Please read this Installation and Operation Manual before installing and using the

product.
Keep this manual carefully for future reference.

JB-QB-GST1500H-EN
JB-QG-GST5000H-EN
JB-QT-GST5000H-EN
JB-QG-GST9000H-EN
JB-QT-GST9000H-EN
Fire Alarm Control Panel / Fire Safety
Linkage Control Panel
Installation and Operation Manual
(Issue 1.09, Jul 2020)
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Preface
JB-QB-GST1500H-EN, JB-QG-GST5000H-EN, JB-QT-GST5000H-EN, JB-QG-GST9000H-EN,
JB-QT-GST9000H-EN fire alarm control panels / fire safety linkage control panels are intelligent
control panels of the next generation integrating alarm and linkage developed by GST based on its
rich engineering experience to accommodate the emerging needs of the fire safety market in
accordance with GB4714-2005 Fire alarm control units and GB16806-2006 Automatic control system
for fire protection and with reference to the draft GB 4717-201X Fire alarm control units for approval
and EN54-2 and EN 54-4.
This family of control panels works with various types of fire detectors and control modules (of
On-Off, analogue, digital intelligent types) from GST to create integrated control units combining
alarm and linkage as well as buses and multiple wires ideal for fire safety works.
This Manual should be kept by designated personnel carefully for future reference.

Caution: The product should only be installed in the operating environment


specified in this Installation and Operation Manual, and it is not intended for use at
places with explosive or corrosive gases (including tobacco warehouses using
aluminum phosphide insecticide). The product is not suitable for use in
environments or facilities with special certification requirements for equipment
(including but not limited to explosive environments, ships, aircrafts, trains, motor
vehicles and other means of transportation). If you have special requirements,
please contact our sales representatives.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

CONTENTS
PART I OVERVIEW...............................................................................................................................1

1. OVERVIEW.....................................................................................................................................2

PART II STRUCTURE, INSTALLATION AND COMMISSIONING ..............................................5

2. DESCRIPTION OF CONTROL PANEL STRUCTURE AND CONFIGURATION................6

2.1 CONFIGURATION METHOD AND STRUCTURE OVERVIEW ...........................................................6


2.1.1 Configuration of Fire Alarm Control Panel / Fire Safety Linkage Control Panel.........6
2.1.2 Structure of JB-QB-GST1500H-EN Fire Alarm Control Panel .....................................6
2.1.3 Structural Layout of JB-QB-GST1500H-EN Control Panel Cabinet Internal Board....7
2.1.4 Structural Layout of JB-QB-GST1500H-EN Control Panel Cabinet Internal...............8
2.1.5 Structure of JB-QG-GST5000H-EN Fire Alarm Control Panel ....................................9
2.1.6 Structure of JB-QT-GST5000H-EN Fire Alarm Control Panel ...................................10
2.1.7 Structure of JB-QG-GST9000H-EN Fire Alarm Control Panel .................................. 11
2.1.8 Structure of JB-QT-GST9000H-EN Fire Alarm Control Panel ...................................12
2.1.9 Internal Structure Layouts of JB-QG/QT-GST5000/9000H-EN Control Panel ..........13
2.1.10 Keys and Panel Settings...............................................................................................15
2.1.11 Structure of Intelligent Manual Startup Panel.............................................................17
2.1.12 Structure of Direct Control Panel ................................................................................18
2.1.13 Mainboard of JB-QG/QT-GST5000/9000H-EN Control Panel...................................18
2.1.14 Internal Structural Layout of JB-QG/QT-GST5000/9000H-EN Control Panel ..........18
2.2 POWER SUPPLY OF CONTROL PANEL ........................................................................................20
2.2.1 Power Supply of JB-QB-GST1500H-EN Control Panel ..............................................20
2.2.2 Power Supply of JB-QG/QT-GST5000/9000H-EN Control Panel ..............................20
2.3 EXTERNAL WIRING TERMINALS OF CONTROL PANEL..............................................................21
2.3.1 JB-QB-GST1500H-EN Control Panel .........................................................................21
2.3.2 JB-QG/QT-GST5000/9000H-EN Control Panel .........................................................22
2.3.3 External Terminals of GST-LWK5000H-FIB Networking Interface Card ...................23
2.3.4 External Terminals of GST-DGNK5000H Multi-Interface Card .................................23
2.4 ALARM OUTPUT WIRING .........................................................................................................23

3. INSTALLATION AND COMMISSIONING ..............................................................................24

3.1 INSPECTION UPON UNPACKING ................................................................................................24


3.2 EXTERIOR DIMENSIONS AND ENVIRONMENTAL REQUIREMENTS .............................................24
3.3 INSPECTION UPON POWER-ON ..................................................................................................25
3.4 INSPECTION OF EXTERNAL EQUIPMENT ...................................................................................25
3.5 WIRING AND SETUP ..................................................................................................................26
3.6 COMMISSIONING ......................................................................................................................26

PART III SYSTEM USE .......................................................................................................................27

4. GENERAL INSTRUCTIONS TO USERS ..................................................................................28

4.1 POWER ON, POWER OFF AND SELF-TEST ..................................................................................28

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


I
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

4.2 KEYS AND INTERFACE OPERATION INSTRUCTIONS ..................................................................32


4.2.1 General Description of Data Input ..............................................................................32
4.2.2 Input of Chinese and English.......................................................................................32
4.2.3 General Description of Menu Operation .....................................................................33
4.2.4 View of Information .....................................................................................................33
4.2.4.1 Definitions ...................................................................................................................33
4.2.4.2 Operation.....................................................................................................................33
4.3 UNLOCK AND LOCK KEYBOARD ..............................................................................................34
4.3.1 Unlock Keyboard .........................................................................................................34
4.3.2 Lock Keyboard .............................................................................................................34
4.4 INFORMATION DISPLAY ............................................................................................................34
4.4.1 Description of Event Message Format ........................................................................34
4.4.2 Event Information Window Categories ........................................................................35
4.4.3 Highlighted Window and Window Switching for Event Information ...........................36
4.4.4 Selection of and Operation with Highlighted Message ...............................................37
4.4.5 Switch Full Screen and Split Screen Display ...............................................................39
4.5 INFORMATION QUERY ..............................................................................................................39
4.5.1 View of Equipment Information ...................................................................................40
4.5.1.1 Query by Circuit ..........................................................................................................40
4.5.1.2 Query by Criteria.........................................................................................................44
4.5.1.3 Query of All Equipment ...............................................................................................45
4.5.1.4 Query of Equipment Status ..........................................................................................46
4.5.2 History Query ..............................................................................................................46
4.5.3 View Linkage Formulas ...............................................................................................47
4.5.4 View Blocking Information ..........................................................................................48
4.5.5 View Start Information.................................................................................................48
4.6 PRINT INFORMATION ................................................................................................................49
4.7 SOUND ALERTS AND SILENCING OF CONTROL PANEL .............................................................49
4.8 HANDLE FIRE ALARM AND FAULT ...........................................................................................50
4.8.1 General Information on Fire Alarm Handling.............................................................50
4.8.2 General Information on Fault Handling .....................................................................50
4.9 SELF-TEST................................................................................................................................50
4.9.1 Self-test of Audible and Visual Components ................................................................51
4.9.2 Output Function Self-Test ............................................................................................51
4.10 USER SETTINGS ........................................................................................................................51
4.10.1 Date and Time Settings ................................................................................................52
4.10.2 Manual Start Settings ..................................................................................................53
4.10.3 Automatic Start Settings ..............................................................................................53
4.10.4 Gas Spraying Settings..................................................................................................54
4.10.5 Automatic Anti-Theft Setting........................................................................................55
4.10.6 Screen Saver Settings ...................................................................................................56
4.11 PRINT SETTINGS .......................................................................................................................56
4.12 BLOCKING AND UNBLOCKING OF EQUIPMENT .........................................................................57
4.12.1 Block Equipment by Equipment Address .....................................................................57

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


II
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

4.12.2 Block Equipment by User-Defined Address .................................................................58


4.12.3 Block a Circuit .............................................................................................................59
4.13 MANUAL STARTING AND STOPPING OF LINKAGE EQUIPMENT .................................................60
4.13.1 Conditions for Manual Starting of Linkage Equipment...............................................60
4.13.2 Start / Stop Controlled Equipment with Keyboard of Control Panel ...........................61
4.13.3 Start / Stop Controlled Equipment Manually with Manual Panel ...............................63
4.13.4 Start / Stop Controlled Equipment Manually with Direct Control Panel ....................63
4.14 AUTOMATIC CONTROL OF LINKAGE EQUIPMENT .....................................................................63
4.14.1 Preconditions for Automatic Linkage ..........................................................................63
4.14.2 Realization of Automatic Linkage Logic ......................................................................63
4.14.3 Cancellation of Delayed Starting and Direct Start Control ........................................63
4.15 START AND STOP GAS FIRE EXTINGUISHING EQUIPMENT ........................................................64
4.15.1 Preconditions for Starting Gas Fire Extinguishing Equipment ...................................64
4.15.2 Manual Starting of Gas Fire Extinguishing Equipment ..............................................65
4.15.3 Automatic Linkage Control of Gas Fire Extinguishing Equipment .............................66
4.15.4 Emergency Stopping of Gas Fire Extinguishing Equipment ........................................67
4.16 RESET .......................................................................................................................................67
4.17 DESCRIPTION OF NETWORKING INFORMATION DISPLAY..........................................................67

5. OPERATING GUIDE FOR SYSTEM ADMINISTRATORS ...................................................68

5.1 DEVICE REGISTRATION ............................................................................................................69


5.1.1 Add Equipment Manually ............................................................................................69
5.2 EQUIPMENT DEFINITION ..........................................................................................................70
5.2.1 Content of Equipment Definition .................................................................................70
5.2.2 Device Definition Procedure .......................................................................................71
5.3 LINKAGE FORMULAS ...............................................................................................................78
5.3.1 Format of Linkage Formulas .......................................................................................78
5.3.2 Edit Linkage Formula..................................................................................................80
5.4 NETWORK SETTINGS ................................................................................................................83
5.4.1 Local Address Setting ..................................................................................................83
5.4.2 Communication Card Settings .....................................................................................84
5.4.3 IP Address Settings ......................................................................................................85
5.4.4 Clearing Faulty Slave ..................................................................................................85
5.4.5 Secondary Address Compatibility ................................................................................86
5.5 OPERATION MODE ....................................................................................................................87
5.5.1 Commissioning Mode Settings.....................................................................................87
5.5.2 Broadcast Synchronization Settings.............................................................................88
5.5.3 Early Warning Setting..................................................................................................89
5.5.4 Fire Alarm Output Settings ..........................................................................................91
5.5.5 Grounding Detection Settings......................................................................................92
5.5.6 Silence Settings of Display Panel ................................................................................92
5.5.7 Silence Settings of Control Panel ................................................................................93
5.5.8 Audible and Visual Alarm Feedback............................................................................94
5.6 PASSWORD SETTINGS ...............................................................................................................95

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


III
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

5.6.1 Types of Passwords ......................................................................................................95


5.6.2 Chang Password ..........................................................................................................95

6. DESCRIPTION OF SYSTEM COMMISSIONING FUNCTIONS..........................................97

6.1 FIXED POINT COMMISSIONING .................................................................................................97


6.2 DIGITAL EQUIPMENT COMMISSIONING ....................................................................................98
6.3 MODIFY EQUIPMENT ADDRESS ................................................................................................99
6.4 DUPLICATE ADDRESS DETECTION IN ALL CIRCUITS ..............................................................100
6.5 DETECTOR POLLUTION COMPENSATION ................................................................................101
6.6 DETECTOR CLEANING AND CORRECTION ..............................................................................101
6.7 PROGRAM UPGRADE ..............................................................................................................102

PARTY IV CONFIGURATION AND CONNECTION OF DIRECT CONTROL PANELS .......103

7. CONFIGURATION AND CONNECTION OF DIRECT CONTROL PANELS...................103

7.1 GENERAL ...............................................................................................................................103


7.2 FEATURES ...............................................................................................................................104
7.3 STRUCTURE CHARACTERISTICS .............................................................................................104
7.3.1 Panel Console ............................................................................................................104
7.3.2 Interior Structure .......................................................................................................104
7.4 WIRING AND APPLICATION .....................................................................................................105
7.5 USE AND OPERATION..............................................................................................................105
7.5.1 Panel Number Setting ................................................................................................105
7.5.2 Turn On......................................................................................................................106
7.5.3 Self-Test......................................................................................................................106
7.5.4 Direct Control Panel Definition ................................................................................106
7.5.5 Manual Control .........................................................................................................107
7.5.6 Automatic Control......................................................................................................107

PART V SPECIAL INSTRUCTIONS................................................................................................108

8. HANDLING OF FAULT AND ABNORMAL INFORMATION AND REGULAR


INSPECTION ......................................................................................................................................109

8.1 GENERAL TROUBLESHOOTING ...............................................................................................109


8.2 PRINTER MAINTENANCE ........................................................................................................109
8.2.1 Replace Printing Paper .............................................................................................109
8.2.2 Self-Test...................................................................................................................... 110
8.2.3 Operation Status ........................................................................................................ 110
8.3 BATTERY MAINTENANCE ....................................................................................................... 110

9. SCRAPPING................................................................................................................................ 110

10. PRECAUTIONS ...................................................................................................................... 110

APPENDIX I TECHNICAL INDICATORS ..................................................................................... 112

APPENDIX II EQUIPMENT TYPE TABLE ................................................................................... 115

APPENDIX III COMMISSIONING FORM .................................................................................... 117

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


IV
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

APPENDIX IV QUICK START GUIDE ........................................................................................... 118

............................................................................................................................................................... 118

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


V
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Part I Overview

 JB-QB-GST1500H-EN

JB-QG/QT-GST5000/9000H-EN

Fire Alarm Control Panel / Fire Safety Linkage Control


Panel Overview

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


1
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

1. Overview

JB-QB-GST1500H-EN and JB-QG/QT-GST5000/9000H-EN fire alarm control panels / fire


linkage control panels (hereinafter referred to as "control panels") are control panels of the new
generation developed GST. To accommodate the needs of engineering design, the control panels
combine linkage and control functions and work with other products of GST to create integrated
linkage and control systems with flexible options. They are suitable for local fire alarm systems in
independent buildings. With powerful networking capability, multiple control panels can be
networked as a distributed fire alarm system.

1.1 High Capacity per Unit, High Reliability and High Output Performance

The control panels meet the design requirements of local fire alarm systems in large independent
buildings. For both linkage and alarm bus equipment, the control panels are equipped with backup
without power failure to ensure that all registered equipment is monitored when the system
commissioning is completed. The control panels have high bus output performance and fully support
two-wire bus equipment. The specific number points are shown in Table 1-1
Table 1-1
Model Structure Max number of circuits Number of alarm points
JB-QB-GST1500H-EN Wall Mount 6 1452
JB-QG-GST5000H-EN Rack Type 20 4840
JB-QT-GST5000H-EN Console Type 20 4840
JB-QG-GST9000H-EN Rack Type 60 14520
JB-QT-GST9000H-EN Console Type 60 14520

1.2 Graphical Color Display Interface and Ease of Operation

The control panel features a graphical color display interface. Different information is displayed
in different windows in different colors. The interface is tidy, easy to use and understand, and intuitive.
The functions provided by the system can be accessed through simple operations (with the number
keys or direction keys of the keypad). In addition, shortcuts are available and greatly improve the
efficiency of users.
① The check lock allows users or inspectors to quickly check the equipment comprising the
system.
② The manual/automatic switch lock and the linkage start button are used to switch the control
status and enter the linkage status quickly in the case of emergency.
③ Touch screen operation (an option available for GST9000H only) allows users to view
information quickly.

1.3 Flexible Modular Structure and Various Functionality Configuration Options

The main control part of the control panel is composed of various functional modules with a
common interface, and can be easily and flexibly configured. Bus equipment can be configured from
1 point to 14520 points by adjusting the number of connected circuit cards. If a network interface card
or other interface card is connected, the system can also be networked with other fire safety
equipment via different ports.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


2
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

GST5000H Control Panel Management Board: This card provides a RS485 communication
interface is used for connection with broadcast and telephone equipment.
GST-NNET-02H Interface Card: This card has RS422 communication interface, which is used to
connect the control panel with graphic display devices or fire alarm transmission devices.
CAN Networking Interface Card: This card has CAN communication interface, which is used for
communication connection between multiple control panels or other devices from GST with CAN
communication capability at the site.
FIB Network Interface Card: This card has optical fiber communication interface, which is used
for communication connection between multiple control panels of this series.
GST-DGNK5000H Multi-Interface Card: This card has three communication interfaces: RS485,
CAN and TCP/IP. The RS485 interface is a standard MODBUS interface, which is used for
connection with third-party equipment; the CAN interface is used for communication connection
between multiple control panels or other devices from GST with CAN communication capability at
the site; the TCP/IP interface is used for communication connection between multiple control panels
of this series.

1.4 Intelligent Manual Startup Panel

The control panel is equipped with an intelligent manual startup panel. Each start/stop key on the
board can be associated with any bus device connected to the system for starting/stopping control the
bus linkage device.

1.5 Direct Control Panel

The control panel is equipped with a direct control panel, which can directly control the key
equipment such as fire pumps, smoke exhaust fans and forced draft fans. The control pad is capable of
detecting output disconnection and short circuit fault for maximizing the reliability of the connection
between the control pad and the terminal equipment. The direct control panel allows control of
start/stop dual control equipment via two wires.

1.6 Modular Switching Power Supply

The modular switching power supply can work within a wide range of voltage with high energy
efficiency. The elaborate charging circuit and reliable multi-level protection extend the service life of
the battery.

