Moulded Case Circuit Breakers Ex9M

■■ Moulded Case Circuit Breakers

■■ Frame sizes M1-M5

■■ Rated current up to 800 A

■■ 3 and 4-pole versions

■■ Rated ultimate short circuit breaking


capacity Icu up to 150 kA, Ics = 100 % Icu

■■ Rated voltage 415 / 690 V AC

■■ Thermomagnetic releases

■■ Fixed versions

Moulded Case Circuit Breakers Ex9M TM are intended for applications in power distribution mainly. Testing
according to IEC / EN 60947-2 standards ensures functions and reliability for wide variety of applications
including isolation.
These breakers are offered with breaking capacities from 36 kA up to extreme 150 kA. Rated impulse with-
stand voltage Uimp 8 kV makes it possible to use them even in system with occurences of transient overvol-
tage waves of high intensity, e.g. in heavy industry.
Utilization category A circuit breakers.

Type Key

Ex9 M 1 S TM AC 100 3P

Product Frame Breaking Release Current Rated


Product Poles
family size capacity technology character current

1: to 125 A 16 — 125
S: 36 kA 3P: 3-pole
2: to 250 A TM: 125 — 250
N: 50 kA 4P4T: 4-pole
Ex9 M: MCCB 3: to 400 A Thermo- AC 250 — 400
H: 100 kA with protected
4: to 630 A magnetic 400 — 630
P: 150 kA N-pole
5: to 800 A 630 — 800

Certification marks

1
Moulded Case Circuit Breakers Ex9M
Internal accessories

1 2 5 1

4 3

1 2 3 4 5

Shunt trip release Undervoltage release Early-make


Auxiliary contact Signal contact
SHT2i UVT2i auxiliary contact
AX21 AL21
1 unit or UVT2i 1 unit or SHT2i EC 2i

Auxiliary contact AX21


Signal contact AL21
Shunt trip releases SHT2i
Undervoltage releases UVT2i
Early-make auxiliary contact EC 2i

All internal accessories for the frame sizes M2+M3 and M4+M5 are identical.

2
Moulded Case Circuit Breakers Ex9M
External accessories

Phase barriers Terminal cover, short Terminal cover, long


PB2i TCV2i TCE2i

Box terminals Tunnel terminals Mounting depth spacers


MC2i MC2i W WG i

Remote operator Direct rotary handle Extended rotary handle


MOD2i RHD2i ERH2i

Phase barriers PB2i


Terminal cover, short TCV2i
Terminal cover, long TCE2i
Remote operators MOD2i
Direct rotary handles RHD2i
Extended rotary handles ERH2i
Connection terminals MC2i
Mounting depth spacers WG i

3
Moulded Case Circuit Breakers Ex9M1
Version Ex9M1S up to 125 A, Icu = 36 kA

• 3 and 4-pole Moulded Case Circuit Breakers


• Ics = Icu = 36 kA at 415 V AC
• Ir can be set in steps (0.8-0.9-1.0) × In
• Ii fixed as 10 × In
• Mounting screws, box terminals as well as phase barriers in the scope of delivery

Poles Rated Overcurrent Instant. Article No. Type Packing


current In release Ir release Ii
3 16 A 12.8—16 A 160 A 100886 Ex9M1S TM AC16 3P 1/8
3 20 A 16—20 A 200 A 100887 Ex9M1S TM AC20 3P 1/8
3 25 A 20—25 A 250 A 100888 Ex9M1S TM AC25 3P 1/8
3 32 A 25.6—32 A 320 A 100889 Ex9M1S TM AC32 3P 1/8
3 40 A 32—40 A 400 A 100890 Ex9M1S TM AC40 3P 1/8
3 50 A 40—50 A 500 A 100891 Ex9M1S TM AC50 3P 1/8
3 63 A 50.4—63 A 630 A 100892 Ex9M1S TM AC63 3P 1/8
3 80 A 64—80 A 800 A 100893 Ex9M1S TM AC80 3P 1/8
3 100 A 80—100 A 1000 A 100894 Ex9M1S TM AC100 3P 1/8
3 125 A 100—125 A 1250 A 100895 Ex9M1S TM AC125 3P 1/8

4 16 A 12.8—16 A 160 A 103062 Ex9M1S TM AC16 4P4T 1/8


4 20 A 16—20 A 200 A 103063 Ex9M1S TM AC20 4P4T 1/8
4 25 A 20—25 A 250 A 103064 Ex9M1S TM AC25 4P4T 1/8
4 32 A 25.6—32 A 320 A 103065 Ex9M1S TM AC32 4P4T 1/8
4 40 A 32—40 A 400 A 103066 Ex9M1S TM AC40 4P4T 1/8
4 50 A 40—50 A 500 A 103067 Ex9M1S TM AC50 4P4T 1/8
4 63 A 50.4—63 A 630 A 103068 Ex9M1S TM AC63 4P4T 1/8
4 80 A 64—80 A 800 A 103069 Ex9M1S TM AC80 4P4T 1/8
4 100 A 80—100 A 1000 A 103070 Ex9M1S TM AC100 4P4T 1/8
4 125 A 100—125 A 1250 A 103071 Ex9M1S TM AC125 4P4T 1/8

Version Ex9M1N up to 125 A, Icu = 50 kA

• 3 and 4-pole Moulded Case Circuit Breakers


• Ics = Icu = 50 kA at 415 V AC
• Ir can be set in steps (0.8-0.9-1.0) × In
• Ii fixed as 10 × In
• Mounting screws, box terminals as well as phase barriers in the scope of delivery

Poles Rated Overcurrent Instant. Article No. Type Packing


current In release Ir release Ii
3 16 A 12.8—16 A 160 A 100896 Ex9M1N TM AC16 3P 1/8
3 20 A 16—20 A 200 A 100897 Ex9M1N TM AC20 3P 1/8
3 25 A 20—25 A 250 A 100898 Ex9M1N TM AC25 3P 1/8
3 32 A 25.6—32 A 320 A 100899 Ex9M1N TM AC32 3P 1/8
3 40 A 32—40 A 400 A 100900 Ex9M1N TM AC40 3P 1/8
3 50 A 40—50 A 500 A 100901 Ex9M1N TM AC50 3P 1/8
3 63 A 50.4—63 A 630 A 100902 Ex9M1N TM AC63 3P 1/8
3 80 A 64—80 A 800 A 100903 Ex9M1N TM AC80 3P 1/8
3 100 A 80—100 A 1000 A 100904 Ex9M1N TM AC100 3P 1/8
3 125 A 100—125 A 1250 A 100905 Ex9M1N TM AC125 3P 1/8

4 16 A 12.8—16 A 160 A 103072 Ex9M1N TM AC16 4P4T 1/8


4 20 A 16—20 A 200 A 103073 Ex9M1N TM AC20 4P4T 1/8
4 25 A 20—25 A 250 A 103074 Ex9M1N TM AC25 4P4T 1/8
4 32 A 25.6—32 A 320 A 103075 Ex9M1N TM AC32 4P4T 1/8
4 40 A 32—40 A 400 A 103076 Ex9M1N TM AC40 4P4T 1/8
4 50 A 40—50 A 500 A 103077 Ex9M1N TM AC50 4P4T 1/8
4 63 A 50.4—63 A 630 A 103078 Ex9M1N TM AC63 4P4T 1/8
4 80 A 64—80 A 800 A 103079 Ex9M1N TM AC80 4P4T 1/8
4 100 A 80—100 A 1000 A 103080 Ex9M1N TM AC100 4P4T 1/8
4 125 A 100—125 A 1250 A 103081 Ex9M1N TM AC125 4P4T 1/8

