You are on page 1of 30

Ruiru Petrol Station Electrical Installation Bills of Quantities

ITEM DESCRIPTION UNIT QTY RATE AMOUNT


(KES) (KES)
1.00 GROUND FLOOR - Car wash, Service Center,
Washroom, Canopy

LIGHTING POINTS AND FITTINGS


Supply, Install, Set to Work, Test and Commission the
following:-
1.01 Lighting points wired in 3x1.5mm2 PVC insulated single No. 50 750.00 37,500.00
core (SC) copper wires drawn in 20mm diameter HG PVC
conduit concealed in walls and or floor slabs with all
accessories but excluding switch and fitting for one way
switching.
1.02 Ditto but for two way switching. No. 4 900.00 3,600.00
1.03 10 meter high galvanized security lighting column made No. 7 35,000.00 245,000.00
from Class 'B' 150mm & 100mm Ø continuosly tapered
planting depth of 1,200m with cable entry notch at 700mm
galvanized steel pipe with plate welded at the bottom and
inspection chamber with hinged door
lockabke at 1,200mm from the ground level to NCC
standards.

1.04 Square luminaire mounting bracket constructed from No. 7 5,000.00 35,000.00
400mm x 400mm MS Angle line for mounting the flood
lights

1.05 Allow for foundation works at the base of each column for No. 7 1,000.00 7,000.00
item 1.03 i.e. excavation, mounting the pole, back filling,
compaction and making good as directed by the Engineer

1.06 Wiring from the lighting fitting to the circuit breaker with Lm 290 250.00 72,500.00
1.5mm² TWE cord.

1.07 Trenching at an average depth of 750 mm laying all Lm 220 250.00 55,000.00
underground cables for the external lighting, 'HATARI'
tilling and backfilling

Supply, Install, set to work,test and Commission the


following as marked on drawings:-
1.08 10A 1 gang 1 way single pole switch No. 12 150.00 1,800.00
1.09 10A 1 gang 2 way single pole switch No. 1 150.00 150.00
1.10 10A 2 gang 2 way single pole switch No. 1 300.00 300.00
1.11 10A 2 gang 1 way single pole switch No. 1 300.00 300.00
1.12 10A 3 gang 1 way single pole switch No. 1 400.00 400.00

Total Carried Forward to the Next Page 458,550.00

Page 1 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

ITEM DESCRIPTION UNIT QTY RATE AMOUNT


(KES) (KES)

Balance Brought Forward from the Previous Page 458,550.00

Supply, Install, set to work, test and Commission the


following as marked on drawings:-

1.13 Type 'F' - Outdoor 50W LED floodlight as Philips No. 8 5,000.00 40,000.00
Catalogue number BVP154 LED52/857 PSU 50W VWB
CE

1.14 Type "B5" - 200W LED External Floodlight pole mounted No. 7 15,000.00 105,000.00
as Philips Cat. No. BVP155 LED210/857 PSU 200W
VWB CE

1.15 Type "Z1": Circular downlighter with 13w LED lamp No. 4 2,000.00 8,000.00

1.16 Type "E2": 18W Circular surface luminaire with opal No. 17 2,000.00 34,000.00

1.17 Type "4": 1x18w 1200mm led tube No. 18 2,000.00 36,000.00

1.18 Type B7: IP65 18W LED External Bulkhead Light fitting No. 3 3,000.00 9,000.00

1.19 Type 2: 1x18w mirror light with ON/OFF toggle switch No. 4 2,500.00 10,000.00

Total Carried Forward to the Next Page 700,550.00

Page 2 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

ITEM DESCRIPTION UNIT QTY RATE AMOUNT


(KES) (KES)

Balance Brought Forward from the Previous Page 700,550.00

POWER POINTS AND OUTLETS


Supply, Deliver, Install, Set to Work and Commission
the following:-
1.20 Power outlet points wired as for a ring main circuit in 3 x No. 13 1,200.00 15,600.00
2.5mm2 PVC single core (SC) copper cables drawn in
25mm dia HG PVC conduits concealed in walls and floors
slabs complete with all accessories but excluding the
socket outlet plate.