1.7 Easy and Fast Commissioning

To facilitate the use by users and staff, some commissioning shortcuts are added in the control to
quickly identify the control equipment status and find problems.
① The equipment status query screen displays the equipment status of the whole circuit, and
the status of alarm, fault and blocking is visible at a glance.
② It can quickly print the pollution conditions of the detectors in the whole circuit, which is
useful in equipment maintenance.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


3
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

③ It supports online upload and download of definitions. One can also upload and download
data, conduct remote commissioning (with support for cloud data upload and download) and
fault diagnosis with a mobile APP via Bluetooth communication.
④ After the detection of identical addresses, the indicators of equipment with identical
addresses flash for easy identification.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


4
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Part II Structure, Installation and


Commissioning

 Description of Control Panel Structure and Configuration

 Installation and Commissioning

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


5
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

2. Description of Control Panel Structure and Configuration

2.1 Configuration Method and Structure Overview


2.1.1 Configuration of Fire Alarm Control Panel / Fire Safety Linkage Control Panel
The configuration of the fire alarm control panels / fire linkage control panels are as follows:
Table 2-1
Configuration GST1500H-EN GST5000H-EN GST9000H-EN
Manual startup panel 1 ≤12 ≤12
Direct control panel 1 ≤24 ≤24
Dual-circuit card ≤3 ≤10 ≤30
Single-circuit card ○ ○ ○
GST-NNET-02H ○ ○ ○
Mainboard plug board

Networking Interface Card


GST-LWK5000H-CAN ○ ○ ○
Networking Interface Card
GST-LWK5000H-FIB ○ ○ ○
Networking Interface Card
GST-DGNK5000H ○ ○ ○
Multi-Interface Card
Max number of slots 5 16 36
(number of cards no more
than number of slots)
GST1500H -EN 1 — —
AC-DC power supply
Linkage power

GST5000H AC-DC power — 1 ≤3


supply

supply
GST-LD-D02H intelligent — ≤2 ≤2
power supply panel
GST-LD-D06H intelligent — ≤2 ≤2
power supply panel
Note: ○ indicates an optional item; - indicates an item not available.
2.1.2 Structure of JB-QB-GST1500H-EN Fire Alarm Control Panel
The appearance of the control panel is shown in Fig. 2-1.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


6
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Main Power Self -Check Fir e Star t


Soun der
Fault
Batt ery Star t D isa
bl e
Dr il
Extimn
Per gituishing Ext
R ingui
equesst hing
Dri l
Star t Delay
Ext
ari tn
St guishing Ext
R in
eleguishant
ased

Feed
back Manual

Pr i nte r Supervisory Auto

Disable Reset

+ 1 ×abc2 =def 3 _ SystemFault Mut e


*
Self -Check Br o
wse User Se
t up
? Fault
ghi 4 jkl 5 mno 6 0
Star t Disable SystemSet up

pqrs 7 tuv 8 wxyz9 & Conf ir m Canc el Mut e Check


Stop Enable Pr inter Setup

Star t-bFace kd Star t -bFeace kd Star t -bFeace kd Star tFe


-b ace kd Star t-bFace kd Star tFe
-b ace kd Star t -bFeace kd Star t -bFeace kd

Dis ab le Enab le
Sta rt Sta rt Sta rt Sta rt Sta rt Sta rt Sta rt Sta rt Sta rt Sta rt Sta rt Sta rt Sta rt Sta rt Sta rt Sta rt
Fee dbac k Fee dbac k Fee dbac k Fee dbac k Fee dbac k Fee dbac k Fee dbac k Fee dbac k
Sto p Sto p Sto p Sto p Sto p Sto p Sto p Sto p
Manu alContro l Fau lt Fau lt Fau lt Fau lt Fau lt Fau lt Fau lt Fau lt

Fig. 2-1

① LCD display

② Printer

③ Operation panel

④ Intelligent manual startup panel

⑤ Direct control panel

2.1.3 Structural Layout of JB-QB-GST1500H-EN Control Panel Cabinet Internal Board


The circuit layout of the internal board inside the cabinet is shown in Fig. 2-2.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


7
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

1
2

Fig. 2-2
① Lamp board
② Main board
③ Operation panel
④ Manual startup panel
⑤ Direct control panel
2.1.4 Structural Layout of JB-QB-GST1500H-EN Control Panel Cabinet Internal
The circuit layout of board inside the cabinet is shown in Fig. 2-3.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


8
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel
1

2
6

Fig. 2-3
① Cabinet sealing plate: Cover plate for internal wiring ports. Remove the sealing plate first before
change the internal wiring.
② Management card: This card should be placed in the first card slot and cannot be interchanged
with other cards.
③ Mainboard: Provides 10P broadcast/telephone ports, DC24V output terminals, sound and light
alarm output terminals.
Circuit cards and communication cards (GST-NNET-02H Networking Interface Card,
GST-LWK5000H-CAN Networking Interface Card, GST-LWK5000H-FIB Networking Interface
Card, and GST-DGNK5000H Multi-Interface Card) may be inserted the slots in any order.
④ Direct control panel output board: Each direct control panel corresponds to an output board, and
each output board has 8 channels of output.
⑤ AC-DC power supply.
⑥ Battery: 2 cells, 14Ah.
2.1.5 Structure of JB-QG-GST5000H-EN Fire Alarm Control Panel
The appearance of the control panel is shown in Fig. 2-4.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


9
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Main Power Self-Check Fir e Start


Sounder
Fa ult
Battery Start Disable
Drill

Extin guishing Extin guishing


Permit Request
Drill
Start Delay
Extin guishing Extin guishant
Start Released

Fe edback Man ual

Printe r Supervisor y Auto

Disable Re set

Syst em Fa ult
+ 1 ×ab c2 = de f3 _
M ute
*
Self-Check Browse User Setup

Fa ult
gh i 4 jkl 5 mn o 6 0
Start Disable Syst em Setup

pq rs 7 tuv 8 wxyz 9 & Confirm Cancel Mute Check


Stop Enable Printer Setu p

Start Fe ed Start Fe ed Start Fe ed Start Fe ed Start Fe ed Start Fe ed Start Fe ed Start Fe ed


-back -back -back -back -back -back -back -back

Start Fe ed Start Fe ed Start Fe ed Start Fe ed Start Fe ed Start Fe ed Start Fe ed Start Fe ed


-back -back -back -back -back -back -back -back

Disable Enable

Start Start Start Start Start Start Start Start


Start Start Start Start Start Start Start Start

Feedback Feedback Feedback Feedback Feedback Feedback Feedback Feedback


Stop Stop Stop Stop Stop Stop Stop Stop
Manual C ontrol Fault Fault Fault Fault Fault Fault Fault Fault

Disable Enable

Start Start
Start Start
Start Start
Start Start
Start Start
Start Start
Start Start
Start Start

Feedback Feedback Feedback Feedback Feedback Feedback Feedback Feedback


Stop Stop Stop Stop Stop Stop Stop Stop
Fault Fault Fault Fault Fault Fault Fault Fault
Manual C ontrol

GST-LD-D02H Intelligent Power Supply

Fig. 2-4
2.1.6 Structure of JB-QT-GST5000H-EN Fire Alarm Control Panel
The appearance of the control panel is shown in Fig. 2-5.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


10
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Sta r t Feed Sta r t Feed Sta r t Feed Sta r t Feed Sta r t Feed Sta r t Feed Sta r t Feed Sta r t Feed
-b ack -b ack -b ack -b ack -b ack -b ack -b ack -b ack

M ai n P ow er S el f- C hec k Fi r e S ta rt
Sou nder
Fa ul t
B at te ry S ta rt Di sa ble
D r il l

E xt ing ui shi ng E xt ing ui shi ng


P er m it R equ est
Dr i l

E xt ing ui shi ng E xt ing ui sha nt S ta rt D ela y

S ta rt R el eas ed

Fe ed back M an ual

Printer S upe rv iso r y A ut o

D is abl e Reset
Di sabl e Ena ble

St ar t St art St ar t St art St ar t St art St ar t St art St ar t St art St ar t St art St ar t St art St ar t St art


S yst em Fa ul t
_
+ 1 ×abc2 = def 3
* Mute Feed back Feed back Feed back Feed back Feed back Feed back Feed back Feed back
St op St op St op St op St op St op St op St op
S el f- C hec k B ro w se U ser Se tu p
Faul t Faul t Faul t Faul t Faul t Faul t Faul t Faul t
? M anual C ontr ol

ghi 4
jkl 5
mno6 0
Fa ul t

S ta rt D is abl e S yst em Se tu p Di sabl e Ena ble

pqrs 7 tuv 8 wxyz 9 & Confir m Cancel M ut e C hec k St ar t


St art
St ar t
St art
St ar t
St art
St ar t
St art
St ar t
St art
St ar t
St art
St ar t
St art
St ar t
St art
S to p E nab le P ri nt er Se tu p Feed back Feed back Feed back Feed back Feed back Feed back Feed back Feed back

St op St op St op St op St op St op St op St op
Faul t Faul t Faul t Faul t Faul t Faul t Faul t Faul t
M anual C ontr ol

Sta r t Feed Sta r t Feed Sta r t Feed Sta r t Feed Sta r t Feed Sta r tFeed Sta r t Feed Sta r t Feed
-b ack -b ack -b ack -b ack -b ack -b ack -b ack -b ack

GST-LD-D02H Inte lligent Powe r S upply

Fig. 2-5
2.1.7 Structure of JB-QG-GST9000H-EN Fire Alarm Control Panel
The appearance of the control panel is shown in Fig. 2-6.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


11
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fi re Start
Sou nder
Fa ult
Disabl e
Dri l

Dr i l
Start
Delay

Fee d Manua l
-back

Su per
-vi se Au to

Disabl e Reset

Sys tem
Fa ult
Mute

Fau lt

Mute Ch ec k

Prin ter

Main Powe r Se lf -t est _


+ 1 ×abc2 = def 3
*
Se lf -t est Browse User Set
Ba t ery Start ?
ghi 4 jkl 5 mno 6 0

Exti ngui shin g Exti ngui shin g Start Disabl e Sys Set
Pe rmi t Request
pqrs 7 tuv 8 wxyz 9 & Confir m Cancel
Exti ngui shin g Ext in g uis hant
Start Relea sed Stop En able Pri nt

Sta r t Feed Sta r t Feed Sta r t Feed Sta r t Feed Sta r t Feed Sta r t Feed Sta r t Feed Sta r t Feed
-b ack -b ack -b ack -b ack -b ack -b ack -b ack -b ack

Sta r t Feed Sta r t Feed Sta r t Feed Sta r t Feed Sta r t Feed Sta r t Feed Sta r t Feed Sta r t Feed
-b ack -b ack -b ack -b ack -b ack -b ack -b ack -b ack

Di sabl e Ena ble

St ar t St art St ar t St art St ar t St art St ar t St art St ar t St art St ar t St art St ar t St art St ar t St art

Feed back Feed back Feed back Feed back Feed back Feed back Feed back Feed back
St op St op St op St op St op St op St op St op
Faul t Faul t Faul t Faul t Faul t Faul t Faul t Faul t
M anual C ontr ol

Di sabl e Ena ble

St ar t St ar t St ar t St ar t St ar t St ar t St ar t St ar t
St art St art St art St art St art St art St art St art

Feed back Feed back Feed back Feed back Feed back Feed back Feed back Feed back
St op St op St op St op St op St op St op St op
Faul t Faul t Faul t Faul t Faul t Faul t Faul t Faul t
M anual C ontr ol

GST-LD-D02H Inte lligent Powe r S upply

Fig. 2-6
2.1.8 Structure of JB-QT-GST9000H-EN Fire Alarm Control Panel
The appearance of the control panel (excluding table panel) is shown in Fig. 2-7.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


12
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Sta r t-b ack


Fee
d Sta r t Fee d
-b ack Sta r t Fee d
-b ack Sta r t Fee d
-b ack Sta r t Fee d
-b ack Sta r t Fee d
-b ack Sta r t Fee d
-b ack Sta r t Fee d
-b ack

Fi re Start
Sou nder
Fa ult
Disabl e
Dri l

Start Dr i l
Delay

Fee d Manua l
-back

Su per
-vi se Au to

Disabl e Reset

Sys tem
Fa ult
Mute

Fau lt
Di sabl e Ena ble

St ar t St ar t St ar t St ar t St ar t St ar t St ar t St ar t
Mute Ch ec k St art St art St art St art St art St art St art St art
Feed back Feed back Feed back Feed back Feed back Feed back Feed back Feed back

St op St op St op St op St op St op St op St op
M anual C ontr ol Faul t Faul t Faul t Faul t Faul t Faul t Faul t Faul t

Di sabl e Ena ble

Prin ter
St ar t St ar t St ar t St ar t St ar t St ar t St ar t St ar t
St art St art St art St art St art St art St art St art

Feed back Feed back Feed back Feed back Feed back Feed back Feed back Feed back

Main Powe r Se lf -t est _ Faul t


St op
Faul t
St op
Faul t
St op
Faul t
St op
Faul t
St op
Faul t
St op
Faul t
St op
Faul t
St op
+ 1 ×abc 2 = def 3 M anual C ontr ol
*
Se lf -t est Browse User Set
Ba t ery Start ?
ghi 4 jkl 5 mno 6 0

Exti ngui shin g Exti ngui shin g Start Disabl e Sys Set
Pe rmi t Request
pqrs 7 tuv 8 wxyz 9 & Confir m Cancel
Exti ngui shin g Ext in g uis hant
Start Relea sed Stop En able Pri nt

GST-LD-D02H Inte lligent Powe r S upply

Fig. 2-7
2.1.9 Internal Structure Layouts of JB-QG/QT-GST5000/9000H-EN Control Panel
The circuit layout of board inside the cabinet is shown in Fig. 2-8.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


13
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

6 关
备电

备电保险
30A
保险熔断

30
电池
+ -
输出3
+ -
输出2
+ -
输出1
+ -
状态信号

主电

主电

高压危险

Fig. 2-8
① Management card: This card should be placed in the first card slot and cannot be interchanged
with other cards.
Circuit cards and communication cards (GST-NNET-02H Networking Interface Card,
GST-LWK5000H-CAN Networking Interface Card, GST-LWK5000H-FIB Networking Interface
Card, and GST-DGNK5000H Multi-Interface Card) may be inserted the slots in any order. Other
cards can be interchanged with each other except the one in the first slot.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


14
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

② Cabinet sealing plate: Mount the sealing plate when a slot is used.
③ Direct control panel output board: Each direct control panel corresponds to an output board, and
each output board has 8 channels of output.
④ AC-DC power module
⑤ Air break switch
⑥ External output terminals
⑦ Adapter plate
⑧ Battery
2.1.10 Keys and Panel Settings
The main control panel includes the LCD display, indicators, keyboard and printer (as shown in
Fig. 2-9).

Fig. 2-9
Indicators:
⚫ Main Power: Green; this indicator is lit when the control panel is powered by AC220V
power supply.
⚫ Battery: Green; this indicator is lit when the control panel is powered by the backup power
supply.
⚫ Self-Check: Yellow; this indicator is lit when the equipment of the system is in self-test
status.
⚫ Start: Red; this indicator stays lit after the control panel sends a start command; it flashes if
when the control panel receive no feedback signal within 10 seconds as required after sending
the start command; it goes out after the control panel is reset.
⚫ Extinguishing Start: Red; when this indicator is lit, it indicates that the control panel has
sent a start command to the gas fire extinguishing equipment.
⚫ Extinguishing Request: Red; this indicator stays lit when there is gas fire extinguishing
equipment in the system in the delayed start status; it goes out after the control panel sends a
start command to the gas fire extinguishing equipment.
⚫ Extinguishing Permit Green; when this indicator is lit, it indicates that the control panel
allows spraying; the gas fire extinguishing equipment may be manually started or automatically

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


15
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

started by means of linkage; when this indicator goes out, it indicates that the control panel does
not allow spraying, and the gas fire extinguishing equipment cannot be started manually or
automatically.
⚫ Extinguishant Released: Red; when this indicator is lit, it indicates that the control panel
receives the feedback signal from the gas fire extinguishing equipment.
⚫ Fire: Red; when this indicator is lit, it indicates that the control panel has detected that an
external detector or manual call point is in fire alarm status. See the LCD for details of the alarm.
This indicator goes out after the fire alarm is handled and the control panel is reset.
⚫ Drill: Red; when this indicator is lit, it indicates that the control panel is in the linkage
status.
⚫ Start delay: Red; when this indicator is lit, it indicates that there is equipment to be delay
started in the system; this indicator goes out after the delay time is over or the control panel is
reset.
⚫ Feedback: Red; when this indicator is lit, it indicates that the control panel receives
feedback information from the external equipment; this indicator goes out after all feedback is
recovered or the control panel is reset.
⚫ Supervisory: Red; when this indicator is lit, it indicates that the control panel has detected
supervision signals of external equipment and the system is in the supervision status. This
indicator goes out after the control panel is reset.
⚫ Disable: Yellow; when external equipment (such as detectors, modules or fire display
panels and local alarms) fails, it can be disabled. After the repair or replacement, the equipment
can be restored by canceling blocking. This indicator is lit when there is any blocked equipment.
⚫ System fault: Yellow; this indicator is lit when the system memory fails or a system
program doesn’t work properly to remind the user the necessity for repairing the control panel
immediately.
⚫ Fault: Yellow, when this indicator is lit, it indicates that the control panel has detected the
fault of external equipment (such as detectors, modules or fire display panel), or of the control
panel itself; it goes out after all the faults have been solved or the control panel is reset.
⚫ Silence: Green; when this indicator is lit, it indicates that the control panel is in the silent
status; it goes off when there is any new fault or fire alarm and the control panel may send out
sound.
⚫ start: Red; this indicator is lit when the control panel sends out the signal for starting sound 批注 [CW1]: Start
and light alarm; it stays lit after the control panel receives feedback from the alarms, or it goes
out.
⚫ Fault/Disable: Yellow; this indicator flashes when there is an audible / visual alarm in the
system fails. This indicator stays lit when an audible / visual alarm in the system is in the
disabled status.
⚫ Manual /Auto: Green; when this indicator stays lit at the manual position, it indicates that
the system is in the status of disabled automatic operation; when this indicator stays lit at the
automatic position, it indicates that the system is in the status of allowed automatic operation;
⚫ Check: Green; when this indicator is lit, it indicates that the control panel is in the check
status. At the same time, the interface displays the information of the control panel.
Key Description:
By function, the keys of the control panel are grouped as information inquiry keys, special

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


16
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

function keys, setting function keys, character keys and operation keys.
⚫ Browse keys: They are used view the information of system equipment and history records
on the control panel.
⚫ Special function keys: These keys are used execute commands and change the system status
when the operating the control panel, including: "Reset", "Silence", "Alarm", "Drill",
"Self-Check", "Start" and "Stop", "Disable" and "Enable".
Drill: This key quickly changes the control panel status to all automatic status.
Check Lock: When the lock position is turned to the check position with a key, it is possible
to see the number of devices in normal status, the number of devices in faulty status, the
number of devices being blocked among the devices registered with the control panel by
equipment type.
Manual / Auto Switch Lock: When the lock position is turned to the manual position with a
key, the manual indicator is lit, and the system is in the status of disabled automatic
operation; when the lock position is turned to the automatic position, the automatic indicator
is lit, and the system is in the status of allowed automatic operation.
⚫ Setting keys: These keys are used to set the parameters of the control panel, conduct
commissioning and change the control panel settings, including "User settings", "System
settings" and "Print settings".
⚫ Character keys: These keys include the number or character keys (as well as various
combination keys) used to input data, including: "Space", number keys (0 ~ 9), "*", "&",
"+", "×", and "=", and the number keys are also the shortcut keys for quick access to the
menu items during menu operation.
⚫ Operation keys: These keys are used in various operations, including: , , or ,
, "OK" and "Cancel".