4
Moulded Case Circuit Breakers Ex9M1
Version Ex9M1H up to 125 A, Icu = 100 kA

• 3 and 4-pole Moulded Case Circuit Breakers


• Ics = Icu = 100 kA at 415 V AC
• Ir can be set in steps (0.8-0.9-1.0) × In
• Ii fixed as 10 × In
• Mounting screws, box terminals as well as phase barriers in the scope of delivery

Poles Rated Overcurrent Instant. Article No. Type Packing


current In release Ir release Ii
3 16 A 12.8—16 A 160 A 100926 Ex9M1H TM AC16 3P 1/8
3 20 A 16—20 A 200 A 100927 Ex9M1H TM AC20 3P 1/8
3 25 A 20—25 A 250 A 100928 Ex9M1H TM AC25 3P 1/8
3 32 A 25.6—32 A 320 A 100929 Ex9M1H TM AC32 3P 1/8
3 40 A 32—40 A 400 A 100930 Ex9M1H TM AC40 3P 1/8
3 50 A 40—50 A 500 A 100931 Ex9M1H TM AC50 3P 1/8
3 63 A 50.4—63 A 630 A 100932 Ex9M1H TM AC63 3P 1/8
3 80 A 64—80 A 800 A 100933 Ex9M1H TM AC80 3P 1/8
3 100 A 80—100 A 1000 A 100934 Ex9M1H TM AC100 3P 1/8
3 125 A 100—125 A 1250 A 100935 Ex9M1H TM AC125 3P 1/8

4 16 A 12.8—16 A 160 A 103102 Ex9M1H TM AC16 4P4T 1/8


4 20 A 16—20 A 200 A 103103 Ex9M1H TM AC20 4P4T 1/8
4 25 A 20—25 A 250 A 103104 Ex9M1H TM AC25 4P4T 1/8
4 32 A 25.6—32 A 320 A 103105 Ex9M1H TM AC32 4P4T 1/8
4 40 A 32—40 A 400 A 103106 Ex9M1H TM AC40 4P4T 1/8
4 50 A 40—50 A 500 A 103107 Ex9M1H TM AC50 4P4T 1/8
4 63 A 50.4—63 A 630 A 103108 Ex9M1H TM AC63 4P4T 1/8
4 80 A 64—80 A 800 A 103109 Ex9M1H TM AC80 4P4T 1/8
4 100 A 80—100 A 1000 A 103110 Ex9M1H TM AC100 4P4T 1/8
4 125 A 100—125 A 1250 A 103111 Ex9M1H TM AC125 4P4T 1/8

Version Ex9M1P up to 125 A, Icu = 150 kA

• 3 and 4-pole Moulded Case Circuit Breakers


• Ics = Icu = 150 kA at 415 V AC
• Ir can be set in steps (0.8-0.9-1.0) × In
• Ii fixed as 10 × In
• Mounting screws, box terminals as well as phase barriers in the scope of delivery

Poles Rated Overcurrent Instant. Article No. Type Packing


current In release Ir release Ii
3 16 A 12.8—16 A 160 A 100946 Ex9M1P TM AC16 3P 1/8
3 20 A 16—20 A 200 A 100947 Ex9M1P TM AC20 3P 1/8
3 25 A 20—25 A 250 A 100948 Ex9M1P TM AC25 3P 1/8
3 32 A 25.6—32 A 320 A 100949 Ex9M1P TM AC32 3P 1/8
3 40 A 32—40 A 400 A 100950 Ex9M1P TM AC40 3P 1/8
3 50 A 40—50 A 500 A 100951 Ex9M1P TM AC50 3P 1/8
3 63 A 50.4—63 A 630 A 100952 Ex9M1P TM AC63 3P 1/8
3 80 A 64—80 A 800 A 100953 Ex9M1P TM AC80 3P 1/8
3 100 A 80—100 A 1000 A 100954 Ex9M1P TM AC100 3P 1/8
3 125 A 100—125 A 1250 A 100955 Ex9M1P TM AC125 3P 1/8

4 16 A 12.8—16 A 160 A 103122 Ex9M1P TM AC16 4P4T 1/8


4 20 A 16—20 A 200 A 103123 Ex9M1P TM AC20 4P4T 1/8
4 25 A 20—25 A 250 A 103124 Ex9M1P TM AC25 4P4T 1/8
4 32 A 25.6—32 A 320 A 103125 Ex9M1P TM AC32 4P4T 1/8
4 40 A 32—40 A 400 A 103126 Ex9M1P TM AC40 4P4T 1/8
4 50 A 40—50 A 500 A 103127 Ex9M1P TM AC50 4P4T 1/8
4 63 A 50.4—63 A 630 A 103128 Ex9M1P TM AC63 4P4T 1/8
4 80 A 64—80 A 800 A 103129 Ex9M1P TM AC80 4P4T 1/8
4 100 A 80—100 A 1000 A 103130 Ex9M1P TM AC100 4P4T 1/8
4 125 A 100—125 A 1250 A 103131 Ex9M1P TM AC125 4P4T 1/8

5
Moulded Case Circuit Breakers Ex9M2
Version Ex9M2S up to 250 A, Icu = 36 kA

• 3 and 4-pole Moulded Case Circuit Breakers


• Ics = Icu = 36 kA at 415 V AC
• Ir can be set in steps (0.8-0.9-1.0) × In
• Ii variable (5-6-7-8-9-10) × In
• Mounting screws, box terminals as well as phase barriers in the scope of delivery

Poles Rated Overcurrent Instant. Article No. Type Packing


current In release Ir release Ii
3 125 A 100-125 A 625-1250 101293 Ex9M2S TM AC125 3P 1/4
3 160 A 128-160 A 800-1600 101294 Ex9M2S TM AC160 3P 1/4
3 180 A 144-180 A 900-1800 101295 Ex9M2S TM AC180 3P 1/4
3 200 A 160-200 A 1000-2000 101296 Ex9M2S TM AC200 3P 1/4
3 225 A 180-225 A 1125-2250 101297 Ex9M2S TM AC225 3P 1/4
3 250 A 200-250 A 1250-2500 101298 Ex9M2S TM AC250 3P 1/4

4 125 A 100-125 A 625-1250 103132 Ex9M2S TM AC125 4P4T 1/4


4 160 A 128-160 A 800-1600 103133 Ex9M2S TM AC160 4P4T 1/4
4 180 A 144-180 A 900-1800 103134 Ex9M2S TM AC180 4P4T 1/4
4 200 A 160-200 A 1000-2000 103135 Ex9M2S TM AC200 4P4T 1/4
4 225 A 180-225 A 1125-2250 103136 Ex9M2S TM AC225 4P4T 1/4
4 250 A 200-250 A 1250-2500 103137 Ex9M2S TM AC250 4P4T 1/4

