 x 1,695 x 765) x 1
(998 x 1,887 x 829) x 1 + (998 x 1,887 x 829) x 1 + (998 x 1,887 x 829) x 1 +
Shipping Dimensions (WxHxD) ㎜ (1,363 x 1,887 x 829) x 1 (1,363 x 1,887 x 829) x 1 (1,363 x 1,887 x 829) x 1

Operating Cooling ℃ -5 ~ 50 -5 ~ 50 -5 ~ 50
Temp. Range Heating ℃ -25 ~ 24 -25 ~ 24 -25 ~ 24

NOTE
• Specification may be subject to change without prior notice.
1) Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°CDB, 19°CWB, Outdoor temperature 35°CDB, 24°CWB
- Heating : Indoor temperature 20°CDB, 15°CWB, Outdoor temperature 7°CDB, 6°CWB
- Equivalent refrigerant pipe length 5m, Level differences 0m
2) Performance of Multiple Module Outdoor unit is weighted average of Single Module outdoor units.
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
2. Specification
Standard - 50/60Hz
Model Name AM440AXVANH/EA AM460AXVANH/EA AM480AXVANH/EA
Outdoor unit module 1 AM200AXVANH/EA AM220AXVANH/EA AM240AXVANH/EA
Outdoor unit module 2 AM240AXVANH/EA AM240AXVANH/EA AM240AXVANH/EA
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Power Supply Ø, #, V, Hz 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60
Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 44 46 48
Performance Cooling kW 123.2 128.8 134.4
Capacity
Heating kW 138.6 144.9 151.2
Maximum number of connectable indoor units EA 64 64 64

Total capacity of the connected Min. kW 61.6 64.4 67.2


Indoor Units Max. kW 160.2 167.4 174.7
Cooling kW 28.98 33.00 33.60
Power Input
Heating kW 30.16 31.67 33.22
Cooling A 46.00 52.60 52.80
Power Current Input
Heating A 47.40 49.80 52.20
MCA A 98.0 99.6 110.0
Current
MFA A 125 125 125
EER Cooling W/W 4.25 3.90 4.00
Efficiency
COP Heating W/W 4.60 4.58 4.55
Body - GI Steel Plate GI Steel Plate GI Steel Plate
Casing Material
Base - GI Steel Plate GI Steel Plate GI Steel Plate
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Type - Inverter Scroll x 3 Inverter Scroll x 4 Inverter Scroll x 4
Output kW x n (8.93 x 1) x 1 + (6.67 x 2) x 1 (6.67 x 2) x 2 (6.67 x 2) x 2
(DS4GM7090FV* x 1) x 1 +
Model Name - (DS4GR7066FV* x 2) x 2 (DS4GR7066FV* x 2) x 2
Compressor (DS4GR7066FV* x 2) x 1
Type - PVE PVE PVE
Oil (1,400 x 1) x 1 +
Initial charge cc x n (1,100 x 2) x 2 (1,100 x 2) x 2
(1,100 x 2) x 1
Type - Propeller Propeller Propeller
Discharge direction - Top Top Top
Quantity EA 4 4 4
Fan ㎥/min 330 x 1 + 344 x 1 330 x 1 + 344 x 1 344 x 2
Air Flow Rate
l/s 5,504 x 1 + 5,741 x 1 5,504 x 1 + 5,741 x 1 5,741 x 2

External Static mmAq 11 11 8


Max.
Pressure Pa 110 110 80
Type - BLDC Motor BLDC Motor BLDC Motor
Fan Motor
Output Wxn (620 x 2) x 2 (620 x 2) x 2 (620 x 2) x 2
2. Specification
Standard - 50/60Hz
Model Name AM440AXVANH/EA AM460AXVANH/EA AM480AXVANH/EA
Outdoor unit module 1 AM200AXVANH/EA AM220AXVANH/EA AM240AXVANH/EA
Outdoor unit module 2 AM240AXVANH/EA AM240AXVANH/EA AM240AXVANH/EA
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Type Braze connection Braze connection Braze connection
Liquid Pipe
Φ, ㎜ (inch) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
Type Braze connection Braze connection Braze connection
Gas Pipe
Φ, ㎜ (inch) 41.28 (1-5/8) 41.28 (1-5/8) 41.28 (1-5/8)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length Max. [Equiv.] m 200[220] 200[220] 200[220]
(ODU-IDU)

Piping Piping length Max. m 90 90 90


(1st Branch-IDU)
Connections
Total piping
Max. m 1,000 1,000 1,000
length (System)
Level difference
(ODU in highest Max. m 110 110 110
position)

Level difference Max. m 110 110 110


(IDU in highest position)

Level difference Max. m 50 50 50


(IDU-IDU)

Transmission Min. ㎟ 0.75 0.75 0.75


Wiring Cable Remark - F1, F2 F1, F2 F1, F2
connections
Both indoor and Both indoor and Both indoor and
Power supply intake -
outdoor unit outdoor unit outdoor unit
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 10.5 x 1 + 14.0 x 1 10.5 x 1 + 14.0 x 1 14.0 x 2
Sound Pressure (Cooling) dB(A) 66 68 68
Sound
Sound Power (Cooling) dB(A) 89 90 90
Net Weight kg 259 x 1 + 317 x 1 292 x 1 + 317 x 1 317 x 2
Shipping Weight kg 276 x 1 + 334 x 1 309 x 1 + 334 x 1 334 x 2
External
Dimension Net Dimensions (WxHxD) ㎜ (1,295 x 1,695 x 765) x 2 (1,295 x 1,695 x 765) x 2 (1,295 x 1,695 x 765) x 2

Shipping Dimensions (WxHxD) ㎜ (1,363 x 1,887 x 829) x 2 (1,363 x 1,887 x 829) x 2 (1,363 x 1,887 x 829) x 2

Operating Cooling ℃ -5 ~ 50 -5 ~ 50 -5 ~ 50
Temp. Range Heating ℃ -25 ~ 24 -25 ~ 24 -25 ~ 24

NOTE
• Specification may be subject to change without prior notice.
1) Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°CDB, 19°CWB, Outdoor temperature 35°CDB, 24°CWB
- Heating : Indoor temperature 20°CDB, 15°CWB, Outdoor temperature 7°CDB, 6°CWB
- Equivalent refrigerant pipe length 5m, Level differences 0m
2) Performance of Multiple Module Outdoor unit is weighted average of Single Module outdoor units.
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
2. Specification
Standard - 50/60Hz
Model Name AM500AXVANH/EA AM520AXVANH/EA AM540AXVANH/EA
Outdoor unit module 1 AM260AXVANH/EA AM260AXVANH/EA AM260AXVANH/EA
Outdoor unit module 2 AM240AXVANH/EA AM260AXVANH/EA AM280AXVANH/EA
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Power Supply Ø, #, V, Hz 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60
Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 50 52 54
Performance Cooling kW 140.0 145.6 151.4
Capacity
Heating kW 154.0 156.8 156.8
Maximum number of connectable indoor units EA 64 64 64