1.21 Power outlet points wired as for a radial circuit in No. 7 1,350.00 9,450.00
3x4.0mm2 PVC single core (SC) copper cables drawn in
32mm diameter HG PVC conduits concealed in walls and
floors slabs complete with all accessories for fuel pumps,
air gauge, and carwash machines but excluding the
isolator.

1.22 Power outlet points wired in 3x1.5mm2 PVC single core No. 11 1,000.00 11,000.00
(SC) copper cables drawn in 20mm diameter HG PVC
conduits concealed in walls and floors slabs complete with
all accessories for signages but excluding the switches.

Total Carried Forward to the Next Page 736,600.00

Page 3 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

ITEM DESCRIPTION UNIT QTY RATE AMOUNT


(KES) (KES)

Balance Brought Forward from the Previous Page 736,600.00

Supply, install, set to work, test and commission the


following as marked on drawings:-

1.23 13A flush mounted twin switched socket outlet No. 13 500.00 6,500.00

1.24 32A single phase isolator switch (fuel pumps, air gauge, No. 7 3,000.00 21,000.00
and carwash machines)

1.25 8 Gang, 1 Way Grid switches for signages No. 2 25,000.00 50,000.00

ELV CABLE WAYS


(TELEPHONE, DATA, TV & SECURITY)
Supply, Install, Set to Work, test and Commission the
1.26 Data & WiFi Access point outlets comprising of 25mm No 0 500.00
diameter HG PVC conduit and draw wire from the adaptor
box to all internal points concealed in the walls and floor
complete with all accessories except faceplate.

1.27 CCTV points comprising of 25mm diameter HG PVC No 7 500.00 3,500.00


conduit and draw wire to all internal points linked to
Network Video Recorder (NVR) location.

Supply, Deliver, Install, Set to Work and Commission


the following:-
1.28 Bullet and Dome CCTV cameras No 7 30,000.00 210,000.00

Total Carried Forward to the Next Page 1,027,600.00

Page 4 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

ITEM DESCRIPTION UNIT QTY RATE AMOUNT


(KES) (KES)

Balance Brought Forward from the Previous Page 1,027,600.00

1.29 RJ45 data outlet point No 0 300.00

FIRE DETECTION AND ALARM


Supply, Deliver, Install, Set to Work and Commission
1.30 Heat detectors No 3 2,500.00 7,500.00

1.31 Manual Break glass (Call point) No. 2 1,800.00 3,600.00

1.32 Electronic sounder No. 2 7,500.00 15,000.00

POWER DISTRIBUTION
Supply, Install, Set to Work, test and Commission the
1.33 125A 4-Way TPN Distribution board complete with 125A No. 2 13,500.00 27,000.00
TP intergral isolator

1.34 10A SP MCB No. 8 450.00 3,600.00

1.35 32A SP MCB No. 8 450.00 3,600.00

1.36 Distribution board blanking plates Item 2 500.00 1,000.00

1.37 Earthing and labelling of the distriution board Item 2 1,000.00 2,000.00

1.38 16mm2 Cu/ XLPE/PVC 4 core + 10 Cu/PVC SC ECC Lm 10 3,000.00 30,000.00


cables from Sub Main LV Switch Board to Consumer
Units

Total Carried Forward to Collection Page 1,120,900.00

Page 5 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

ITEM DESCRIPTION UNIT QTY RATE AMOUNT


(KES) (KES)
2.00 GROUND FLOOR - Supermarket, Shop, and
Restaurant

LIGHTING POINTS AND FITTINGS


Supply, Install, Set to Work, Test and
Commission the following:-
2.01 Lighting points wired in 3x1.5mm2 PVC insulated No. 14 750.00 10,500.00
single core (SC) copper wires drawn in 20mm
diameter HG PVC conduit concealed in walls and
or floor slabs with all accessories but excluding
switch and fitting for one way switching.
2.02 Ditto but for two way switching. No. 21 900.00 18,900.00