Version Ex9M2N up to 250 A, Icu = 50 kA

• 3 and 4-pole Moulded Case Circuit Breakers


• Ics = Icu = 50 kA at 415 V AC
• Ir can be set in steps (0.8-0.9-1.0) × In
• Ii variable (5-6-7-8-9-10) × In
• Mounting screws, box terminals as well as phase barriers in the scope of delivery

Poles Rated Overcurrent Instant. Article No. Type Packing


current In release Ir release Ii
3 125 A 100-125 A 625-1250 101299 Ex9M2N TM AC125 3P 1/4
3 160 A 128-160 A 800-1600 101300 Ex9M2N TM AC160 3P 1/4
3 180 A 144-180 A 900-1800 101301 Ex9M2N TM AC180 3P 1/4
3 200 A 160-200 A 1000-2000 101302 Ex9M2N TM AC200 3P 1/4
3 225 A 180-225 A 1125-2250 101303 Ex9M2N TM AC225 3P 1/4
3 250 A 200-250 A 1250-2500 101304 Ex9M2N TM AC250 3P 1/4

4 125 A 100-125 A 625-1250 103138 Ex9M2N TM AC125 4P4T 1/4


4 160 A 128-160 A 800-1600 103139 Ex9M2N TM AC160 4P4T 1/4
4 180 A 144-180 A 900-1800 103140 Ex9M2N TM AC180 4P4T 1/4
4 200 A 160-200 A 1000-2000 103141 Ex9M2N TM AC200 4P4T 1/4
4 225 A 180-225 A 1125-2250 103142 Ex9M2N TM AC225 4P4T 1/4
4 250 A 200-250 A 1250-2500 103143 Ex9M2N TM AC250 4P4T 1/4

6
Moulded Case Circuit Breakers Ex9M2
Version Ex9M2H up to 250 A, Icu = 100 kA

• 3 and 4-pole Moulded Case Circuit Breakers


• Ics = Icu = 100 kA at 415 V AC
• Ir can be set in steps (0.8-0.9-1.0) × In
• Ii variable (5-6-7-8-9-10) × In
• Mounting screws, box terminals as well as phase barriers in the scope of delivery

Poles Rated Overcurrent Instant. Article No. Type Packing


current In release Ir release Ii
3 125 A 100-125 A 625-1250 101317 Ex9M2H TM AC125 3P 1/4
3 160 A 128-160 A 800-1600 101318 Ex9M2H TM AC160 3P 1/4
3 180 A 144-180 A 900-1800 101319 Ex9M2H TM AC180 3P 1/4
3 200 A 160-200 A 1000-2000 101320 Ex9M2H TM AC200 3P 1/4
3 225 A 180-225 A 1125-2250 101321 Ex9M2H TM AC225 3P 1/4
3 250 A 200-250 A 1250-2500 101322 Ex9M2H TM AC250 3P 1/4

4 125 A 100-125 A 625-1250 103156 Ex9M2H TM AC125 4P4T 1/4


4 160 A 128-160 A 800-1600 103157 Ex9M2H TM AC160 4P4T 1/4
4 180 A 144-180 A 900-1800 103158 Ex9M2H TM AC180 4P4T 1/4
4 200 A 160-200 A 1000-2000 103159 Ex9M2H TM AC200 4P4T 1/4
4 225 A 180-225 A 1125-2250 103160 Ex9M2H TM AC225 4P4T 1/4
4 250 A 200-250 A 1250-2500 103161 Ex9M2H TM AC250 4P4T 1/4

Version Ex9M2P up to 250 A, Icu = 150 kA

• 3 and 4-pole Moulded Case Circuit Breakers


• Ics = Icu = 150 kA at 415 V AC
• Ir can be set in steps (0.8-0.9-1.0) × In
• Ii variable (5-6-7-8-9-10) × In
• Mounting screws, box terminals as well as phase barriers in the scope of delivery

Poles Rated Overcurrent Instant. Article No. Type Packing


current In release Ir release Ii
3 125 A 100-125 A 625-1250 101329 Ex9M2P TM AC125 3P 1/4
3 160 A 128-160 A 800-1600 101330 Ex9M2P TM AC160 3P 1/4
3 180 A 144-180 A 900-1800 101331 Ex9M2P TM AC180 3P 1/4
3 200 A 160-200 A 1000-2000 101332 Ex9M2P TM AC200 3P 1/4
3 225 A 180-225 A 1125-2250 101333 Ex9M2P TM AC225 3P 1/4
3 250 A 200-250 A 1250-2500 101334 Ex9M2P TM AC250 3P 1/4

4 125 A 100-125 A 625-1250 103168 Ex9M2P TM AC125 4P4T 1/4


4 160 A 128-160 A 800-1600 103169 Ex9M2P TM AC160 4P4T 1/4
4 180 A 144-180 A 900-1800 103170 Ex9M2P TM AC180 4P4T 1/4
4 200 A 160-200 A 1000-2000 103171 Ex9M2P TM AC200 4P4T 1/4
4 225 A 180-225 A 1125-2250 103172 Ex9M2P TM AC225 4P4T 1/4
4 250 A 200-250 A 1250-2500 103173 Ex9M2P TM AC250 4P4T 1/4

7
Moulded Case Circuit Breakers Ex9M3
Version Ex9M3S up to 400 A, Icu = 36 kA

• 3 and 4-pole Moulded Case Circuit Breakers


• Ics = Icu = 36 kA at 415 V AC
• Ir can be set in steps (0.8-0.9-1.0) × In
• Ii variable (5-6-7-8-9-10) × In
• Mounting screws and phase barriers in the scope of delivery

Poles Rated Overcurrent Instant. Article No. Type Packing


current In release Ir release Ii
3 250 A 200-250 A 1250-2500 101454 Ex9M3S TM AC250 3P 1/2
3 315 A 252-315 A 1575-3150 101455 Ex9M3S TM AC315 3P 1/2
3 350 A 280-350 A 1750-3500 101456 Ex9M3S TM AC350 3P 1/2
3 400 A 320-400 A 2000-4000 101457 Ex9M3S TM AC400 3P 1/2

4 250 A 200-250 A 1250-2500 103174 Ex9M3S TM AC250 4P4T 1/2


4 315 A 252-315 A 1575-3150 103175 Ex9M3S TM AC315 4P4T 1/2
4 350 A 280-350 A 1750-3500 103176 Ex9M3S TM AC350 4P4T 1/2
4 400 A 320-400 A 2000-4000 103177 Ex9M3S TM AC400 4P4T 1/2

Version Ex9M3N up to 400 A, Icu = 50 kA

• 3 and 4-pole Moulded Case Circuit Breakers


• Ics = Icu = 50 kA at 415 V AC
• Ir can be set in steps (0.8-0.9-1.0) × In
• Ii variable (5-6-7-8-9-10) × In
• Mounting screws and phase barriers in the scope of delivery

Poles Rated Overcurrent Instant. Article No. Type Packing


current In release Ir release Ii
3 250 A 200-250 A 1250-2500 101458 Ex9M3N TM AC250 3P 1/2
3 315 A 252-315 A 1575-3150 101459 Ex9M3N TM AC315 3P 1/2
3 350 A 280-350 A 1750-3500 101460 Ex9M3N TM AC350 3P 1/2
3 400 A 320-400 A 2000-4000 101461 Ex9M3N TM AC400 3P 1/2