2.1.11 Structure of Intelligent Manual Startup Panel


The appearance of the intelligent manual fire control panel of the control panel (hereinafter
referred to as the "manual panel") is shown in Fig. 2-10: Each manual panel has 128 units, and each
unit has a button, two indicators and a label. Among them, the key is for start / stop control. If the
control key of a unit is pressed, the start indicator of the unit is lit (red) and a control command is sent.
If the controlled device responds, the feedback indicator is lit (red). The user may write the device
name corresponding to each key on the device label, and then fix it on the manual panel together with
the film.

启动 反馈 启动 反馈 启动 反馈 启动 反馈 启动 反馈 启动 反馈 启动 反馈 启动 反馈

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


17
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 2-10
Each manual panel has a unique number. That is, no two manual panels share the same address in
one control panel. Fig. 2-11 shows the setting of manual panel numbers.
The number of a manual panel has six binary bits and is represented with the X1 pins on each
manual panel in an ascending order.
1号盘
Panel 1 2号盘
Panel 2 3号盘
Panel 3 Panel
4号盘 4
1 1 1 1
2 2 2 2
3 3 3 3
4 4 4 4
5 5 5 5
6 6 6 6

Panel
5号盘 5 Panel 6
6号盘 Panel 7
7号盘 Panel 8
8号盘
1 1 1 1
2 2 2 2
3 3 3 3
4 4 4 4
5 5 5 5
6 6 6 6
... and so on
Fig. 2-11
2.1.12 Structure of Direct Control Panel
The structure of a direct control panel is shown in Fig. 2-12. Each direct control panel has two
keys, three indicators and a label marking the location of the device to be started.

Fig. 2-12
See Part V "Configuration and Connection of Direct Control Panels" for details on direct control
panels.
2.1.13 Mainboard of JB-QG/QT-GST5000/9000H-EN Control Panel
The JB-QG/QT-GST5000/9000H-EN control panel numbers the mainboard with pair pins M0
and M1, as shown in Fig. 2-13:

M0 M1 M0 M1 M0 M1 M0 M1

No. 1
1号 No. 2
2号 No.
3号3 No.
4号4
Fig. 2-13
2.1.14 Internal Structural Layout of JB-QG/QT-GST5000/9000H-EN Control Panel
The circuit layout of board inside the cabinet is shown in Fig. 2-14.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


18
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

6 关
备电

备电保险
30A
保险熔断

30
电池
+ -
输出3
+ -
输出2
+ -
输出1
+ -
状态信号

主电

主电

高压危险

Fig. 2-14
① Management card: This card should be placed in the first card slot and cannot be interchanged
with other cards.
② Circuit cards and communication cards (GST-NNET-02H Networking Interface Card,
GST-LWK5000H-CAN Networking Interface Card, GST-LWK5000H-FIB Networking Interface
Card, and GST-DGNK5000H Multi-Interface Card) may be inserted the slots in any order. Other
cards can be interchanged with each other except the one in the first slot.
③ Cabinet sealing plate: Mount the sealing plate when a slot is used.
④ Direct control panel output board: Each direct control panel corresponds to an output board, and
each output board has 8 channels of output.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


19
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

⑤ AC-DC power module


⑥ Air break switch
⑦ Adapter plate
⑧ Adapter plate
⑨ Battery

2.2 Power Supply of Control Panel


2.2.1 Power Supply of JB-QB-GST1500H-EN Control Panel
The power supply system of the control panel consists of the primary power supply and backup
power supply, including the main unit power supply and a battery. The terminals of the main unit
power supply are shown in Fig. 2-15.
The GST1500H-EN AC-DC power supply has a power conversion circuit that converts 220VAC
into two channels of output, one of which supplies power to the load and the other charges the backup
power supply. When AC power is down or the power supply fails, the backup power supply supplies
power for the load, and the total output power is greater than or equal to 195W.
The voltage of the primary power supply and backup power supply is as follows:
Primary power supply: AC 220V, voltage range -15% ~ +10%
Backup power supply: 12V14Ah VRLA battery (2 cells)

Output
指控盘输出板board Control
指控盘输出板 board Signal
状态信号status

of direct of direct

control panel control panel

AC220V

- +
Battery 1 Battery 2
蓄电池2
蓄电池1

+ -

Fig. 2-15
2.2.2 Power Supply of JB-QG/QT-GST5000/9000H-EN Control Panel
The power supply system of the control panel consists of the main unit power supply and the
linkage power supply. Each kind of power supply has two parts: the primary power input and the
backup power input. The system is composed of the main unit power supply, GST-LD-D02H
intelligent power supply panel, GST-LD-D06H intelligent power supply panel and a battery.
The main unit power GST5000H AC-DC power supply has a power conversion circuit that
converts 220VAC into four channels of output, three of which supplies power to the load and the other

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


20
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

charges the backup power supply with a total output power of more than 650W. When the primary
power supply is down or encounters over-voltage or under voltage fault, the backup power supply
supplies power to the load.
The GST-LD-D02H intelligent power supply panel has a power conversion circuit that converts
220 VAC into three channels of output, two of which is supplied to the load, and one charges the
backup power supply, including one channel of 24V/8A output. When the primary power supply is
down or encounters over-voltage or under voltage fault, the backup power supply supplies power to
the load.
The GST-LD-D06H intelligent power supply panel has a power conversion circuit that converts
220 VAC into four channels of output, three of which is supplied to the load, and one charges the
backup power supply, including three channels of 24V/8A output. When the primary power supply is
down or encounters over-voltage or under voltage fault, the backup power supply supplies power to
the load.
The display operation panel of the power panel is shown in Fig. 2-16. The output voltage display,
output current dis, battery level dis, power supply status indicator and keys are described below:
1) Output voltage display: The output voltage is shown with a LED display in red.
2) Output current display: The sum of the output current is shown with a LED display in red.
3) Power supply status indicator: The working status of power supply is shown with a LED
display.
4) Silence: In the case of fault alarm, press the "Silence" key to stop the sound signal; when there
is a new fault, it will sound again. This key has no response under normal working conditions.
5) Self-Test: press the "Self-Test" key, the LED displays and the indicator stay lit.

Fig. 2-16

2.3 External Wiring Terminals of Control Panel


2.3.1 JB-QB-GST1500H-EN Control Panel
The external wiring terminals of the control panel are shown in Fig. 2-17.
Power Supply:
L N PE

C19+ C19- C18+ C18- C17+ C17- C16+ C16- C15+ C15- C14+ C14- C13+ C13- C12+ C12- C11+ C11- C10+ C10- C9+ C9- C8+ C8- C7+ C7- C6+ C6-

Mainboard:
Z6 Z5 Z4 Z3 Z2 Z1
C5+ C5- C4+ C4- C3+ C3- C2+ C2- C1+ C1- S+ S- FO1 FO2 24V+ 24V- A5 B5 A4 B4 A3 B3 A2 B2 A1 B1 1 2 1 2 1 2 1 2 1 2 1 2

+ - + - RS485 + - + - + - + - + - + - + - + - + - + -
24V Sounder L1 L2 L3 L4 L5 L6 L7 L8 L9 L10

Output board of direct control panel:

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


21
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

C1+ C1- C2+ C2- C3+ C3- C4+ C4- C5+ C5- C6+ C6- C7+ C7- C8+ C8-

Fig. 2-17
Terminals:

L, N, PE: AC 220V terminals and case protection grounding terminal;


Ln (n=1~10): Detector bus (without polarity); also for connection with
CAN networking H, L: Communication bus terminals for connection with other control panels
(optional);
Communication card R+, R-, T+, T-: Terminals for connection with CRT image display equipment
(optional);
Optical fiber networking: Communication bus terminals for connection with other control panels
(optional);
Multi-interface card: Communication bus terminals for connection with other control panels
(optional)
24V+, 24V-: 24V/0.5A auxiliary power output terminals;
Sounder+, Sounder-: Alarm bell output terminals, 24V/0.15A active output;
RS485: Broadcasting / telephone port;
Cn+, Cn- (n=1~8): Direct control output terminals.
2.3.2 JB-QG/QT-GST5000/9000H-EN Control Panel
The external wiring terminals of the control panel are shown in Fig. 2-18.
Air break switch:
L N PE

C19+ C19- C18+ C18- C17+ C17- C16+ C16- C15+ C15- C14+ C14- C13+ C13- C12+ C12- C11+ C11- C10+ C10- C9+ C9- C8+ C8- C7+ C7- C6+ C6-

Mainboard:
Z6 Z5 Z4 Z3 Z2 Z1
C5+ C5- C4+ C4- C3+ C3- C2+ C2- C1+ C1- S+ S- FO1 FO2 24V+ 24V- A5 B5 A4 B4 A3 B3 A2 B2 A1 B1 1 2 1 2 1 2 1 2 1 2 1 2
RS485 L1+ L1- L2+ L2- L3+ L3- L4+ L4- L5+ L5- L6+ L6- L7+ L7- L8+ L8- L9+ L9- L10+ L10- L11+ L11- L12+ L12- L13+ L13- L14+ L14- L15+ L15- L16+ L16- L17+ L17- L18+ L18- L19+ L19- L20+ L20-

+ -
Sounder

Output board of direct control panel:


C1+ C1- C2+ C2- C3+ C3- C4+ C4- C5+ C5- C6+ C6- C7+ C7- C8+ C8-

Wiring terminals:

Fig. 2-18
Terminals:

L, N, PE: AC 220V terminals and case protection grounding terminal;

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


22
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

RS485: Broadcasting / telephone port;


Ln (n=1~20): Detector bus (without polarity); also for connection with
CAN networking H, L: Communication bus terminals for connection with other
control panels (optional);
Communication card R+, R-, T+, T-: Terminals for connection with CRT image
display equipment (optional);
Optical fiber networking: Communication bus terminals for connection with other
control panels (optional);
Multi-interface card: Communication bus terminals for connection with other control
panels (optional)
Sounder+, Sounder-: Alarm bell output terminals, 24V/0.15A active output;
Cn+, Cn- (n=1~8): Direct control output terminals;
External wiring terminals: External output terminals of 24V power supply.
2.3.3 External Terminals of GST-LWK5000H-FIB Networking Interface Card

Ethernet port RS485


以太网口
通讯口port
communication

Fig. 2-19

2.3.4 External Terminals of GST-DGNK5000H Multi-Interface Card

TX RX TX RX
接口1
Port 1 接口2
Port 2

Fig. 2-20

2.4 Alarm Output Wiring


The wiring of audible / visual alarms is shown in Fig. 2-21.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


23
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Sounder + Diode Diode


4.7k terminal
Sounder Sounder resistor

Sounder-

Fig. 2-21
Procedure: Remove the terminal resistor and keep it carefully. Connect the wires while pay
attention to the polarity during wiring. Connect a 4.7k resistor at the end of the output circuit of
each audible / visual alarm.

3. Installation and Commissioning

3.1 Inspection upon Unpacking


Inspect the field equipment before installation.
3.1.1 Inspection against Project Configuration
Check whether the contents of the control equipment’s packing list are consistent with the
configuration of the project. After unpacking, check the items in the package one by one against the
contents of the packing list. The inspection should mainly cover the installation and operation
manuals, fuses and other items supplied with the equipment. After the check, inspect the appearance
of the control panel as necessary. Please contact the Technical Service Department of GST if any
non-compliance is found during the inspection.
3.1.2 Inspection of Configuration and Connection Inside Control Panel
Check the internal configuration of the control panel against the descriptions in Chapter 2 of this
manual, such as the number of circuit cards and the configuration of manual panels. Also check the
connection between the components and make necessary records for reference during the following
installation and commissioning. Please contact the Technical Service Department of GST if loose
connecting cables, non-compliance to the manuals or illegible identification.
3.2 Exterior Dimensions and Environmental Requirements
JB-QB-GST1500H-EN Fire Alarm Control Panel / Fire Safety Linkage Control Panel
Dimensions (L×W×H): 500mm×170mm×700mm
JB-QG-GST5000H-EN Fire Alarm Control Panel / Fire Safety Linkage Control Panel
Dimensions (L×W×H): 550mm×460mm×1715mm
JB-QT-GST5000H-EN Fire Alarm Control Panel / Fire Safety Linkage Control Panel
Dimensions (L×W×H): 1050mm×863mm×1273mm
JB-QG-GST9000H-EN Fire Alarm Control Panel / Fire Safety Linkage Control Panel
Dimensions (L×W×H): 550mm×460mm×1715mm
JB-QT-GST9000H-EN Fire Alarm Control Panel / Fire Safety Linkage Control Panel
Dimensions (L×W×H): 1050mm×863mm×1273mm
Ambient Temperature: 0ºC~+40ºC
Relative Humidity: ≤95%, no condensation

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


24
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Installation Distance: The width of the maintenance access behind of the control panel should be
greater than 1m
JB-QB-GST1500H-EN fire alarm control panel / fire linkage control panel is wall mounted, and
its installation dimensions are shown in Fig. 3-1.

Fig. 3-1
3.3 Inspection upon Power-on
After the control panel is delivered to the site, inspect the control panel upon power-on. The
inspection should cover:
a) Check whether the LCD displays and indicators of the control panel work properly.
b)In the self-test status, observe whether the indicators of the control panel and manual panels are
turned on, and whether the alarm sound test is successful.
c) After registration, check whether the displayed system configuration (including the number of
circuit cards, manual panels, direct control panels, etc.) is consistent with the actual ones in existence.
d)After entry into the standby mode, observe whether there is power failure, whether the main
operation keyboard and manual panel keyboard send out beep sounds, and whether any auxiliary
equipment works properly.
e) If any abnormality is found in a step, handle it as described in Chapter 8. If the problem persists,
notify the Technical Service Department of GST.
3.4 Inspection of External Equipment
Use the commissioning devices to check the conditions of the equipment in the circuit, that is,
whether the number, addressing and working status of the equipment meet the design requirements,

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


25
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

eliminate identified faults, and prepare for the system connection.

3.5 Wiring and Setup


If all test results meet the requirements after the inspection of the main unit and external
equipment, connect the external equipment and the main unit correctly, and set the direct control
panels and manual panels according to the relevant instructions in Chapter 2. Upon completion of
each step of connection, conduct test and record the results in "Appendix III Commissioning Form"
for commissioning and subsequent programming and definition.
The recommended screw torque is 7 lbf.in for wiring.

3.6 Commissioning
After the wiring is completed, conduct start-up commissioning after careful examination by
observing the following steps:
⚫ Enter the commissioning status according to the instructions for commissioning in Chapter 6.
⚫ Check whether the registration of bus equipment is consistent with that recorded in "Appendix
III Commissioning Form". If a large number of devices are missing, first check the linkage
power supply and bus isolators on each floor, check individual devices and then try to register
the equipment again to see whether the registration is complete.
⚫ Refer to Chapter 5 on equipment definition to define the bus devices and each key of the direct
control panels. For the linkage equipment, define the manual panel operation keys, prepare
labels for the manual panels and the direct control panels and insert or paste them at the
corresponding positions.
⚫ Conduct test of detector alarms, fire display panel alarm and direct control panel operation.
⚫ Exit the commissioning status and enter the standby mode.
⚫ Check the equipment definitions thoroughly and correct the any improper element.
⚫ Edit the linkage formula and conduct automatic linkage test.
⚫ Connect important equipment (for example, gas fire-fighting equipment), and train operators to
operate correctly.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


26
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Part III System Use

 General Instructions To Users

 Operating Guide for System Administrators

 System Commissioning Functions

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


27
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

4. General Instructions To Users

4.1 Power on, Power off and Self-Test


After commissioning the control panel, one may start the control panel for operation.
 Turn on the primary power switch and then the backup power switch in the cabinet of the
control panel.
 The system bootstrap starts and takes about 10 seconds (as shown in Fig. 4-1).

Fig. 4-1
 Start-up in commissioning status (as shown in Fig. 4-2)
After the bootstrap completes, if the control panel is currently in the commissioning status, the
screen will display the information of the control panel itself, and prompt the user to select the options
for operation. If you choose no operation, you will log in directly after 10 seconds.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


28
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 4-2
If you choose registration, you will enter the registration screen (as shown in Fig. 4-3), and the
registration progress bar shows the current registration progress.

Fig. 4-3
After registration, you will be prompted whether to read the details of bus devices, including
automatic identification of device types and reading of configuration information from the devices, as
shown in Fig. 4-4. If you press the Cancel key, the registration results of the devices will be displayed,
including the change of the number of system devices before and after registration, as shown in Fig.
4-6.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


29
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 4-4
Select "OK" (as shown in Fig. 4-5).

Fig. 4-5
The reading bus device details lasts about 5~120 seconds, and the time depends on the number of
bus devices connected to the control panel. After reading the information, the registration results are
displayed as shown in Fig. 4-7.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


30
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 4-6
 Start-up in monitoring status:
If the control panel is currently in the standby status, the screen will display the information of
the control panel itself, and prompts the user whether to conduct the audio-visual self-test operation,
as shown in Fig. 4-7. If you choose no operation, the control panel will enter the normal operation
status after 10 seconds.

Fig. 4-7
If you choose the self-test operation, all indicators on the control panel console will be lit, the
speaker will beep, and the display will show the key operation instructions on the console.
After registration or self-test upon power-on, the control panel enters the normal operation screen

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


31
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

(as shown in Fig. 4-8). Now, the startup operation process is finished.

Fig. 4-8
Fig. 4-8 is the window during normal operation. The dark blue area at the bottom of the window
is the status bar, which lists the current working status, software version and current time of the
control panel.

