Professional Documents
Culture Documents
Chapter Page
2. Operations 18
4. Installation 75
Conditions.
The content of this manual may be copied as required for operational use
on the vessel in which the equipment is installed. This Manual must not
be copied, in full or in part, for disclosure to third part.
JOWA AB
Tulebo 865
428 34 Kållered Gothenburg, SWEDEN
Telephone +46 31 795 00 40
1
JOWA CLEANTOIL 9000 Operations and Technical Manual.
2
JOWA CLEANTOIL 9000 Operations and Technical Manual.
3
JOWA CLEANTOIL 9000 Operations and Technical Manual.
1.1 Introduction
The JOWA CLEANTOIL 9000 Oil Content Meter is approved in accordance with
the test and performance requirements for "second generation" monitors,
contained in IMO Resolution A.586(14) and MEPC.51(32). The requirements of
the MARPOL Convention are that all oil tankers with a gross tonnage of 150
GRT and above must have an oil discharge monitoring and control system
installed, incorporating and approved oil content meter.
A type "B" system is required in new oil tankers of less than 4000 dwt. Such
system must employ a computing unit and the system need not have a starting
interlock, nor any automatic overboard valve control system.
4
JOWA CLEANTOIL 9000 Operations and Technical Manual.
The complete oil discharge monitoring and control system must be installed in
accordance with an approved installation specification, being part of a "plan
approval" package, the content of which is specified in detail in the Resolution
mentioned above. The approval of such documentation is in principle a
responsibility of the flag administration of the tanker but most administrations
have authorised the recognised classification societies to perform the
examination and approval of the installation documentation as well as the
completed installation.
The plan approval documentation must contain at least all the following:
- a description of the complete monitoring and control system as being installed
in the particular tanker, including description of the vessels pumping and piping
systems and the procedures for handling of oil contaminated water.
- an operations and descriptive technical manual for the complete system as
installed , including operational procedures for the various phases of the
overboard discharging.
-procedures for normal operation of the system and procedures for the
operation in case of equipment malfunction.
- detailed technical information covering the entire system, including information
about fault finding.
- a technical installation specification, detailing the installation of components
and the means for complying with relevant gas tightness and space safety
requirements.
- recommended test and check-out procedures for the entire system as
installed.
- complete technical and operations manuals for the oil content meter and other
main components of the system.
The normal way of complying with these requirements, and the way required by
most classification societies, is that of development of a complete, ship specific,
systems manual, covering all the above aspects, and in which this oil content
meter manual is incorporated as one main part.
It is further required that the manual for the oil content meter must only contain
information relevant for the particular installation. This manual, being of general
validity for a range of Cleantoil configurations, may then have to be adjusted by
removal of excess information.
5
JOWA CLEANTOIL 9000 Operations and Technical Manual.
6
JOWA CLEANTOIL 9000 Operations and Technical Manual.
Guidelines and specifications for oil discharge monitoring and control systems
for tankers.
Category A: Tankers > 4000 DWT
Category B: Tankers >150 Gross Tons - < 4000 DWT
Feature Category
A B
Input Information
A A
PPM A M
Flow Rate A M
Speed A A
Date and Time
Starting interlock A M
Discharge
Valve Control A M
Output Information
L/mile A* A*
Total Quantity A* A*
Date and Time A* A*
PPM A* A*
A: Automatic Function
M: Manually inserted data from installed source
*: Information presented or permanent record
7
JOWA CLEANTOIL 9000 Operations and Technical Manual.
JOWA CLEANTOIL 9000 oil content meter is certified to meet the requirements
of IMO Resolution A.586(14) and MEPC.51(32).
JOWA CLEANTOIL 9000 is robust, easy to install, easy to use and easy to
maintain.
JOWA CLEANTOIL 9000 is a high quality product. The most exposed parts are
made of stainless steel. The components of the electrical and electronic
sections are designed for obtaining long lifetime.
JOWA CLEANTOIL 9000 oil content meter consists of the following main parts:
A sample feed pump of gear type, intended to be installed in the pump room
from the analysing unit.
8
JOWA CLEANTOIL 9000 Operations and Technical Manual.
One standard alternative for applications with crude oils, "black" and "white"
products and oil like substances.
3 alternatives for applications with crude oils, "black" and "white" products. This
alternatives should only be used where alternative 1/ isn’t applicable.
The measuring cell is flushed with clean water and a cleaning solution for a
short moment once a minute during operation in order to keep the cell clean.
9
JOWA CLEANTOIL 9000 Operations and Technical Manual.
The computer unit is located in the control room and is connected to the valve
control console for overboard valve operation/starting interlock and for valve
position information.
The converting unit is mounted in the engine room as well as armature and
controls for water and air supply to the components in the pump room.
The analysing unit is mounted in the pump room side of the bulkhead above the
bulkhead penetrations for small diameter piping for water and control air as well
as for electrical wiring of the intrinsically safe circuitry of the measuring system
are arranged at a suitable location, making the connections as short as
possible.
Sample probes and sample return probes are arranged in the overboard piping
as required, as well as the flow meter. The sample probe valves may optionally
be remote controlled from CLEANTOIL, and connected to the converting unit.
10
JOWA CLEANTOIL 9000 Operations and Technical Manual.
JOWA CLEANTOIL receives the following signals from components being part
of the equipment and from other components.
8. Signal from push button for running the cleaning solution pump manually.
10 Signal from manual override switch to control the overboard discharge valve
Purpose: To enable, in case of failure, overboard discharges independent
of the CLEANTOIL equipment.
11a Voltage free switch input for indication of overboard valve open position.
Purpose: To indicate overboard valve position.