Supply, Install, set to work,test and Commission


the following as marked on drawings:-

2.03 10A 1 gang 1 way single pole switch No. 5 150.00 750.00
2.04 10A 1 gang 2 way single pole switch No. 1 150.00 150.00
2.05 10A 2 gang 2 way single pole switch No. 3 300.00 900.00
2.06 10A 2 gang 1 way single pole switch No. 1 300.00 300.00
2.07 10A 3 gang 1 way single pole switch No. 0 400.00

Total Carried Forward to the Next Page 31,500.00

Page 6 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

Balance Brought Forward from the Previous Page 31,500.00

Supply, Install, set to work, test and Commission


the following as marked on drawings:-

2.08 600mm, 4x18w LED tube lamps with louvres No. 17 3,000.00 51,000.00

2.09 Type "B5" - 200W LED External Floodlight pole No. 0 15,000.00
mounted as Philips Cat. No. BVP155 LED210/857
PSU 200W VWB CE

2.10 Type "Z1": Circular downlighter with 13w LED No. 13 2,000.00 26,000.00
lamp
2.11 Type "E2": 18W Circular surface luminaire with No. 0 2,000.00
opal glass

2.12 Type "4": 1x18w 1200mm led tube No. 3 2,000.00 6,000.00

2.13 Type B7: IP65 18W LED External Bulkhead Light No. 2 3,000.00 6,000.00
fitting

2.14 Type 2: 1x18w mirror light with ON/OFF toggle No. 0 2,500.00
switch

Total Carried Forward to the Next Page 120,500.00

Page 7 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

Balance Brought Forward from the Previous Page 120,500.00

POWER POINTS AND OUTLETS


Supply, Deliver, Install, Set to Work and
Commission the following:-
2.15 Power outlet points wired as for a ring main circuit No. 28 1,200.00 33,600.00
2
in 3 x 2.5mm PVC single core (SC) copper cables
drawn in 25mm dia HG PVC conduits concealed in
walls and floors slabs complete with all accessories
but excluding the socket outlet plate.

2.16 Power outlet points wired as for a radial circuit in No. 0 1,350.00
2
3x4.0mm PVC single core (SC) copper cables
drawn in 32mm diameter HG PVC conduits
concealed in walls and floors slabs complete with
all accessories for fuel pumps, air gauge, and
carwash machines but excluding the isolator.

2.17 Power outlet points wired in 3x1.5mm2 PVC single No. 4 1,000.00 4,000.00
core (SC) copper cables drawn in 20mm diameter
HG PVC conduits concealed in walls and floors
slabs complete with all accessories for signages but
excluding the switches.

Total Carried Forward to the Next Page 158,100.00

Page 8 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

Balance Brought Forward from the Previous Page 158,100.00

2.18 Power outlet points wired as for a radial circuit in No. 2 1,800.00 3,600.00
2
3x6.0mm PVC single core (SC) copper cables
drawn in 32mm diameter HG PVC conduits
concealed in walls and floors slabs complete with
all accessories for cooker unit but excluding the
cooker control DP unit.

Supply, install, set to work, test and commission


the following as marked on drawings:-

2.19 13A flush mounted twin switched socket outlet No. 28 500.00 14,000.00

2.20 45A Cooker control unit with switched single No. 2 600.00 1,200.00

2.21 45A Cooker connection unit No. 2 300.00 600.00

2.22 8 Gang, 1 Way Grid switches for signages No. 0 25,000.00

ELV CABLE WAYS


(TELEPHONE, DATA, TV & SECURITY)
Supply, Install, Set to Work, test and
2.23 Data & WiFi Access point outlets comprising of No 5 500.00 2,500.00
25mm diameter HG PVC conduit and draw wire
from the adaptor box to all internal points concealed
in the walls and floor complete with all accessories
except faceplate.