4 250 A 200-250 A 1250-2500 103178 Ex9M3N TM AC250 4P4T 1/2


4 315 A 252-315 A 1575-3150 103179 Ex9M3N TM AC315 4P4T 1/2
4 350 A 280-350 A 1750-3500 103180 Ex9M3N TM AC350 4P4T 1/2
4 400 A 320-400 A 2000-4000 103181 Ex9M3N TM AC400 4P4T 1/2

8
Moulded Case Circuit Breakers Ex9M3
Version Ex9M3H up to 400 A, Icu = 100 kA

• 3 and 4-pole Moulded Case Circuit Breakers


• Ics = Icu = 100 kA at 415 V AC
• Ir can be set in steps (0.8-0.9-1.0) × In
• Ii variable (5-6-7-8-9-10) × In
• Mounting screws and phase barriers in the scope of delivery

Poles Rated Overcurrent Instant. Article No. Type Packing


current In release Ir release Ii
3 250 A 200-250 A 1250-2500 101470 Ex9M3H TM AC250 3P 1/2
3 315 A 252-315 A 1575-3150 101471 Ex9M3H TM AC315 3P 1/2
3 350 A 280-350 A 1750-3500 101472 Ex9M3H TM AC350 3P 1/2
3 400 A 320-400 A 2000-4000 101473 Ex9M3H TM AC400 3P 1/2

4 250 A 200-250 A 1250-2500 103190 Ex9M3H TM AC250 4P4T 1/2


4 315 A 252-315 A 1575-3150 103191 Ex9M3H TM AC315 4P4T 1/2
4 350 A 280-350 A 1750-3500 103192 Ex9M3H TM AC350 4P4T 1/2
4 400 A 320-400 A 2000-4000 103193 Ex9M3H TM AC400 4P4T 1/2

Version Ex9M3P up to 400 A, Icu = 150 kA

• 3 and 4-pole Moulded Case Circuit Breakers


• Ics = Icu = 150 kA at 415 V AC
• Ir can be set in steps (0.8-0.9-1.0) × In
• Ii variable (5-6-7-8-9-10) × In
• Mounting screws and phase barriers in the scope of delivery

Poles Rated Overcurrent Instant. Article No. Type Packing


current In release Ir release Ii
3 250 A 200-250 A 1250-2500 101478 Ex9M3P TM AC250 3P 1/2
3 315 A 252-315 A 1575-3150 101479 Ex9M3P TM AC315 3P 1/2
3 350 A 280-350 A 1750-3500 101480 Ex9M3P TM AC350 3P 1/2
3 400 A 320-400 A 2000-4000 101481 Ex9M3P TM AC400 3P 1/2

4 250 A 200-250 A 1250-2500 103198 Ex9M3P TM AC250 4P4T 1/2


4 315 A 252-315 A 1575-3150 103199 Ex9M3P TM AC315 4P4T 1/2
4 350 A 280-350 A 1750-3500 103200 Ex9M3P TM AC350 4P4T 1/2
4 400 A 320-400 A 2000-4000 103201 Ex9M3P TM AC400 4P4T 1/2

9
Moulded Case Circuit Breakers Ex9M4
Version Ex9M4S up to 630 A, Icu = 36 kA

• 3 and 4-pole Moulded Case Circuit Breakers


• Ics = Icu = 36 kA at 415 V AC
• Ir can be set in steps (0.8-0.9-1.0) × In
• Ii variable (5-6-7-8-9-10) × In
• Mounting screws and phase barriers in the scope of delivery

Poles Rated Overcurrent Instant. Article No. Type Packing


current In release Ir release Ii
3 400 A 320-400 A 2000-4000 103373 Ex9M4S TM AC400 3P 1/1
3 500 A 400-500 A 2500-5000 103374 Ex9M4S TM AC500 3P 1/1
3 630 A 500-630 A 3150-6300 103375 Ex9M4S TM AC630 3P 1/1

4 400 A 320-400 A 2000-4000 103415 Ex9M4S TM AC400 4P4T 1/1


4 500 A 400-500 A 2500-5000 103416 Ex9M4S TM AC500 4P4T 1/1
4 630 A 500-630 A 3150-6300 103417 Ex9M4S TM AC630 4P4T 1/1

Version Ex9M4N up to 630 A, Icu = 50 kA

• 3 and 4-pole Moulded Case Circuit Breakers


• Ics = Icu = 50 kA at 415 V AC
• Ir can be set in steps (0.8-0.9-1.0) × In
• Ii variable (5-6-7-8-9-10) × In
• Mounting screws and phase barriers in the scope of delivery

Poles Rated Overcurrent Instant. Article No. Type Packing


current In release Ir release Ii
3 400 A 320-400 A 2000-4000 103376 Ex9M4N TM AC400 3P 1/1
3 500 A 400-500 A 2500-5000 103377 Ex9M4N TM AC500 3P 1/1
3 630 A 500-630 A 3150-6300 103378 Ex9M4N TM AC630 3P 1/1

4 400 A 320-400 A 2000-4000 103418 Ex9M4N TM AC400 4P4T 1/1


4 500 A 400-500 A 2500-5000 103419 Ex9M4N TM AC500 4P4T 1/1
4 630 A 500-630 A 3150-6300 103420 Ex9M4N TM AC630 4P4T 1/1

10
Moulded Case Circuit Breakers Ex9M4
Version Ex9M4H up to 630 A, Icu = 100 kA

• 3 and 4-pole Moulded Case Circuit Breakers


• Ics = Icu = 100 kA at 415 V AC
• Ir can be set in steps (0.8-0.9-1.0) × In
• Ii variable (5-6-7-8-9-10) × In
• Mounting screws and phase barriers in the scope of delivery

Poles Rated Overcurrent Instant. Article No. Type Packing


current In release Ir release Ii
3 400 A 320-400 A 2000-4000 103385 Ex9M4H TM AC400 3P 1/1
3 500 A 400-500 A 2500-5000 103386 Ex9M4H TM AC500 3P 1/1
3 630 A 500-630 A 3150-6300 103387 Ex9M4H TM AC630 3P 1/1

4 400 A 320-400 A 2000-4000 103427 Ex9M4H TM AC400 4P4T 1/1


4 500 A 400-500 A 2500-5000 103428 Ex9M4H TM AC500 4P4T 1/1
4 630 A 500-630 A 3150-6300 103429 Ex9M4H TM AC630 4P4T 1/1

Version Ex9M4P up to 630 A, Icu = 150 kA

• 3 and 4-pole Moulded Case Circuit Breakers


• Ics = Icu = 150 kA at 415 V AC
• Ir can be set in steps (0.8-0.9-1.0) × In
• Ii variable (5-6-7-8-9-10) × In
• Mounting screws and phase barriers in the scope of delivery

Poles Rated Overcurrent Instant. Article No. Type Packing


current In release Ir release Ii
3 400 A 320-400 A 2000-4000 103391 Ex9M4P TM AC400 3P 1/1
3 500 A 400-500 A 2500-5000 103392 Ex9M4P TM AC500 3P 1/1
3 630 A 500-630 A 3150-6300 103393 Ex9M4P TM AC630 3P 1/1