11b. Voltage free switch input for indication of overboard valve close position.
the input is only used in "extended" valve control logic option.
11c. Voltage free switch input for indication of slop tank valve open position.
The input is only used in "extended" valve control logic option.
11d. Voltage free switch input for indication of slop tank valve close position.
The input is only used in "extended" valve control logic option.
11
JOWA CLEANTOIL 9000 Operations and Technical Manual.
5. Fresh water valve control relay output. External solenoid valve is included.
Purpose: To facilitate automatic cleaning of the analysing unit.
11b Computer unit overboard valve close output. Only used in extended mode.
11c Computer unit slop tank valve open output. Only used in extended mode.
11d Computer unit slop tank valve close output. Only used in extended mode.
12
JOWA CLEANTOIL 9000 Operations and Technical Manual.
12. Printer.
Purpose: To record the operation of the equipment.
13
JOWA CLEANTOIL 9000 Operations and Technical Manual.
The computer unit contains all facilities, necessary to carry out the computing
and recording of the overboard discharges, as specified in the Convention and
the related Resolutions. The computer calculates the oil content in the sample
water, using information from the sensors in the analysing unit. The computer
unit calculates the rate of discharge of oil and the total quantity discharged
during a voyage from the oil content and flow meter input information. All
calculations are identified to time and date, using a built- in time information
generator. Failures and malfunctions are monitored. Alarms are given at
exceedence of discharge limits and at failures. All information is printed in a
durable format on a printer. Additionally the computer unit has the overall
control functions of the remaining parts of the entire system.
Weight: 35 Kg
Power supply: 220VAC +-10 % 50/60 Hz 50VA The power supply should be
equipped with a main switch or a detachable power supply
connector and a fuse size of max. 6 A.
14
JOWA CLEANTOIL 9000 Operations and Technical Manual.
Installation place:
Bulkhead mounted in engine room or equivalent non-hazardous area.
Weight: 44 Kg
Physical arrangement:
The converting unit is built into a enamel lacquer coated steel cabinet, divided in
two sections. The left hand compartment contains electrical components for
external equipment, e.g. relays, transformers, Zener barriers and connection
terminals. The right hand compartment contains the tank and pump for the
measuring cell cleaning solution, related controls and solenoid valves for
pneumatically operated components.
Electrical supply:
1. The standard model is designed for electrically powered pump motor and has
the following supply specification:
3 phase 440/380VAC +- 10% 60/50Hz 1200VA.
The power supply should be equipped with a main
switch or a detachable power supply connector and
a fuse size of 3 x 10 A.
15
JOWA CLEANTOIL 9000 Operations and Technical Manual.
16
JOWA CLEANTOIL 9000 Operations and Technical Manual.
17
JOWA CLEANTOIL 9000 Operations and Technical Manual.
Safety approvals: The electrical components of the analysing unit have the
following approvals:
The measuring unit
EEx ia IIC T4 Tamb0-65C SP Ex88601x
The pressure transmitter
EEx ia IIC T4 Ta 80c BAS Ex802217x
EEx ia IIC T4 Ta 80c BAS Ex89c2251
EEx ia IIC T4 Ta 80c LCIE No 87.B6024x/
LCIE No 88.8001X
18
JOWA CLEANTOIL 9000 Operations and Technical Manual.
19
JOWA CLEANTOIL 9000 Operations and Technical Manual.
Physical arrangement: The pump unit consists of a gear pump of bronze. The
motor and pump are mounted on each side of a circular
bulkhead plate. The drive axis is sealed by double lip
seals, and the intermediate space is oil filled. A
transparent oil reservoir is available on the engine room
side.
Approval: Crude oils, "black" and "white" products and oil like
substances.
20
JOWA CLEANTOIL 9000 Operations and Technical Manual.
The following parts are included in one set of JOWA CLEANTOIL 9000
equipment:
1 Analysing unit.
1 Fresh water valve unit, comprising of a solenoid valve, a shut off valve, a
check valve and a vacuum check valve.
2 Cleaning solution / 5 l.
2 Cleaning brush.
2 Printer ribbons
21
JOWA CLEANTOIL 9000 Operations and Technical Manual.
Chapter 2 - Operations
22
JOWA CLEANTOIL 9000 Operations and Technical Manual.
This section contains a brief description of the function of the computer unit,
including information about its operation and use.
Detailed procedures for the operation of the equipment are given in the
following sections, see:
2.2 Operations Procedures
2.3 Cleantoil Computer Unit Program Description
2.4 Programming of Operational Parameters.
2.5 Alarm, Warning and Reset Procedures
23
JOWA CLEANTOIL 9000 Operations and Technical Manual.
A detailed description of the input and output signals from the Cleantoil
computer unit is contained in paragraphs 1.3.1 and 1.3.2 of Chapter 1.
24
JOWA CLEANTOIL 9000 Operations and Technical Manual.
This section contains the information needed for normal operation of the
Cleantoil equipment. Detailed information about programming, alarm conditions
etc. is given in sections 2.3 to 2.5.
This paragraph gives a brief description of the normal starting up procedure for
the CLEANTOIL system. For detailed information about programming of
operational parameters, see section 2.5.
Detailed information about the computer program and its use is given in section
2.4.
1 Check the level in the Cleaning solution tank and open valve pos. 34 (see
Drw. MJC-10-1 for location). The cleaning solution consumption is approx.
0.1 l / hour. The bottom 5 cm liquid should not be counted as usable.
Drain the Control air supply water trap (pos. 36).
Open the Control air supply valves and check the pressure to be 4,5 - 6 bar
Open the fresh water supply valves (pos. 31 and 35).