4.2 Keys and Interface Operation Instructions


4.2.1 General Description of Data Input
To input data, there is a cursor on the screen to indicate the position where the data is input. Press

or to move the cursor’s position. When there are multiple fields, press or to
switch between the fields. When inputting data, press the character keys as necessary. To change the
data which has been input, move the cursor to the corresponding position and press the character keys
as necessary.
In the process of data input, an exit delay bar is displayed at the bottom of the screen. When no
keyboard operation occurs, the exit delay bar will gradually shorten. After the exit delay bar
disappears, the system automatically exits the current data input status without storing the data.
4.2.2 Input of Chinese and English
The control panel has national standard level-1 and level-2 libraries of characters, which allows
input of Chinese and English characters when inputting the user name for setting the password,
equipment annotation for equipment definition, project name, etc. The control panel has three input
methods: T9, location code input method and English character input method. To input Chinese or
English characters, press ?
and the control panel is ready for inputting Chinese and English
characters. Press "*" to switch between the three input methods. After necessary Chinese characters
are input, press ?
again to exit the Chinese character input status.
Please note that all Chinese characters in the level-1 library can be input with the full
pinyin input method and the T9 input method, those in the Level 2 library can be input only

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


32
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

with the location code input method.


T9 input method description:
 According to the Pinyin of the desired Chinese characters, select and press the number keys
(2 ~ 9) where each letters are located, and press each key once only, regardless of the order
of the letters on the key. After a key is pressed, a list of candidate Pinyin combinations and
characters is shown on the LCD display and will be constantly with the most likely and
commonly used Pinyin combinations and Chinese characters.

 Press or to select the desired Pinyin in the list of candidates, and press "OK" to
finish Pinyin selection.
 Press the number keys (1~9) to select the desired Chinese characters. If the required

Chinese characters are not in the current screen, press , , , to turn


pages in the list, and then select Chinese characters as necessary.
4.2.3 General Description of Menu Operation
When operating the menu in the control panel, there are two ways to select the menu: One is to
press the number key corresponding to the menu item with the keyboard; the other is to make the
button to be selected highlighted (the menu button is pressed) with or , and then press
the "OK" key.
During the menu operation, press the "Cancel" key to return to the upper menu.
4.2.4 View of Information
4.2.4.1 Definitions
Highlighted message: A message displayed on the screen with black characters on a white
background is one being highlighted.
Highlighted window: The window where a highlighted message is located is called the
highlighted window, and the icon indicates the highlighted window.
Event information: Fire alarm, early warning, supervision, blocking, startup, feedback and other
information are collectively referred to as event information.
4.2.4.2 Operation
Information view mainly includes system event information, equipment information, linkage
formula and operation records. The basic procedure is described as follows:

⚫ To view event information, press the or key to turn pages on the screen. Press
the "OK" key to select a message. Now, press the or key to scroll the
highlighted message.
⚫ To view equipment information, enter the system equipment inspection / view by circuit

screen, and the screen lists the circuit registration information; press the "OK" key or

key to select a single message, and press the "OK" key or key again to display more
details of the message. Press the or key to view messages one by one or
between pages (If there is a selected equipment message, the messages will be viewed one
by one, otherwise, it will be viewed between pages; pressing the "OK" key to select a single

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


33
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

message). If a single message is selected, press the "Cancel" key or the key to exit the
selected status and return to the previous screen.
⚫ To view the linkage formula, enter the linkage formula number to be queried, press the
"OK" key to view the linkage formula, and press the or key to view the
linkage formula one by one.
⚫ To view the operation records, the highlighted message is the latest event message or
operation message, and can be viewed by pressing or pressing the or key one
by one or between pages (If there is a selected equipment message, the messages will be
viewed one by one, otherwise, it will be viewed between pages).

4.3 Unlock and Lock Keyboard


4.3.1 Unlock Keyboard
The keyboard of the control panel is locked when the control panel is turned on. If a function key
(except the "Query" and "Silence" keys) is operated, the LCD display will display a prompt box for
password input. Enter the correct password and press "OK" to unlock the keyboard (as shown in Fig.
4-9).

Fig. 4-9
4.3.2 Lock Keyboard
The control panel has the function of automatic keyboard locking. When the LCD of the control
panel displays the normal standby screen or alarm information screen, the control panel will
automatically lock the keyboard if there is no keyboard operation for 120 seconds and no new
message occurs.
Tips: After the operation, confirm that the keyboard is locked before leaving to avoid other
misoperation by others.
4.4 Information Display
4.4.1 Description of Event Message Format
The information display screen is divided into two parts: the upper half and the lower half of the

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


34
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

screen. The upper half of the screen is used to display information such as fire alarm, early warning,
supervision failure, blocking, etc.; the lower half screen is used to display feedback, action, startup
and delay information. If there is only one type of information on the upper screen or the lower screen,
it is displayed in full screen. The screen display is shown in Fig. 4-11 and Fig. 4-12
The display formats of various event information of JB-QB-GST1500H-EN and
JB-QG/QT-GST5000/9000H-EN control panels are exactly the same. An event message contains the
time and location of the event. The specific format is shown in Fig. 4-10.
Date and time of event

Location information
User-defined Code
Control panel No.
Message No.

Device type
Loop No.

001 06-14 10:29:39 Panel 001 Loop02 010002-193 MCP 1st Floor Lobby

Fig. 4-10

4.4.2 Event Information Window Categories

Fig. 4-11

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


35
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 4-12
Each type of information is arranged in the time sequence of occurrence. Each information
window displays the type of information, the total number of messages and the latest message. If there
is a fire alarm, the first alarm message will always be displayed at the top of the screen (as shown in
Fig. 4-13).

Fig. 4-13
4.4.3 Highlighted Window and Window Switching for Event Information

indicates the highlighted window of the current information. You can also switch the

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


36
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

highlighted window by pressing the or key, or scroll the information in the current
information window by pressing the or key, as shown in Fig. 4-14.

Fig. 4-14
4.4.4 Selection of and Operation with Highlighted Message
In an information window, press the "OK" key to select a message in the current information
window. Now, press the or key to scroll the messages (as shown in Fig. 4-15).

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


37
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 4-15
When a message is selected, press the "OK" key again and the screen prompts the operation with the
device (as shown in Fig. 4-16):

Fig. 4-16
⚫ After selecting a message in the fire alarm window, press the "OK" key: prompt whether to
query the fire alarm curve and deactivate linkage operation.
⚫ After selecting a message in the fault window, press the "OK" key: prompt whether to
conduct blocking operation.
⚫ After selecting a message in the blocking window, press the "OK" key to prompt whether
to cancel the blocking operation.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


38
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

⚫ After selecting a message in the delay window, press the "OK" key: prompt whether to
conduct instant start and instant stop operation.
4.4.5 Switch Full Screen and Split Screen Display
In the monitoring (commissioning) status or when there is information being displayed, press the

key under the information window to switch between split screen and full screen display, as shown
in Fig. 4-17.

Fig. 4-17

4.5 Information Query


Press the "Query" key and the LCD display is as shown in Fig. 4-18.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


39
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 4-18
4.5.1 View of Equipment Information
Select "1. Equipment information query" is the screen shown in Fig. 4-18 to check all the current
configuration of the system and have an understanding of the equipment information quickly. The
control panel offers a variety of methods for viewing the equipment: by circuit, by criteria, all
equipment, equipment status query. Users may choose from the methods according to their own needs
(as shown in Fig. 4-19).

Fig. 4-19
4.5.1.1 Query by Circuit
Select "1. Query by circuit" in the screen shown in Fig. 4-19, and the screen will display the

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


40
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

detailed information of all circuit cards, manual panels, direct control panels and communication
cards registered with the control panel (as shown in Fig. 4-20).

Fig. 4-20
Select a card and press "OK". The information and real-time data corresponding to the card is
shown (as shown in Fig. 4-21)

Fig. 4-21
After confirming the information of circuit 01, the details of the circuit can be displayed. Fig.
4-22 shows the information of the bus devices registered to circuit 01, including the total number of
registered devices and the bus grounding of the circuit. The displayed information includes circuit
number, equipment number, user-defined address (i.e. secondary address), equipment type, equipment

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


41
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

characteristics and annotation. Among them, the equipment characteristics of heat and smoke
detectors are sensitivity information, ant those of action equipment are pulse output or level output.

Fig. 4-22
The first six digits of equipment number are user-defined, and "-" is followed by the device's
own number, which cannot be changed. Format of an entry of device information (as shown in Fig.
4-23):
Location information
User-defined Code

Device Sensitivity
Device Type
Device Icon

100001-002 Smoke Lvl 01 1st Floor Meeting


Room

Fig. 4-23
In the screen shown in Fig. 4-22, press the "?" key to switch between the circuit information,
physical address, defined unregistered device information and circuit device status, as shown in Fig.
4-24.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


42
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


43
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 4-24
※ In the screen shown in Fig. 4-20, select a manual panel or direct control panel and press
the "OK" button to display the definition information of the manual panel or the direct control
panel.
4.5.1.2 Query by Criteria
In the screen shown in Fig. 4-19, select "2. Query by criteria" to enter the query screen by secondary
address criteria (as shown in Fig. 4-25).
Enter the user-defined address of the device to be queried in the input box. After confirmation,
the list of all matched devices is shown. The list is arranged by user-defined address in ascending
order.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


44
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 4-25
Format of an entry of information (as shown in Fig. 4-26):
Location information
User-defined

Device Type
Device No.

Loop No.
Panel No.
No.

00002 100001-002 Smoke Panle -001 Loop-01 1st Floor Lobby

Fig. 4-26
4.5.1.3 Query of All Equipment
In the screen shown in Fig. 4-19, select "3. Query of all equipment" to enter the query screen of
all equipment (as shown in Fig. 4-27).
The screen will list the information of all the devices registered with the control panel. See
4.5.1.2 for the information display mode and format.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


45
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 4-27
4.5.1.4 Query of Equipment Status
In the screen shown in Fig. 4-19, select "4. Query of equipment status" to enter the query screen
of all equipment (as shown in Fig. 4-28). Press the or key to view different circuits.

Fig. 4-28
4.5.2 History Query
In the screen shown in Fig. 4-18, select "2. Record check" to query operation records, fire alarm
records and operation records, as shown in Fig. 4-29.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


46
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 4-29
Enter "1. Operation record query" to check the operation records. The operation records include
all alarm information, commands sent and settings made. Each entry includes the serial number,
information type, time of event occurrence, secondary address, equipment type and annotation. The
control panel allows query of the latest 9,999 entries of records of the system.
Enter "2. Fire record query" to check the fire records. Each entry includes the serial number, time
of fire occurrence, secondary address, equipment type and annotation. The control panel allows query
of the latest 1,000 entries of fire alarm records.
Enter "3. Operation record query" to check the operation records. The operation records contains
the user login information and records all manual operations by users. Each entry includes the serial
number, operation type, time of operation and annotation. The control panel allows query of the latest
1,000 entries of operation records.
By pressing the "?" key in the query screen, you can define the view of event records, including
the start time, end time and event type to facilitate viewing of the records.
4.5.3 View Linkage Formulas
In the screen shown in Fig. 4-18, select "3. Linkage formula query" to enter the query screen of
linkage formulas.
After entering the formula number, press "OK", and the linkage formula of this number will be
displayed on the screen, as shown in Fig. 4-30. You may also browse other linkage formulas by
pressing or .

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


47
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 4-30
4.5.4 View Blocking Information
In the screen shown in Fig. 4-18, select "4. Blocking information query" to enter the query screen
of blocking information, as shown in Fig. 4-31.
The screen will display information of all the blocked equipment, which is arranged by
user-defined address in ascending order. See 4.5.1.2 for the format of information display.

Fig. 4-31
4.5.5 View Start Information
In the screen shown in Fig. 4-18, select "5. Start information query" to enter the query screen of
start information, as shown in Fig. 4-32.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


48
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

The screen will display the information of all started bus devices, which are arranged by
user-defined address in ascending order. See 4.5.1.2 for the format of information display.

Fig. 4-32

4.6 Print Information


When viewing records, if the printer is currently in the "Printing selected" status, you can select
the entry to be printed, and press the "OK" key to print the information. If the control panel is in the
"Instant printing" or "Fire alarm printing" status, the control panel can print the information in the
system at any time.
The printing format is shown in Fig. 4-33.

Event
- + - + - + - + - + - + - + - + - + - + - + - + Time of event
Secondary Fire alarm 2012-07-19 11:23:09
address
001030-001 Point type smoke detector Equipment
Location of Elevator hall of building 04 of People's typeHospital
event
-+-+-+-+-+-+-+-+-+-+-+-+
Fig. 4 -33
4.7 Sound Alerts and Silencing of Control Panel
In the case of fire alarm or fault alarm, the speaker of the control panel will send out
corresponding alarm sound as alerts. When there are multiple alarm messages, the control panel will
send out corresponding alarm sound in the following order:
1) Sound alert of gas spraying (machine gun sound)
2) Sound alert of gas spraying about to start (gas start delay) prompt tone (rapid beeps at an
interval of 0.12 second)
3) Sound alert of fire alarm and early warning (fire engine sound)
4) Sound alert of start up (beeps at an interval of 0.5 second)
5) Sound alert of action, feedback, supervision (beeps at an interval of 1 second)
6) Sound alert of fault (ambulance sound)

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


49
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Press the "Silence" key to stop the alarm sound from the control panel, if necessary. If a new
alarm occurs, the control panel will send out alarm sound again.
4.8 Handle Fire Alarm and Fault
4.8.1 General Information on Fire Alarm Handling
When fire alarm occurs, identify the location of the fire alarm first and confirm whether there is a
fire.
If the fire is confirmed, notify the fire brigade immediately and organize evacuation.
In the case of false alarm, record the equipment number and time of the false alarm, identify and
record the site conditions of the equipment giving the false alarm, such as whether there is dense dust,
water vapor, drastic temperature change, air flow, large object movement, etc. If false alarm occurs
frequently, please contact our technical service personnel for solution.
4.8.2 General Information on Fault Handling
Faults can be generally divided into two categories. One is the fault caused with the internal
components of the control panel, such as fault with the primary and backup power supply, buses, etc.;
the other is the fault with field equipment, such as fault with detectors, modules, etc. When the fault
occurs, press the "Silence" key to stop the fault alarm sound if necessary.
 When the primary power supply fails, the backup power supply is used and, with full energy
level, can support the control panel working for more than 8 hours until the automatic
protection is activated for the backup power supply. After automatic protection of the
backup power supply, to alert the user that the fire alarm system has been turned off, the
control panel will send out fault sound for 1 hour. After the backup power supply is empty,
the primary power supply should be restored as soon as possible and the battery should be
charged for 48 hours to prevent the battery from being damaged.
 If the system fails, it should be repaired in a timely manner. If the system has to be shut down,
keep detailed records as necessary.
 If a field device fails, it should be repaired in a timely manner. If the fault cannot be solved in
a timely manner due to special reasons, the device should be blocked from the system
temporarily with the blocking function provided by the system. After the fault is solved, use
the blocking to restore the device.

4.9 Self-Test
The system provides self-test for audible and visual components and alarm output to determine
whether the system components are working properly. After pressing the "Self-test" key, the screen
display is as shown in Fig. 4-34.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


50
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 4-34
4.9.1 Self-test of Audible and Visual Components
In the system self-test screen (Fig. 4-34), select "1. Audible and visual self-test". The system will
carry out self-test with the indicator, LCD display, speaker, manual panel and direct control panel of
the control panel console. During the self-test, the LCD display displays the color of red, yellow and
blue in full screen in turn. The console indicators are lit all first and then in turn; all the indicators of
the manual panels and the direct control panels are lit; the speaker beeps. The control panel returns to
the screen shown in 4-8 after the self-test.
4.9.2 Output Function Self-Test
In the self-test screen (Fig. 4-34), select "2. Alarm output self-test", and the system will start the
alarm of the machine and light up the "Self-test" indicator on the control panel; After 10 seconds of
self-test, the alarm is activated, and the "Self-test" indicator on the control panel goes out.
4.10 User Settings
Press "User Settings" and input the first-level password to enter the user setting screen (as shown
in Fig. 4-35).

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


51
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 4-35
These settings are used to change the running configuration of the control panel, and you may
make the settings according to your own actual needs. All the setting values will not be lost after
power failure, remain effective after setting and will not be affected by power on or off until the next
time the settings are changed.
4.10.1 Date and Time Settings
In the screen shown in Fig. 4-35, select and enter "1. Time and date settings", as shown in Fig.
4-36. The date and time on the screen is the current system date and time, which can be edited and
modified. After confirmation, the new system date and time takes effect.

Fig. 4-36

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


52
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Note: The date and time set here is the reference time of the control panel operation records, so
the settings must be accurate.
4.10.2 Manual Start Settings
In the screen shown in Fig. 4-35, select and enter "2. Manual startup settings"" as shown in Fig.
4-37.

Fig. 4-37

The checked option indicates the current manual start status. You can switch the manual

start status by pressing the or keys or the or keys. Press the "OK" key to
save the current setting and exit.
⚫ If the control panel is set to have manual start disabled, it is impossible to start and stop the
relevant devices with the start / stop key and manual panel keys. Due to the importance of
the equipment controlled with the direct control panels, the keys of the direct control panel
are not subject to this setting. There is an electronic lock on a direct control panel to control
whether manual operation is allowed or not. Manual operation can be allowed or prohibited
by setting the key.
4.10.3 Automatic Start Settings
In the screen shown in Fig. 4-35, select and enter "3. Automatic start setting", as shown in Fig.
4-38.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


53
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 4-38

The checked option indicates the current automatic start status. You can switch the

automatic start status by pressing the or keys or the or keys. Press the
"OK" key to save the current setting and exit.
Automatic start refers to the process that the control panel automatically starts or stops the
linkage equipment according to the linkage formula if the conditions of the linkage formula are met
after linkage formula has been programmed in the control panel. Three modes are available: all
automatic, partial automatic and simulated linkage.
⚫ All automatic: In this mode, when the linkage conditions are met, all the linkage formulas
with the equal sign "=", "= ", "==" or "== "may participate in the linkage.
⚫ Partial automatic: In this mode, only linkage formulas with equal sign "==" or "== " may
participate in linkage when the linkage conditions are met.
⚫ Simulated linkage: This function is only used for commissioning. In this mode, when the
linkage conditions are met, the red light of the manual fire protection start key that meets
the linkage conditions is lit, and it starts to flash after 10 seconds, indicating that the linkage
formula has been correctly implemented. However, no external controlled equipment will
be started in this mode.
4.10.4 Gas Spraying Settings
In the screen shown in Fig. 4-35, select and enter "4. Gas spraying settings", as shown in Fig.
4-39.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


54
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 4-39
4.10.5 Automatic Anti-Theft Setting
In the screen shown in Fig. 4-35, select and enter "5. Automatic anti-theft setting" screen, as
shown in Fig. 4-40.