Total capacity of the connected Min. kW 70.0 72.8 75.7


Indoor Units Max. kW 182.0 189.3 196.8
Cooling kW 35.66 37.72 42.79
Power Input
Heating kW 33.80 34.38 34.80
Cooling A 56.40 60.00 68.00
Power Current Input
Heating A 53.10 54.00 54.70
MCA A 115.0 120.0 121.0
Current
MFA A 150 150 150
EER Cooling W/W 3.93 3.86 3.54
Efficiency
COP Heating W/W 4.56 4.56 4.51
Body - GI Steel Plate GI Steel Plate GI Steel Plate
Casing Material
Base - GI Steel Plate GI Steel Plate GI Steel Plate
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Type - Inverter Scroll x 4 Inverter Scroll x 4 Inverter Scroll x 4
Output kW x n (6.67 x 2) x 2 (6.67 x 2) x 2 (6.67 x 2) x 2

Model Name - (DS4GR7066FV* x 2) x 2 (DS4GR7066FV* x 2) x 2 (DS4GR7066FV* x 2) x 2


Compressor
Type - PVE PVE PVE
Oil
Initial charge cc x n (1,100 x 2) x 2 (1,100 x 2) x 2 (1,100 x 2) x 2

Type - Propeller Propeller Propeller


Discharge direction - Top Top Top
Quantity EA 4 4 4
Fan ㎥/min 353 x 1 + 344 x 1 353 x 2 353 x 2
Air Flow Rate
l/s 5,882 x 1 + 5,741 x 1 5,882 x 2 5,882 x 2

External Static mmAq 8 8 8


Max.
Pressure Pa 80 80 80
Type - BLDC Motor BLDC Motor BLDC Motor
Fan Motor
Output Wxn (620 x 2) x 2 (620 x 2) x 2 (620 x 2) x 2
2. Specification
Standard - 50/60Hz
Model Name AM500AXVANH/EA AM520AXVANH/EA AM540AXVANH/EA
Outdoor unit module 1 AM260AXVANH/EA AM260AXVANH/EA AM260AXVANH/EA
Outdoor unit module 2 AM240AXVANH/EA AM260AXVANH/EA AM280AXVANH/EA
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Type Braze connection Braze connection Braze connection
Liquid Pipe
Φ, ㎜ (inch) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
Type Braze connection Braze connection Braze connection
Gas Pipe
Φ, ㎜ (inch) 41.28 (1-5/8) 41.28 (1-5/8) 41.28 (1-5/8)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length Max. [Equiv.] m 200[220] 200[220] 200[220]
(ODU-IDU)

Piping Piping length Max. m 90 90 90


(1st Branch-IDU)
Connections
Total piping
Max. m 1,000 1,000 1,000
length (System)
Level difference
(ODU in highest Max. m 110 110 110
position)

Level difference Max. m 110 110 110


(IDU in highest position)

Level difference Max. m 50 50 50


(IDU-IDU)

Transmission Min. ㎟ 0.75 0.75 0.75


Wiring Cable Remark - F1, F2 F1, F2 F1, F2
connections
Both indoor and Both indoor and Both indoor and
Power supply intake -
outdoor unit outdoor unit outdoor unit
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 14.0 x 2 14.0 x 2 14.0 x 2
Sound Pressure (Cooling) dB(A) 68 68 68
Sound
Sound Power (Cooling) dB(A) 90 90 90
Net Weight kg 317 x 2 317 x 2 317 x 2
Shipping Weight kg 334 x 2 334 x 2 334 x 2
External
Dimension Net Dimensions (WxHxD) ㎜ (1,295 x 1,695 x 765) x 2 (1,295 x 1,695 x 765) x 2 (1,295 x 1,695 x 765) x 2

Shipping Dimensions (WxHxD) ㎜ (1,363 x 1,887 x 829) x 2 (1,363 x 1,887 x 829) x 2 (1,363 x 1,887 x 829) x 2

Operating Cooling ℃ -5 ~ 50 -5 ~ 50 -5 ~ 50
Temp. Range Heating ℃ -25 ~ 24 -25 ~ 24 -25 ~ 24

NOTE
• Specification may be subject to change without prior notice.
1) Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°CDB, 19°CWB, Outdoor temperature 35°CDB, 24°CWB
- Heating : Indoor temperature 20°CDB, 15°CWB, Outdoor temperature 7°CDB, 6°CWB
- Equivalent refrigerant pipe length 5m, Level differences 0m
2) Performance of Multiple Module Outdoor unit is weighted average of Single Module outdoor units.
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
2. Specification
Standard - 50/60Hz
Model Name AM560AXVANH/EA AM580AXVANH/EA AM600AXVANH/EA
Outdoor unit module 1 AM280AXVANH/EA AM260AXVANH/EA AM260AXVANH/EA
Outdoor unit module 2 AM280AXVANH/EA AM320AXVANH/EA AM340AXVANH/EA
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Power Supply Ø, #, V, Hz 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60
Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 56 58 60
Performance Cooling kW 157.2 162.4 168.0
Capacity
Heating kW 156.8 173.6 173.6
Maximum number of connectable indoor units EA 64 64 64

Total capacity of the connected Min. kW 78.6 81.2 84.0


Indoor Units Max. kW 204.4 211.1 218.4
Cooling kW 47.86 46.43 50.59
Power Input
Heating kW 35.22 38.34 38.82
Cooling A 76.00 73.40 79.90
Power Current Input
Heating A 55.40 60.30 61.00
MCA A 122.0 128.6 133.0
Current
MFA A 150 150 150
EER Cooling W/W 3.28 3.50 3.32
Efficiency
COP Heating W/W 4.45 4.53 4.47
Body - GI Steel Plate GI Steel Plate GI Steel Plate
Casing Material
Base - GI Steel Plate GI Steel Plate GI Steel Plate
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Type - Inverter Scroll x 4 Inverter Scroll x 4 Inverter Scroll x 4
Output kW x n (6.67 x 2) x 2 (6.67 x 2) x 1 + (8.93 x 2) x 1 (6.67 x 2) x 1 + (8.93 x 2) x 1
(DS4GR7066FV* x 2) x 1 + (DS4GR7066FV* x 2) x 1 +
Model Name - (DS4GR7066FV* x 2) x 2
Compressor (DS4GM7090FV* x 2) x 1 (DS4GM7090FV* x 2) x 1
Type - PVE PVE PVE
Oil (1,100 x 2) x 1 + (1,100 x 2) x 1 +
Initial charge cc x n (1,100 x 2) x 2
(1,400 x 2) x 1 (1,400 x 2) x 1
Type - Propeller Propeller Propeller
Discharge direction - Top Top Top
Quantity EA 4 4 4
Fan ㎥/min 353 x 2 353 x 1 + 412 x 1 353 x 1 + 412 x 1
Air Flow Rate
l/s 5,882 x 2 5,882 x 1 + 6,860 x 1 5,882 x 1 + 6,860 x 1

External Static mmAq 8 8 8


Max.
Pressure Pa 80 80 80
Type - BLDC Motor BLDC Motor BLDC Motor
Fan Motor
Output Wxn (620 x 2) x 2 (620 x 2) x 1 + (630 x 2) x 1 (620 x 2) x 1 + (630 x 2) x 1
2. Specification
Standard - 50/60Hz
Model Name AM560AXVANH/EA AM580AXVANH/EA AM600AXVANH/EA
Outdoor unit module 1 AM280AXVANH/EA AM260AXVANH/EA AM260AXVANH/EA
Outdoor unit module 2 AM280AXVANH/EA AM320AXVANH/EA AM340AXVANH/EA
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Type Braze connection Braze connection Braze connection
Liquid Pipe
Φ, ㎜ (inch) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
Type Braze connection Braze connection Braze connection
Gas Pipe
Φ, ㎜ (inch) 41.28 (1-5/8) 41.28 (1-5/8) 41.28 (1-5/8)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length Max. [Equiv.] m 200[220] 200[220] 200[220]
(ODU-IDU)