3 Open the manual sample probe valves at the sample points to be used
(18a, 18b, 19a and 19b for location see Drw. MJC-10-1).
4 Check the Flow Meter valves VF1 and VF2 to be open and VF3 should be
closed ( for location see Drw. MJC-10-1).
25
JOWA CLEANTOIL 9000 Operations and Technical Manual.
Computer keyboard with the following keys for operation and control of the
functioning of the equipment:
7 8 9
^
INS UP PG UP
4 5 6
< >
LEFT RIGHT
1 2 3
v
RET DOWN PG DN
. 0 -
RESET ALT CLN OBV
STEP PF AV
Underlined characters are marked with blue colour. The "blue" functions are
obtained by keeping ALT pressed.
Below is a short description of the 27 key functions (15 marked with black and
12 with blue text) of the keyboard.
PG UP Moving to the page above. The move will be to the head line of the
page.
RET Termination of writing. The modified line is fed into the computer.
Note. All writing/changing must be terminated by a RETURN.
All new line functions will cancel characters that were previously
written on the line and not terminated with the return key.
26
JOWA CLEANTOIL 9000 Operations and Technical Manual.
PG DN Moving to the page below. The move will be to the head line of
the page.
RESET Reset of the alarm and warning. The alarm and warning
outputs are activated whilst the reset key is activated.
0123456789.- Character writing. Accepted only after INS and then press ALT .
27
JOWA CLEANTOIL 9000 Operations and Technical Manual.
This should be done even if the sample point valves aren’t remote controlled to
get a complete record on the printer.
.2 Check or select the oil Type in line 2.2 on the computer unit.
Check paragraph 2.4.4 for guidance to correct selection of oil type.
e.g.
.3 Check the discharge mode (15ppm / 30 l/nm) line 2.3 on the computer unit.
"OIL DISCHARGE" indicates that the equipment is operating in the 30 l/nm
mode.
e.g.
.4 Check or adjust the flow rate input in line 2.4 on the computer unit.
Manually inserted value is shown as the first set of digits outside the
parenthesis, automatically received value is represented by the second set
of digits.
e.g.
.5 Check or adjust the speed input in line 2.5 on the computer unit. Manually
inserted value is shown as the first set of digits outside the parenthesis,
automatically received value is represented by the second set of digits.
e.g.
28
JOWA CLEANTOIL 9000 Operations and Technical Manual.
.6 Program or check the overboard total quantity discharged and total quantity
alarm in lines 2.6 on the computer unit.
e.g.
.7 Check or adjust the warning limits in lines 2.7 on the computer unit.
e.g.
6 Press the RESET key on the computer unit to erase any old alarms
After a successful start up, the overboard valve opens. If any alarm appears the
overboard valve will be controlled closed. If the alarm disappears the overboard
valve will open again. Press the OBV key to initiate additional valve opening or
closing.
During measuring the starting interlock output relay is activated, removing the
blocking of the overboard valve.
At start up the OBV LED lights intermittently.
When the OBV LED lights intermittently the overboard valve switch be in the
closed position.
After a successful start up the OBV LED lights continuously.
29
JOWA CLEANTOIL 9000 Operations and Technical Manual.
When the OBV LED lights continuously the overboard valve may be opened.
The position of the manual overboard valve should always be manually
indicated by the overboard valve switch on the computer unit.
3 The Cleantoil is now performing a cleaning cycle. Wait until the cleaning
cycle is completed or stop the cleaning cycle by pressing the CLN key.
4 Close the sample probe valves (pos. 18a, 18b, 19a and 19b, see Drw.
MJC-10-1 for location).
Close the Analysing unit inlet and outlet valves.
4. Open top screw at analysing unit and clean the cell manually with the brush
and concentrated cleaning solution.
30
JOWA CLEANTOIL 9000 Operations and Technical Manual.
ˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆ
ˆ
P.11 MANUAL OVERRIDE OVERBOARD VALVE
ˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆ
ˆ
P.12 MANUAL OVERRIDE OVERBOARD VALVE ENDS
31
JOWA CLEANTOIL 9000 Operations and Technical Manual.
This section contains a brief description of the computer program and the
means of operation. The function of the keyboard is described in detail in
paragraph 2.2.1.b in Chapter 2.
The LCD information is controlled by the keys PAGE UP, PAGE DOWN, LINE
UP and LINE DOWN.
Below is a description of the LCD information in short form. Item numbers to the
left of the text below, are used for facilitating this documentation and are not
showed on the LCD.
1 DISPLAY HEADLINE
32
JOWA CLEANTOIL 9000 Operations and Technical Manual.
2 PAGE PROGRAMMING
33
JOWA CLEANTOIL 9000 Operations and Technical Manual.
Description of the most important parameters for the 30 l/nm mode. From the
left - oil content in ppm (AUTO= automatic, MAN = manual), flow rate of oil
discharged overboard per nautical mile and ships speed.
Description of line, one step below headline, it’s purpose is just for checking that
the calculation formula works or when you want to simulate an high ppm alarm
or exceeding the 30 l/nm limit.
If you entering manual mode during discharging operation the overboard valve
closes.
When you are in manual mode the LED lamp PF lights intermittently.
34
JOWA CLEANTOIL 9000 Operations and Technical Manual.
Oil quality. Selection is preceded by pressing the INS key, then selection is
made by using <- and -> keys. Selection is terminated by the RET key.
35
JOWA CLEANTOIL 9000 Operations and Technical Manual.
Total amount of oil pumped overboard. The value is programmable and should
be reset to zero at the beginning of a new ballast voyage.
Warning limit for high rate of oil pumped overboard. The value is programmable
but is normally recommended to be set to 25 l/nm.
High oil content warning limit. The value is programmable.