2.24 CCTV points comprising of 25mm diameter HG No 4 500.00 2,000.00


PVC conduit and draw wire to all internal points
linked to Network Video Recorder (NVR) location.

Supply, Deliver, Install, Set to Work and


Commission the following:-
2.25 Bullet and Dome CCTV cameras No 4 30,000.00 120,000.00

Total Carried Forward to the Next Page 302,000.00

Page 9 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

Balance Brought Forward from the Previous Page 302,000.00

2.26 RJ45 data outlet point No 5 300.00 1,500.00

FIRE DETECTION AND ALARM


Supply, Deliver, Install, Set to Work and
2.27 Heat detectors No 5 2,500.00 12,500.00

2.28 Manual Break glass (Call point) No. 0 1,800.00

2.29 Electronic sounder No. 0 7,500.00

POWER DISTRIBUTION
Supply, Install, Set to Work, test and
2.30 63A 4-Way SPN Consumer unit complete with No. 1 5,000.00 5,000.00
63A Single phase intergral isolator (Shop)

2.31 63A 6-Way SPN Consumer unit complete with 63A No. 1 6,000.00 6,000.00
Single phase intergral isolator (Supermarket)

2.32 63A 10-Way SPN Consumer unit complete with No. 1 8,000.00 8,000.00
63A Single phase intergral isolator (Restaurant)

2.33 10A SP MCB No. 4 450.00 1,800.00

2.34 32A SP MCB No. 8 450.00 3,600.00

2.35 Distribution board blanking plates Item 3 500.00 1,500.00

2.36 Earthing and labelling of the distriution board Item 3 1,000.00 3,000.00

2.37 16mm2 Cu/ XLPE/PVC 4 core + 10 Cu/PVC SC Lm 130 3,000.00 390,000.00


ECC cables from Sub Main LV Switch Board to
Consumer Units

Total Carried Forward to Collection Page 734,900.00

Page 10 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

ITEM DESCRIPTION UNIT QTY RATE AMOUNT


(KES) (KES)
3.00 FIRST FLOOR - Offices and Common areas

LIGHTING POINTS AND FITTINGS


Supply, Install, Set to Work, Test and
Commission the following:-
3.01 Lighting points wired in 3x1.5mm2 PVC insulated No. 14 750.00 10,500.00
single core (SC) copper wires drawn in 20mm
diameter HG PVC conduit concealed in walls and or
floor slabs with all accessories but excluding switch
and fitting for one way switching.
3.02 Ditto but for two way switching. No. 4 900.00 3,600.00

Supply, Install, set to work,test and Commission


the following as marked on drawings:-
3.03 10A 1 gang 1 way single pole switch No. 5 150.00 750.00
3.04 10A 1 gang 2 way single pole switch No. 2 150.00 300.00

Total Carried Forward to the Next Page 15,150.00

Page 11 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

Balance Brought Forward from the Previous Page 15,150.00

Supply, Install, set to work, test and Commission


the following as marked on drawings:-

3.05 600mm, 4x18w LED tube lamps with louvres No. 7 3,000.00 21,000.00

3.06 Type "Z1": Circular downlighter with 13w LED No. 11 2,000.00 22,000.00
lamp

Total Carried Forward to the Next Page 58,150.00

Page 12 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

Balance Brought Forward from the Previous Page 58,150.00

POWER POINTS AND OUTLETS


Supply, Deliver, Install, Set to Work and
Commission the following:-
3.07 Power outlet points wired as for a ring main circuit No. 8 1,200.00 9,600.00
2
in 3 x 2.5mm PVC single core (SC) copper cables
drawn in 25mm dia HG PVC conduits concealed in
walls and floors slabs complete with all accessories
but excluding the socket outlet plate.

Total Carried Forward to the Next Page 67,750.00

Page 13 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

Balance Brought Forward from the Previous Page 67,750.00

Supply, install, set to work, test and commission


the following as marked on drawings:-

3.08 13A flush mounted twin switched socket outlet No. 8 500.00 4,000.00

ELV CABLE WAYS


(TELEPHONE, DATA, TV & SECURITY)
Supply, Install, Set to Work, test and
3.09 Data & WiFi Access point outlets comprising of No 8 500.00 4,000.00
25mm diameter HG PVC conduit and draw wire
from the adaptor box to all internal points concealed
in the walls and floor complete with all accessories
except faceplate.

