DCA30142

BUILDING SERVICES 2
TOPIC 2:
FIRE PROTECTION SYSTEM
(APPLICATION OF FIRE PROTECTION SYSTEM INTO
DESIGN-BASED TASK)
TODAY’S LEARNING OUTCOMES
(PART 3 OF 3 PARTS)
At the end of this topic, students must be able to:

2.1 Apply knowledge of fire protection system into design-based task (people habitat/
community building):
2.1.7 Identify the passive fire protection system in a building according to the UBBL
2.1.8 Choose the suitable active fire protection system in a building according to the UBBL
2.1.9 Construct diagram of fire protection system in a building with appropriate label and
explanation
CONTENT OF TODAY’S LECTURE
1. Selection of Appropriate Passive Fire Protection System
2. Selection of Appropriate Active Fire Protection System
3. Construct Diagram of Fire Protection System
APPLICATION OF FIRE PROTECTION SYSTEM
INTO DESIGN-BASED TASK
INSTRUCTIONS:
1. Choose Appropriate Passive Fire
Protection System
2. Choose Appropriate Active Fire
Protection System
3. Construct Diagram of Fire Hotel Suria
Protection System • Number of storey= 10
• Total height= 35 m
• Floor area= 2000 m²
• Volume= 5500 m³
• Number of room= 40
rooms each floor
1. Choose Passive Fire Protection System
BUILDING PURPOSE- REFER TO 5TH SCHEDULE IN THE UBBL

Refer to UBBL 168, 175, 176, 177 & 181


Maximum Travel Distance= 45 m with sprinkler system (7th
Schedule)

Dead End Limit= 10 m (7th Schedule)

Occupant Load= 2 pax per room = 80 pax/ floor (By Law


175)

Capacity of Exits= 45 pax (By Law 176, 7th Schedule).


Need for 2 fire exit staircases

Exit width required= 80/ 45= 1.77m= 1.8 (By Law 176, 7th
Schedule)

Total Exit Width Required=


1.8 x 550mm= 990mm (By Law 176, 7th Schedule).
2.0 x 550mm= 1100mm (By Law 177 & 181)
Maximum Travel Distance= 45 m with sprinkler system (7th Schedule)

Dead End Limit= 10 m (7th Schedule)


Occupant Load= 2 pax per room = 80 pax/
floor (By Law 175)

Capacity of Exits= 45 pax (By Law 176, 7th


Schedule). Need for 2 fire exit staircases
Exit width required= 80/ 45= 1.77m= 1.8 (By Law 176, 7th Schedule)

Therefore, Total Exit Width Required=


1.8 x 550mm= 990mm (By Law 176, 7th Schedule).
2.0 x 550mm= 1100mm (By Law 177 & 181)
1. Choose Active Fire Protection System
Portable Fire Extinguisher….. Along the corridor and at the lobby
Hose Reel……………………..Along the corridor and at the lobby
Fire Alarm……………………..Along the corridor and at the lobby
Manual Break Point…………..Along the corridor and at the lobby
Fire sprinkler system…………At the ceiling along the corridor, at the lobby and in all
rooms
Smoke Detector………………At the ceiling along the corridor, at the lobby and in all
rooms
Exit (KELUAR) Sign………….At every exit doors
Emergency Light……………...At the ceiling along the corridor, at the lobby and in
stairways
SUMMATIVE ASSESSMENT
ASSIGNMENT 1(b)
END OF TOPIC 2