Fig. 4-40
◆ When the anti-theft function is turned off, the alarm signals from devices with the device
type "anti-theft module" will not be displayed.
◆ When the anti-theft function is activated, the alarm signals from devices with the device
type "anti-theft module" will be displayed.
◆ In the automatic anti-theft mode, you may set the time for starting and closing the anti-theft

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


55
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

function. Within the set time period, the control panel is in the anti-theft mode, and beyond
the set time period, the control panel is in the anti-theft off status. The set time period is
effective every day.
4.10.6 Screen Saver Settings
In the screen shown Fig. 4-35, select and enter "6. Screen saver settings", as shown in Fig. 4-41.

Fig. 4-41
4.11 Print Settings
Press "Print Settings" and input the first-level password to enter the print setting screen (as
shown in Fig. 4-42).

Fig. 4-42

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


56
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

The checked option indicates the current printing status. You can switch the printing status

by pressing the or keys or the or keys. Press the "OK" key to save the
current setting and exit.
⚫ Printing disabled: No information will be printed
⚫ Instant printing: Print all information immediately
⚫ Instant printing without telephone number: Print all information except telephone number
immediately
⚫ Fire alarm printing: Print fire alarm information immediately
⚫ Printing selected: Press "OK" in the record view screen to print the selected records.

4.12 Blocking and Unblocking of Equipment


When external equipment (such as detectors, modules and fire display panels) fails, it can be
blocked. After the repair or replacement, the equipment can be restored by canceling blocking.
Press the "Block" key (if the control panel is in the key locked status, enter the user password to
unlock), and the screen display is shown in Fig. 4-43, prompting the user to select the corresponding
blocking operation.

Fig. 4-43
4.12.1 Block Equipment by Equipment Address
In the screen shown Fig. 4-43, select "1. Block equipment by equipment address" to enter the
blocking operation screen against equipment address, as shown in Fig. 4-44.
The blocking operation is applicable when the operator is familiar with the equipment to be
blocked and clearly knows their circuit numbers and equipment addresses.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


57
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 4-44
Input the circuit number and equipment address of the equipment to be blocked, and press the
"Confirm blocking" key to block the device.
4.12.2 Block Equipment by User-Defined Address
In the screen shown Fig. 4-43, select "2. Block equipment by user-defined address" to enter the
blocking operation screen against user-defined address, as shown in Fig. 4-45.
Input the secondary address of the equipment to be blocked in the prompt box for blocking the
device, and then press "Confirm blocking" to directly block the equipment. When it is necessary to
select the secondary address of the equipment in the list of the equipment to be blocked, press ? to
enter the list of the equipment to be blocked, press or to select the secondary address
of the device, and the selected secondary address of the device will be highlighted. Press the "Confirm
blocking" key to populate the secondary address of the selected device into the prompt box, and press
"Confirm blocking" again to block the device.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


58
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 4-45
To block the local alarm, the first six digits of the user-defined address are the user-defined
secondary address, and the device type is "76 - Alarm output". After confirmation, the local alarm
output will be blocked and the alarm blocking indicator will be lit. The operation of unblocking is not
described here as it is similar to the operation of blocking.
To block the local fire alarm transmission device, the first six digits of the user-defined address
are the user-defined secondary address, and the device type is "77 - Alarm transmission". After
confirmation, the local fire alarm transmission device will be blocked and the alarm transmission
fault/blocking indicator will be lit constantly.
The operation of unblocking is not described here as it is similar to the operation of blocking.
4.12.3 Block a Circuit
In the screen shown Fig. 4-43, select "3. Block a circuit" to enter the circuit blocking screen, as
shown in Fig. 4-46.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


59
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 4-46
After inputting and confirming the circuit number to be blocked, the circuit is blocked.
※After the circuit is blocked, the equipment of the blocked circuit will be powered off and
report no information. Blocking of circuits should be performed by professionals only!
Note: When inputting a device address in the operations of "Confirm blocking", "Unblocking",
"Start / stop", etc., the wild card "*" can be used to indicate that this bit can be any number from 0 to
9. This feature makes it simple for operators to block, unblock, start or stop a group of devices. For
example, to block all the anti-theft detectors in the system, you just input "******-*** 48" during the
blocking operation, and then all the anti-theft modules will be blocked. In the string, "48" is the
equipment type code of anti-theft modules. The operation of unblocking is not described here as it is
similar to the operation of blocking.

4.13 Manual Starting and Stopping of Linkage Equipment


4.13.1 Conditions for Manual Starting of Linkage Equipment
Please bear in mind that such external equipment are for fire protection only. Improper operation
may lead to unnecessary loss as well as impairment to performance in fire protection. Operators
should conduct the operation carefully!
The starting operation of external equipment shall meet the following conditions:
1)The operators must be qualified personnel who have been trained in the operation of the
control panel.
2)Understand the environment and controlled area of the equipment to be started.
3)Know the functionality of the equipment to be started, and be able to anticipate the results
after starting the equipment.
The linkage equipment can be started / stopped with the start / stop function of the control
panel’s keyboard, manual panels and direct control panels. It is a common method to use the start /
stop function of the control panel’s keyboard to conduct the operation. In this case, it is necessary to
input or select the secondary address and type of the device to be started. The use of manual panels
for operation is a fast and special method. To do so, it is necessary to program and define the manual

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


60
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

keys on the manual panel and the corresponding devices during installation and commissioning, and
indicate the names of devices beside the manual keys controlling the devices. Some important devices
are directly connected to the direct control panels and can be started or stopped directly with keys of
the direct control panels.
Whether the keyboard of the control panel or manual panels are used to start and stop the linkage
equipment manually, the start command can be sent only when the control panel is in the "Manual
allowed" status. When the control panel is in the "Manual disabled" status or a device to be started is
in the blocked or fault status, the start operation does not work.
The manual start with a direct control panel is subject to the manual operation lock of the direct
control panel. Only when the manual operation lock is in the allowed status, can the direct control
panel start the device with its key.
4.13.2 Start / Stop Controlled Equipment with Keyboard of Control Panel
Press the "Start" key in the main keyboard area of the control panel (if the control panel is in the
key locked status, it is necessary to input the first-level password to unlock), and the screen display is
shown in Fig. 4-47.

Fig. 4-47
There are two ways to start a device with the keyboard of the control panel.
1. Start a device with its equipment address: The operator clearly knows the circuit number and
equipment address of the device to be started, and only one device can be started at a time.
2. Start a device with its user-defined address: Start a device with its user-defined addresses
defined in advance, and multiple devices can be started at a time.
⚫ In the screen shown Fig. 4-47, select "1. Start equipment by equipment address" to enter the
starting operation screen against equipment address, as shown in Fig. 4-48.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


61
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 4-48
Input the circuit number and equipment address of the device to be started, and the device
will be started after "Confirm Starting".
⚫ In the screen shown Fig. 4-47, select "2. Start equipment by user-defined address" to enter
the starting operation screen against user-defined address, as shown in Fig. 4-49.

Fig. 4-49
Input the secondary address of the equipment to be started in the prompt box for starting the
device, and then press "Confirm Start" to directly start the equipment. When it is necessary to select

the secondary address of the equipment in the list of the equipment to be started, press to enter
the list of the equipment to be started, press or to select the secondary address of the

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


62
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel


device, and the selected secondary address of the device will be highlighted. Press the key to
populate the secondary address of the selected device into the prompt box, and press "1. Confirm
starting" again to start the device.
※ The operation of stopping the equipment is not described as it is similar to the operation
of starting.
4.13.3 Start / Stop Controlled Equipment Manually with Manual Panel
To start a controlled bus device, first find the unit corresponding to the device to be started
according to the label information of the manual panel. Press the manual key of this unit, and the
command light is lit, indicating that the start command is sent out; Press the key again, and the
command indicator goes out, indicating that the start command is terminated.
※ If the start key pressed is not defined or the defined device does not exist, a prompt will
pop up in the window to inform the operator that the key is not defined or the device does not
exist.
4.13.4 Start / Stop Controlled Equipment Manually with Direct Control Panel
When the output is set to the level output mode, press the key of the direct control panel, the
control line corresponding to the key sends out the start signal, and the corresponding start indicator
on the key is lit; press the stop key, the output is terminated, and the start indicator goes out.
When the output is set to the pulse output mode, press the key of the direct control panel, and the
control line corresponding to the key sends out the pulse start signal; press the key again to send the
pulse start signal again.

4.14 Automatic Control of Linkage Equipment


4.14.1 Preconditions for Automatic Linkage
Only when the control panel is in the "Partial automatic" or "All automatic" status, can the
control panel send the start automatic linkage command. You may check the current status of the
control panel through the status bar on the screen or change the automatic linkage status of the control
panel in the working status setting screen.
When an operator is on duty, it should be set to the "Automatic disabled" status. After the alarm
is confirmed by the operator on duty, it may be changed to the automatic status. When the control
panel is changed from the automatic disabled status to automatic status, it will automatically execute
the commands that meets the requirements of linkage formulas.
4.14.2 Realization of Automatic Linkage Logic
When the logical relationship in a linkage formula is met, if the equipment associated with the
linkage relationship has no required for delayed starting or stopping, the control panel will
automatically send the starting or stopping command to start or stop the corresponding equipment. If
the equipment associated with the linkage relationship has delay start requirements, the system will
start delay countdown after the logical relationship is met, and the start command will be sent when
the delay time is over.
4.14.3 Cancellation of Delayed Starting and Direct Start Control
The control panel allows canceling delayed starting and changing from delayed starting to direct
starting. That is, when the highlighted screen is showing the delay information, press the "OK" key, as
shown in Fig. 4-50. Now, pressing "1" key will cancel the delay of the selected device, and
immediately start the selected device, and pressing "2" key will cancel the delay of the selected device
immediately.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


63
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

After that, press "OK".

Fig. 4-50
⚫ When performing the operation described above, first switch the highlighted screen to the delay
screen by pressing the window switch key.
⚫ If more than one entry of delay information exists, press the or key to highlight
an entry.

4.15 Start and Stop Gas Fire Extinguishing Equipment


4.15.1 Preconditions for Starting Gas Fire Extinguishing Equipment
Please bear in mind that gas fire extinguishing equipment is controlled equipment which would
finish the spraying and extinguishing immediately after receiving an effective start command. On one

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


64
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

hand, improper operation of gas fire-extinguishing equipment will lead to significant and irreparable
losses, even casualties, as well as impairment to the fire protection performance of important places
for a certain period of time. Be extremely careful when starting such equipment! The equipment type
of gas fire extinguishing equipment is "Gas start (37)".
Besides the preconditions for starting general equipment, the starting of gas fire-extinguishing
equipment shall meet the following preconditions:
a) The personnel who start the gas fire extinguishing equipment must be qualified personnel
who have received the knowledge training on fire extinguishing with gases.
b) Confirm that the fire really requires starting the gas fire extinguishing equipment.
c) Confirm that all personnel have been evacuated in the protected area where the gas fire
extinguishing equipment is to spray the gas.
The gas fire-extinguishing equipment has two addressed control points, i.e. "Start Gas" and "Stop
Gas" on the control panel for gas fire-extinguishing. For the automatic linkage or manual starting
operation of the "Start Gas" equipment. Besides that the control panel is in "Partial automatic"
(linkage formulas containing "= =" are included in the linkage), "All automatic" (linkage formulas
including "=" and "= =" are included in the linkage) or the "Manual allowed" mode, the control panel
must also be in the "Spray allowed" status. The operation of "Gas Stop" is not controlled by "Spray
allowed".
4.15.2 Manual Starting of Gas Fire Extinguishing Equipment
Like general equipment, the manual starting of gas fire-extinguishing equipment may also be
started with the keyboard of the control panel or manual panels, and the operation methods are
similar.
Normally, manual panels should be use, because this method is fast and not prone to mistakes.
Just find the unit corresponding to the gas fire extinguishing equipment according to the label
information of the manual panel, and press the command key of this unit.
In special cases, if no manual panel is defined for the device, the keyboard of the control panel
may also be used to start the device.
To prevent improper operation of the gas fire extinguishing equipment,
the control panel’s screen will automatically display two prompts after pressing the corresponding
manual key or input the user-defined address for the gas fire extinguishing equipment in the start
menu. Assume that the gas fire extinguishing equipment with the address of 111111-021 is started.
The screen prompt is shown in Fig. 4-51.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


65
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 4-51
Now, select "Confirm Start" and a prompt will appear on the screen as shown in Fig. 4-52. Select
"Cancel Start" to give up.

Fig. 4-52
In the screen shown in Fig. 4-52, select "Cancel Start" to give up; select "Confirm start" to send
out the command to start the gas fire extinguishing equipment immediately! The warning window has
a time limit, by which the operation will be given up if no operation occurs within 30 seconds.
4.15.3 Automatic Linkage Control of Gas Fire Extinguishing Equipment
In the case of manual starting, the gas fire-extinguishing equipment is started immediately after
confirmation. When the gas fire-extinguishing equipment is controlled by means of automatic linkage,

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


66
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

the control panel directly sends out commands to the gas fire-extinguishing control panel. After
receiving the commands, the gas fire-extinguishing control panel sends start signal to the cylinder
solenoid valves controlling the gas fire-extinguishing equipment after a delay (settable).
4.15.4 Emergency Stopping of Gas Fire Extinguishing Equipment
During the delay before the gas fire extinguishing control panel sends out the immediate start
command, the gas fire extinguishing equipment can be stopped in either both the central control room
or at the site.
At the site, press the "Emergency Stop" button to directly terminate the delayed starting of gas
fire extinguishing equipment.

4.16 Reset
When a fire alarm or fault is solved, reset the control panel by pressing the "Reset" key, input the
user password and confirm the operation. Resetting gives the following results:
⚫ Clearing all existing fire alarms, faults and feedbacks.
⚫ Resetting all linkage devices.
⚫ Resetting all bus controlled equipment and status indicators on manual panels and direct
control panels.
⚫ Clearing the commands requesting starting or delayed starting.
⚫ Clearing the silencing status.
⚫ Clearing the display of all fire display panels.

4.17 Description of Networking Information Display


GST1500H-EN/5000H/9000H control panels can be networked with each other and with
GST100, GST200, GST500, GST5000, GST9000, GSTN1500, GSTN3200 control panels of GST for
transmission of event information and control between them.
When multiple control panels are networked, one control panel should be defined as the central
machine, and the other control panels should be local machines. For the networking settings, the
central machine should have all options checked for network command sending and other commands
checked for network command receiving. Local machines should have other commands checked for
network command receiving and network command sending.
Because GST1500/5000/9000H control panels show information with 9-digit addresses,
GST1500/5000/9000H uses 9-digit addresses for transmission of information and commands between
them and the normal mode is used for transmission between them.
Control panels like GST100 and GST200 use 6-digit addresses. When they are networked with
GST1500/5000/9000H control panels, the formats of information display and command transmission
are as follows:
⚫ When the information and commands on the GST1500/5000/9000H control panel are
transmitted to other types of control panels, in the case of the last six digits unchanged, only
the last six digits of the 9-digit secondary addresses are displayed. For example, when fire
alarm at photoelectric smoke detector 001002-013 03 occurs in a GST1500/5000/9000H
control panel, the fire alarm at 002013 03 photoelectric smoke detector is shown on a
GST500 control panel. In the case of the first six digits unchanged, only the first six digits
of the 9-digit secondary addresses are displayed. For example, when fire alarm at
photoelectric smoke detector 001002-013 03 occurs in a GST1500/5000/9000H control
panel, the fire alarm at 001002 03 photoelectric smoke detector is shown on a GST500
control panel.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


67
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

⚫ When the information from other control panels is transmitted to a GST1500/5000/9000H


control panel, in the case of the last six digits unchanged, the first three digits of the 6-digit
secondary address is added to the current control panel’s network number. For example, fire
alarm at photoelectric smoke detector 00201203 occurs in a GST500 control panel with
network number 003, the fire alarm at 003002-01203 photoelectric smoke detector is shown
on a GST1500H-EN/5000H/9000H control panel. In the case of the first six digits
unchanged, the last three digits of the 6-digit secondary address are added to the current
control panel’s network number. For example, fire alarm at photoelectric smoke detector
occurs 00201203 in a GST500 control panel with network number 003, the fire alarm at
002012-00303 photoelectric smoke detector is shown on a GST1500H-EN/5000H/9000H
control panel.
⚫ When a command sent by other control panels is transmitted to a
GST1500-EN/5000/9000H control panel, in the case of the last six digits unchanged, ***
are added before the 6-digit secondary address. For example, when a GST500 control panel
starts fire damper 00201822, the command is shown as ***002-01822 when it is transmitted
to a GST1500H-EN/5000H/9000H control panel. In the case of the first six digits
unchanged, *** are added after the 6-digit secondary address. For example, when a GST500
control panel starts fire damper 00201822, the command is shown as 002018-***22 when it
is transmitted to a GST1500H-EN/5000H/9000H control panel.

5. Operating Guide for System Administrators

Press the "Set" key to enter the system setting menu (as shown in Fig. 5-1), and then press the
corresponding number keys to enter the corresponding screens.
To enter the system setting screen, you need to use the administrator password (or a higher-level
password) to unlock it before operation.

Fig. 5-1

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


68
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

5.1 Device Registration


In the screen shown Fig. 5-1, select "1. Device registration" to enter the registration mode
selection screen, as shown in Fig. 5-2.

Fig. 5-2
1. Register additional devices: Additional bus devices are registered on the basis of the existing
registered devices, and the total number of registered devices increases.
2. Update all registration: All boards and bus devices are re-registered.
3. Update card registration: Only manual panels, direct control panels and communication cards
are re-registered, while bus devices are not re-registered.
For the procedure of 1-3, please refer to the operation instructions on registration upon power-on in
4.1 for startup, shutdown and self-test.
5.1.1 Add Equipment Manually
In the screen shown Fig. 5-2, select "Add equipment manually" to enter the screen for manually
adding equipment, as shown in Fig. 5-3.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


69
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 5-3
Input the circuit number and equipment address of the device to be added. After confirmation,
the device will be registered immediately. The registration information of the device can be viewed in
the equipment view screen.
※ The operation of manually reducing equipment is not described as it is similar to the
operation of adding equipment manually.