New printer paper. Press RETURN key after installation of a new printer paper.
The computer will print all operation data and reset the paper line counter.
36
JOWA CLEANTOIL 9000 Operations and Technical Manual.
The sampling point is identified together with the related overboard valve.
The 15 ppm mode for monitoring of clean ballast may be used when desired for
the monitoring of discharges of arrival ballast.
Press the keys until line 2.3 is visible on the display. If the line indicates "OIL
DISCHARGE" at the end, the Cleantoil is in 30 l/nm mode. In that case select
the 15 ppm mode by pressing the STEP key. The 15 ppm mode is indicated by
"OIL CONCENTRATION".
The 30 l/nm mode is the normal and mandatory mode in which Cleantoil
monitors the oil content and computes the discharge rate of oil and compares
this to the permitted value of 30 l/nm. This monitoring function must be in
operation at all times when discharge overboard of oil contaminated water takes
place.
Press the keys until line 2.3 is visible on the display. If the line displays "OIL
CONCENTRATION" at the end, the Cleantoil is in 15 ppm mode. In that case
select the 301/nm mode by pressing the STEP key until the display shows "OIL
DISCHARGE".
37
JOWA CLEANTOIL 9000 Operations and Technical Manual.
38
JOWA CLEANTOIL 9000 Operations and Technical Manual.
Sahara Blend
Arabian Light Cr
Nigerian Med Cr
Bachaquero 17 Cr
Minas Crude
Kerosene
Ekofish
Autom Gas (gasoline)
Bunker C
L Dsl, No.2 F Oil (diesel oil)
Oil type no 10
Oil type no 11
Oil type no 12
Oil type no 13
Oil type no 14
Oil type no 15
The first ten oil types correspond to the IMO reference oils. The options "Oil
type no 10" to "Oil type no 15" provide additional flexibility in selecting pre-
programmed settings, covering a wide range of oil characteristics. The following
guidance should be used for selection oil type setting for oils of various kinds:
39
JOWA CLEANTOIL 9000 Operations and Technical Manual.
Annex 2
XYLENES
p-CYMENE
OCTANE
DIPENTENE
CYCLOHEXANE
NONANE
TOULENE
DODECANE
ETHYLCYCLOHEXANE
HEXENE
PENTANE
METHYLCYCLOHEXANE
HEPTANE
HEXANE
DIETHYLBENZENE
CYCLOPENTANE
PROPYLENE DIMER
PENTENE
40
JOWA CLEANTOIL 9000 Operations and Technical Manual.
2.4.7 Select AUT flow measuring mode or MAN flow rate input.
Automatic input of flow rate is required at all times on vessels required to have a
flow meter. Only in case of flow meter failure may manual insertion be applied.
In vessels not required to be equipped by a flow meter, the current overboard
flow value , as determined from pump curves, must be inserted and be updated
as often as any substantial change of the pumping rate is made.
41
JOWA CLEANTOIL 9000 Operations and Technical Manual.
This warning feature is not mandatory and the suitable warning level may be
selected as desired. 25 l/nm is suggested as a suitable warning level.
This warning feature is not mandatory and the oil content warning level may be
selected as desired. A warning of 10 ppm is suggested as suitable level.
42
JOWA CLEANTOIL 9000 Operations and Technical Manual.
-The alarm relay and the buzzer being deactivated by the RESET key. The
alarm LED is deactivated only when the cause for applies to certain alarms
which might be encountered during ballast water discharge, such as
During periods at which this kind of alarms are activated the overboard valve is
closed. When the alarm is deactivated the overboard valve opens again
automatically.
The operator, for the sake of acknowledgement, has to press the RESET key.
43
JOWA CLEANTOIL 9000 Operations and Technical Manual.
ˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆ
ˆ
P.1 ******** POWER OFF ********
44
JOWA CLEANTOIL 9000 Operations and Technical Manual.
ˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆ
ˆ
P.1 ******** POWER OFF ********
ˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆ
ˆ
P.2 ******** POWER ON ********
ˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆ
ˆ
P.3 ****** MANUAL RESET ******
Manual reset of alarm supervision logic, initiated by pressing the computer reset
key.
This line is followed by time and date of the manual reset.
ˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆ
ˆ
P.4 ****** MANUAL MATH-ERROR RESET ******
Reset of floating point math error was made on the time and date indicated on
the following line.
ˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆ
ˆ
P.5 ****** MANUAL MEMORY-ERROR RESET ******
Reset of memory error was made on the time and date indicated on the
following line.
ˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆ
ˆ
P.6 ****** Start Oil-measuring ******
Start of oil measuring, initiated by pressing the CLEANTOIL computer OBV key
when the system is in stand by mode.
This line is followed by time and date for the oil-measuring start.
45
JOWA CLEANTOIL 9000 Operations and Technical Manual.
ˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆ
ˆ
P.7 ****** Converting Unit Start ******
This line is added to P.6 if start of oil-measuring was initialised from the
Converting unit instead of pressing the CLEANTOIL computer OBV key.
ˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆ
ˆ
P.8 ****** Stop Oil-measuring ******
Stop of Oil measuring, initiated by pressing the CLEANTOIL computer OBV key
when the system is in measuring mode.
This line is followed by time and date for the oil-measuring stop.
ˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆ
ˆ
P.9 ****** EXIT TESTMODE ******
Exit of testmode, initiated by pressing the CLEANTOIL computer INS key when
line 8.0 is visible on the display, and the testmode was previously entered.
This line is followed by time and date for the exit of testmode.
ˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆ
ˆ
P.10 ****** ENTER TESTMODE ******
ˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆ
ˆ
P.11 MANUAL OVERRIDE OVERBOARD VALVE
Manual override, initiated by turning the manual override key on the computer
panel to OFF position.