Piping Piping length Max. m 90 90 90


(1st Branch-IDU)
Connections
Total piping
Max. m 1,000 1,000 1,000
length (System)
Level difference
(ODU in highest Max. m 110 110 110
position)

Level difference Max. m 110 110 110


(IDU in highest position)

Level difference Max. m 50 50 50


(IDU-IDU)

Transmission Min. ㎟ 0.75 0.75 0.75


Wiring Cable Remark - F1, F2 F1, F2 F1, F2
connections
Both indoor and Both indoor and Both indoor and
Power supply intake -
outdoor unit outdoor unit outdoor unit
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 14.0 x 2 14.0 x 1 + 15.5 x 1 14.0 x 1 + 15.5 x 1
Sound Pressure (Cooling) dB(A) 68 68 69
Sound
Sound Power (Cooling) dB(A) 90 90 91
Net Weight kg 317 x 2 317 x 1 + 390 x 1 317 x 1 + 390 x 1
Shipping Weight kg 334 x 2 334 x 1 + 416 x 1 334 x 1 + 416 x 1
External (1,295 x 1,695 x 765) x 1 + (1,295 x 1,695 x 765) x 1 +
Dimension Net Dimensions (WxHxD) ㎜ (1,295 x 1,695 x 765) x 2
(1,860 x 1,695 x 765) x 1 (1,860 x 1,695 x 765) x 1
(1,363 x 1,887 x 829) x 1 + (1,363 x 1,887 x 829) x 1 +
Shipping Dimensions (WxHxD) ㎜ (1,363 x 1,887 x 829) x 2
(1,928 x 1,887 x 829) x 1 (1,928 x 1,887 x 829) x 1

Operating Cooling ℃ -5 ~ 50 -5 ~ 50 -5 ~ 50
Temp. Range Heating ℃ -25 ~ 24 -25 ~ 24 -25 ~ 24

NOTE
• Specification may be subject to change without prior notice.
1) Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°CDB, 19°CWB, Outdoor temperature 35°CDB, 24°CWB
- Heating : Indoor temperature 20°CDB, 15°CWB, Outdoor temperature 7°CDB, 6°CWB
- Equivalent refrigerant pipe length 5m, Level differences 0m
2) Performance of Multiple Module Outdoor unit is weighted average of Single Module outdoor units.
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
2. Specification
Standard - 50/60Hz
Model Name AM620AXVANH/EA AM640AXVANH/EA AM660AXVANH/EA
Outdoor unit module 1 AM280AXVANH/EA AM300AXVANH/EA AM320AXVANH/EA
Outdoor unit module 2 AM340AXVANH/EA AM340AXVANH/EA AM340AXVANH/EA
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Power Supply Ø, #, V, Hz 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60
Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 62 64 66
Performance Cooling kW 173.8 179.2 184.8
Capacity
Heating kW 173.6 189.7 190.4
Maximum number of connectable indoor units EA 64 64 64

Total capacity of the connected Min. kW 86.9 89.6 92.4


Indoor Units Max. kW 225.9 233.0 240.2
Cooling kW 55.66 54.43 59.30
Power Input
Heating kW 39.24 42.17 42.78
Cooling A 87.90 85.40 93.30
Power Current Input
Heating A 61.70 66.30 67.30
MCA A 134.0 138.0 141.6
Current
MFA A 150 175 175
EER Cooling W/W 3.12 3.29 3.12
Efficiency
COP Heating W/W 4.42 4.50 4.45
Body - GI Steel Plate GI Steel Plate GI Steel Plate
Casing Material
Base - GI Steel Plate GI Steel Plate GI Steel Plate
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Type - Inverter Scroll x 4 Inverter Scroll x 4 Inverter Scroll x 4
Output kW x n (6.67 x 2) x 1 + (8.93 x 2) x 1 (8.93 x 2) x 2 (8.93 x 2) x 2
(DS4GR7066FV* x 2) x 1 +
Model Name - (DS4GM7090FV* x 2) x 2 (DS4GM7090FV* x 2) x 2
Compressor (DS4GM7090FV* x 2) x 1
Type - PVE PVE PVE
Oil (1,100 x 2) x 1 +
Initial charge cc x n (1,400 x 2) x 2 (1,400 x 2) x 2
(1,400 x 2) x 1
Type - Propeller Propeller Propeller
Discharge direction - Top Top Top
Quantity EA 4 4 4
Fan ㎥/min 353 x 1 + 412 x 1 412 x 2 412 x 2
Air Flow Rate
l/s 5,882 x 1 + 6,860 x 1 6,860 x 2 6,860 x 2

External Static mmAq 8 8 8


Max.
Pressure Pa 80 80 80
Type - BLDC Motor BLDC Motor BLDC Motor
Fan Motor
Output Wxn (620 x 2) x 1 + (630 x 2) x 1 (630 x 2) x 2 (630 x 2) x 2
2. Specification
Standard - 50/60Hz
Model Name AM620AXVANH/EA AM640AXVANH/EA AM660AXVANH/EA
Outdoor unit module 1 AM280AXVANH/EA AM300AXVANH/EA AM320AXVANH/EA
Outdoor unit module 2 AM340AXVANH/EA AM340AXVANH/EA AM340AXVANH/EA
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Type Braze connection Braze connection Braze connection
Liquid Pipe
Φ, ㎜ (inch) 22.22 (7/8) 22.22 (7/8) 22.22 (7/8)
Type Braze connection Braze connection Braze connection
Gas Pipe
Φ, ㎜ (inch) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length Max. [Equiv.] m 200[220] 200[220] 200[220]
(ODU-IDU)

Piping Piping length Max. m 90 90 90


(1st Branch-IDU)
Connections
Total piping
Max. m 1,000 1,000 1,000
length (System)
Level difference
(ODU in highest Max. m 110 110 110
position)

Level difference Max. m 110 110 110


(IDU in highest position)

Level difference Max. m 50 50 50


(IDU-IDU)

Transmission Min. ㎟ 0.75 0.75 0.75


Wiring Cable Remark - F1, F2 F1, F2 F1, F2
connections
Both indoor and Both indoor and Both indoor and
Power supply intake -
outdoor unit outdoor unit outdoor unit
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 14.0 x 1 + 15.5 x 1 15.5 x 2 15.5 x 2
Sound Pressure (Cooling) dB(A) 69 69 69
Sound
Sound Power (Cooling) dB(A) 91 91 91
Net Weight kg 317 x 1 + 390 x 1 390 x 2 390 x 2
Shipping Weight kg 334 x 1 + 416 x 1 416 x 2 416 x 2
External (1,295 x 1,695 x 765) x 1 +
Dimension Net Dimensions (WxHxD) ㎜ (1,860 x 1,695 x 765) x 2 (1,860 x 1,695 x 765) x 2
(1,860 x 1,695 x 765) x 1
(1,363 x 1,887 x 829) x 1 +
Shipping Dimensions (WxHxD) ㎜ (1,928 x 1,887 x 829) x 2 (1,928 x 1,887 x 829) x 2
(1,928 x 1,887 x 829) x 1

Operating Cooling ℃ -5 ~ 50 -5 ~ 50 -5 ~ 50
Temp. Range Heating ℃ -25 ~ 24 -25 ~ 24 -25 ~ 24