3.10 CCTV points comprising of 25mm diameter HG No 5 500.00 2,500.00


PVC conduit and draw wire to all internal points
linked to Network Video Recorder (NVR) location.

Supply, Deliver, Install, Set to Work and


Commission the following:-
3.11 Bullet and Dome CCTV cameras No 5 30,000.00 150,000.00

Total Carried Forward to the Next Page 228,250.00

Page 14 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

Balance Brought Forward from the Previous Page 228,250.00

3.12 RJ45 data outlet point No 8 300.00 2,400.00

3.13 32 Channel Network Video Recorder for CCTV No. 1 100,000.00 100,000.00
Cameras with High Definition Capability

FIRE DETECTION AND ALARM


Supply, Deliver, Install, Set to Work and
3.14 Fire alarm control panel No. 1 28,000.00 28,000.00

3.15 Heat detectors No 4 2,500.00 10,000.00

3.16 Manual Break glass (Call point) No. 2 1,800.00 3,600.00

3.17 Electronic sounder No. 2 7,500.00 15,000.00

Total Carried Forward to Collection Page 387,250.00

Page 15 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

ITEM DESCRIPTION UNIT QTY RATE AMOUNT


(KES) (KES)
4.00 GROUND FLOOR - Supermarket, Shop, and
Restaurant

LIGHTING POINTS AND FITTINGS


Supply, Install, Set to Work, Test and
Commission the following:-
4.01 Lighting points wired in 3x1.5mm2 PVC insulated No. 16 750.00 12,000.00
single core (SC) copper wires drawn in 20mm
diameter HG PVC conduit concealed in walls and or
floor slabs with all accessories but excluding switch
and fitting for one way switching.
4.02 Ditto but for two way switching. No. 6 900.00 5,400.00

Supply, Install, set to work,test and Commission


the following as marked on drawings:-

4.03 10A 1 gang 1 way single pole switch No. 7 150.00 1,050.00
4.04 10A 1 gang 2 way single pole switch No. 2 150.00 300.00

Total Carried Forward to the Next Page 18,750.00

Page 16 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

Balance Brought Forward from the Previous Page 18,750.00

Supply, Install, set to work, test and Commission


the following as marked on drawings:-

4.05 600mm, 4x18w LED tube lamps with louvres No. 14 3,000.00 42,000.00

4.06 Type "B5" - 200W LED External Floodlight pole No. 0 15,000.00
mounted as Philips Cat. No. BVP155 LED210/857
PSU 200W VWB CE

4.07 Type "Z1": Circular downlighter with 13w LED No. 7 2,000.00 14,000.00

4.08 Type "E2": 18W Circular surface luminaire with No. 0 2,000.00
opal glass

4.09 Type "4": 1x18w 1200mm led tube No. 1 2,000.00 2,000.00

Total Carried Forward to the Next Page 76,750.00

Page 17 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

Balance Brought Forward from the Previous Page 76,750.00

POWER POINTS AND OUTLETS


Supply, Deliver, Install, Set to Work and
Commission the following:-
4.10 Power outlet points wired as for a ring main circuit No. 22 1,200.00 26,400.00
in 3 x 2.5mm2 PVC single core (SC) copper cables
drawn in 25mm dia HG PVC conduits concealed in
walls and floors slabs complete with all accessories
but excluding the socket outlet plate.

Total Carried Forward to the Next Page 103,150.00

Page 18 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

Balance Brought Forward from the Previous Page 103,150.00

Supply, install, set to work, test and commission


the following as marked on drawings:-

4.11 13A flush mounted twin switched socket outlet No. 22 500.00 11,000.00

ELV CABLE WAYS


(TELEPHONE, DATA, TV & SECURITY)
Supply, Install, Set to Work, test and Commission
4.12 Data & WiFi Access point outlets comprising of No 12 500.00 6,000.00
25mm diameter HG PVC conduit and draw wire
from the adaptor box to all internal points concealed
in the walls and floor complete with all accessories
except faceplate.