This line is followed by time and date for entering the manual override mode.
46
JOWA CLEANTOIL 9000 Operations and Technical Manual.
ˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆ
ˆ
P.12 MANUAL OVERRIDE OVERBOARD ENDS
End of manual override, initiated by turning the manual override key on the
CLEANTOIL computer panel to OFF position.
This line is followed by time and date for exiting the manual override mode.
ˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆ
ˆ
P.13 Previous paper had 01056 printouts.
Number of lines printed on the previous paper. This is printed at the beginning
of each paper.
ˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆˆ
ˆ
P.14 1997.12.30 19:27 00056:00675 ALARM
P.15 Oil25.00 ppm 13.1 l/nm Σ13.011 OBV OPEN #2
P.16 Oil25.00 ppm OBV OPEN #2
P.17 Arabian light cr FA780.7m3/h SM12.2kn
Lines P.14, P.15, P.16 and P.17 are printed during measuring, every 10 minute
or when the discharge rate of oil is changed by 10 l/nm
Line P.15
Oil content in ppm.
Discharge rate of oil in l/nm
Total amount of oil discharged.
Line P.16
Number of selected sample point.
Position of overboard valve.
Line P.17
Flow rate and if the flow was manually or automatically measured.
Speed and if the speed was manually or automatically measured.
Oil type.
47
JOWA CLEANTOIL 9000 Operations and Technical Manual.
1. Loosen the old paper from the paper roller, by unscrewing the screw
at the right hand side of the roller. Pull the loop together with the
paper towards the right.
2. Open the front cover of the printer. Cut the new paper in order to get a
tip in the middle. Slip the tip of the paper into the intended slot. Press
at the same time the FEED key on the printer until the paper tip
reaches the paper roller.
3. Mount the loop on the paper roller and fasten the new paper under the
loop at the same time.
48
JOWA CLEANTOIL 9000 Operations and Technical Manual.
Open the right hand door of the converting unit. Disconnect the two cables at
the top cover of the cleaning solution tank. Fill up the empty tank or replace the
tank with a new one. Screw on the top cover and connect the two cables. If the
cleaning solution tubing is empty, press the cleaning solution pump key
positioned inside the converting unit valve part enclosure on the left gable. The
pump will now work for 5 min or until the key is pressed a second time. Close
the door of the converting unit.
Note: Use only JOWA CLEANTOIL CLEANING SOLUTION to obtain the best
result.
Open the analysing valve by pressing the AV key on the front of the computer
unit. Close the analysing unit outlet and inlet valves. Open the top cover and
drain valve. Clean inside the measuring unit cell with the brush provided and
some Cleantoil cleaning solution. Remount the top cover and reset the valves to
normal operating positions.
This part does only apply to Cleantoil versions with bulkhead penetration
sample feed pumps.
The oil reservoir is positioned on the engine room side. Remove the oil reservoir
cover nut. Be careful no to turn the reservoir from the pump. Refill up to the
thread with recommended oil type. Be careful not to harm the plastic reservoir
when the cover nut is mounted. Turn the cover nut Counter Clock Wise until it is
in right position.
49
JOWA CLEANTOIL 9000 Operations and Technical Manual.
This chapter contains instructions for fault finding and necessary corrective
actions related to computer unit and other complex parts of the system. The
instructions include information about a complete functional check of the
computer programme.
Page
3.1 Description of Alarms and their Programming. 45
3.1.1 List of Alarms and Warning Functions. 45 - 47
50
JOWA CLEANTOIL 9000 Operations and Technical Manual.
The computer program contains a number of warning and alarm functions for
internal malfunctions and abnormal operational conditions. This section gives a
summary of these functions, their functioning, their programming, where
appropriate, and how they are used in fault finding. Some of the information
given may only be useful for experienced computer and electronics engineers,
other parts are useful for normal fault finding in the entire system.
4 ALARM IR-REFERENCES
Hardware error, refer to manual.
51
JOWA CLEANTOIL 9000 Operations and Technical Manual.
17 ALARM 15 ppm
18 ALARM 30 l/nm
19 ALARM ACC.TOTAL
52
JOWA CLEANTOIL 9000 Operations and Technical Manual.
53
JOWA CLEANTOIL 9000 Operations and Technical Manual.
1
ALARM MATH ERROR
check program reset.
2
ALARM MEMORY ERROR
Check program before reset.
Computer error.
Probably cause: Computer PC battery failure.
3
ALARM COMMUNICATION ERROR
BETWEEN COMPUTER AND CONV UNIT
Check the fuses located inside the electrical part of the converting
unit. See Drawing MJC-30-4 for fuse location.
54
JOWA CLEANTOIL 9000 Operations and Technical Manual.
6
ALARM PRESSURE SWITCH
check air supply shut off valve
The air pressure that supply the analysing valve is below pressure
switch set limit ( min. 4 bar ). check air supply or check and adjust the
pressure switch limit
55
JOWA CLEANTOIL 9000 Operations and Technical Manual.
Check cables Cb5, Cb6 and Cb7, see Dwg MJC-10-2 for details.
If the alarm still remains it may indicate a more severe defect,
e.g. the quarts tube in the measuring unit being broken.
For further trouble shooting, carry out the following checks:
Verify with respect to earth:
The voltage at converting unit terminal z1 to be +6 to +8 v.
The voltage at converting unit terminal z2 to be,
intermittently, 0 to -0,5v.
The voltage at converting unit terminal z3 to be,
intermittently, 0 to -0,5v.
The voltage at converting unit terminal z4 to be -6 to -8v.
The voltage at converting unit terminal z5 to be,
intermittently, 0 to -0,5v.
