You are on page 1of 3

0811-215 Electra242-final.

qxp 2/02/09 14:22 Page 25

TECHNICAL BROCHURE
368
WG
Operating environment of voltage A3.18
grading capacitors
applied to high voltage
circuit-breakers
Members:

M. Runde, Convenor (NO), A. Bosma (SE), P.F. Coventry (UK), S. Dick (AU),
E. Kynast (DE), C. Paul (DE), A. Ribeiro (BR), J. Rickmann (CH),
E. Savary (CH), B.R. Sunga (CA), D. Yoshida (JP), J.K. Schjølberg, Guest (NO)

The figure opposite shows a two unit 300 kV circuit-


breaker with the grading capacitors in separate porce-
Voltage grading capacitors are accessories to high- lain housings in parallel with the bigger porcelain hous-
voltage circuit-breakers used to control the voltage dis- ings containing the SF6 filled interrupting chambers.
tribution across each breaking unit / interrupting cham- Service problems and failures of grading capacitors
ber of multi-unit circuit-breakers, both when the do not seem to have been a matter of great concern for
circuit-breaker is in open position and during making most utilities when considering the overall service expe-
and breaking operations. Grading capacitors are always rience of their circuit-breakers. However, exceptions exist.
mounted in parallel with each chamber. A few utilities have in recent years reported about sub-
stantial problems, including leaks, disruptive dielectric
failures and mechanical fatigue problems.
Grading capacitors are during service subjected to a
wide variety of electrical, mechanical and environmen-
tal conditions. But there has been little common consen-
sus within the switchgear community regarding the true
nature of the stresses. Moreover, no internationally
accepted standards for testing of grading capacitors exist.
Against this background SC A3 established WG A3.18
in July 2003. The tasks assigned to the WG include review-
ing all aspects of the operating environment of grading
capacitors, and correlating this with state of the art testing
procedures and failure history. Based on this, recommen-
dations with regard to improved, commonly applicable test
procedures for grading capacitors should be given.

Representatives from more than twenty utilities from


nine countries around the world have been contacted
and interviewed about service experience and failure his-
tory of their grading capacitors.
The vast majority of the service problems reported
Two unit circuit-breaker concern leaks and corrosion. Leaks were most widely
with grading capacitors reported as oil leaking from grading capacitors in

No. 242 - February 2009 E L E C T R A 25


0811-215 Electra242-final.qxp 2/02/09 14:22 Page 27

TECHNICAL BROCHURE
368
Air Insulated Substations (AIS). A significant number of failure usually occurred on or shortly after an opening
WG
cases of SF6 leaking into oil filled grading capacitors used operation (although the internal damage of course may A3.18
in Gas Insulated Switchgear (GIS) were reported, have been created during the previous closing or open-
although these were confined to a few utilities. In some ing operation).
cases, oil leaks from GIS capacitors had been observed. Examinations of partly damaged shunt reactor cir-
Moisture ingress into AIS grading capacitors was cuit-breaker capacitors suggest that the failure origi-
reported in a significant number of cases. nates in dielectric stresses of an unforeseen nature and
There was no correlation with the number of oper- magnitude, but detailed and convincing explanations
ations or switching duty, but a clear correlation with age. were not found. For the involved parties considered
Leaks were most common for older grading capacitors. this an unsatisfactory situation, as the understanding
Most of the affected capacitors had been in service for of the phenomena of course is essential for finding
20 years or more. remedies.
In some cases, a significant proportion of the grad- A few cases where metal foil conductors connect-
ing capacitor population of a certain type of design was ing the capacitor elements inside the grading capacitor
affected. One large utility estimated that more than 5 000 have suffered mechanical fatigue and broken off have
out of its total grading capacitor population of approx- been disclosed. Broken conductors may cause internal
imately 25 000 had been replaced due to leaks. arcing, pressure rise and eventually lead to a disruptive
The figure hereafter shows a typical appearance of a failure. Hence, the mechanical stresses the capacitors are
leak from the flange of a AIS grading capacitor. subjected to is a concern.
Some instances of disruptive dielectric failure of
grading capacitors were reported. The number of cases,
a few dozens, was small compared to the total number
of circuit-breakers covered in the survey. The failures had
occurred on both GIS and AIS circuit-breakers. Most had Viewed in the light of the large number of
occurred within less than 15 years of service. reported leaks it is important to subject grading
A dielectric disruptive failure is a highly disturb- capacitors to tests that verify their tightness and cor-
ing event, usually causing major damages to the rest of rosion resistance.
the circuit breaker and in some cases also affecting Corrosion tests for AIS grading capacitors should
equipment installed in the vicinity of the circuit- consider the usual environmental stresses that all out-
breaker. door equipment is subjected to. Grading capacitors in
In general there was a clear correlation between dis- GIS have to withstand SF6 by-products. Tightness tests
ruptive dielectric failures and switching duty. Most of the should take account of oil and gas tightness both when
circuit-breakers concerned had been switching low the external pressure is higher than the internal pressure
inductive currents associated with shunt reactors, and of the grading capacitor, and vice versa.
To check the tightness it is recommended to, as a
design test, subject the grading capacitor to ten ther-
mal cycles between the upper and lower service tem-
peratures specified, typically from -40 °C to +90 °C for
GIS and from -55 °C to +75 °C for grading capacitors
used in AIS. For oil filled capacitors leakage tests are
done by visual inspection. For SF6 impregnated capac-
itors, SF6 or helium leakage detection systems should
be used.
The tightness of oil filled capacitors is routine tested
with a pressure of the liquid above the operating pres-
sure for 24 h. For capacitors used in GIS, both vacuum
(1 Pa) and air pressure (0.8 MPa) should be applied dur-
ing the routine test at the highest rated service temper-
ature of the application, typically 90°C. The reason for
this test is that the capacitor is subjected to both vacuum
Oil leak in grading capacitor (by the circuit-breaker manufacturer before filling SF6)
of circuit-breaker and SF6 overpressure (in service).