NOTE
• Specification may be subject to change without prior notice.
1) Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°CDB, 19°CWB, Outdoor temperature 35°CDB, 24°CWB
- Heating : Indoor temperature 20°CDB, 15°CWB, Outdoor temperature 7°CDB, 6°CWB
- Equivalent refrigerant pipe length 5m, Level differences 0m
2) Performance of Multiple Module Outdoor unit is weighted average of Single Module outdoor units.
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
2. Specification
Standard - 50/60Hz
Model Name AM680AXVANH/EA AM700AXVANH/EA AM720AXVANH/EA
Outdoor unit module 1 AM340AXVANH/EA AM220AXVANH/EA AM220AXVANH/EA
Outdoor unit module 2 AM340AXVANH/EA AM240AXVANH/EA AM240AXVANH/EA
Outdoor unit module 3 - AM240AXVANH/EA AM260AXVANH/EA
Outdoor unit module 4 - - -
Power Supply Ø, #, V, Hz 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60
Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 68 70 72
Performance Cooling kW 190.4 196.0 201.6
Capacity
Heating kW 190.4 220.5 223.3
Maximum number of connectable indoor units EA 64 64 64

Total capacity of the connected Min. kW 95.2 98.0 100.8


Indoor Units Max. kW 247.5 254.8 262.1
Cooling kW 63.46 49.80 51.86
Power Input
Heating kW 43.26 48.28 48.86
Cooling A 99.80 79.00 82.60
Power Current Input
Heating A 68.00 75.90 76.80
MCA A 146.0 154.6 159.6
Current
MFA A 175 175 175
EER Cooling W/W 3.00 3.94 3.89
Efficiency
COP Heating W/W 4.40 4.57 4.57
Body - GI Steel Plate GI Steel Plate GI Steel Plate
Casing Material
Base - GI Steel Plate GI Steel Plate GI Steel Plate
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Type - Inverter Scroll x 4 Inverter Scroll x 6 Inverter Scroll x 6
Output kW x n (8.93 x 2) x 2 (6.67 x 2) x 3 (6.67 x 2) x 3

Model Name - (DS4GM7090FV* x 2) x 2 (DS4GR7066FV* x 2) x 3 (DS4GR7066FV* x 2) x 3


Compressor
Type - PVE PVE PVE
Oil
Initial charge cc x n (1,400 x 2) x 2 (1,100 x 2) x 3 (1,100 x 2) x 3

Type - Propeller Propeller Propeller


Discharge direction - Top Top Top
Quantity EA 4 6 6
Fan ㎥/min 412 x 2 330 x 1 + 344 x 2 330 x 1 + 344 x 1 + 353 x 1
Air Flow Rate
l/s 6,860 x 2 5,504 x 1 + 5,741 x 2 5,504 x 1 + 5,741 x 1 + 5,882 x 1

External Static mmAq 8 11 11


Max.
Pressure Pa 80 110 110
Type - BLDC Motor BLDC Motor BLDC Motor
Fan Motor
Output Wxn (630 x 2) x 2 (620 x 2) x 3 (620 x 2) x 3
2. Specification
Standard - 50/60Hz
Model Name AM680AXVANH/EA AM700AXVANH/EA AM720AXVANH/EA
Outdoor unit module 1 AM340AXVANH/EA AM220AXVANH/EA AM220AXVANH/EA
Outdoor unit module 2 AM340AXVANH/EA AM240AXVANH/EA AM240AXVANH/EA
Outdoor unit module 3 - AM240AXVANH/EA AM260AXVANH/EA
Outdoor unit module 4 - - -
Type Braze connection Braze connection Braze connection
Liquid Pipe
Φ, ㎜ (inch) 22.22 (7/8) 22.22 (7/8) 22.22 (7/8)
Type Braze connection Braze connection Braze connection
Gas Pipe
Φ, ㎜ (inch) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length Max. [Equiv.] m 200[220] 200[220] 200[220]
(ODU-IDU)

Piping Piping length Max. m 90 90 90


(1st Branch-IDU)
Connections
Total piping
Max. m 1,000 1,000 1,000
length (System)
Level difference
(ODU in highest Max. m 110 110 110
position)

Level difference Max. m 110 110 110


(IDU in highest position)

Level difference Max. m 50 50 50


(IDU-IDU)

Transmission Min. ㎟ 0.75 0.75 0.75


Wiring Cable Remark - F1, F2 F1, F2 F1, F2
connections
Both indoor and Both indoor and Both indoor and
Power supply intake -
outdoor unit outdoor unit outdoor unit
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 15.5 x 2 10.5 x 1 + 14.0 x 2 10.5 x 1 + 14.0 x 2
Sound Pressure (Cooling) dB(A) 69 69 69
Sound
Sound Power (Cooling) dB(A) 91 91 91
Net Weight kg 390 x 2 292 x 1 + 317 x 2 292 x 1 + 317 x 2
Shipping Weight kg 416 x 2 309 x 1 + 334 x 2 309 x 1 + 334 x 2
External
Dimension Net Dimensions (WxHxD) ㎜ (1,860 x 1,695 x 765) x 2 (1,295 x 1,695 x 765) x 3 (1,295 x 1,695 x 765) x 3

Shipping Dimensions (WxHxD) ㎜ (1,928 x 1,887 x 829) x 2 (1,363 x 1,887 x 829) x 3 (1,363 x 1,887 x 829) x 3

Operating Cooling ℃ -5 ~ 50 -5 ~ 50 -5 ~ 50
Temp. Range Heating ℃ -25 ~ 24 -25 ~ 24 -25 ~ 24

NOTE
• Specification may be subject to change without prior notice.
1) Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°CDB, 19°CWB, Outdoor temperature 35°CDB, 24°CWB
- Heating : Indoor temperature 20°CDB, 15°CWB, Outdoor temperature 7°CDB, 6°CWB
- Equivalent refrigerant pipe length 5m, Level differences 0m
2) Performance of Multiple Module Outdoor unit is weighted average of Single Module outdoor units.
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
2. Specification
Standard - 50/60Hz
Model Name AM740AXVANH/EA AM760AXVANH/EA AM780AXVANH/EA
Outdoor unit module 1 AM240AXVANH/EA AM240AXVANH/EA AM260AXVANH/EA
Outdoor unit module 2 AM240AXVANH/EA AM260AXVANH/EA AM260AXVANH/EA
Outdoor unit module 3 AM260AXVANH/EA AM260AXVANH/EA AM260AXVANH/EA
Outdoor unit module 4 - - -
Power Supply Ø, #, V, Hz 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60
Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 74 76 78
Performance Cooling kW 207.2 212.8 218.4
Capacity
Heating kW 229.6 232.4 235.2
Maximum number of connectable indoor units EA 64 64 64

Total capacity of the connected Min. kW 103.6 106.4 109.2


Indoor Units Max. kW 269.4 276.6 283.9
Cooling kW 52.46 54.52 56.58
Power Input
Heating kW 50.41 50.99 51.57
Cooling A 82.80 86.40 90.00
Power Current Input
Heating A 79.20 80.10 81.00
MCA A 170.0 175.0 180.0
Current
MFA A 200 200 200
EER Cooling W/W 3.95 3.90 3.86
Efficiency
COP Heating W/W 4.55 4.56 4.56
Body - GI Steel Plate GI Steel Plate GI Steel Plate
Casing Material
Base - GI Steel Plate GI Steel Plate GI Steel Plate
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Type - Inverter Scroll x 6 Inverter Scroll x 6 Inverter Scroll x 6
Output kW x n (6.67 x 2) x 3 (6.67 x 2) x 3 (6.67 x 2) x 3