The voltage at converting unit terminal z6 to be,
intermittently, 0 to -0,5v.
The voltage at converting unit terminal z7 to be,
intermittently, -1,8v.
The voltage at converting unit terminal z8 to be,
intermittently, -0,6V.
56
JOWA CLEANTOIL 9000 Operations and Technical Manual.
min
8.4 IR-data 4-7 (reference signals)
00400 00400 00400 01600
max
8.3 IR-data 0-3 (dark signals)
RI+100 RI+100 RI+100 RI+100
max
IR-data 8-11 (measuring signals)
8.5
2xR4+1000 R1+100 R1+100 R1+100
57
JOWA CLEANTOIL 9000 Operations and Technical Manual.
9
ALARM CLEANING PRESSURE = 7.00 bar
Check water supply shut off valve
58
JOWA CLEANTOIL 9000 Operations and Technical Manual.
max
Analogue Lowref, Flow, Highref, Press
8.2
inputs 00300 00227 02200 00700
59
JOWA CLEANTOIL 9000 Operations and Technical Manual.
11
ALARM CLEANING ERROR
detector data 34.16 .8892 1.189 .2643
Unexpected cleaning value detected in the measuring unit.
Probable cause : The measuring unit is dirty or dry.
Detector data is displayed in order to simplify trouble shooting.
12
ALARM FLOW MIN LIMIT
Low flow or hardware error
max
8.2 Analogue Lowref, Flow, Highref, Press
inputs 00300 00300 02200 00663
60
JOWA CLEANTOIL 9000 Operations and Technical Manual.
min
Analogue Lowref, Flow, Highref, Press
8.2
inputs 00150 00150 01600 00663
14
ALARM SPEED MIN LIMIT
Low speed or hardware error
15
ALARM SPEED MAX LIMIT
hardware error, refer to manual
61
JOWA CLEANTOIL 9000 Operations and Technical Manual.
16
HIGH ppm FAILURE
17
ALARM 15ppm
18
ALARM 30 l/nm
19
ALARM ACC.TOTAL
62
JOWA CLEANTOIL 9000 Operations and Technical Manual.
21
STV indicating both open and closed.
Hardware error, refer to manual
This indicates that the feedback signal from the overboard valve
does not correspond to the computer unit signal.
Probably cause: same as 3.20 above
22
OBV no FEEDBACK within time-out.
Hardware error, refer to manual
63
JOWA CLEANTOIL 9000 Operations and Technical Manual.
The slop tank valve position feedback signal has not acknowledged
the corresponding output signal on time.
This fault is only relevant in installation in "EXTENDED" versions
Stop overboard discharging. The slop tank valve may be in the wrong
position due to some part of the overboard discharge valve system
or the power supply for the valve control system has failed.
24
WARNING CLEANING SOLUTION
Refill cleaning solution
26
Warning OC 10.0 ppm
64
JOWA CLEANTOIL 9000 Operations and Technical Manual.
27
WARNING ACC.TOTAL 90%
65
JOWA CLEANTOIL 9000 Operations and Technical Manual.
66
JOWA CLEANTOIL 9000 Operations and Technical Manual.
4.1
Flow max limit= 1000 m3/h
min limit= 50 m3/h Delay 20(05)s
Overboard discharge flow, max. and min. limits and alarm delay time.
4.3
Flowlinj = insig(20.00%) * 1.260 + - .260
Flow = 300 * Flowlinj ** 0.5000 m3/h
The second formula is needed if the signal from the flow meter
is not proportional to the real flow. The values in this example
are for a flow input signal that is proportional to the square root
of the actual flow.
4.4
Log input = 200 pulses/h
Log generates = 200.0 pulses/nm
67
JOWA CLEANTOIL 9000 Operations and Technical Manual.
5.0
PAGE IR-DETECTOR
5.2
Calibration values: Reference solution
detector data 61.90 17.80 22.60 12.10 %
5.3
Measuring
detector data 56.50 19.50 22.50 15.50 %
68
JOWA CLEANTOIL 9000 Operations and Technical Manual.
3.1
ALARM CLEANING ERROR
detector data 44.10 1.520 2.189 1.264
3.7
ALARM IR-DETECTOR FAILURE
detector data 34.16 .0092 1.189 .2643
5.10
Reference solution
Oil content 190. 106. 86.0 72.0 ppm
69
JOWA CLEANTOIL 9000 Operations and Technical Manual.
6.0
PAGE PRESSURE
6.1
Pressure in analysing unit = .28 bar
OPEN water with STEP
70
JOWA CLEANTOIL 9000 Operations and Technical Manual.
6.5
Pressure insignal = 20.12 %
Pressure = insignal * .3125 + - 6.25 bar
71
JOWA CLEANTOIL 9000 Operations and Technical Manual.
This page shows the timers that control the measuring and cleaning
cycles. The procedure is explained below and at next page
7.0
Side TIMERS AND COUNTERS
7.2
Number of cleaning meas. Cycles 03(03)
aftercleaning Cycles 03(03)
Press STEP key and you will find out the length of the measuring and
cleaning states.
7.4
Delay OBV, STV feedback 60(60) sec
Delay Overb. valve changes 60(60)sec
The first line displays the maximum delay in seconds for the
overboard and slop tank valve feedback signal
Values inside parenthesis are actual delay times for the 2 valves.
The second line displays the minimum delay in seconds for
the overboard valve to be closed, in order to prevent
continuous opening and closing of it.
72
JOWA CLEANTOIL 9000 Operations and Technical Manual.
or an
The current state, and the time of the current state is indicated by line 7.1
Press the STEP key and you will find out the length of the measuring states.
