Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 20, 2023 Date: 6/20/2023
Fastening point:
Specifier's comments:
1 Input data
Anchor type and diameter: HST3-R M20 hef2
Return period (service life in years): 50
Item number: not available
Effective embedment depth: hef,act = 150.0 mm (hef,limit = - mm), hnom = 165.0 mm
Material: A4
Evaluation Service Report: ETA 98/0001
Issued I Valid: 11/3/2022 | -
Proof: Design Method EN 1992-4, Mechanical
Stand-off installation: without clamping (anchor); restraint level (anchor plate): 2.00; eb = 5.0 mm; t = 20.0 mm
2
Hilti Grout: CB-G EG, epoxy, fc,Grout = 120.00 N/mm
Anchor plate :
R lx x ly x t = 500.0 mm x 500.0 mm x 20.0 mm; (Recommended plate thickness: not calculated)
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
1
Hilti PROFIS Engineering 3.0.85
www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 20, 2023 Date: 6/20/2023
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
2
Hilti PROFIS Engineering 3.0.85
www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 20, 2023 Date: 6/20/2023
Fastening point:
Anchor forces are calculated based on the assumption of a rigid anchor plate.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
Hilti PROFIS Engineering 3.0.85
www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 20, 2023 Date: 6/20/2023
Fastening point:
N
NEd £ NRd,s = Rk,s EN 1992-4, Table 7.1
gM,s
y c · NRk,p
NEd £ NRd,p = EN 1992-4, Table 7.1
gM,p
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
4
Hilti PROFIS Engineering 3.0.85
www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 20, 2023 Date: 6/20/2023
Fastening point:
N
NEd £ NRd,c = Rk,c EN 1992-4, Table 7.1
gM,c
0 Ac,N
NRk,c = NRk,c · 0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eN,1
scr,N )
1
y ec2,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eN,2
scr,N )
y M,N =1 EN 1992-4, Eq. (7.7)
2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] fc,cyl [N/mm ]
552,500 202,500 225.0 450.0 50.00
Group anchor ID
1, 2, 4, 6, 7
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
5
Hilti PROFIS Engineering 3.0.85
www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 20, 2023 Date: 6/20/2023
Fastening point:
V
VEd £ VRd,s = Rk,s EN 1992-4, Table 7.2
gM,s
0
VRk,s = k7 · VRk,s EN 1992-4, Eq. (7.35)
0
VRk,s [kN] k7 VRk,s [kN] gM,s VRd,s [kN] VEd [kN]
97.200 1.000 97.200 1.250 77.760 2.684
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
6
Hilti PROFIS Engineering 3.0.85
www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 20, 2023 Date: 6/20/2023
Fastening point:
V
VEd £ VRd,cp = Rk,cp EN 1992-4, Table 7.2
gM,c,p
VRk,cp = k8 · NRk,c EN 1992-4, Eq. (7.39a)
0 A
NRk,c = NRk,c · c,N
0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,1
scr,N )
1
y ec2,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,2
scr,N )
y M,N =1 EN 1992-4, Eq. (7.7)
2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] k8 fc,cyl [N/mm ]
722,500 202,500 225.0 450.0 3.200 50.00
Group anchor ID
1-8
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
7
Hilti PROFIS Engineering 3.0.85
www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 20, 2023 Date: 6/20/2023
Fastening point:
a a
bN + bV £ 1.0
Concrete failure
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements are
valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not included in
this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
8
Hilti PROFIS Engineering 3.0.85
www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 20, 2023 Date: 6/20/2023
Fastening point:
7 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EN 1992-4, Annex A!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 6.1 of EN 1992-4! For larger diameters of the
clearance hole see section 6.2.2 of EN 1992-4!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to be
followed to ensure a proper installation.
• For the determination of the y re,v (concrete edge failure) the minimum concrete cover defined in the design settings is used as the concrete
cover of the edge reinforcement.
• The characteristic bond resistances depend on the return period (service life in years): 50
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
9
Hilti PROFIS Engineering 3.0.85
www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 20, 2023 Date: 6/20/2023
Fastening point:
8 Installation data
2 2
Anchor plate, steel: S 235; E = 210,000.00 N/mm ; fyk = 235.00 N/mm Anchor type and diameter: HST3-R M20 hef2
Profile: Square hollow, 200 x 200 x 5; (L x W x T) = 200.0 mm x 200.0 mm x Item number: not available
5.0 mm
Hole diameter in the fixture: df = 22.0 mm Maximum installation torque: 180 Nm
Plate thickness (input): 20.0 mm Hole diameter in the base material: 20.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 185.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 209.0 mm
Cleaning: No cleaning of the drilled hole is required
Hilti HST3 stud anchor with 150 mm embedment, M20 hef2, Stainless steel, installation per ETA 98/0001
y
250.0 250.0
50.0
6 7 8
250.0
200.0
4 5
x
200.0
250.0
1 2 3
50.0
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
10
Hilti PROFIS Engineering 3.0.85
www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 11
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 20, 2023 Date: 6/20/2023
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
11
Hilti PROFIS Engineering 3.0.85
www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 12
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jun 20, 2023 Date: 6/20/2023
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan