You are on page 1of 1

1 2 3 4 5 6 7 8

FROM 11 KV DISTRIBUTOR
A A
LEGEND
P TR
* SHORT CIRCUIT
* OVER CURRENT
* EARTH FAULT
STANDBY GENERATOR
G TRANSFORMER (1)
1600 KVA
TRANSFORMER (2)
1600 KVA
* PHASE SEQUENCE /
1250KVA 11/0.4 KV 11/0.4 KV PHASE FAILURE / (UNDER
380VOLT
/ OVER VOLTAGE)
8//[4x300] CU/XLPE/PVC BUS DUCT 3200 A
M TR
B (0.6/1)KV, 50KH B
* PHASE CURRENT
* VOLTAGE
* FREQUENCY
* POWER FACTOR
* KW,KVA,KVAR
MDB Panel * KWH
Electric & Mechanical Interlock
P GEN
(2 Out of 4 ) Electricaly Operated
* SHORT CIRCUIT
* OVER CURRENT
ACB
2500A , 50KA
ACB
3200A , 50KA
ACB
3200A , 50KA
* EARTH FAULT
* PHASE SEQUENCE / PHASE FAILURE
I> I> I>
/ (UNDER / OVER VOLTAGE)
C C
* REVERSE POWER
RST RST RST
* UNDER / OVER FREQUENCY
P GEN P TR P TR
ON OFF TRIP ON OFF TRIP ONOFF TRIP
M GEN M TR M TR
ON OFF ON OFF M GEN
* PHASE CURRENT
C.T
3PH+N+E ,3200A ,50KA ,380V ,50HZ ,CU,TIN PLATTED
(2500/5)A C.T
(3200/5)A
C.T
(3200/5)A
Stage-2
* VOLTAGE
* FREQUENCY
P.F REG-1.
1 1
P.F REG.-2
/ 2.1:E
* POWER FACTOR
-F
HRCF HRCF
-F * KW,KVA,KVAR
70A 2 40A 2
ON OFF TRIP ON OFF TRIP
* KWH
ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP
MCCB
400A , 50KA
1 1 1 1
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
-F -F 200A ,50KA 250A ,50KA 20A ,50KA 63A ,50KA 100A ,50KA 125A ,50KA
ACB ACB ACB
125A , 50KA 100A , 50KA 63A , 50KA 32A ,50KA 20A ,50KA 400A , 50KA -F -F
HRCF HRCF 1600A ,50KA 2000A ,50KA 1600A ,50KA 1 1
HRCF HRCF
P-CAP
D D
2 40A 2 150A I> I> I> I> I> I> I> I> I> I> I> I> I> I> I> I> 150A 2 40A 2
-K -K
Capacitor
Contactor 2
Capacitor
Contactor 2
* SHORT CIRCUIT
1 1