4 400 A 320-400 A 2000-4000 103433 Ex9M4P TM AC400 4P4T 1/1


4 500 A 400-500 A 2500-5000 103434 Ex9M4P TM AC500 4P4T 1/1
4 630 A 500-630 A 3150-6300 103435 Ex9M4P TM AC630 4P4T 1/1

11
Moulded Case Circuit Breakers Ex9M5
Version Ex9M5S up to 800 A, Icu = 36 kA

• 3 and 4-pole Moulded Case Circuit Breakers


• Ics = Icu = 36 kA at 415 V AC
• Ir can be set in steps (0.8-0.9-1.0) × In
• Ii variable (5-6-7-8-9-10) × In
• Mounting screws and phase barriers in the scope of delivery

Poles Rated Overcurrent Instant. Article No. Type Packing


current In release Ir release Ii
3 630 A 500-630 A 3150-6300 103394 Ex9M5S TM AC630 3P 1/1
3 700 A 560-700 A 3500-7000 103395 Ex9M5S TM AC700 3P 1/1
3 800 A 640-800 A 4000-8000 103396 Ex9M5S TM AC800 3P 1/1

4 630 A 500-630 A 3150-6300 103436 Ex9M5S TM AC630 4P4T 1/1


4 700 A 560-700 A 3500-7000 103437 Ex9M5S TM AC700 4P4T 1/1
4 800 A 640-800 A 4000-8000 103438 Ex9M5S TM AC800 4P4T 1/1

Version Ex9M5N up to 800 A, Icu = 50 kA

• 3 and 4-pole Moulded Case Circuit Breakers


• Ics = Icu = 50 kA at 415 V AC
• Ir can be set in steps (0.8-0.9-1.0) × In
• Ii variable (5-6-7-8-9-10) × In
• Mounting screws and phase barriers in the scope of delivery

Poles Rated Overcurrent Instant. Article No. Type Packing


current In release Ir release Ii
3 630 A 500-630 A 3150-6300 103397 Ex9M5N TM AC630 3P 1/1
3 700 A 560-700 A 3500-7000 103398 Ex9M5N TM AC700 3P 1/1
3 800 A 640-800 A 4000-8000 103399 Ex9M5N TM AC800 3P 1/1

4 630 A 500-630 A 3150-6300 103439 Ex9M5N TM AC630 4P4T 1/1


4 700 A 560-700 A 3500-7000 103440 Ex9M5N TM AC700 4P4T 1/1
4 800 A 640-800 A 4000-8000 103441 Ex9M5N TM AC800 4P4T 1/1

12
Moulded Case Circuit Breakers Ex9M5
Version Ex9M5H up to 800 A, Icu = 100 kA

• 3 and 4-pole Moulded Case Circuit Breakers


• Ics = Icu = 100 kA at 415 V AC
• Ir can be set in steps (0.8-0.9-1.0) × In
• Ii variable (5-6-7-8-9-10) × In
• Mounting screws and phase barriers in the scope of delivery

Poles Rated Overcurrent Instant. Article No. Type Packing


current In release Ir release Ii
3 630 A 500-630 A 3150-6300 103406 Ex9M5H TM AC630 3P 1/1
3 700 A 560-700 A 3500-7000 103407 Ex9M5H TM AC700 3P 1/1
3 800 A 640-800 A 4000-8000 103408 Ex9M5H TM AC800 3P 1/1

4 630 A 500-630 A 3150-6300 103448 Ex9M5H TM AC630 4P4T 1/1


4 700 A 560-700 A 3500-7000 103449 Ex9M5H TM AC700 4P4T 1/1
4 800 A 640-800 A 4000-8000 103450 Ex9M5H TM AC800 4P4T 1/1

Version Ex9M5P up to 800 A, Icu = 150 kA

• 3 and 4-pole Moulded Case Circuit Breakers


• Ics = Icu = 150 kA at 415 V AC
• Ir can be set in steps (0.8-0.9-1.0) × In
• Ii variable (5-6-7-8-9-10) × In
• Mounting screws and phase barriers in the scope of delivery

Poles Rated Overcurrent Instant. Article No. Type Packing


current In release Ir release Ii
3 630 A 500-630 A 3150-6300 103412 Ex9M5P TM AC630 3P 1/1
3 700 A 560-700 A 3500-7000 103413 Ex9M5P TM AC700 3P 1/1
3 800 A 640-800 A 4000-8000 103414 Ex9M5P TM AC800 3P 1/1

4 630 A 500-630 A 3150-6300 103454 Ex9M5P TM AC630 4P4T 1/1


4 700 A 560-700 A 3500-7000 103455 Ex9M5P TM AC700 4P4T 1/1
4 800 A 640-800 A 4000-8000 103456 Ex9M5P TM AC800 4P4T 1/1

13
Technical Data Ex9M1
Moulded Case Circuit Breakers up to 125 A

General parameters
Suitable for household as well as industrial applications
Thermal release adjustable (0.8-0.9-1) x In
Instantaneous short-circuit current release fixed 10 x In
Internal accessories
Auxiliary contact unit AX21 101395
Alarm contact unit AL21 101396
Early-make auxiliary contact EC 21 106317
Shunt trip releases SHT21 101397-101405
Undervoltage releases UVT21 101406-101407
Max. number of installed internal accessories is 2 pcs of AX21, 1 pc of AL21 or EC 21 and 1 pc of a release (SHT21 or UVT21)
External accessories
Direct rotary handle RHD21 101410
Extended rotary handle ERH21 101409
Remote motor operators MOD21 101411-101415
Terminal cover, short TCV21 3P, 4P 101439, 102372
Terminal cover, long TCE21 3P, 4P 101440, 102373
Phase barrier set PB21 3P, 4P 101441, 104852
Connection terminals MC21 103705-103708
DIN-rail adaptor DRA21 106319
Mounting screws, box terminals as well as phase barriers in the scope of delivery

Electrical parameters
Ex9M1S Ex9M1N Ex9M1H Ex9M1P
Tested according to IEC/EN 60947-2
Rated op. voltage Ue 415/690 V AC
Rated insulation voltage Ui 800 V
Rated impulse withstand voltage Uimp 8 kV
Rated frequency 50/60 Hz
Rated ultimate short-circuit breaking 36 kA / 415 V 50 kA / 415 V 100 kA / 415 V 150 kA / 415 V
capacity Icu 5 kA / 690 V 5 kA / 690 V 6 kA / 690 V 8 kA / 690 V
Rated service short-circuit breaking 36 kA / 415 V 50 kA / 415 V 100 kA / 415 V 150 kA / 415 V
capacity Ics 5 kA / 690 V 5 kA / 690 V 6 kA / 690 V 8 kA / 690 V
Rated short-circuit making 75.6 kA / 415 V 105 kA / 415 V 220 kA / 415 V 330 kA / 415 V
capacity Icm 7.5 kA / 690 V 7.5 kA / 690 V 9 kA / 690 V 13.6 kA / 690 V
Rated current 16 — 125 A
Overvoltage category III / 3
Utilization category A
Mechanical service life 15 000 operation cycles
Electrical service life 5 000 operation cycles
Maximum frequency of switch. cycles 120 operating cycles per hour
Total disconnection time at short circuit < 2 ms
Internal resistance per pole at 125 A 0.80 mΩ
Power loss per pole at 125 A 12.5 W
Line voltage connection arbitrary above or below