Model Name - (DS4GR7066FV* x 2) x 3 (DS4GR7066FV* x 2) x 3 (DS4GR7066FV* x 2) x 3


Compressor
Type - PVE PVE PVE
Oil
Initial charge cc x n (1,100 x 2) x 3 (1,100 x 2) x 3 (1,100 x 2) x 3

Type - Propeller Propeller Propeller


Discharge direction - Top Top Top
Quantity EA 6 6 6
Fan ㎥/min 344 x 2 + 353 x 1 344 x 1 + 353 x 2 353 x 3
Air Flow Rate
l/s 5,741 x 2 + 5,882 x 1 5,741 x 1 + 5,882 x 2 5,882 x 3

External Static mmAq 8 8 8


Max.
Pressure Pa 80 80 80
Type - BLDC Motor BLDC Motor BLDC Motor
Fan Motor
Output Wxn (620 x 2) x 3 (620 x 2) x 3 (620 x 2) x 3
2. Specification
Standard - 50/60Hz
Model Name AM740AXVANH/EA AM760AXVANH/EA AM780AXVANH/EA
Outdoor unit module 1 AM240AXVANH/EA AM240AXVANH/EA AM260AXVANH/EA
Outdoor unit module 2 AM240AXVANH/EA AM260AXVANH/EA AM260AXVANH/EA
Outdoor unit module 3 AM260AXVANH/EA AM260AXVANH/EA AM260AXVANH/EA
Outdoor unit module 4 - - -
Type Braze connection Braze connection Braze connection
Liquid Pipe
Φ, ㎜ (inch) 22.22 (7/8) 22.22 (7/8) 22.22 (7/8)
Type Braze connection Braze connection Braze connection
Gas Pipe
Φ, ㎜ (inch) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length Max. [Equiv.] m 200[220] 200[220] 200[220]
(ODU-IDU)

Piping Piping length Max. m 90 90 90


(1st Branch-IDU)
Connections
Total piping
Max. m 1,000 1,000 1,000
length (System)
Level difference
(ODU in highest Max. m 110 110 110
position)

Level difference Max. m 110 110 110


(IDU in highest position)

Level difference Max. m 50 50 50


(IDU-IDU)

Transmission Min. ㎟ 0.75 0.75 0.75


Wiring Cable Remark - F1, F2 F1, F2 F1, F2
connections
Both indoor and Both indoor and Both indoor and
Power supply intake -
outdoor unit outdoor unit outdoor unit
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 14.0 x 3 14.0 x 3 14.0 x 3
Sound Pressure (Cooling) dB(A) 70 70 70
Sound
Sound Power (Cooling) dB(A) 92 92 92
Net Weight kg 317 x 3 317 x 3 317 x 3
Shipping Weight kg 334 x 3 334 x 3 334 x 3
External
Dimension Net Dimensions (WxHxD) ㎜ (1,295 x 1,695 x 765) x 3 (1,295 x 1,695 x 765) x 3 (1,295 x 1,695 x 765) x 3

Shipping Dimensions (WxHxD) ㎜ (1,363 x 1,887 x 829) x 3 (1,363 x 1,887 x 829) x 3 (1,363 x 1,887 x 829) x 3

Operating Cooling ℃ -5 ~ 50 -5 ~ 50 -5 ~ 50
Temp. Range Heating ℃ -25 ~ 24 -25 ~ 24 -25 ~ 24

NOTE
• Specification may be subject to change without prior notice.
1) Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°CDB, 19°CWB, Outdoor temperature 35°CDB, 24°CWB
- Heating : Indoor temperature 20°CDB, 15°CWB, Outdoor temperature 7°CDB, 6°CWB
- Equivalent refrigerant pipe length 5m, Level differences 0m
2) Performance of Multiple Module Outdoor unit is weighted average of Single Module outdoor units.
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
2. Specification
Standard - 50/60Hz
Model Name AM800AXVANH/EA AM820AXVANH/EA AM840AXVANH/EA
Outdoor unit module 1 AM260AXVANH/EA AM260AXVANH/EA AM240AXVANH/EA
Outdoor unit module 2 AM260AXVANH/EA AM280AXVANH/EA AM260AXVANH/EA
Outdoor unit module 3 AM280AXVANH/EA AM280AXVANH/EA AM340AXVANH/EA
Outdoor unit module 4 - - -
Power Supply Ø, #, V, Hz 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60
Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 80 82 84
Performance Cooling kW 224.2 230.0 235.2
Capacity
Heating kW 235.2 235.2 249.2
Maximum number of connectable indoor units EA 64 64 64

Total capacity of the connected Min. kW 112.1 115.0 117.6


Indoor Units Max. kW 291.5 299.0 305.8
Cooling kW 61.65 66.72 67.39
Power Input
Heating kW 51.99 52.41 55.43
Cooling A 98.00 106.00 106.30
Power Current Input
Heating A 81.70 82.40 87.10
MCA A 181.0 182.0 188.0
Current
MFA A 200 200 225
EER Cooling W/W 3.64 3.45 3.49
Efficiency
COP Heating W/W 4.52 4.49 4.50
Body - GI Steel Plate GI Steel Plate GI Steel Plate
Casing Material
Base - GI Steel Plate GI Steel Plate GI Steel Plate
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Type - Inverter Scroll x 6 Inverter Scroll x 6 Inverter Scroll x 6
Output kW x n (6.67 x 2) x 3 (6.67 x 2) x 3 (6.67 x 2) x 2 + (8.93 x 2) x 1
(DS4GR7066FV* x 2) x 2 +
Model Name - (DS4GR7066FV* x 2) x 3 (DS4GR7066FV* x 2) x 3
Compressor (DS4GM7090FV* x 2) x 1
Type - PVE PVE PVE
Oil (1,100 x 2) x 2 +
Initial charge cc x n (1,100 x 2) x 3 (1,100 x 2) x 3
(1,400 x 2) x 1
Type - Propeller Propeller Propeller
Discharge direction - Top Top Top
Quantity EA 6 6 6
Fan ㎥/min 353 x 3 353 x 3 344 x 1 + 353 x 1 + 412 x 1
Air Flow Rate
l/s 5,882 x 3 5,882 x 3 5,741 x 1 + 5,882 x 1 + 6,860 x 1

External Static mmAq 8 8 8


Max.
Pressure Pa 80 80 80
Type - BLDC Motor BLDC Motor BLDC Motor
Fan Motor
Output Wxn (620 x 2) x 3 (620 x 2) x 3 (620 x 2) x 2 + (630 x 2) x 1
2. Specification
Standard - 50/60Hz
Model Name AM800AXVANH/EA AM820AXVANH/EA AM840AXVANH/EA
Outdoor unit module 1 AM260AXVANH/EA AM260AXVANH/EA AM240AXVANH/EA
Outdoor unit module 2 AM260AXVANH/EA AM280AXVANH/EA AM260AXVANH/EA
Outdoor unit module 3 AM280AXVANH/EA AM280AXVANH/EA AM340AXVANH/EA
Outdoor unit module 4 - - -
Type Braze connection Braze connection Braze connection
Liquid Pipe
Φ, ㎜ (inch) 22.22 (7/8) 22.22 (7/8) 22.22 (7/8)
Type Braze connection Braze connection Braze connection
Gas Pipe
Φ, ㎜ (inch) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length Max. [Equiv.] m 200[220] 200[220] 200[220]
(ODU-IDU)