5.2 Equipment Definition


5.2.1 Content of Equipment Definition
The external field equipment connected to the control panel includes fire detectors, linkage
modules, fire display panels, direct control panels, etc. These external devices need to be addressed.
Each device corresponds to an original address and a field address. Equipment definition is to set the
field address of a device with an original address. The devices to be defined may be those registered
on the control panel or not registered on the control panel.
Original address: The original address is composed of the circuit number where the equipment
is located and its own address number. The circuit number of a circuit card or communication card is
set consecutively from 1, and the original address has nothing to do with the field wiring.
By changing the original address, a different field device can be selected for field addressing,
including secondary address, equipment type, equipment characteristics, key value and equipment
annotation.
Secondary address: The secondary address is a user-defined address, which is composed of 9
digits from 0 to 9. It is a group of numbers defined artificially to represent the specific site setting
where the device is located. With this address, a user can easily know the location of the
corresponding device and other information related to the location. The first six digits of the
secondary address are any numbers defined by the user, and the last three digits are the device's own
address and cannot be changed.
Equipment type: Refer to the equipment types in "Appendix II Equipment Type Table". By
entering two digits, and the information of corresponding equipment type will be displayed in Chinese.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


70
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel


When inputting a device type, you can also enter the input and selection box by pressing the key,

select the equipment type with the , , or keys, and then press the "OK" key
to get the device type.
Equipment characteristics: Some devices have variable configuration which can be changed
with this setting. Devices with variable configuration include:
⚫ Point type smoke detector: The sensitivity (threshold) of point type smoke detectors for
detecting smoke can be changed with 1 = sensitivity 1, 2 = sensitivity 2, 3 = sensitivity 3.
The corresponding sensitivity characteristics are shown in Table 5-1.
Table 5-1
Sensitivity
Detector threshold (dBm-1)
category
Sensitivity 1 0.1 - 0.21
Sensitivity 2 0.21 - 0.35
Sensitivity 3 0.35 - 0.56
Note: The smaller the sensitivity number, the more sensitive the detector is, which can send out alarm
for less smoke.
⚫ Output module: For modules, this item is for selecting the output control mode, "00"
represents a general pulse output control mode module; "01" represents a general
continuous level output mode module.
Key value: For a linkage device in the system, this item is used to define the start key on the
manual panel corresponding to the device. This item consists of 4 digits with the first two digits
indicating the number of the manual panel, and the last two digits indicating the manual key number.
Device annotation: Device annotation gives the location of the device or other related reminder
information in Chinese. You can enter up to 40 characters in this field. Each numeral character
or letter take up 1 place, and each Chinese character take up 2 places.
5.2.2 Device Definition Procedure
Enter the "2. Device definition" screen, which will display the device definition selection menu
as shown in Fig. 5-4. This menu includes: bus device definition, manual panel definition, direct
control panel definition, broadcast / telephone panel definition, networking control panel definition,
custom device type, circuit annotation definition and project name.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


71
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 5-4
5.2.2.1 Continuous Equipment Definition
Select "1. Bus device definition" -> "1. Continuous definition" to enter the device continuous
definition status (as shown in Fig. 5-5). In this status, the system deems the devices are undefined by
default.

Fig. 5-5
Define all the fields in Fig. 5-5, and press "OK" to save them after input. When inputting the
device type, you can input it directly or press the ? key to select it in the input selection box on the
right side of the screen.
After the first device definition is completed and confirmed, the next device is defined as the

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


72
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

same to the previous device by default, which provides the following advantage:
 The device address is added by 1 automatically when it is less than its maximum value;
 The secondary address is added by 1 automatically;
 The equipment type remains unchanged;
 The equipment characteristics remain unchanged;
 When the key value is set, the key value is added by 1 automatically;
The device annotation remains unchanged.
5.2.2.2 Equipment Definition Inheritance
Select "1. Bus device definition" -> "2. Inherit definition" to enter the device definition
inheritance status (as shown in Fig. 5-6). In this status, the defined device information is called from
the system and may be modified.
For example, external equipment 001 of circuit 15 is defined as a point type smoke detector
with the secondary address of 001001-001. The equipment definition may be inherited in the way
described below.
Enter the equipment definition inheritance screen and input the circuit number of 15 and
equipment address of 001. The LCD display shows the information of the photoelectric smoke
detector with the secondary address of 001001-001. You can modify the existing definition. After you
press the "OK" key to save the definition, the display automatically shows the definition information
of device 002 on circuit 15.

Fig. 5-6
5.2.2.3 Quick Definition of Equipment
Select "1. Bus device definition" -> "3. Quick definition" to enter the quick device definition
status (as shown in Fig. 5-7). In this status, you can quickly define multiple devices. After inputting
the complete equipment information (in the same way as that for continuous equipment definition),
press the "OK" key, and the secondary address of the devices will increase automatically by a
specified increment. If the device type is defined as module (i.e. the device type number is greater
than 11) and a legal manual key value is defined, the manual key value will increase automatically.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


73
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Press the "OK" key to complete the definition.

Fig. 5-7
5.2.2.4 Manual Startup Panel Definition
Select "2. Manual panel definition" -> "1. Continuous manual panel definition" to enter the
screen of continuous manual panel definition, as shown in Fig. 5-8.

Fig. 5-8
Input the manual panel number and key number to be defined, then input the device address and
device type to be controlled by the key, and press the "OK" key to complete the definition of the
manual key.
In the process of definition, the wildcard "*" is used when inputting the secondary addresses of

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


74
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

controlled devices, which allow the control of multiple devices with one manual key.
※ The procedure for manual key inheritance definition is not described as it is similar to
that for continuous definition operation.
5.2.2.5 Direct Control Panel Definition
Select "3. Direct control panel definition" -> "Continuous definition" to enter the screen of direct
control panel definition, as shown in Fig. 5-9.

Fig. 5-9
Input the direct control panel number and key number to be defined, and then input the device
address, equipment type and annotation to be controlled by the key to complete the definition of the
direct control point.
When the function switch is set to "Circuit check disabled", the control panel will not check the
direct control output.
※ The procedure for direct control key inheritance definition is not described as it is
similar to that for continuous definition operation.
5.2.2.6 Radio / Telephone Panel Definition
Select "4. Broadcast / telephone panel definition" -> "Continuous definition" to enter the screen
of broadcast / telephone panel definition, as shown in Fig. 5-10.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


75
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 5-10
Input the communication card number and panel number to be defined, and then
input the area address, secondary address and equipment type to complete the definition of
the broadcast telephone panel.
5.2.2.7 Network Controller Definition
Like other devices, such controllers also have their own addresses, that is, the secondary address
of the network slaves.
Input the 9-digit secondary address and annotation, and press the "OK" key to save the
information, as shown in Fig. 5-11.

Fig. 5-11

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


76
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

5.2.2.8 Custom Device Type


To meet the actual needs of a project site, the control panel allows users to customize the text
description of custom equipment types 63, 64 and 65 at the site, and the information will be displayed,
recorded and printed as set here.
Select "Manual customization" to modify the description of the three device types. You may also
select "Restore default" to set the three device types to the default settings, as shown in Fig. 5-12.

Fig. 5-12
5.2.2.9 Circuit Annotation definition
Circuit annotation refers to the explanatory information in China related to the circuit. You can
enter up to 40 characters in this field. Each numeral character or letter take up 1 place, and each
Chinese character take up 2 places, as shown in Fig. 5-12.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


77
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 5-13
5.2.2.10 Project Name
Enter the project name setting screen, as shown in Fig. 5-14. You can input up to 20 Chinese
characters here. The project name will be displayed in the normal monitoring screen.

Fig. 5-14

5.3 Linkage Formulas


5.3.1 Format of Linkage Formulas
Linkage formulas are logical expressions used to define the linkage relationships between alarm
devices and controlled devices in the system. When the detectors in the system send out alarms or the
status of the control modules changes, the control panel will automatically perform "Immediate start",

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


78
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

"Delayed start" or "Immediate stop" operations of the controlled equipment according to these logic
expressions. The linkage formulas of this system is divided into two parts: the first part represents the
condition, which is composed of secondary address, equipment type and relation operator, and the
second part represents the equipment to be linked and is composed of secondary address, equipment
type and delay start time.
Example 1:

001001-001 03 X 001001-002 03 = 001001-003 22 000 001001-004 13 020

1 2 3 4 5 6 7 8

① Linkage trigger device 1: legal characters (0 ~ 9, *, &), i.e. the secondary address and device type
of the device, 11 places
② Linkage condition: legal character (+, x), 1 place
③ Linkage trigger device 2: legal characters (0 ~ 9, *, &), i.e. the secondary address and device type
of the device, 11 places
④ Linkage execution mode: legal characters (=, = =, = x, = = x), 1-3 places
⑤ Linkage execution device 1: legal characters (0 ~ 9, *, &), i.e. the secondary address and device
type of the device, 11 places
⑥ Delay time of linkage execution device 1: legal characters (0-9), 3 places
⑦ Linkage execution device 2: legal characters (0 ~ 9, *, &), i.e. the secondary address and device
type of the device, 11 places
⑧ Delay time of linkage execution device 2: legal characters (0-9), 3 places
The linkage formula represents that:
when point type smoke detector 001001-001 and point type smoke detector 001001-002 alarm at the
same time, fire damper 001001-003 will start immediately, and audible and visual sounder
001001-004 will start 20 seconds later.
Note:
◆ In a linkage formula, any device before or after the equal sign is required to be composed
of a secondary address and an equipment type, and the equipment type cannot be omitted.
◆ There are four expressions of the equal sign in linkage formulas, i.e. "=", "= =", "=", "= =". If
the equal sign in a linkage formula is "=" or "=", when the linkage conditions are met, the
control point can perform linkage operation only in the "All automatic" status ("=" represents
linkage start and "=" represents linkage stop). If the equal sign in a linkage formula is "==" or
"==", when the linkage conditions are met, the control point can perform linkage operation in
the "Partial automatic" or "All automatic" status ("==" represents linkage start and "=="
represents linkage stop).
◆ Only one equal sign indicating causality may exist in a linkage formula.
◆ There are two relation symbols: "or" and "and", with "+" stands for "or" and "×"stands
for "and".
◆ The delay time of the linkage equipment following the equal sign is 000-600, and the delay
time range is 0s ~ 600s.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


79
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

◆ In a linkage formula, wildcards are allowed with "*" representing any number between 0 and 9.
A wildcard may appear in either the condition part or the linkage part of a formula to
simplify the linkage formula appropriately. When a wildcard appears in the condition part,
the "or" relationship is implied between the devices. For example, 0*0013-003 15
represents:
000013-003 15+010013-003 15+020013-003 15+030013-003 15+040013-003 15+
050013-003 15+060013-003 15+070013-003 15+080013-003 15+090013-003 15.
◆ The "&" wildcard for causality consistency is allowed in linkage formulas. The use of "&"
is similar to that of "*". "&" is used to represent any number between 0-9, but its meaning
is different from "*". When the secondary address of a device is consistent with the
formula conditions, if the secondary address number corresponding to the place where
"&" stands has not appeared, the number is saved as the conditional number. When the
formula is established, and the corresponding place in the formula result item is also the
"&" symbol, the "&" symbol will be replaced by the corresponding conditional number
which has been saved to complete the linkage. When there is a new equipment secondary
address is processed, the above rule still applies to complete the linkage with the same
logical relationship in different areas.
◆ The equipment type in the linkage part of a linkage formula cannot contain wildcard "*"
or "&".
For example, the formula of &&&***-*** 03 = &&&***-*** 13000 means that when any
point type smoke detector in a certain area sends out alarm, any sounder in the same area will
start immediately. That is, when device 121***-*** 03 gives an alarm, device 121***-*** 13
starts without delay; when device 122***-*** 03 gives an alarm, device 122***-*** 13 starts
without delay; and so on.
5.3.2 Edit Linkage Formula
In the system setting menu, select item 3 to enter the linkage programming menu (as shown in
Fig. 5-15). There are three buttons in the menu: New linkage formula, Modify linkage formula and
Delete linkage formula.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


80
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 5-15
5.3.2.1 New Linkage Formula
Enter the "1. New linkage formula" screen (as shown in Fig. 5-16). The system automatically
assigns a serial number to the formula. After entering the linkage formula to be defined and
confirming it, the linkage formula is saved in the first available entry in the storage area. This system
will check the syntax of linkage formulas. That is, illegal characters are not allowed in the process of
input.

Fig. 5-16
Tips: The control panel provides association in the linkage formula input process, which display
all the devices that meet the input conditions in the list box for selection in the same way as that with

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


81
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

other list boxes. When all occurrences of the secondary address of a device in the formula are
completely changed to 0, the secondary address will not be recorded in the formula. That is, the
device is deleted from the linkage formula.
5.3.2.2 Modify Linkage Formula
Entering the serial number of the formula to be modified. After confirmation, the control panel
will display the linkage formula of this serial number and wait for edition and modification (as shown
in Fig. 5-17). After the modification is completed, press "OK" to save the modified linkage formula,
or press "Cancel" to discard the modification without saving.

Fig. 5-17
5.3.2.3 Delete Linkage Formula
After entering and confirming the formula number to be deleted, the control panel will display
the linkage formula of the serial number. Select "Confirm deletion" to perform the deletion or select
"Cancel deletion" to keep the linkage formula, as shown in Fig. 5-18.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


82
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 5-18

5.4 Network Settings


In the screen shown in Fig. 5-1, select "4. Network settings" to enter the screen for selection of
network settings, as shown in Fig. 5-19.

Fig. 5-19
5.4.1 Local Address Setting
In the screen shown in Fig. 5-19, select "1. Local address setting" to enter the screen for setting
the local address, as shown in Fig. 5-20.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


83
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 5-20
Input the network address of the unit in the screen, and the address range is 1-240.
※ The local network address is a unique number assigned to the control panel in the
network, and the addresses of different control panels cannot be the same.

5.4.2 Communication Card Settings


In the screen shown in Fig. 5-19, select "2. Communication card settings" to enter the screen for
communication card configuration, as shown in Fig. 5-21.

Fig. 5-21
Enter the network card number in the field behind the communication card. After pressing the

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


84
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

"OK" key, you may choose whether to display network information and whether to allow sending and
receiving various network commands.
5.4.3 IP Address Settings
When the control panel is connected with GST-DGNK5000H multi-interface card, the IP address,
mask address and gateway address should be set for the communication card. In the screen shown in
Fig. 5-19, select "3. IP address settings" to enter the screen for setting the local IP address setting, as
shown in Fig. 5-22.

Fig. 5-22
5.4.4 Clearing Faulty Slave
In the screen shown in Fig. 5-19, select "4. Clear fault slaves" to enter the screen for clearing
fault slaves, as shown in Fig. 5-23.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


85
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 5-23
In the commissioning stage and the following operation, when the network slaves change or
decrease in the GST network, the control panel will report the corresponding slave fault. If the
network change is permanent and the control panel is supposed not report the corresponding slave
fault, all the slaves reported to be faulty can be cleared from the network registry with this menu.
Commands for this function are sent across the network. Other slaves connected to the network
will also clear all slaves reported to be faulty from their network registry.
5.4.5 Secondary Address Compatibility
In the screen shown in Fig. 5-19, select "5. Secondary address compatibility" to enter the screen
of secondary address compatibility, as shown in Fig. 5-24.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


86
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 5-24
This function is designed to handle compatibility with earlier control panels. The
high-performance bus controller takes the 6-digit secondary address of an earlier control panel as the
six higher digits of a 9-digit secondary address, and the three lower digits are taken from the network

controller number of the earlier control panel. The checked option indicates the current status.

You can switch the secondary address alignment status by pressing the or keys or the
or keys. Press the "OK" key to save the current setting and exit.

5.5 Operation Mode


In the screen shown in Fig. 5-1, select "5. Operation mode" to enter the screen for selection of
operation mode, as shown in Fig. 5-25.

Fig. 5-25
5.5.1 Commissioning Mode Settings
In the screen shown in Fig. 5-25, select "1. Commissioning mode setting" to enter the screen for
setting of the commissioning mode, as shown in Fig. 5-26..

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


87
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 5-26
The status bar at the bottom of the control panel display screen indicates "commissioning" when
the control panel is in the commissioning mode or "monitoring" when the control panel is back to the
normal monitoring mode. The control panel running in the commissioning mode will automatically
return to the normal monitoring mode after 24:00 o’clock .
When the control system is formally put into use after commissioning, re-enter this menu and
select the monitoring status after ensuring that the control panel registration is correct. This is to
ensure that the control panel will generate fault alarm when any registered device is lost upon
power-on or off of the control panel!
5.5.2 Broadcast Synchronization Settings
In the screen shown in Fig. 5-25, select "2. Broadcast synchronization settings" to enter the
screen for setting broadcast synchronization, as shown in Fig. 5-27.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


88
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 5-27

The checked option indicates the current status. You can switch the broadcast

synchronization status by pressing the or keys or the or keys. Press the


"OK" key to save the current setting and exit.
◆ Parallel mode: When the fire alarm is linked with the audible and visual alarms and
broadcasting, the audible and visual sounders and the broadcasting are allowed to send out
sound at the same time.
◆ Alternate mode: When the fire alarm is linked with the audible and visual alarms and
broadcasting, the audible and visual alarms and the broadcasting send out sound alternate at
intervals configurable.
5.5.3 Early Warning Setting
In the screen shown in Fig. 5-25, select "3. Early warning setting" to enter the screen for setting
early warning. The control panel can be set to have early warning on or on, as shown in Fig. 5-28.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


89
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 5-28
When the early warning is on:
 If a detector that meets the conditions of early warning association sends out alarm, the
control panel enters the early warning status, and the LCD display of the control panel will
display the early warning message and send out the fire alarm sound, but it will not output
automatic linkage alarm or make linkage formula judgment.
 If another detector meeting the early-warning association conditions also sends out alarm
after the control panel has entered the early-warning status for 5 minutes, the early-warning
association conditions are met, the early-warning is regarded as fire alarm, the control panel
enters the fire alarm status, lights up the fire alarm indicator, output automatic linkage alarm
and complete the automatic start-up operation according to the linkage formula (the alarm
output and automatic start-up are also subject to the settings made by the user).
 If no other device sends out alarm after the control panel has entered the early-warning
status for 5 minutes, the control panel automatically clears the early warning message and
reset the device sending out the alarm.
 The alarm raised by the manual call points is not affected by the early warning settings, and
directly leads to the fire alarm status.
By enabling early warning permission, improper operation caused by the false alarm from a
certain device can be effectively avoided. In the early warning status, when a fire alarm is confirmed
manually, one may press any manual call point to make the control panel enter the fire alarm status
immediately.
You may set the alarm association according to the actual conditions of the site. The control
panel can have up to 32 early warning association formulas. The formula shown in Fig. 5-28 is
defined as follows: When the system detects alarm from a detector meeting curtain conditions, the
system enters the early warning status, and causes the speaker to send out fire alarm sound without
activating linkage output.
If the system detects fire alarm from another detector meeting the conditions within 5 minutes,

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


90
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

the system will enter the fire alarm status and activate the linkage output; if no subsequent detector
alarm is received within 5 minutes, the system will reset the detector sending out alarm and clear the
early warning message.
5.5.4 Fire Alarm Output Settings
In the screen shown Fig. 5-25, select and enter "4. Fire alarm output settings", as shown in Fig.
5-29.