14
Technical Data Ex9M1
Moulded Case Circuit Breakers up to 125 A

Mechanical parameters
Device width 3P / 4P 90 mm / 120 mm
Device height 140 mm
Device depth 81.6 mm
Mounting onto panel
Degree of protection IP40, IP20 terminals
Terminals box
Terminal capacity 4 — 95 mm2
Fastening torque of terminals 8 Nm
Ambient temperature -25 — +70 °C
Altitude ≤ 2 000 m
Relative humidity ≤ 50 % at 40 °C, ≤ 90 % monthly average
Resistance to humidity and heat class 2
Pollution degree 3
Weight 3P / 4P 1.2 kg / 1.7 kg
Mounting position vertical, can be rotated by 90° in each axis

Wiring diagram

3P 4P
N N

Dimensions N N

15
0.002
0.001

0.5
0.7
1

2
3
4
6
8In
10
12In

20
30
50

70
100

200
300
400

600
1 200
I/Ir

Technical Data Ex9M1


Ex9M1 (40A, 50A)
Time [s] 10 000
Moulded Case Circuit
7 200 Breakers up to 125 A
3 600

Installation space
2 000
1 000
500

200
100
50

20
10
5

2
1
0.5

0.2
0.1
0.05

0.02
0.01
0.005

0.002
0.001
0.5
0.7
1

2
3
4
6
8In
10
12In

20
30
50

70
100

200
300
400

600
1 200
I/Ir

Tripping characteristics
Ex9M1 (100A, 125A)
Time [s] 10 000
7 200
3 600 Ex9M1
Time [s] 10
2 000
7
1 200
000
3 600
500
2 000
200
1 000
100
500
50
200
20
100
50
10
5
20
2
10
5
1
0.5
2
0.2
1
0.5
0.1
0.05
0.2
0.1
0.02
0.01
0.05
0.005
0.02
0.01
0.002
0.005
0.001
0.5
0.7
1

2
3
4
6
8In
10
12In

20
30
50

70
100

200
300
400

600
1 200

0.002 I/Ir
0.001
0.5
0.7
1

2
3
4
6
8In
10
12In

20
30
50

70
100

200
300
400

600
1 200

I/Ir

Ex9M1 (40A, 50A)


Ex9M2
Time
Time [s]
[s] 10
10 000
000
7
7 200
200
3
3 600
600
2
2 000
000 16
1
1 000
000
500
500
Technical Data Ex9M2
Moulded Case Circuit Breakers up to 250 A

General parameters
Suitable for household as well as industrial applications
Thermal release adjustable (0.8-0.9-1) x In
Instantaneous short-circuit current release (5-6-7-8-9-10) x In
Internal accessories
Auxiliary contact unit AX21 101395
Alarm contact unit AL21 101396
Early-make auxiliary contact EC 21 106317
Shunt trip releases SHT22 101416-101424
Undervoltage releases UVT22 101425-101426
Max. number of installed internal accessories is 2 pcs of AX21, 1 pc of AL21 or EC 21 and 1 pc of a release (SHT22 or UVT22)
External accessories
Direct rotary handle RHD22 101429
Extended rotary handle ERH22 101428
Remote motor operators MOD22 101430-101434
Terminal cover, short TCV22 3P, 4P 101442, 102374
Terminal cover, long TCE22 3P, 4P 101443, 102375
Phase barrier set PB22 3P, 4P 101444, 104853
Connection terminals MC22 103709-103714
DIN-rail adaptor DRA22 106320
Mounting screws, box terminals as well as phase barriers in the scope of delivery

Electrical parameters
Ex9M2S Ex9M2N Ex9M2H Ex9M2P
Tested according to IEC/EN 60947-2
Rated op. voltage Ue 415/690 V AC
Rated insulation voltage Ui 800 V
Rated impulse withstand voltage Uimp 8 kV
Rated frequency 50/60 Hz
Rated ultimate short-circuit breaking 36 kA / 415 V 50 kA / 415 V 100 kA / 415 V 150 kA / 415 V
capacity Icu 6 kA / 690 V 6 kA / 690 V 8 kA / 690 V 10 kA / 690 V
Rated service short-circuit breaking 36 kA / 415 V 50 kA / 415 V 100 kA / 415 V 150 kA / 415 V
capacity Ics 6 kA / 690 V 6 kA / 690 V 8 kA / 690 V 10 kA / 690 V
Rated short-circuit making 75.6 kA / 415 V 105 kA / 415 V 220 kA / 415 V 330 kA / 415 V
capacity Icm 7.5 kA / 690 V 7.5 kA / 690 V 9 kA / 690 V 13.6 kA / 690 V
Rated current 125 — 250 A
Overvoltage category III / 3
Utilization category A
Mechanical service life 15 000 operation cycles
Electrical service life 5 000 operation cycles
Maximum frequency of switch. cycles 120 operating cycles per hour
Total disconnection time at short circuit < 2 ms
Internal resistance per pole at 250 A 0.40 mΩ
Power loss per pole at 250 A 25 W
Line voltage connection arbitrary above or below

17
Technical Data Ex9M2
Moulded Case Circuit Breakers up to 250 A

Mechanical parameters
Device width 3P / 4P 105 mm / 140 mm
Device height 157 mm
Device depth 91.5 mm
Mounting onto panel
Degree of protection IP40, IP20 terminals
Terminals box
Terminal capacity 10 — 120 mm2
Fastening torque of terminals 25 Nm
Ambient temperature -25 — +70 °C
Altitude ≤ 2 000 m
Relative humidity ≤ 50 % at 40 °C, ≤ 90 % monthly average
Resistance to humidity and heat class 2
Pollution degree 3
Weight 3P / 4P 1.7 kg / 2.2 kg
Mounting position vertical, can be rotated by 90° in each axis

Wiring diagram

3P 4P
N N

Dimensions
N N

18
0.002
0.001

0.5
0.7
1

2
3
4
6
8In
10
12In

20
30
50

70
100

200
300
400

600
1 200
I/Ir

Technical Data Ex9M2


Moulded Case Circuit Breakers up to 250 A Ex9M1 (100A, 125A)
Time [s] 10 000
Installation space
7 200
3 600 Ex9M1
Time [s] 10
2 000
7
1 200
000
3 600
500
2 000
200
1 000
100
500
50
200
20
100
50
10
5
20
2
10
5
1
0.5
2
0.2
1
0.5
0.1
0.05
0.2
0.1
0.02
0.01
0.05
0.005
0.02
0.01
0.002
0.005
0.001
0.5
0.7
1

2
3
4
6
8In
10
12In

20
30
50

70
100

200
300
400

600
1 200
0.002 I/Ir

Tripping characteristics
0.001
0.5
0.7
1

2
3
4
6
8In
10
12In

20
30
50

70
100

200
300
400

600
1 200 I/Ir

Ex9M1 (40A, 50A)


Ex9M2
Time
Time [s]
[s] 10
10 000
000
7
7 200
200
3
3 600
600
2
2 000
000
1
1 000
000
500
500