Piping Piping length Max. m 90 90 90


(1st Branch-IDU)
Connections
Total piping
Max. m 1,000 1,000 1,000
length (System)
Level difference
(ODU in highest Max. m 110 110 110
position)

Level difference Max. m 110 110 110


(IDU in highest position)

Level difference Max. m 50 50 50


(IDU-IDU)

Transmission Min. ㎟ 0.75 0.75 0.75


Wiring Cable Remark - F1, F2 F1, F2 F1, F2
connections
Both indoor and Both indoor and Both indoor and
Power supply intake -
outdoor unit outdoor unit outdoor unit
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 14.0 x 3 14.0 x 3 14.0 x 2 + 15.5 x 1
Sound Pressure (Cooling) dB(A) 70 70 70
Sound
Sound Power (Cooling) dB(A) 92 92 92
Net Weight kg 317 x 3 317 x 3 317 x 2 + 390 x 1
Shipping Weight kg 334 x 3 334 x 3 334 x 2 + 416 x 1
External (1,295 x 1,695 x 765) x 2 +
Dimension Net Dimensions (WxHxD) ㎜ (1,295 x 1,695 x 765) x 3 (1,295 x 1,695 x 765) x 3
(1,860 x 1,695 x 765) x 1
(1,363 x 1,887 x 829) x 2 +
Shipping Dimensions (WxHxD) ㎜ (1,363 x 1,887 x 829) x 3 (1,363 x 1,887 x 829) x 3
(1,928 x 1,887 x 829) x 1

Operating Cooling ℃ -5 ~ 50 -5 ~ 50 -5 ~ 50
Temp. Range Heating ℃ -25 ~ 24 -25 ~ 24 -25 ~ 24

NOTE
• Specification may be subject to change without prior notice.
1) Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°CDB, 19°CWB, Outdoor temperature 35°CDB, 24°CWB
- Heating : Indoor temperature 20°CDB, 15°CWB, Outdoor temperature 7°CDB, 6°CWB
- Equivalent refrigerant pipe length 5m, Level differences 0m
2) Performance of Multiple Module Outdoor unit is weighted average of Single Module outdoor units.
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
2. Specification
Standard - 50/60Hz
Model Name AM860AXVANH/EA AM880AXVANH/EA AM900AXVANH/EA
Outdoor unit module 1 AM260AXVANH/EA AM280AXVANH/EA AM280AXVANH/EA
Outdoor unit module 2 AM260AXVANH/EA AM260AXVANH/EA AM280AXVANH/EA
Outdoor unit module 3 AM340AXVANH/EA AM340AXVANH/EA AM340AXVANH/EA
Outdoor unit module 4 - - -
Power Supply Ø, #, V, Hz 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60
Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 86 88 90
Performance Cooling kW 240.8 246.6 252.4
Capacity
Heating kW 252.0 252.0 252.0
Maximum number of connectable indoor units EA 64 64 64

Total capacity of the connected Min. kW 120.4 123.3 126.2


Indoor Units Max. kW 313.0 320.6 328.1
Cooling kW 69.45 74.52 79.59
Power Input
Heating kW 56.01 56.43 56.85
Cooling A 109.90 117.90 125.90
Power Current Input
Heating A 88.00 88.70 89.40
MCA A 193.0 194.0 195.0
Current
MFA A 225 225 225
EER Cooling W/W 3.47 3.31 3.17
Efficiency
COP Heating W/W 4.50 4.47 4.43
Body - GI Steel Plate GI Steel Plate GI Steel Plate
Casing Material
Base - GI Steel Plate GI Steel Plate GI Steel Plate
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Type - Inverter Scroll x 6 Inverter Scroll x 6 Inverter Scroll x 6
Output kW x n (6.67 x 2) x 2 + (8.93 x 2) x 1 (6.67 x 2) x 2 + (8.93 x 2) x 1 (6.67 x 2) x 2 + (8.93 x 2) x 1
(DS4GR7066FV* x 2) x 2 + (DS4GR7066FV* x 2) x 2 + (DS4GR7066FV* x 2) x 2 +
Model Name -
Compressor (DS4GM7090FV* x 2) x 1 (DS4GM7090FV* x 2) x 1 (DS4GM7090FV* x 2) x 1
Type - PVE PVE PVE
Oil (1,100 x 2) x 2 + (1,100 x 2) x 2 + (1,100 x 2) x 2 +
Initial charge cc x n
(1,400 x 2) x 1 (1,400 x 2) x 1 (1,400 x 2) x 1
Type - Propeller Propeller Propeller
Discharge direction - Top Top Top
Quantity EA 6 6 6
Fan ㎥/min 353 x 2 + 412 x 1 353 x 2 + 412 x 1 353 x 2 + 412 x 1
Air Flow Rate
l/s 5,882 x 2 + 6,860 x 1 5,882 x 2 + 6,860 x 1 5,882 x 2 + 6,860 x 1

External Static mmAq 8 8 8


Max.
Pressure Pa 80 80 80
Type - BLDC Motor BLDC Motor BLDC Motor
Fan Motor
Output Wxn (620 x 2) x 2 + (630 x 2) x 1 (620 x 2) x 2 + (630 x 2) x 1 (620 x 2) x 2 + (630 x 2) x 1
2. Specification
Standard - 50/60Hz
Model Name AM860AXVANH/EA AM880AXVANH/EA AM900AXVANH/EA
Outdoor unit module 1 AM260AXVANH/EA AM280AXVANH/EA AM280AXVANH/EA
Outdoor unit module 2 AM260AXVANH/EA AM260AXVANH/EA AM280AXVANH/EA
Outdoor unit module 3 AM340AXVANH/EA AM340AXVANH/EA AM340AXVANH/EA
Outdoor unit module 4 - - -
Type Braze connection Braze connection Braze connection
Liquid Pipe
Φ, ㎜ (inch) 22.22 (7/8) 22.22 (7/8) 22.22 (7/8)
Type Braze connection Braze connection Braze connection
Gas Pipe
Φ, ㎜ (inch) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length Max. [Equiv.] m 200[220] 200[220] 200[220]
(ODU-IDU)

Piping Piping length Max. m 90 90 90


(1st Branch-IDU)
Connections
Total piping
Max. m 1,000 1,000 1,000
length (System)
Level difference
(ODU in highest Max. m 110 110 110
position)

Level difference Max. m 110 110 110


(IDU in highest position)

Level difference Max. m 50 50 50


(IDU-IDU)

Transmission Min. ㎟ 0.75 0.75 0.75


Wiring Cable Remark - F1, F2 F1, F2 F1, F2
connections
Both indoor and Both indoor and Both indoor and
Power supply intake -
outdoor unit outdoor unit outdoor unit
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 14.0 x 2 + 15.5 x 1 14.0 x 2 + 15.5 x 1 14.0 x 2 + 15.5 x 1
Sound Pressure (Cooling) dB(A) 70 70 70
Sound
Sound Power (Cooling) dB(A) 92 92 92
Net Weight kg 317 x 2 + 390 x 1 317 x 2 + 390 x 1 317 x 2 + 390 x 1
Shipping Weight kg 334 x 2 + 416 x 1 334 x 2 + 416 x 1 334 x 2 + 416 x 1
External (1,295 x 1,695 x 765) x 2 + (1,295 x 1,695 x 765) x 2 + (1,295 x 1,695 x 765) x 2 +
Dimension Net Dimensions (WxHxD) ㎜ (1,860 x 1,695 x 765) x 1 (1,860 x 1,695 x 765) x 1 (1,860 x 1,695 x 765) x 1
(1,363 x 1,887 x 829) x 2 + (1,363 x 1,887 x 829) x 2 + (1,363 x 1,887 x 829) x 2 +
Shipping Dimensions (WxHxD) ㎜ (1,928 x 1,887 x 829) x 1 (1,928 x 1,887 x 829) x 1 (1,928 x 1,887 x 829) x 1