Fig. 5-29
Fire alarm output settings are used to set the sound and light alarm output signal of the control
panel, and two modes are available: direct starting with fire alarm and starting with linkage formula.
⚫ In the case of direct starting with fire alarm, as long as fire alarm appears in the control
panel, the alarm will be started directly, and the fire alarm transmission equipment will be
started immediately to transmit the fire alarm message. This is not affected by the automatic
settings.
⚫ In the case of starting with linkage formula, when fire alarm appears in the control panel,
the alarm output and fire alarm transmission will not be automatically output. Alarm output
and fire alarm transmission should be included in a linkage formula and started
automatically with the linkage formula.

The checked option indicates the current status. You can switch the fire alarm output status

by pressing the or keys or the or keys. Press the "OK" key to save the
current setting and exit.
In the case of "Linkage Start", secondary addresses may be created in the following format:

001001-000 76
Control
控制器号 Cabinet
机箱号 Constantly
固定000 Equipment
设备类型
No. No. 000 type

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


91
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

5.5.5 Grounding Detection Settings


In the screen shown in Fig. 5-25, the screen after selecting "5. Grounding detection settings" is
shown in Fig. 5-30.

Fig. 5-30

The checked option indicates the current status. You can switch the grounding detection

status by pressing the or keys or the or keys. Press the "OK" key to save
the current setting and exit. When "Stop detection" is selected, the control panel will not report the
ground fault.
5.5.6 Silence Settings of Display Panel
In the screen shown Fig. 5-25, select and enter "6. Silence settings of display panel", as shown in
Fig. 5-31.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


92
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 5-31

The checked option indicates the current status. You can switch the silence status of

display panel by pressing the or keys or the or keys. Press the "OK" key
to save the current setting and exit.
※ This function is only used in the commissioning mode. When the Silent commissioning
status is selected, the bus display panel will not receive the fire alarm.
5.5.7 Silence Settings of Control Panel
In the screen shown Fig. 5-25, select and enter "7. Silence settings of control panel", as shown in
Fig. 5-32.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


93
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 5-32

The checked option indicates the current status. You can switch the silence status of

control panel by pressing the or keys or the or keys. Press the "OK" key
to save the current setting and exit.
5.5.8 Audible and Visual Alarm Feedback
In the screen shown Fig. 5-25, select and enter "8. Audible and visual alarm feedback", as shown
in Fig. 5-33.

Fig. 5-33

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


94
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

The checked option indicates the current status. You can switch the status of audible and

visual alarm feedback being allowed or not by pressing the or keys or the or
keys. Press the "OK" key to save the current setting and exit. This function is used to set
whether the control panel receives the feedback information from audible and visual alarms.

5.6 Password Settings


5.6.1 Types of Passwords
If a function key (except the "Query" and "Silence" keys) is operated, the LCD screen will
display a prompt box for password input. Enter the correct password and press "OK" before further
operation. By the security level of the system, the passwords are defined as user password, gas
password and system password from low to high, and a higher level password can be used in lieu of a
lower level password.
The operations that can be performed with a user-level password include: user-level settings
(such as changing the system date and time), start / stop, block / unblock, self-test / cancel self-test,
reset and alarm silencing / starting, and direct control of fire alarm transmission.
To set operations for gas spray control, the screen will prompt for input of a password. Enter a
gas-level password (or a system-level password) and perform related operations. The session expires
when you exit the setting menu. The password will be required when re-enter the menu.
To make system-level settings, such as equipment definition, linkage programming, changing the
important data in the system, the system password is required.
Note: A higher level password can be used in lieu of a lower level password complete all
operations allowed by the low level password.
5.6.2 Chang Password
In the screen shown in Fig. 5-1, Select “6. Password settings" and the password selection button
as shown in Fig. 5-34 will be displayed on the screen.

Fig. 5-34

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


95
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Select the password to be set, and the password setting screen appears (as shown in Fig. 5-34). In
this screen, follow the prompt to enter the user name and new password. To prevent error in inputting,
the control panel requires input of the new password again for confirmation.
If the two passwords input are the same, the control panel will exit the password setting status,
indicating that the password is set successfully; if there is an error, the screen will prompt for
confirming the password input and wait for correction, as shown in Fig. 5-35.

Fig. 5-35

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


96
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

6. Description of System Commissioning Functions

The control panel provides a series of commissioning methods and means to professional
personnel for commissioning of the whole hardware system. The personnel for commissioning the
system must be formally trained and have a clear understanding of the hardware configuration of the
whole system. General operators are not allowed to commission the system; otherwise the normal
operation of the whole system will be impaired!
※ Before commissioning the system, please change the operation mode of the control panel
to "Commissioning".
Press the "System settings" key to enter the setting menu, and select "7. Other settings" to enter
the equipment commissioning selection menu, as shown in Fig. 6-1.

Fig. 6-1

6.1 Fixed Point Commissioning


In the screen shown in Fig. 6-1, select "1. Fixed point commissioning" to enter the screen for
fixed-point commissioning, as shown in Fig. 6-2.
The commissioning personnel can analyze the working condition of the bus equipment and the
interference with the bus cables by making judgment on the code return pulse width of the buses.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


97
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 6-2
In the screen shown in Fig. 6-2, input the circuit number and equipment address of the equipment
to be monitored. After confirmation, select the command mode from options 1~4. After confirmation,
monitoring of the equipment is started. The code return pulse width list returns the code return pulse
width value of the current device.
Note:
◆ The bus device will be started during the fixed-point commissioning. Be careful in
commissioning as this is risky!

6.2 Digital Equipment Commissioning


In the screen shown in Fig. 6-1, select "2. Digital equipment commissioning" to enter the screen
for digital equipment commissioning, as shown in Fig. 6-3.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


98
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 6-3
In the screen shown in Fig. 6-3, Input the circuit number and equipment address of the digital
equipment to be commissioned. After pressing the "OK" key, the commissioning command will be
sent to the digital equipment.

6.3 Modify Equipment Address


In the screen shown Fig. 6-1, select "3. Modify equipment address" to enter the screen for
equipment address modification, as shown in Fig. 6-4.

Fig. 6-4
In the screen shown Fig. 6-4, input the circuit number and equipment address of the equipment to
be changed. After pressing the "OK" key, the secondary address and internal information of the

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


99
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

equipment will appear. After entering the new address, select "Confirm modification" to change the
original address to the new address. Select "Cancel modification" to discard the modification.

6.4 Duplicate Address Detection in All Circuits


The control panel is able to detect duplicate addresses on buses. Duplicate address detection is
used to identify the equipment with duplicate addresses and the number of the duplicate addresses in
the circuits to help the installation and commissioning personnel find the reason for the insufficient
number of registration and eliminate the duplicate addresses. After detection, the results of duplicate
address detection are displayed on the right side of the screen, and the information on duplicate
addresses is written into the running recorder and operation records. In the screen shown in Fig. 6-1,
select "4. Duplicate address detection in all circuits" to start duplicate address detection, as shown in
Fig. 6-5.

Fig. 6-5
Note: After the control panel has completed the equipment registration, the installation and
commissioning personnel should check the number and location of the devices in each circuit
registered in the system. When the number of registered devices is less than the actual installed
number in the circuit, a possible reason is that there are problems in the installation and wiring
of the equipment, or that two or more external devices have the same address (i.e., duplicate
address).
The number of registered devices is less than the number of actually installed devices if
there are duplicate addresses or problems in the installation and wiring of the equipment. The
equipment control panel may fail to display the alarm and fault information of devices not
registered, Therefore, any two devices may have the same address in the same circuit. The
installation and commissioning personnel should ensure that the number of devices registered
by the control panel is consistent with the actual installed ones. If not, GST shall not be liable
for any legal liability for the loss of personnel and property.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


100
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

6.5 Detector Pollution Compensation


During the operation of detectors, the dust pollution in the working environment may lead to the
false alarm raised by the detectors. To reduce false alarm, the control panel provides detector pollution
compensation and correction .
In the screen shown in Fig. 6-1, select "5. Detector pollution compensation" to enter the screen
for detector pollution compensation, as shown in Fig. 6-6.

Fig. 6-6

You can switch the mode by pressing the or keys or the or keys. Press the
"OK" key to save the current setting and exit.
The setting range of pollution compensation value is 105~255. After setting, select "Confirm
modification" to save, or select "Cancel modification" to discard the change and exit the screen.

6.6 Detector Cleaning and Correction


In the screen shown in Fig. 6-1, select "6. Detector cleaning and correction" to start cleaning of
smoke detectors in all circuits, and complete the correction, as shown in Fig. 6-7.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


101
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Fig. 6-7

6.7 Program Upgrade


In the screen shown in Fig. 6-1, select and enter "7. Program upgrade". To upgrade the program
of the main unit, follow the instructions strictly shown in Fig. 6-8.

Fig. 6-8

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


102
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Party IV Configuration and Connection of


Direct Control Panels

 Direct Control Panels

7. Configuration and Connection of Direct Control Panels

7.1 General
JB-QB-GST1500H-EN, JB-QG-GST5000H-EN, JB-QT-GST5000H-EN,
JB-QG-GST9000H-EN, JB-QT-GST9000H-EN Fire Alarm Control Panel / Fire Safety Linkage
Control Panel can be equipped with GST-LD-KZ08H direct control panels.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


103
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

A direct control panel is connected with controlled devices via dedicated cables featuring high
performance and are mainly used for starting and stopping of key equipment such as fire pumps,
smoke exhaust fans and forced draft fans.
7.2 Features
1. Two-wire connection with terminators is adopted to realize the start and stop control of
controlled devices and save wiring costs.
2. With modular design, the number of pads is configured as required (within the maximum number
specified in Appendix I), and each pad has 8 control outputs.
3. Circuit check is provided to identify short circuit and open circuit of the circuits.
4. Key pressing is effective only it is allowed by the manual lock to enhance reliability.
5. The status indication is clear and readily understandable. Each circuit has a separate indicator to
represent the start-up, feedback and fault status.
7.3 Structure Characteristics
7.3.1 Panel Console
The console of the direct control panel has manual locks, start keys, stop keys and status
indicators. Each control unit consists of 2 keys and 3 indicators, as shown in Fig. 7-1. The
components are described below:

Fig. 7-1 Console of direct control panel


① Manual lock: This lock is used to enable or disable manual operation, which can be set as
manual operation disabled or manual operation enabled.
② Disabled indicator: Green; this indicator is lit when the manual lock is in the manual
operation disabled status.
③ Enabled indicator: Green; this indicator is lit when the manual lock is in the manual
operation enabled status.
④ Start key: Green; pressing this key sends a command to start the controlled device.
⑤ Stop key: Red; pressing this key sends a command to stop the controlled device.
⑥ Start indicator: Red; this indicator is lit after a start command is sent; it flashes if no
feedback signal is received within 10 seconds after sending of the start command; it goes
out after the a stop command is sent.
⑦ Feedback indicator: Red; this indicator is lit when feedback signal is received; this
indicator goes out after the feedback signal is recovered.
⑧ Fault indicator: Yellow; this indicator is lit in the case of short circuit or open circuit; this
indicator goes out after the fault is solved.
⑨ Label section: This part is used to mark the location information of controlled equipment.
7.3.2 Interior Structure
The direct control panel is composed of a control console and a output board, which are
connected via flat wires; the control console of direct control panel is connected with the main control
part of the control panel via flat wires; the power supply of the direct control panel is DC24 V, which
is provided by the AC-DC power supply of the control panel or a power supply panel, as shown in Fig.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


104
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

7-2.
Control panel
控制器
Output board
输出板

Control console
控制面板 Panel No.
盘号设置setting
X1

DC24V
power
电源盘supply

Fig. 7-2 Internal connection of direct control panel


7.4 Wiring and Application
The external wiring terminals of the direct control panel are shown in Fig. 7-3:

C1+ C1- C2+ C2- C3+ C3- C4+ C4- C5+ C5- C6+ C6- C7+ C7- C8+ C8-

Fig. 7-3 Wiring terminals of direct control panel


Among the terminals:
Cn+, Cn- (n=1~8): Direct control output terminals, connected to a ZD-02 direct control panel
terminator.
Wiring requirements: BV copper core cables are preferred with cross section≥1.0mm2 and
length ≤1km.
The output of the direct control panel adopts 2-wire cables and is connected to controlled devices
via ZD-02 direct control panel terminators. One channel of output is enough for control of devices
allowing starting and stopping, as shown in Fig. 7-4.
The contact capacity of ZD-02 direct control panel terminator is 5A220VAC or 5A24VDC.
DC or AC
DC或AC


drirect control panel

Controlled
equipment

C1+ C+ 被
ZD
Output board of

控 NC
Equipment side

控 - 控
Control panel

盘 设

制 输 02 NO 备


Feedback side
terminator

出 终 端
板 C1- C- 端 I 反
器 馈
G 端

Fig. 7-4 Application of direct control panel


7.5 Use and Operation
7.5.1 Panel Number Setting
In a control panel, each direct control panel has a unique pad number. A pad number is composed
of 5 binary digits.
Pad numbers can be set with 5P pins on the back of direct control panels. If there is a short
circuit block on a pin, it means that the bit is 1; if there is no short circuit block, the bit is 0; the binary

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


105
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

weight corresponding to each number is shown in table 7-1


Table 7-1 Binary weight
Bit No. 5 4 3 2 1
With short 16 8 4 2 1
circuit
block
Without 0 0 0 0 0
short circuit
block

Pad number calculation formula:


Pad number = (5th weight + 4th weight + 3rd weight + 2nd weight + 1st weight) + 1
For example, with X1 pins arranged as shown in Fig. 7-5, the pad number = (0 + 0 + 4 + 0 + 1) +
1=6

Panel 6
6号盘

Fig. 7-5
7.5.2 Turn On
After the pad numbers are set, turn on the power supply of the control panel after checking that
the wiring is correct. The total number of direct control panels registered by the control panel should
be consistent with the actual total number.
7.5.3 Self-Test
All the indicators of the direct control panels can be checked with the "sound and light signal
self-check" function of the control panel. After the self-test starts, all the indicators on the console of
the direct control panels are lit, and then the indicators of each channel are lit in turn. After the
self-test, the indicators return to the status before the self-test.
7.5.4 Direct Control Panel Definition
The devices controlled by the direct control panels should be defined first before use. See "5.2
Equipment Definition" for details.
In the screen for direct control panel definition, the "Device characteristics" field is used to set
the control output mode of each channel being "Level output" or "Pulse output".
• When the output is set to the "Level output" mode, press the Start key to start signal output,
which will be held until pressing of the stop key.
• When the output is set to the "Pulse output" mode, press the Start key to start signal output,
which will be turned off automatically about 5 seconds after the pressing.
In the screen for direct control panel definition the "Function switch" field is used to set the
output circuit check function of each channel, which can be set as "Circuit check enabled" or "Circuit
check disabled".
• If it is set to "Circuit check enabled", when there is an open circuit or short circuit between
the output and the terminator on the equipment side, the direct control panel will report the
circuit fault, and the "Fault" indicator for the output will be lit;
• If it is set to "Circuit check disabled", the direct control panel do not check fault in the
external circuit.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


106
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Note: For the channels connected with controlled devices, to ensure real-time monitoring of
circuit fault, "Circuit check enabled" should be set for these channels"! "Circuit check disabled" may
be set for channels not in use.
7.5.5 Manual Control
You may set the operation authority with the manual lock on a direct control panel. When the
lock is in the "Allowed" position, operation with the start or stop key is effective; otherwise, the key
operation is invalid.
In the "Manual allowed" mode:
 When the "Start" key of a channel is pressed, the "Start" indicator is lit, and the start
command is sent, and the corresponding controlled device should act. When the direct control
panel receives feedback signal from the controlled device, the "Feedback" indicator of the channel
is lit. If no feedback signal is received from the channel within 10 seconds after the start command
is sent by the direct control panel, the "Start" indicator flashes.
 Press the "Stop" key of the channel, the "Start" indicator goes out, the stop command is sent,
and the start signal of the controlled device is revoked.
Note:
⚫ To ensure the reliability of key operation, wait for more than 1 second before the next key
pressing.
⚫ Usually, the manual lock should be set to "Not allowed" status to avoid misoperation.
7.5.6 Automatic Control
You may enable automatic control of the control output of the direct control panels with the
preset linkage formulas on the control panel. First, write linkage formulas according to the definitions
of the direct control panels, and make them the equipment items of the linkage formulas. In the
"Automatic allowed" mode, the control panel will automatically execute the start or stop control
output by the direct control panels after the conditions of the linkage formulas are met.
Note: Automatic control is not subject to the manual lock’s authority and is possible in the
"Manual not allowed" mode.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


107
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Part V Special Instructions