4.13 CCTV points comprising of 25mm diameter HG No 2 500.00 1,000.00


PVC conduit and draw wire to all internal points
linked to Network Video Recorder (NVR) location.

Supply, Deliver, Install, Set to Work and


Commission the following:-
4.14 Bullet and Dome CCTV cameras No 2 30,000.00 60,000.00

Total Carried Forward to the Next Page 181,150.00

Page 19 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

Balance Brought Forward from the Previous Page 181,150.00

4.15 RJ45 data outlet point No 12 300.00 3,600.00

FIRE DETECTION AND ALARM


Supply, Deliver, Install, Set to Work and
4.16 Heat detectors No 2 2,500.00 5,000.00

4.17 Manual Break glass (Call point) No. 0 1,800.00

4.18 Electronic sounder No. 0 7,500.00

POWER DISTRIBUTION
Supply, Install, Set to Work, test and Commission
4.19 63A 4-Way SPN Consumer unit complete with 63A No. 6 5,000.00 30,000.00
Single phase intergral isolator (Lettable spaces)

4.20 10A SP MCB No. 6 450.00 2,700.00

4.21 32A SP MCB No. 6 450.00 2,700.00

4.22 Distribution board blanking plates Item 6 500.00 3,000.00

4.23 Earthing and labelling of the distriution board Item 6 1,000.00 6,000.00

4.24 16mm2 Cu/ XLPE/PVC 4 core + 10 Cu/PVC SC Lm 230 3,000.00 690,000.00


ECC cables from Sub Main LV Switch Board to
Consumer Units

Total Carried Forward to Collection Page 924,150.00

Page 20 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

ITEM DESCRIPTION UNIT QTY RATE AMOUNT


(KES) (KES)
5.00 ATTIC - Bar and Common Areas

LIGHTING POINTS AND FITTINGS


Supply, Install, Set to Work, Test and
Commission the following:-
5.01 Lighting points wired in 3x1.5mm2 PVC insulated No. 33 750.00 24,750.00
single core (SC) copper wires drawn in 20mm
diameter HG PVC conduit concealed in walls and
or floor slabs with all accessories but excluding
switch and fitting for one way switching.
5.02 Ditto but for two way switching. No. 4 900.00 3,600.00

Supply, Install, set to work,test and Commission


the following as marked on drawings:-

5.03 10A 1 gang 1 way single pole switch No. 6 150.00 900.00
5.04 10A 1 gang 2 way single pole switch No. 3 150.00 450.00
5.05 10A 2 gang 2 way single pole switch No. 0 300.00
5.06 10A 2 gang 1 way single pole switch No. 1 300.00 300.00
5.07 10A 3 gang 1 way single pole switch No. 0 400.00

Total Carried Forward to the Next Page 30,000.00

Page 21 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

Balance Brought Forward from the Previous Page 30,000.00

Supply, Install, set to work, test and


Commission the following as marked on
drawings:-

5.08 Type "Z1": Circular downlighter with 13w LED No. 24 2,000.00 48,000.00
lamp

5.09 Type "E2": 18W Circular surface luminaire with No. 8 2,000.00 16,000.00
opal glass

5.10 Type "4": 1x18w 1200mm led tube No. 2 2,000.00 4,000.00

5.11 Type B7: IP65 18W LED External Bulkhead Light No. 1 3,000.00 3,000.00
fitting

5.12 Type 2: 1x18w mirror light with ON/OFF toggle No. 2 2,500.00 5,000.00
switch

Total Carried Forward to the Next Page 106,000.00

Page 22 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

Balance Brought Forward from the Previous Page 106,000.00

POWER POINTS AND OUTLETS


Supply, Deliver, Install, Set to Work and
Commission the following:-
5.13 Power outlet points wired as for a ring main No. 11 1,200.00 13,200.00
circuit in 3 x 2.5mm2 PVC single core (SC) copper
cables drawn in 25mm dia HG PVC conduits
concealed in walls and floors slabs complete with
all accessories but excluding the socket outlet
plate.