Operating Cooling ℃ -5 ~ 50 -5 ~ 50 -5 ~ 50
Temp. Range Heating ℃ -25 ~ 24 -25 ~ 24 -25 ~ 24

NOTE
• Specification may be subject to change without prior notice.
1) Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°CDB, 19°CWB, Outdoor temperature 35°CDB, 24°CWB
- Heating : Indoor temperature 20°CDB, 15°CWB, Outdoor temperature 7°CDB, 6°CWB
- Equivalent refrigerant pipe length 5m, Level differences 0m
2) Performance of Multiple Module Outdoor unit is weighted average of Single Module outdoor units.
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
2. Specification
Standard - 50/60Hz
Model Name AM920AXVANH/EA AM940AXVANH/EA AM960AXVANH/EA
Outdoor unit module 1 AM260AXVANH/EA AM260AXVANH/EA AM300AXVANH/EA
Outdoor unit module 2 AM320AXVANH/EA AM340AXVANH/EA AM320AXVANH/EA
Outdoor unit module 3 AM340AXVANH/EA AM340AXVANH/EA AM340AXVANH/EA
Outdoor unit module 4 - - -
Power Supply Ø, #, V, Hz 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60
Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 92 94 96
Performance Cooling kW 257.6 263.2 268.8
Capacity
Heating kW 268.8 268.8 284.9
Maximum number of connectable indoor units EA 64 64 64

Total capacity of the connected Min. kW 128.8 131.6 134.4


Indoor Units Max. kW 334.9 342.2 349.4
Cooling kW 78.16 82.32 82.00
Power Input
Heating kW 59.97 60.45 63.32
Cooling A 123.30 129.80 128.80
Power Current Input
Heating A 94.30 95.00 99.60
MCA A 201.6 206.0 206.6
Current
MFA A 225 250 250
EER Cooling W/W 3.30 3.20 3.28
Efficiency
COP Heating W/W 4.48 4.45 4.50
Body - GI Steel Plate GI Steel Plate GI Steel Plate
Casing Material
Base - GI Steel Plate GI Steel Plate GI Steel Plate
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Type - Inverter Scroll x 6 Inverter Scroll x 6 Inverter Scroll x 6
Output kW x n (6.67 x 2) x 1 + (8.93 x 2) x 2 (6.67 x 2) x 1 + (8.93 x 2) x 2 (8.93 x 2) x 3
(DS4GR7066FV* x 2) x 1 + (DS4GR7066FV* x 2) x 1 +
Model Name - (DS4GM7090FV* x 2) x 3
Compressor (DS4GM7090FV* x 2) x 2 (DS4GM7090FV* x 2) x 2
Type - PVE PVE PVE
Oil (1,100 x 2) x 1 + (1,100 x 2) x 1 +
Initial charge cc x n (1,400 x 2) x 3
(1,400 x 2) x 2 (1,400 x 2) x 2
Type - Propeller Propeller Propeller
Discharge direction - Top Top Top
Quantity EA 6 6 6
Fan ㎥/min 353 x 1 + 412 x 2 353 x 1 + 412 x 2 412 x 3
Air Flow Rate
l/s 5,882 x 1 + 6,860 x 2 5,882 x 1 + 6,860 x 2 6,860 x 3

External Static mmAq 8 8 8


Max.
Pressure Pa 80 80 80
Type - BLDC Motor BLDC Motor BLDC Motor
Fan Motor
Output Wxn (620 x 2) x 1 + (630 x 2) x 2 (620 x 2) x 1 + (630 x 2) x 2 (630 x 2) x 3
2. Specification
Standard - 50/60Hz
Model Name AM920AXVANH/EA AM940AXVANH/EA AM960AXVANH/EA
Outdoor unit module 1 AM260AXVANH/EA AM260AXVANH/EA AM300AXVANH/EA
Outdoor unit module 2 AM320AXVANH/EA AM340AXVANH/EA AM320AXVANH/EA
Outdoor unit module 3 AM340AXVANH/EA AM340AXVANH/EA AM340AXVANH/EA
Outdoor unit module 4 - - -
Type Braze connection Braze connection Braze connection
Liquid Pipe
Φ, ㎜ (inch) 25.40 (1) 25.40 (1) 25.40 (1)
Type Braze connection Braze connection Braze connection
Gas Pipe
Φ, ㎜ (inch) 53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length Max. [Equiv.] m 200[220] 200[220] 200[220]
(ODU-IDU)

Piping Piping length Max. m 90 90 90


(1st Branch-IDU)
Connections
Total piping
Max. m 1,000 1,000 1,000
length (System)
Level difference
(ODU in highest Max. m 110 110 110
position)

Level difference Max. m 110 110 110


(IDU in highest position)

Level difference Max. m 50 50 50


(IDU-IDU)

Transmission Min. ㎟ 0.75 0.75 0.75


Wiring Cable Remark - F1, F2 F1, F2 F1, F2
connections
Both indoor and Both indoor and Both indoor and
Power supply intake -
outdoor unit outdoor unit outdoor unit
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 14.0 x 1 + 15.5 x 2 14.0 x 1 + 15.5 x 2 15.5 x 3
Sound Pressure (Cooling) dB(A) 70 70 70
Sound
Sound Power (Cooling) dB(A) 92 92 92
Net Weight kg 317 x 1 + 390 x 2 317 x 1 + 390 x 2 390 x 3
Shipping Weight kg 334 x 1 + 416 x 2 334 x 1 + 416 x 2 416 x 3
External (1,295 x 1,695 x 765) x 1 + (1,295 x 1,695 x 765) x 1 +
Dimension Net Dimensions (WxHxD) ㎜ (1,860 x 1,695 x 765) x 3
(1,860 x 1,695 x 765) x 2 (1,860 x 1,695 x 765) x 2
(1,363 x 1,887 x 829) x 1 + (1,363 x 1,887 x 829) x 1 +
Shipping Dimensions (WxHxD) ㎜ (1,928 x 1,887 x 829) x 3
(1,928 x 1,887 x 829) x 2 (1,928 x 1,887 x 829) x 2

Operating Cooling ℃ -5 ~ 50 -5 ~ 50 -5 ~ 50
Temp. Range Heating ℃ -25 ~ 24 -25 ~ 24 -25 ~ 24

NOTE
• Specification may be subject to change without prior notice.
1) Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°CDB, 19°CWB, Outdoor temperature 35°CDB, 24°CWB
- Heating : Indoor temperature 20°CDB, 15°CWB, Outdoor temperature 7°CDB, 6°CWB
- Equivalent refrigerant pipe length 5m, Level differences 0m
2) Performance of Multiple Module Outdoor unit is weighted average of Single Module outdoor units.
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
2. Specification
Standard - 50/60Hz
Model Name AM980AXVANH/EA
Outdoor unit module 1 AM300AXVANH/EA
Outdoor unit module 2 AM340AXVANH/EA
Outdoor unit module 3 AM340AXVANH/EA
Outdoor unit module 4 -
Power Supply Ø, #, V, Hz 3,4,380~415,50/60
Mode - HEAT PUMP
HP HP 98
Performance Cooling kW 274.4
Capacity
Heating kW 284.9
Maximum number of connectable indoor units EA 64