73
JOWA CLEANTOIL 9000 Operations and Technical Manual.
The pressure diagram showed at the bottom line indicates in which state the
pressure in the analysing unit is checked.
If the pressure fails an
3.9 ALARM CLEANING PRESSURE = 6.00 bar
Check water supply shut off valve.
or an
The current state, and the time of the current state is indicated by line 7.1
Press the STEP key and you will find out the length of the cleaning states.
The cleaning cycle is repeated as many times as indicated by line 7.2 after
"aftercl:".
74
JOWA CLEANTOIL 9000 Operations and Technical Manual.
8.0
PAGE TEST
Enter testmode by pressing STEP
8.1
Communication (ok 05678/Err 00003)
Tx send 2035 Tx rec 2035 Rx rec 90
Transmitted value
Bit Description
0 Cleaning solution
1 Water valve
2 Pump backward
3 Pump forward
4 Sample tube valve
5 Spare output
6 Overboard valve or sample tube valve number 2.
7 Not used
75
JOWA CLEANTOIL 9000 Operations and Technical Manual.
8 Internal output B.
9 Overboard pump or Overboard valve relay output.
10 Analysing valve output.
11 Not used
12 Internal output 0.
13 Internal output 1.
14 Internal output 2.
15 Internal output A.
Received Value
Bit Description
0 Start/Stop
1 Cleaning solution low level alarm
2 Sample feeding pump overcurrent relay
3 Cleaning solution pump start.
4 Pneumatic pressure switch
5 Converting unit in test mode. This mode is
obtained by connecting a jumper on the
converting unit PC. Should normally be =.
6 Internal input A.
7 Internal input B.
8.2
Analogue Lowref, Flow, Highref, Press
inputs 00223 00227 01694 00505
Analogue signals from the pressure transducer and the flow meter.
Lowref and Highref are internal voltage reference that correspond
to 0% and 100% input signal respectively.
8.4
IR-data 4-7 (reference signals)
00446 00446 00445 01956
8.5
IR-data 8-11 (measuring signals)
04296 00544 00620 00490
8.7
I/O Computer 00100010 11001100 00001000
Move: <- ->, changes , OBV LAMP
Output
"INTERNAL 1" Internal output
"INTERNAL "" Internal output
"STV CLOSE" Slop tank valve close relay output,
only used in "EXTENDED" configuration.
"STV OPEN" Slop tank valve open relay output,
only used in "EXTENDED" configuration.
STV LAMP" Slop tank valve led indicator on the
CLEANTOIL computer front panel.
"PAPER ROLLER" Paper roller output
"INTERNAL 3" Internal output
"OBV LAMP" Overboard valve led indicator on the
CLEANTOIL computer front panel.
"INTERNAL 4" Internal output
"OBV CLOSE" Overboard valve close relay output,
only used in "EXTENDED" configuration.
"OVERRIDE" Override relay output.
"INTERNAL 5" Internal output
"BEEPER" Alarm buzzer output
"OBV OPEN" Overboard valve open rely output
"ALARM RELAY" Alarm relay output
"WARNING RELAY" Warning relay output
Input
"INTERNAL &" Internal input
"STV CLOSED INP" Close feedback signal from slop tank valve,
only used in "EXTENDED" configuration.
"STV OPEN INP" Open feedback signal from slop tank valve
only used in "EXTENDED" configuration.
"OBV CLOSED INP" close feedback signal from overboard valve,
only used in "EXTENDED ”configuration.
"LOG INP" Input from ships log.
"OBV OPEN INP" Open feedback signal from overboard valve.
"OVERRIDE INP" Signal to monitor the override input key.
77
JOWA CLEANTOIL 9000 Operations and Technical Manual.
8.8
COMDATA 00010010 11010000 00000001
Move:<- ->, change: STEP, CLEANING PUMP
Transmitted value
Bit Description
"NOT USED" Not used
"SAMPLE POINT 2" Overboard valve or sample tube valve No.2.
"SPARE RELAY 2" Spare output 2.
"SAMPLE POINT 1" Sample tube valve.
"PUMP FORWARD" Pump forward
"PUMP BACKWARD" Pump backward
"WATER VALVE" Water valve
"CLEANING PUMP" Cleaning solution pump.
Received value
Bit Description
"INTERNAL 7" Internal input B
"INTERNAL 8" Internal input A.
"CU TEST MODE" Converting unit in test mode. This mode is
obtained by connecting a jumper on the
Converting unit PC. Should normally be O.
"P SWITCH" Pneumatic pressure switch.
"CL PUMP START" Cleaning solution pump start key.
"OVERCURRENT" Sample feeding pump overcurrent relay and
overheating switch.
"CL LEVEL" Cleaning solution low level alarm
"MEAS STARTER" Start/Stop
78
JOWA CLEANTOIL 9000 Operations and Technical Manual.
2.11
Memory printout with STEP
79
JOWA CLEANTOIL 9000 Operations and Technical Manual.
80
JOWA CLEANTOIL 9000 Operations and Technical Manual.
Chapter 4 - Installation
81
JOWA CLEANTOIL 9000 Operations and Technical Manual.
82
JOWA CLEANTOIL 9000 Operations and Technical Manual.
83
JOWA CLEANTOIL 9000 Operations and Technical Manual.
84
JOWA CLEANTOIL 9000 Operations and Technical Manual.
85
JOWA CLEANTOIL 9000 Operations and Technical Manual.
86
JOWA CLEANTOIL 9000 Operations and Technical Manual.
The supply air should be clean and dry instrument air or control air.
The pressure should be 4 - 6 bar.
The air supply should be provided with a shut of
valve and if necessary the specified air filter.