No. 242 - February 2009 E L E C T R A 27


0811-215 Electra242-final.qxp 2/02/09 14:22 Page 29

TECHNICAL BROCHURE
368
WG
during pre-striking and during re-ignition, due to the
rapid rate of change of voltage and the high amplitude
A3.18
It appears that the circuit-breaker operations cause currents that will result.
the most severe mechanical stresses. Broadband accel- It has however, not been possible to verify the results
eration measurements directly on the grading capac- of the modeling since experimental data is not presently
itors during switching operations have been carried available. There is a need for more research in this area.
out on around ten different circuit-breaker models, Still it is felt necessary to specify additional require-
both minimum oil and SF 6 technology (AIS as well ments and type tests for grading capacitors for shunt
as GIS). reactor switching in order to ensure their strength and
The vibration measurements typically show maxi- capability for this application.
mum acceleration values of several tens of g’s, but these
high values occur for very high frequencies (tens of kHz)
and are of less concern, since the associated displace-
ments are very small (mm and less).
A grading capacitor is probably much more vul- The WG has addressed the various types of stresses
nerable to vibrations with frequencies around its grading capacitors experience in service. It is fairly obvi-
mechanical resonance frequencies. These are typically ous that many of the old capacitor designs were insuf-
below 100 - 200 Hz. By low pass filtering the acceleration ficient with regard to tightness and resistance against cor-
measurements it appears that for frequencies below rosion. Comprehensive leak problems caused the lifetime
200 Hz the acceleration values rarely exceed 10g dur- of many capacitors to be substantially less than the life-
ing circuit-breaker operations. time of the circuit-breaker itself. However, improvements
Hence, with regard to design and type testing of with regard to corrosion protection, sealing designs and
capacitors it is proposed to use a shaking table and sub- quality assurance have made this a lesser problem on
ject the complete capacitor assembly to half sine mechan- newer designs.
ical shocks with a duration corresponding to a frequency A solid, verified explanation of the disruptive capac-
lower than the mechanical resonance frequency, as deter- itor failures occurring during switching of shunt reactors
mined by a frequency sweep recording. has not been found, so this matter remains somewhat elu-
In addition, to verify the mechanical strength and sive. More work, including full scale measurements is
integrity of the capacitor housing, it is recommended required to reach a full understanding of the dielectric
to carry out bending tests and pressure tests accord- stresses the capacitors are exposed to.
ing to the IEC standard for hollow ceramic or glass Finally, it is the hope of the WG that the information
insulators. that has been collected about the service experience and
operating environment in the future can be used as a basis
for international standards for grading capacitors. ■

The service experience clearly indicates that a care-


ful investigation into the dielectric stresses that may
occur during switching of small inductive currents is
appropriate. The figure opposite shows an example
where the capacitor stack has experienced voltages
beyond its capability.
Careful modeling indicates that current chopping
and unequal voltage sharing between the grading capac-
itors during switching (particular those that might arise
during re-ignition) can impose significant stresses on the
grading capacitors.
Moreover, accounts needs to be taken of the ability
of a grading capacitor to be discharged through the near Short-circuited capacitor elements of a grading
short circuit loop closed by its associated interrupter, capacitor removed from a reactor breaker

No. 242 - February 2009 E L E C T R A 29

You might also like