Total capacity of the connected Min. kW 137.2


Indoor Units Max. kW 356.7
Cooling kW 86.16
Power Input
Heating kW 63.80
Cooling A 135.30
Power Current Input
Heating A 100.30
MCA A 211.0
Current
MFA A 250
EER Cooling W/W 3.18
Efficiency
COP Heating W/W 4.47
Body - GI Steel Plate
Casing Material
Base - GI Steel Plate
Type - Fin & Tube
Heat Fin - Al
Material
Exchanger Tube - Cu
Fin Treatment - Anti-corrosion
Type - Inverter Scroll x 6
Output kW x n (8.93 x 2) x 3

Model Name - (DS4GM7090FV* x 2) x 3


Compressor
Type - PVE
Oil
Initial charge cc x n (1,400 x 2) x 3

Type - Propeller
Discharge direction - Top
Quantity EA 6
Fan ㎥/min 412 x 3
Air Flow Rate
l/s 6,860 x 3

External Static mmAq 8


Max.
Pressure Pa 80
Type - BLDC Motor
Fan Motor
Output Wxn (630 x 2) x 3
2. Specification
Standard - 50/60Hz
Model Name AM980AXVANH/EA
Outdoor unit module 1 AM300AXVANH/EA
Outdoor unit module 2 AM340AXVANH/EA
Outdoor unit module 3 AM340AXVANH/EA
Outdoor unit module 4 -
Type Braze connection
Liquid Pipe
Φ, ㎜ (inch) 25.40 (1)
Type Braze connection
Gas Pipe
Φ, ㎜ (inch) 53.98 (2-1/8)
Heat Insulation - Both liquid and gas pipes
Piping length Max. [Equiv.] m 200[220]
(ODU-IDU)

Piping Piping length Max. m 90


(1st Branch-IDU)
Connections
Total piping
Max. m 1,000
length (System)
Level difference
(ODU in highest Max. m 110
position)

Level difference Max. m 110


(IDU in highest position)

Level difference Max. m 50


(IDU-IDU)

Transmission Min. ㎟ 0.75


Wiring Cable Remark - F1, F2
connections
Both indoor and
Power supply intake -
outdoor unit
Type - R410A
Refrigerant
Factory Charging kg 15.5 x 3
Sound Pressure (Cooling) dB(A) 70
Sound
Sound Power (Cooling) dB(A) 92
Net Weight kg 390 x 3
Shipping Weight kg 416 x 3
External
Dimension Net Dimensions (WxHxD) ㎜ (1,860 x 1,695 x 765) x 3

Shipping Dimensions (WxHxD) ㎜ (1,928 x 1,887 x 829) x 3

Operating Cooling ℃ -5 ~ 50
Temp. Range Heating ℃ -25 ~ 24

NOTE
• Specification may be subject to change without prior notice.
1) Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°CDB, 19°CWB, Outdoor temperature 35°CDB, 24°CWB
- Heating : Indoor temperature 20°CDB, 15°CWB, Outdoor temperature 7°CDB, 6°CWB
- Equivalent refrigerant pipe length 5m, Level differences 0m
2) Performance of Multiple Module Outdoor unit is weighted average of Single Module outdoor units.
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
4. Dimensional Drawing
Outdoor unit

• AM080/100AXVANH/EA Unit: mm (inches)

NOTE

1 Detail A and SECTION B-B indicate the dimension


after fixing the attached piping.
2 Item 3-6: Knock-out hole
3 View C indicate the dimension of knock-out hole
(bottom)
4 Pipe [Ø, mm(inch)]: Brazing connection

HP Liquid pipe Gas pipe


8 9.52(3/8) 19.05(3/4)
10 9.52(3/8) 22.22(7/8)

NO Table of descriptions Remark NO Table of descriptions Remark


1 Gas Ref.pipe See NOTE 4. 5 Knock-out Hole for Ref.Piping (bottom)
2 Liquid Ref.pipe See NOTE 4. 6 Knock-out Hole for Ref.Piping (front)
3 Power wiring conduit Ø44
4 Communication wiring conduit Ø34
4. Dimensional Drawing
Outdoor unit

• AM120/140AXVANH/EA Unit: mm (inches)

NOTE

1 Detail A and SECTION B-B indicate the dimension


after fixing the attached piping.
2 Item 3-6: Knock-out hole
3 View C indicate the dimension of knock-out hole
(bottom)
4 Pipe [Ø, mm(inch)]: Brazing connection

HP Liquid pipe Gas pipe


12 12.70(1/2) 28.58(1-1/8)
14 12.70(1/2) 28.58(1-1/8)

NO Table of descriptions Remark NO Table of descriptions Remark


1 Gas Ref.pipe See NOTE 4. 5 Knock-out Hole for Ref.Piping (bottom)
2 Liquid Ref.pipe See NOTE 4. 6 Knock-out Hole for Ref.Piping (front)
3 Power wiring conduit Ø44
4 Communication wiring conduit Ø34
4. Dimensional Drawing
Outdoor unit

• AM160/180/200/220/240/260/280AXVANH/EA Unit: mm (inches)

NOTE

1 Detail A and SECTION B-B indicate the dimension


after fixing the attached piping.
2 Item 3-6: Knock-out hole
3 View C indicate the dimension of knock-out hole
(bottom)
4 Pipe [Ø, mm(inch)]: Brazing connection

HP Liquid pipe Gas pipe


16 12.70(1/2) 28.58(1-1/8)
18 15.88(5/8) 28.58(1-1/8)
20 15.88(5/8) 28.58(1-1/8)
22 15.88(5/8) 28.58(1-1/8)
24 15.88(5/8) 34.92(1-3/8)
26 19.05(3/4) 34.92(1-3/8)
28 19.05(3/4) 34.92(1-3/8)

NO Table of descriptions Remark NO Table of descriptions Remark


1 Gas Ref.pipe See NOTE 4. 5 Knock-out Hole for Ref.Piping (bottom)
2 Liquid Ref.pipe See NOTE 4. 6 Knock-out Hole for Ref.Piping (front)
3 Power wiring conduit Ø44
4 Communication wiring conduit Ø34
4. Dimensional Drawing
Outdoor unit

• AM300/320/340AXVANH/EA Unit: mm (inches)

NOTE

1 Detail A and SECTION B-B indicate the dimension


after fixing the attached piping.
2 Item 3-6: Knock-out hole
3 View C indicate the dimension of knock-out hole
(bottom)
4 Pipe [Ø, mm(inch)]: Brazing connection

HP Liquid pipe Gas pipe


30 19.05(3/4) 34.92(1-3/8)
32 19.05(3/4) 34.92(1-3/8)
34 19.05(3/4) 34.92(1-3/8)

NO Table of descriptions Remark NO Table of descriptions Remark


1 Gas Ref.pipe See NOTE 4. 5 Knock-out Hole for Ref.Piping (bottom)
2 Liquid Ref.pipe See NOTE 4. 6 Knock-out Hole for Ref.Piping (front)
3 Power wiring conduit Ø44
4 Communication wiring conduit Ø34