Total Carried Forward to the Next Page 119,200.00

Page 23 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

Balance Brought Forward from the Previous Page 119,200.00

Supply, install, set to work, test and commission


the following as marked on drawings:-

5.14 13A flush mounted twin switched socket outlet No. 11 500.00 5,500.00

ELV CABLE WAYS


(TELEPHONE, DATA, TV & SECURITY)
Supply, Install, Set to Work, test and
5.15 Data & WiFi Access point outlets comprising of No 2 500.00 1,000.00
25mm diameter HG PVC conduit and draw wire
from the adaptor box to all internal points
concealed in the walls and floor complete with all
accessories except faceplate.

5.16 CCTV points comprising of 25mm diameter HG No 2 500.00 1,000.00


PVC conduit and draw wire to all internal points
linked to Network Video Recorder (NVR)
location.

Supply, Deliver, Install, Set to Work and


Commission the following:-
5.17 Bullet and Dome CCTV cameras No 2 30,000.00 60,000.00

Total Carried Forward to the Next Page 186,700.00

Page 24 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

Balance Brought Forward from the Previous Page 186,700.00

5.18 RJ45 data outlet point No 2 300.00 600.00

FIRE DETECTION AND ALARM


Supply, Deliver, Install, Set to Work and
5.19 Heat detectors No 2 2,500.00 5,000.00

5.20 Manual Break glass (Call point) No. 1 1,800.00 1,800.00

5.21 Electronic sounder No. 1 7,500.00 7,500.00

POWER DISTRIBUTION
Supply, Install, Set to Work, test and
5.22 63A 4-Way SPN Consumer unit complete with No. 1 5,000.00 5,000.00
63A Single phase intergral isolator (Bar)

5.23 10A SP MCB No. 1 450.00 450.00

5.24 32A SP MCB No. 1 450.00 450.00

5.25 Distribution board blanking plates Item 1 500.00 500.00

5.26 Earthing and labelling of the distriution board Item 1 1,000.00 1,000.00

5.27 16mm2 Cu/ XLPE/PVC 4 core + 10 Cu/PVC SC Lm 35 3,000.00 105,000.00


ECC cables from Sub Main LV Switch Board to
Consumer Units

Total Carried Forward to Collection Page 314,000.00

Page 25 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

ITEM DESCRIPTION UNIT QTY RATE AMOUNT


(KES) (KES)
6.00 MAIN POWER DISTRIBUTION
Supply, Deliver, Install, Set to Work and
Commission the following:-
6.01 Customized LV Switch Board , IP-65 to house the No. 1 500,000.00 500,000.00
following:-
- 1no 250A, TP KPLC Cutouts
- 2no TP, 10no SP Direct Prepaid KPLC Meter
- 1no 250A, 25kA, type C, 4P MCCB (Mains Incomer)
- 1no 250A, 25kA, type C, 4P MCB (Generator
Incomer)
- 10no 63A, 6kA, type C, SP MCBs
- 2no 125A, 6kA, type C, TP MCB (To Ground Floor
DBs)
- 2nos 63A, 6kA, type C, TP Spareways
- Surge divertor furse ESP 415, 20kA, Type 1 and 2
including its circuit protection
LED Indicating lamps {MAINS AVAIL (RYB), MAINS
On LOAD ), GEN AVAIL (RYB), GEN ON LOAD )}

EARTHING
Supply, Deliver, Install, Set to Work and
Commission the following:-
6.02 Complete Earthing/bonding of the LV Board to IEE Item 1 5,000.00 5,000.00
requirements
6.03 300mm x 300mm concrete Earth inspection pit complete No. 1 5,400.00 5,400.00
with heavy duty manhole covers.
6.04 Bare conductor copper from LV Board to earth electrode Lm 5 200.00 1,000.00