Air pipes other than Tb1 and Tb6 have configuration dependent
purposes.
Refer to the configuration drawing applicable to the to the unit being
installed.
A general pneumatic controlled valve system is described in Drw.
MJC-60-22 and Drw. MJC-10-1
Valves for remote control of selected sample point
may be replaced by manual valves in systems also having
manual overboard valve operation.
87
JOWA CLEANTOIL 9000 Operations and Technical Manual.
Tube Nn Size
Tb7 8x1
Tb8 15 x 1
The water supply should be provided with one shut off and
one vacuum check valve and one check valve. The water temperature
should be higher than the sample water temperature . Suitable
temperature is approximate 20 centigrade warmer than the sample
water temperature- The water should , however, not be warmer than
45 centigrade. It is recommended to install a temperature
controlled mixer to achieve proper water temperature.
88
JOWA CLEANTOIL 9000 Operations and Technical Manual.
89
JOWA CLEANTOIL 9000 Operations and Technical Manual.
90
JOWA CLEANTOIL 9000 Operations and Technical Manual.
91
JOWA CLEANTOIL 9000 Operations and Technical Manual.
92
JOWA CLEANTOIL 9000 Operations and Technical Manual.
Connect a multimeter on the terminal block CK+ and CK- and check
that you have 4mA, if not, turn the adjustment screw until
you read the right signal 4mA on the multimeter.
Close the middle valve VF3 and open the other valve you closed
before VF1 or VF2, the system is now in operation and should
be ok. You can keep the mode switch in position 0.
3. Span adjust:
Warning ! don’t try to adjust the span (mode switch in pos.1),
because this is done by the manufacturer.
93
JOWA CLEANTOIL 9000 Operations and Technical Manual.
94
JOWA CLEANTOIL 9000 Operations and Technical Manual.
This chapter contains information about spare parts for the cleantoil
equipment and consumables, related to normal operation of the
equipment. Spare parts are identified with reference used in the
drawings in chapter 7.
Page
6.1 Computer unit spare parts. 89
6.7 Consumables. 91
95
JOWA CLEANTOIL 9000 Operations and Technical Manual.
96
JOWA CLEANTOIL 9000 Operations and Technical Manual.
97
JOWA CLEANTOIL 9000 Operations and Technical Manual.
6.7 Comsumables
98
JOWA CLEANTOIL 9000 Operations and Technical Manual.
Page
7.1 Register of identifications used in the drawings. 93
7.3 Drawings. 96
99
JOWA CLEANTOIL 9000 Operations and Technical Manual.
In order to improve the clarity of the drawings, all significant items are
identified by an unambiguous designation number, as shown in the
listing below. All items included in this register are not parts of a
JOWA CLEANTOIL 9000, adapted for a certain ship.
See paragraph 1.4 about JOWA CLEANTOIL 9000 delivery extent.
1. Computer unit.
3. Converting unit.
8. Water valve.
10. Analysing unit.
14. Sample feed pump.
15. Inlet filter.
18. Sample outlet probe valve.
19. Sample inlet probe valve.
20. Sample outlet probe.
21. Sample inlet probe.
22. Flow transmitter.
27. Overboard valve.
29. Water check valve.
30. Air shut off valve
31. Water shut off valve.
33. Water vacuum check valve.
34. Cleaning solution shut off valve.
35. Water shut off valve.
36. Valve air supply pressure regulator and water separator.
Tb1. Valve air supply 6mm
Tb6. Analysing unit valve actuator pipe. (Open) 6mm
Tb7. Cleaning solution pipe. 8mm
Tb8. Water pipe. 1/2”
Tb11. Analysing unit outlet pipe. 3/4”
Tb12 Analysing unit inlet pipe. 1/2”
Tb13 Pump unit inlet pipe. 3/4”
Cb1. Converting unit power supply.
Cb2. Electrically powered pump power supply.
Cb3. Intrinsically safe flowmeter supply.
Cb4. Analysing unit pressure transmitter cable.
Cb5. Computer unit and converting unit interconnection cable.
Cb6. Measuring unit part 1 cable.
Cb7. Measuring unit part 2 cable.
Cb8a. Overboard valve or interlock cable from computer unit.
Cb8b. Computer unit power supply.
Cb9a. Alarm output cable.
Cb9b. Warning output cable.
Cb10. Flowmeter signal cable.
Cb11. Water solenoid cable.
Cb12. Log cable.
100
JOWA CLEANTOIL 9000 Operations and Technical Manual.
101
JOWA CLEANTOIL 9000 Operations and Technical Manual.
102
JOWA CLEANTOIL 9000 Operations and Technical Manual.
7.3 Drawings
103
JOWA CLEANTOIL 9000 Operations and Technical Manual.
Content
CO871203.10A Oil Content Meter Computing Unit
CO871204.10A Oil Content Meter Analysing /Converting Unit
CO880120.10A Oil Content Meter Sample Feed Pump
104
JOWA CLEANTOIL 9000 Operations and Technical Manual.
105
JOWA CLEANTOIL 9000 Operations and Technical Manual.
106
JOWA CLEANTOIL 9000 Operations and Technical Manual.
107
JOWA CLEANTOIL 9000 Operations and Technical Manual.
108
JOWA CLEANTOIL 9000 Operations and Technical Manual.
a)
Z1
ISC 1
Z2
Z3
Z4
Z5
Z6 Cb 6
b)
Z7 ISC 2
Z8 Cb 7
c)
Z9 ISC 3
Z10 Cb 4 P
Failures
d)
Z7 ISC 2
Jm
Z8 Cb 7
e)
Z7 ISC 2
li
Z8 Cb 7
109