200
200
100
100
50
50

20
20
10
10
5
5

2
2
1
1
0.5
0.5

0.2
0.2
0.1
0.1
0.05
0.05

0.02
0.02
0.01
0.01
0.005
0.005

0.002
0.002
0.001
0.001
0.5
0.7
11

22
33
4In4
66
8In
10
12In

20
30
50

70
100

200
300
400

600
200
0.5
0.7

8
10
12In

20
30
50

70
100

200
300
400

600
11 200

I/Ir
I/Ir

Ex9M1 (100A, 125A)


Time [s] 10 000
7 200
19
3 600
2 000
1 000
Technical Data Ex9M3
Moulded Case Circuit Breakers up to 400 A

General parameters
Suitable for household as well as industrial applications
Thermal release adjustable (0.8-0.9-1) x In
Instantaneous short-circuit current release (5-6-7-8-9-10) x In
Internal accessories
Auxiliary contact unit AX21 101395
Alarm contact unit AL21 101396
Early-make auxiliary contact EC 23 106317
Shunt trip releases SHT22 101416-101424
Undervoltage releases UVT22 101425-101426
Max. number of installed internal accessories is 3 pcs of AX21, 1 pc of AL21 or EC 23 and 1 pc of a release (SHT22 or UVT22)
External accessories
Direct rotary handle RHD23 101483
Extended rotary handle ERH23 101482
Remote motor operators MOD23 101484-101488
Terminal cover, short TCV23 3P, 4P 101489, 102376
Terminal cover, long TCE23 3P, 4P 101490, 102377
Phase barrier set PB23 3P, 4P 101491, 104854
Connection terminals MC23 103715-103722
Mounting screws as well as phase barriers in the scope of delivery

Electrical parameters
Ex9M3S Ex9M3N Ex9M3H Ex9M3P
Tested according to IEC/EN 60947-2
Rated op. voltage Ue 415/690 V AC
Rated insulation voltage Ui 800 V
Rated impulse withstand voltage Uimp 8 kV
Rated frequency 50/60 Hz
Rated ultimate short-circuit breaking 36 kA / 415 V 50 kA / 415 V 100 kA / 415 V 150 kA / 415 V
capacity Icu 6 kA / 690 V 6 kA / 690 V 8 kA / 690 V 10 kA / 690 V
Rated service short-circuit breaking 36 kA / 415 V 50 kA / 415 V 100 kA / 415 V 150 kA / 415 V
capacity Ics 3 kA / 690 V 3 kA / 690 V 4 kA / 690 V 5 kA / 690 V
Rated short-circuit making 75.6 kA / 415 V 105 kA / 415 V 220 kA / 415 V 330 kA / 415 V
capacity Icm 7.5 kA / 690 V 7.5 kA / 690 V 9 kA / 690 V 13.6 kA / 690 V
Rated current 250 — 400 A
Overvoltage category III
Utilization category A
Mechanical service life 10 000 operation cycles
Electrical service life 2 000 operation cycles
Maximum frequency of switch. cycles 60 cycles per hour
Total disconnection time at short circuit < 2 ms
Internal resistance per pole at 400 A 0.15 mΩ
Power loss per pole at 400 A 24 W
Line voltage connection arbitrary above or below

20
Technical Data Ex9M3
Moulded Case Circuit Breakers up to 400 A

Mechanical parameters
Device width 3P / 4P 140 mm / 185 mm
Device height 255 mm
Device depth 118.5 mm
Mounting onto panel
Degree of protection IP40, IP20 terminals
Terminals M10 screws
Busbar thickness ≤ 8 mm
Busbar width ≤ 30 mm
Cable lug width ≤ 30 mm
Fastening torque of terminals 25 — 30 Nm
Ambient temperature -25 — +70 °C
Altitude ≤ 2 000 m
Relative humidity ≤ 50 % at 40 °C, ≤ 90 % monthly average
Resistance to humidity and heat class 2
Pollution degree 3
Weight 3P / 4P 5 kg / 6.6 kg
Mounting position vertical, can be rotated by 90° in each axis

Wiring diagram

3P 4P
N N

Dimensions N N

21
2 000
1 000
500

Ex9M2 (200A, 225A, 250A)


Technical Data Ex9M3
200
Time [s] 10 100
000
7 200
50
3 600
Moulded Case Circuit 20 Breakers
2 000 up to 400 A
10
1 000
Installation space 5
500

2002
1001
0.5
50

0.2
20
0.1
10
0.05
5

0.022
0.011
0.5
0.005

0.002
0.2
0.001
0.1
0.5
0.7
1

2
3
4In
6
8
10
12In

20
30
50

70
100

200
300
400

600
1 200
0.05 I/Ir

0.02
0.01
0.005

0.002
0.001
0.5
0.7
1

2
3
4In
6
8
10
12In

20
30
50

70
100

200
300
400

600
1 200
I/Ir

Ex9M3
Time [s] 10 000
7 200
Tripping characteristics
3 600
2 000
1 000
500

200 Ex9M3
Time [s] 10 100
000
7 200
50
3 600
20
2 000
10
1 000
5
500

2002
1001
0.5
50

0.2
20
0.1
10
0.05
5

0.022
0.011
0.5
0.005

0.002
0.2
0.001
0.1
0.5
0.7
1

2
3
4In
6
8
10
12In

20
30
50

70
100

200
300
400

600
1 200

0.05 I/Ir

0.02
0.01
0.005

0.002
0.001
0.5
0.7
1

2
3
4In
6
8
10
12In

20
30
50

70
100

200
300
400

600
1 200

I/Ir

Ex9M4
Time [s] 10 000
7 200
3 600
22
2 000
1 000
Technical Data Ex9M4
Moulded Case Circuit Breakers up to 630 A

General parameters
Suitable for industrial applications
Thermal release adjustable (0.8-0.9-1) x In
Instantaneous short-circuit current release (5-6-7-8-9-10) x In
Internal accessories
Auxiliary contact unit AX21 101395
Alarm contact unit AL21 101396
Early-make auxiliary contact EC 23 106317
Shunt trip releases SHT24 103723-103730
Undervoltage releases UVT24 103722-103740
Max. number of installed internal accessories is 4 pcs of AX21, 1 pc of AL21 or EC 23 and 1 pc of a release (SHT24 or UVT24)
External accessories
Direct rotary handle RHD24 103742
Extended rotary handle ERH24 103741
Remote motor operators MOD24 103743-103747
Terminal cover, short TCV24 3P, 4P 103748, 103750
Terminal cover, long TCE24 3P, 4P 103749, 104855
Phase barrier set PB24 3P, 4P 103751, 104856
Connection terminals MC24 106314
Mounting screws as well as phase barriers in the scope of delivery