ON OFF TRIP
50 kVAR 25 kVAR
1 1
* OVER CURRENT
-K -K x1 x1 -K -K
ON OFF
M-MOT1
Capacitor Capacitor -C -C Capacitor Capacitor
2 Contactor 2 Contactor Contactor 2 Contactor 2
400Vac, 50Hz x2 400Vac, 50Hz x2
25 kVAR 70 kVAR SS 70 kVAR 25 kVAR
50 kVAR 25 kVAR
BUS COUPLER
*PHASE CURRENT
x1 x1 x1 x1
-C
400Vac, 50Hz
-C
400Vac, 50Hz
-C
400Vac, 50Hz
-C
400Vac, 50Hz
* RUN HOUR METER
x2 x2 x2 x2
25 kVAR 70 kVAR 70 kVAR 25 kVAR
M-MOT2
* PHASE CURRENT
P-MOT1
* SHORT CIRCUIT
E * OVER LOAD E
* OVER TEMP. FOR WINDING AND
BERING
* EARTH LEAKAGE
P-MOT2
* SHORT CIRCUIT
X=1 X=1 X=4 X=4 X=1 X=1 X=1 X=1 X=1 X=1 X=3 X=4 X=2
*OVER LOAD
Load Name Qty. Load Name Qty. Qty. Qty. Qty. Load Name Qty. Load Name Qty. Qty.
X=1
150kVAR
X=4 FIRE FIGHTING
Load Name Load Name
Chlorination
Load Name Load Name Qty. Load Name Qty. Load Name Qty. Load Name
Chlorination
Qty. Load Name Qty. Load Name
X=4
150kVAR
X=1
* OVER TEMP. FOR WINDING
1 Lift pump 2 Sludge Treatment Air Blowers Air Blowers Sludge Treatment
Mechanical Screen 1 BUILDING 1 Aeration Tank 1 1 Aeration Tank Mechanical Screen 1
Load Name Qty. Load Name Qty. PUMP
GRC Bridge
MCC Feeder -1 MCC FEEDER-1 1 MCC FEEDER-1 1 MCC Feeder-1 MCC Feeder-2 MCC FEEDER-2 1
MCC FEEDER-2
1 BUILDING
MCC Feeder- 2
1 Guard room 1
GRC Bridge
Load Name Qty. Load Name Qty. * EARTH LEAKAGE
25kVAR P.F STEP 4 70 kVAR P.F FICED 1 (End Carriage) & (End Carriage) & 70 kVAR P.F FIXED 1 25kVAR P.F STEP 4
1 External lighting 1 Generator lighting 1
(lifting) Administration building 1 & Ventilation 1 (lifting)
M-OUT
F Penstocks for DC
of Aeration Tank
2
Workshop &
store lighting 1 Electrical building Generator crane 1 * PHASE CURRENT F
lighting & Ventilation 1
Spare 1 Spare 1
M-MCC
*PHASE
*VOLTAGE
*FREQUENCY
*POWER FACTOR
P-MCC
* SHORT CIRCUIT
* PHASE SEQUENCE
/ PHASE FAILURE
G * OVER CURRENT G
/ UNDER VOLTAGE
* EARTH LEAKAGE
NOTE
- C.B FOR MOTORS WILL
BE RATED ACCORDING TO
MANUFACTURER
COORDINATION TABLES
H H
OWNER CONSULTANTS CONTRACTOR
‫دﻓﺎع‬ѧѧѧѧѧѧѧ‫وزارة اﻟ‬ PROJECT ‫ﻧﮭور‬ѧѧѧ‫ﺣﻰ ﺳ‬ѧѧѧ‫رف اﻟﺻ‬ѧѧѧ‫ﺔ اﻟﺻ‬ѧѧѧ‫ﺔ ﻣﻌﺎﻟﺟ‬ѧѧѧ‫روع ﻣﺣط‬ѧѧѧ‫ﻣﺷ‬ MDB Panel(SLD-1) Rev
Page
00
‫ﻛرﯾﺔ‬ѧѧѧѧѧѧѧѧ‫ﻣﺎﻟﯾﮫ اﻟﻌﺳ‬ѧѧѧѧѧѧѧѧ‫ﮫ اﻟﺷ‬ѧѧѧѧѧѧѧѧ‫ﺎدة اﻟﻣﻧطﻘ‬ѧѧѧѧѧѧѧѧ‫ﻗﯾ‬ ‫ل‬ѧѧѧѧѧѧѧѧ‫رو ﻓﻠﯾﻔ‬ѧѧѧѧѧѧѧѧ‫ﻋﻣ‬.‫د‬.‫ﯾﺔ ا‬ѧѧѧѧѧѧѧѧ‫ﺎرات اﻟﮭﻧدﺳ‬ѧѧѧѧѧѧѧѧ‫و ﻟﻼﺳﺗﺷ‬ѧѧѧѧѧѧѧѧ‫اﯾﻛ‬ ‫ﺎوﻻت‬ѧѧѧѧѧѧѧ‫ﺔ واﻟﻣﻘ‬ѧѧѧѧѧѧѧ‫دات اﻟﻌﺎﻣ‬ѧѧѧѧѧѧѧ‫ﻰ ﻟﻠﺗورﯾ‬ѧѧѧѧѧѧѧ‫اﻻﻗﺻ‬ ‫ﺔ‬ѧѧѧѧѧѧ‫ﺑطﺎﻗ‬10.000 ‫ م‬3 – ‫وم‬ѧѧѧѧ‫ ﯾ‬/ 15.000 ‫ م‬3 ‫وم‬ѧѧѧѧ‫ ﯾ‬/ Drawn Checked Approved Date Size
‫ﯾﮫ‬ѧѧѧѧѧѧѧѧѧѧ‫ﻌﺑﮫ اﻟﮭﻧدﺳ‬ѧѧѧѧѧѧѧѧѧѧ‫اﻟﺷ‬ ‫ﯾرة‬ѧѧѧѧѧѧѧ‫ﺔ اﻟﺑﺣ‬ѧѧѧѧѧѧѧ‫ور – ﻣﺣﺎﻓظ‬ѧѧ‫رﻛز دﻣﻧﮭ‬ѧѧ‫ﻣ‬ O.E A.A A.E 11/01/2024 A2 1
1 2 3 4 5 6 7 8

You might also like