 Handling of Fault and Abnormal Information and Regular


Inspection

 Precautions

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


108
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

8. Handling of Fault and Abnormal Information and Regular

Inspection

8.1 General Troubleshooting


Table 8-1
S/N Fault Cause Solution
1 The display shows a. Abnormality in power a. Check the power supply
nothing or works supply b. Check the connecting
abnormally after b. Poor connection of cables
startup backlight board cables
2 "Primary power a. No AC power supply a. Check and properly connect
supply failure" b. Broken AC fuse the AC power cable
appears after startup b. Replace the AC fuse (See
the label for parameters)
3 "Backup power a. Broken fuse a. Replace the fuse (See label
supply failure" after b. Poor connection of for parameters)
startup cable b. Open the power box and
c. Empty or damaged check the related connectors
battery c. Keep the machine on with AC
power supply for more than 8
hours. Replace the battery if the
fault persists
4 Incorrect registration a. Circuit cards not in a. Check and plug in the
of circuit cards place boards properly
b. Wrong mainboard b. Check and set the
number setting mainboard number again
5 Failure to register Wrong or poor connection Check the power cable and
external display panel of communication cables communication cable of the fire
display panel
6 Failure to print a. Not in print mode a. Try to set the print mode
b. Poor connection of b. Check and connect the
printer cable cable properly
c. Broken printer c. Change the printer
7 No response when Poor connection of manual Check and connect the cables
pressing the manual panel cables properly
key
8 Device failure a. The device is a. Check the connection
disconnected b. Change the device
b. The equipment is
damaged
9 Bus fault Bus short circuit Check the bus
10 Clock failure, a. Interference from the a. Check if the grounding is
storage failure, environment proper
circuit failure, etc., b. Aging of certain parts b. Inform the Technical
Service Department of GST
11 The measured value The short circuit block of Pull out the short circuit block
of insulation the board corresponding to and re-measure the resistance
resistance exceeds the terminal is not pulled After the measurement, plug it
the standard values. out in again

8.2 Printer Maintenance


8.2.1 Replace Printing Paper
The printer is composed of the turnable front cover of the panel, paper roll, printer head, etc. Turn

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


109
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

open the front cover of the panel to remove the printing paper roll. Replace the printing paper when it
is used out. The change procedure is described as follows:
1) Turn on the front cover, press down the ends of the paper axis inside printer and take it out;
2) Put the new thermal printing paper into the printer. Be careful to put the smooth surface
(heat-sensitive surface) of the printing paper facing upward, and then close the front panel of the
printer.
8.2.2 Self-Test
When the printer is powered on and in the standby mode (no printing or paper feeding in progress),
press and hold the paper feeding button for a while (2 seconds), and the printer will print out a self-test
list. This is used to check whether the printer works normally except the parts, especially the working
condition of the print head.
8.2.3 Operation Status
 Normal standby status: The green indicator is lit;
 Out of paper: The green indicator flashes four times at intervals;
 Over-temperature: The green indicator flashes slowly;
Note: In the process of use, keep the printing paper roll in a tight status. The diameter of the
paper roll will increase when it is loose, handicapping paper fed through the printing head.
8.3 Battery Maintenance
When the machine is turn off, the backup power switch must be turned off too. Otherwise, the
backup power supply will be consumed by circuits inside the control panel to the empty level, leading
to the risk of damaging the battery. The maintenance free lead-acid battery used by the control panel
has a small discharge current, it needs to be regularly charged and maintained. If the control panel is
not used for an extended period of time, it should be charged for 48 hours every month. If the control
panel relies on the backup power supply due to failure of the primary power supply, the backup power
supply may become empty, so it is necessary to restore the primary power supply as soon as possible
and charge the battery for 48 hours. If the backup power supply remains empty for more than one
week, the battery may be damaged. It is recommended that the battery be replaced at least every three
years.

9. Scrapping

The scrapping of the product shall be subject to GB 29837 Maintenance and discard for fire
detection and alarm. Generally, the service life of a fire detection / alarm device does not exceed 12
years, and the service life of gas sensors in combustible gas detectors and lasers in optical fiber
products does not exceed 5 years. The product should be scrapped when its service life expires. To use
the product after its service life expires, the party using or monitoring the product shall inspect and
test the product every year according to the said standard, and carry out system performance test. The
product can be used further after all the inspection and test results are found acceptable.

10. Precautions

 The control panel is a sophisticated electronic product, which should be supervised by


dedicated personnel and not operated by others without authorization.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


110
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

 The operators should keep records on duty carefully. If there is an alarm, press the "Silence"
key on the control panel first and quickly confirm the fire conditions and then deal with it
appropriately. After the fire alarm is dealt with, keep records of the operation, and then press
the "Reset" key to clear it. If it is confirmed as false alarm, after the records are kept, the
detector or module raising the alarm may be blocked, and the Technical Service Department
of GST should be contract for servicing.

 GST is responsible for servicing the control panel during its warranty period. Please contact
the Technical Service Department of GST in a timely manner if you have any problem with
the control panel. Do not try to disassemble or repair the controller by yourself, otherwise
you are solely liable for consequences arising from such acts.

 The product should only be installed in the operating environment specified in this
Installation and Operation Manual, and it is not intended for use at places with explosive or
corrosive gases (including tobacco warehouses). The product is not suitable for use in
environments or facilities with special certification requirements for equipment (including
but not limited to explosive environments, ships, aircrafts, trains, motor vehicles and other
means of transportation). If you have special requirements, please contact our sales
representatives.

 The users shall install, configure, use and maintain the control panel in accordance with the
relevant applicable national and industrial standards for fire detection and alarm, and in
accordance with the installation and operation manual and / or user manual supplied with the
product. When using this product with third-party products, the users should follow the
relevant national or industrial regulations and product specifications, and carry out system
testing to ensure the electrical and mechanical compatibility between these products. GST
shall not be liable for any matter, liability or loss caused by non-compliance with the above
requirements. If you have special requirements, please contact our sales representatives.

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


111
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Appendix I Technical Indicators


LCD Display:

JB-QB-GST1500H-EN: 800 × 480 pixels, 7.0" color LCD display

JB-QG/QT-GST5000H: 800 × 480 pixels, 7.0" color LCD display

JB-QG/QT-GST9000H: 800 × 600 pixels, 10.4" color LCD display, optional touch screen

Chinese characters: standard first- and second- level font library

Control Panel Capacity:

JB-QB-GST1500H-EN Control Panel:


Circuit card: Up to 3 circuit cards, 6 bus circuits and 1,452 points depending on actual project
needs.
Manual panel: Up to 1 piece, 128 channels.
Direct control panel: Up to 1 piece, 8 channels.
Up to 5 circuit cards / communication boards in total.
JB-QG/QT-GST5000H control panel:
Circuit card: Up to 10 circuit cards, 20 bus circuits and 4,840 points depending on actual
project needs.
Manual panel: Up to 12 piece, 128 channels.
Direct control panel: Up to 24 piece, 8 channels.
Up to 16 circuit cards / communication boards in total.
JB-QG/QT-GST9000H control panel:
Up to 60 bus circuits, 242 address points per circuit.
Up to 12 manual panels depending on actual project needs.
Up to 24 direct control panels depending on actual project needs.
Up to 36 circuit cards / communication boards in total.
Ambient Temperature: 0ºC~+40ºC
Relative Humidity: ≤95%, no condensation
Enclosure Protection Class: IP30

Power Supply:

JB-QB-GST1500H-EN Control Panel

Primary Power Supply: AC 220V (3.15A), -15%~+10%

Backup Power Supply: DC 24V, 12V/14Ah, sealed lead acid battery (2 cells)

JB-QG/QT-GST5000/9000H-EN control panel

Primary Power Supply: AC 220V (6.3A), -15%~+10%

Backup Power Supply: DC 24V, 12V/50Ah, sealed lead acid battery (2 cells)

GST-LD-D02H intelligent power supply panel

Output 1: 24V/2A (output voltage changes with the back power supply when the back power
supply is used)

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


112
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Output 1 + Output 2: 24V/8A (output voltage changes with the back power supply when the
back power supply is used)

GST-LD-D06H intelligent power supply panel

Output 1: 24V/8A (output voltage changes with the back power supply when the back power
supply is used)

Output 2: 24V/8A (output voltage changes with the back power supply when the back power
supply is used)

Output 3: 24V/8A (output voltage changes with the back power supply when the back power
supply is used)

Circuit Load Capacity: The maximum output capacity of each circuit is 700mA. The actual load
capacity shall be calculated based on maximum working current of load and the length and
cross-section area of cables. To ensure the reliable operation of the equipment, the terminal voltage
of the cables shall be ≥ 16V.

The following table gives the number of two-wire audible and visual alarms that can be
connected to one circuit under different wire diameters and is for information only.

Number of two-wire
Cross-section area Length of test cable Number of standby audible and visual
of test cable (mm2) (m) devices (points) alarms (points) to be
started

1.0 70

1.5 1000 242 110

2.5 170

Wire System:
Category Cable Distance Remarks
BV cable of
AC220V input cable 3 conductors
1.0mm²-4.0mm²
The actual distance is related to
the wire diameter and load
BV cable of
DC24V output cable current. 4.0 mm2 are
2.5mm²-4.0mm²
recommended for trunk cables
and 2.5 mm2 for branch cables.
The actual distance is related to
1.0 mm2 the wire diameter and load
Twisted pair cables are ≤2km current. The test condition of
recommended 2km is that the maximum load
current is 150mA.
The actual distance is related to
24V two-wire bus
1.5 mm2 the wire diameter and load
without polarity.
Twisted pair cables are ≤3km current. The test condition of
recommended 3km is that the maximum load
current is 150mA.
2.5mm2 The actual distance is related to
Twisted pair cables are ≤3km the wire diameter and load
recommended current. The test condition of

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


113
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

3km is that the maximum load


current is 250mA.
Direct control panel Support for start/stop dual
BV cable ≥1.0mm2 ≤1km
output cable control via two wires
Audible and visual
BV cable ≥1.0mm2 ≤1km
alarm output cable
RS-485 Shielded twisted pair Modbus communication with
≤1.2km
communication bus cable ≥1.0 mm2 third-party equipment
Communication with graphic
RS-422 Shielded twisted pair
≤1.2km display devices or fire alarm
communication bus cable ≥1.0 mm2
transmission devices
CAN Shielded twisted pair
≤3km Networking of control panel
communication bus cable ≥1.0mm2
Optical fiber 2-cable single mode Optical fiber attenuation
communication fiber, light wavelength ≤20km coefficient ≤0.5dB/km
cable 1,310nm, LC connector Networking of control panel
Ethernet
communication CAT5.E cable ≤100m Networking of control panel
cable
Control Panel Monitoring Power Consumption (1500H-EN)
Monitoring power consumption = basic power consumption 7W (no load) + single dual-circuit
card monitoring power consumption 6W (484 bus devices) * circuit card number
Maximum Power Consumption of Control Panel (1500H-EN)
Alarm power consumption = basic power consumption 7W (no load) + alarm power consumption
of single double-circuit card 12W (484 bus devices) * circuit card number + 12W (24V output)

Control Panel Monitoring Power Consumption (5000H)


Monitoring power consumption = basic power consumption 8W (no load) + single circuit-board
monitoring power consumption 6W (484 bus devices) * circuit card number
Maximum Power Consumption of Control Panel (5000H)
Alarm power consumption = basic power consumption 8W (no load) + alarm power consumption
of single circuit card 12W (484 bus devices) * circuit card number + 220W (24V output)
Control Panel Monitoring Power Consumption (9000H)
Monitoring power consumption = basic power consumption 8W (no load) + single circuit-board
monitoring power consumption 6W (484 bus devices) * circuit card number
Maximum Power Consumption of Control Panel (9000H)
Alarm power consumption = basic power consumption 8W (no load) + alarm power consumption
of single circuit card 12W (484 bus devices) * circuit card number + 220W (24V output)

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


114
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Appendix II Equipment Type Table


External Device Definition
Code Equipment Code Equipment Code Equipment Code Equipment
type type type type
00 Not defined 23 Smoke 46 Evacuation 69 Combustibl
exhaust valve indication e gas
01 Grating 24 Air supply 47 Spray 70 Backup
temperature valve indication indication
measureme
nt
02 Point type 25 Solenoid 48 Anti-theft 71 Door lamp
heat valve module
detector
03 Point type 26 Rolling 49 Signal disc 72 Standby
smoke shutter door - valve work
detector middle
04 Alarm 27 Rolling 50 Fire 73 Equipment
interface shutter door - protection fault
bottom smoke
exhaust
valve
05 Combined 28 Normally 51 Water 74 Sensor
flame closed door curtain
pump
06 Optical 29 Pressure 52 Floor 75 Power
light beam switch number sign supply for
smoke lamp clock
detector
07 Ultraviolet 30 Water flow 53 Equipment 76 Audible and
flame indicator stop visual alarm
08 Line heat 31 Lift 54 Pump fault 77 Alarm
detector transmissio
n
09 Aspirating 32 Air 55 Emergency 78 Loop switch
smoke conditioning start key
detector unit
10 Combined 33 Diesel power 56 Emergency 79 Broadcastin
detector generation stop key g branch
line
11 Manual key 34 Lighting 57 Deluge 80 Reserved
power pump
distribution
12 Fire 35 Utility power 58 Upper 81 Fire hydrant
broadcastin distribution computer
g
13 Sounder 36 Water curtain 59 Circuit 82 Cable type
solenoid valve heat
detector
14 Fire 37 Gas start 60 Air 83 Aspirating
telephone compressor smoke
detector

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


115
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

15 Fire hydrant 38 Gas stop 61 Linkage 84 Aspirating


power fire alarm
supply
16 Fire hydrant 39 Slave 62 Telephone 85 Aspirating
pump jack early
warning
detector
17 Sprinkler 40 Fire indicator 63 Partial 88 Home
pump panel equipment smoke
detector
18 Stabilized 41 Home 64 Deluge 89 Leakage
pressure computer valve alarm
pump
19 Fume 42 Normally 65 External 95 Leakage
extractor open door control and
allowed temperature
measurement
20 Forced draft 43 Foam pump 66 Fault output
fan
21 Fresh air 44 Fire power 67 Manual
fan supply allowed
22 Fireproof 45 Emergency 68 Automatic
valve lighting allowed

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


116
Installation and Operation Manual for Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Appendix III Commissioning Form


Bus device
Bus Termina Insulation Impedance Actual Registered Remarks
Circuit No. l name resistance (Zn1-Zn2/Zn2-Zn1) number of number of
loads loads
1
2
3
4
5
6
7
8
9
10
Fire display panel
Bus Terminal Insulation Impedance Actual Registered Remarks
Circuit name resistance (A-B) number number
No.
1
2
Manual startup panel
Total of manual Registered total
startup panel
No. Location Circuit No. Pad No. Remarks
1
2
3
4
Direct control panel
Pad No. Chann Output mode Function Switch (On/Off) Remarks
el No. (level/pulse)

Gulf Security Technology Co., Ltd. http://www.gst.com.cn


117
Installation and Operation Manual for JB-QB-GST1500H-EN/ JB-QG/QT-GST5000/9000H Fire Alarm Control Panel / Fire Safety Linkage Control Panel

Appendix IV Quick Start Guide

Quick Start Guide


Handle Fire Alarm:
 In the case of abnormal sound or light indication, smell, etc., turn off the power supply
When a fire alarm is raised, first press "Silence" to stop the alarm sound. Check the location immediately and contact the installation contractor or manufacturer as soon as possible;
where the fire alarm is initiated with the alarm information in the control pane. If there is fire,
Start / Stop:
take necessary measures depending on the fire conditions. For example:
 Start audible and visual alarms at the site to send out alarm sound and light to evacuate of When the occurrence of fire is ascertained, manually start the firefighting equipment quickly.
the personnel at the site; First confirm whether the devices are bus devices or directly controlled device.
 Call the fire brigade;  Bus device: Find the unit corresponding to the device to be started according to the
 Start firefighting equipment, etc. information in the glass window of the manual panel. Press the manual key of this unit, and the
In case of false alarm, take the following measures: command light is lit, indicating that the start command is sent out. Press the key again, and the
 Check whether there is too much dust or unduly high temperature in the fire alarm area, command light goes out, indicating that the start command is terminated.
and confirm whether it is caused by human or other factors;  Directly controlled device: Find the unit corresponding to the device to be started
 Press "Reset" to restore the control panel to the normal status, and observe whether there according to the label of the direct control panel. Press the manual key of this unit, and the
is any further false alarm; if so, block the detector raising the false alarm if necessary and contact command light is lit, indicating that the start command is sent out. If the device is in the level
the installation contractor or manufacturer for servicing as soon as possible. control mode, by pressing this key again, the command light goes out and the start command will
be terminated; if the device is in the pulse control mode, it is necessary to find the unit for
Handle Fault and Abnormal Information
stopping the device and press the manual key of the unit, and then the start command is
When a fault occurs, first press "Silence" to stop the alarm sound. Check the location where terminated.
the fault occurs with the alarm information in the control pane. If there is fault, take necessary  If the linkage formula has been defined, the corresponding equipment can be started
measures depending on the actual conditions. through the linkage start key.
 When a fault of the primary power supply is reported, check whether there is a mains
Unlock Keyboard
power failure; if not, check whether the wiring or fuses of the primary power supply is broken.
When the primary power supply is off, the backup power supply can provide power continuously The keyboard of the control panel is locked when the control panel is turned on. If a
for 8 hours; function key (except the "Query" and "Silence" keys) is operated, the LCD screen will display a
 When a fault of the backup power supply is reported, check the connectors and wiring of prompt box for password input. Enter the correct user password and press "OK" to unlock the
the standby battery; when the standby battery has been used to provide power continuously for keyboard and conduct further operation.
more than 8 hours, the fault may be caused by excessive low voltage of the standby battery;
Protection of Backup Power Supply:
 In the case of a fault with the field equipment, have the equipment serviced in a timely
manner. If the fault cannot be solved in a timely manner due to special reasons, block the device When using the backup power supply, note that the backup power supply should not be used
if necessary, and unblock it after the fault is solved; for more than 8 hours. When the backup power supply has been used for 8 hours, turn off the
 When the cause of the fault is unknown or cannot be solved, contact the installation contractor or backup power supply of the control panel, and turned it only when the primary power supply is
manufacturer for servicing as soon as possible; restored to prevent battery damage.

Gulf Security Technology Co., Ltd . http://www.gst.com.cn


118
E03

Gulf Security Technology Co., Ltd.


No. 80, Changjiang East Road, QETDZ, Qinhuangdao,
Hebei, P. R. China
Tel: 0335-8502468
Fax: 0335-8508942
Post Code: 066004
Service hotline in China: 400 612 0119

http://www.gst.com.cn 30313208
E-mail:gst.qhd@fs.utc.com

You might also like