CABLE LAYING
6.05 1x50mm diameter HG PVC conduit Power Lm 15 250.00 3,750.00
6.06 1x50mm diameter HG PVC conduit ICT Lm 15 250.00 3,750.00
6.07 450mm x 450mm x 600mm concrete power and ICT No. 6 6,000.00 36,000.00
manholes complete with heavy duty manhole covers.
6.08 200mm x 200mm x 75mm x20SWG IP54 steel No. 1 1,200.00 1,200.00
galvanized cable adaptable box with 20SWG prepainted
screwed cover.
6.09 Trenching at an average depth of 750 mm laying all Lm 160 250.00 40,000.00
underground cables, 'HATARI' tilling and backfilling

Total Carried Forward to Summary Page 596,100.00

Page 26 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

ITEM DESCRIPTION UNIT QTY RATE AMOUNT


(KES) (KES)

7.00 LIGHTNING PROTECTION

Supply, Deliver, Install, Set to Work and Commission


the following:-
7.01 Lighting Protection including the following: Item 1 500,000.00 500,000.00
-Air termination bolted to canopy and roof top with water
tight rubber washers.
-25mm by 3mm Copper tape on tape clip fixed at intervals
-Lugs including fixing bolts to roof conductors.
-PVC insulated copper conductor enclosed in HG
concealed PVC conduit from copper tape to test joint to
earth electrode
-Test clamps
-Rod to earth conductors clamps
-1.2 meters earth rod with driving stud, and spike driven
into ground.
-deep boxes with cover and marked safety earth installed
columns.
-Concrete earthing inspection pits
-Allow for bonding and clamping to all metal work
including water pipes,water tanks at roof top etc and the
main earth for the building/ switch gear earth.
'-Allow for testing and commissioning for entire lightning
protection and grounding system and log in the results

-
-
-

Total Carried Forward to Summary Page 500,000.00

Page 27 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

ITEM DESCRIPTION AMOUNT


(KES)

8.0 PC SUMS

8.1 KPLC Connection 105,000.00

8.2 Internet Connection, Wifi Access Points & Cabling 125,000.00

8.3 100kVA 415V, 3ph Generator 3,000,000.00

8.4 100kVA Automatic Voltage Stabiliser 500,000.00

8.5 CCTV Installation 130,000.00

Total Carried Forward to Summary Page 3,860,000.00

Page 28 of 29
Ruiru Petrol Station Electrical Installation Bills of Quantities

ITEM DESCRIPTION AMOUNT


(KES)
MAIN SUMMARY PAGE

1.00 Service Station 1,120,900.00

2.00 Supermarket and Restaurant 734,900.00

3.00 FF Offices and Common areas 387,250.00

4.00 FF Restaurant & Lettable spaces 924,150.00

5.00 Attic 314,000.00

6.00 Power Distribution 596,100.00

7.00 Lighting Protection 500,000.00

Electrical Installation Sub-Total 4,577,300.00

8.00 Provisional Sums


KPLC Connection 105,000.00
Internet Connection, Wifi Access Points & Cabling 125,000.00
100kVA 415V, 3ph Generator 3,000,000.00
100kVA Automatic Voltage Stabiliser 500,000.00
CCTV Installation 130,000.00

Total Electrical Installation Incl. of VAT 8,437,300.00

Amount in Words: Kenya Shillings……........................................................................…………..………………..….....

…….....................................................................………...…………………………………………………………………

Official Stamp & Address:……..........................................................................………………..…………………………

……….........................................................................………………..……………………………………...……………

Tenderer’s Signature:…….……………………………. Date:…………..................................................................

Witness’ Name:…………..…………………………… Witness’ Signature:...………………...…………….........

Address:………………………..……………….....................................................................…………………………..…

Page 29 of 30
Ruiru Petrol Station Electrical Installation Bills of Quantities

Page 30 of 30

You might also like