Electrical parameters
Ex9M4S Ex9M4N Ex9M4H Ex9M4P
Tested according to IEC/EN 60947-2
Rated op. voltage Ue 415/690 V AC
Rated insulation voltage Ui 800 V
Rated impulse withstand voltage Uimp 8 kV
Rated frequency 50/60 Hz
Rated ultimate short-circuit breaking 36 kA / 415 V 50 kA / 415 V 100 kA / 415 V 150 kA / 415 V
capacity Icu 10 kA / 690 V 10 kA / 690 V 12 kA / 690 V 15 kA / 690 V
Rated service short-circuit breaking 36 kA / 415 V 50 kA / 415 V 100 kA / 415 V 150 kA / 415 V
capacity Ics 5 kA / 690 V 5 kA / 690 V 6 kA / 690 V 7.5 kA / 690 V
Rated short-circuit making 75.6 kA / 415 V 105 kA / 415 V 220 kA / 415 V 330 kA / 415 V
capacity Icm 17 kA / 690 V 17 kA / 690 V 24 kA / 690 V 30 kA / 690 V
Rated current 400 — 630 A
Overvoltage category III
Utilization category A
Mechanical service life 10 000 operation cycles
Electrical service life 2 000 operation cycles
Maximum frequency of switch. cycles 60 cycles per hour
Total disconnection time at short circuit < 2 ms
Internal resistance per pole at 630 A 0.08 mΩ
Power loss per pole at 630 A 31.8 W
Line voltage connection arbitrary above or below

23
Technical Data Ex9M4
Moulded Case Circuit Breakers up to 630 A

Mechanical parameters
Device width 3P / 4P 196 / 260 mm
Device height 300 mm
Device depth 142 mm
Mounting onto panel
Degree of protection IP40, IP20 terminals
Terminals M12 screws
Busbar thickness ≤ 10 mm
Busbar width ≤ 50 mm
Cable lug width ≤ 50 mm
Fastening torque of terminals 25 — 30 Nm
Ambient temperature -25 — +70 °C
Altitude ≤ 2 000 m
Relative humidity ≤ 50 % at 40 °C, ≤ 90 % monthly average
Resistance to humidity and heat class 2
Pollution degree 3
Weight 3P / 4P 10.2 kg / 13.5 kg
Mounting position vertical, can be rotated by 90° in each axis

Wiring diagram

3P 4P
N N

Dimensions N N

24
0.
0.

4I

1
12I

2
3
5

7
10

20
30
40

60
1 20
I/Ir

Ex9M3
Time [s] 10 000

Technical Data Ex9M4 7 200


3 600
2 000
1 000
Moulded Case Circuit500
Breakers up to 630 A

Installation space 200


Ex9M3
Time [s] 100
10 000
7 200
50
3 600
20
2 000
10
1 000
5
500

2002
1001
0.5
50

0.2
20
0.1
10
0.05
5

0.022
0.011
0.5
0.005

0.002
0.2
0.001
0.1
0.5
0.7
1

2
3
4In
6
8
10
12In

20
30
50

70
100

200
300
400

600
1 200
0.05 I/Ir

0.02
0.01
0.005

0.002
0.001
0.5
0.7
1

2
3
4In
6
8
10
12In

20
30
50

70
100

200
300
400

600
1 200
Tripping characteristics I/Ir

Ex9M4
Time [s] 10 000
7 200
3 600
2 000
1 000
500

200 Ex9M4
Time [s] 100
10 000
7 200
50
3 600
20
2 000
10
1 000
5
500

2002
1001
0.5
50

0.2
20
0.1
10
0.05
5

0.022
0.011
0.5
0.005

0.002
0.2
0.001
0.1
0.5
0.7
1

2
3
4In
6
8
10
12In

20
30
50

70
100

200
300
400

600
1 200

0.05 I/Ir

0.02
0.01
0.005

0.002
0.001
0.5
0.7
1

2
3
4In
6
8
10
12In

20
30
50

70
100

200
300
400

600
1 200

I/Ir
25
Technical Data Ex9M5
Moulded Case Circuit Breakers up to 800 A

General parameters
Suitable for industrial applications
Thermal release adjustable (0.8-0.9-1) x In
Instantaneous short-circuit current release (5-6-7-8-9-10) x In
Internal accessories
Auxiliary contact unit AX21 101395
Alarm contact unit AL21 101396
Early-make auxiliary contact EC 23 106317
Shunt trip releases SHT24 103723-103730
Undervoltage releases UVT24 103722-103740
Max. number of installed internal accessories is 4 pcs of AX21, 1 pc of AL21 or EC 23 and 1 pc of a release (SHT24 or UVT24)
External accessories
Direct rotary handle RHD24 103742
Extended rotary handle ERH24 103741
Remote motor operators MOD24 103743-103747
Terminal cover, short TCV24 3P, 4P 103748, 103750
Terminal cover, long TCE24 3P, 4P 103749, 104855
Phase barrier set PB24 3P, 4P 103751, 104856
Connection terminals MC24 106314
Mounting screws as well as phase barriers in the scope of delivery

Electrical parameters
Ex9M5S Ex9M5N Ex9M5H Ex9M5P
Tested according to IEC/EN 60947-2
Rated op. voltage Ue 415/690 V AC
Rated insulation voltage Ui 800 V
Rated impulse withstand voltage Uimp 8 kV
Rated frequency 50/60 Hz
Rated ultimate short-circuit breaking 36 kA / 415 V 50 kA / 415 V 100 kA / 415 V 150 kA / 415 V
capacity Icu 10 kA / 690 V 10 kA / 690 V 12 kA / 690 V 15 kA / 690 V
Rated service short-circuit breaking 36 kA / 415 V 50 kA / 415 V 100 kA / 415 V 150 kA / 415 V
capacity Ics 5 kA / 690 V 5 kA / 690 V 6 kA / 690 V 7.5 kA / 690 V
Rated short-circuit making 75.6 kA / 415 V 105 kA / 415 V 220 kA / 415 V 330 kA / 415 V
capacity Icm 17 kA / 690 V 17 kA / 690 V 24 kA / 690 V 30 kA / 690 V
Rated current 630 — 800 A
Overvoltage category III
Utilization category A
Mechanical service life 10 000 operation cycles
Electrical service life 2 000 operation cycles
Maximum frequency of switch. cycles 60 cycles per hour
Total disconnection time at short circuit < 2 ms
Internal resistance per pole at 800 A 0.08 mΩ
Power loss per pole at 800 A 51.2 W
Line voltage connection arbitrary above or below

26
Technical Data Ex9M5
Moulded Case Circuit Breakers up to 800 A

Mechanical parameters
Device width 3P / 4P 196 / 260 mm
Device height 300 mm
Device depth 142 mm
Mounting onto panel
Degree of protection IP40, IP20 terminals
Terminals M12 screws
Busbar thickness ≤ 10 mm
Busbar width ≤ 50 mm
Cable lug width ≤ 50 mm
Fastening torque of terminals 25 — 30 Nm
Ambient temperature -25 — +70 °C
Altitude ≤ 2 000 m
Relative humidity ≤ 50 % at 40 °C, ≤ 90 % monthly average
Resistance to humidity and heat class 2
Pollution degree 3
Weight 3P / 4P 10.2 kg / 13.5 kg
Mounting position vertical, can be rotated by 90° in each axis

Wiring diagram

3P 4P
N N

Dimensions N N

27
Technical Data Ex9M5
Moulded Case Circuit Breakers up to 800 A

Installation space

Tripping characteristics

Ex9M5
Time [s] 10 000
7 200
3 600
2 000
1 000
500

200
100
50

20
10
5

2
1
0.5

0.2
0.1
0.05

0.02
0.01
0.005

0.002
0.001
0.5
0.7
1

2
3
4In
6
8
10
12In

20
30
50

70
100

200
300
400

600
1 200

I/Ir