Professional Documents
Culture Documents
Introduction
The concept of using evaporative cooling is widely employed The above problem can be eliminated if an alternative system,
in cooling towers for air conditioning systems for large facili- e.g., media pad evaporative cooler is used. Media pads are cellu-
ties and to provide cooling for agricultural greenhouses. It is a lose bound cardboard structures which are cross-fluted to increase
proven concept (ASHRAE, 1989) but is used on a very limited the transfer area. The average life expectancy of the media pad
basis for the residential and small commercial air conditioning evaporative cooler is of the order of five years. With clean water,
systems, which are usually air-to-air compression-type systems. it may last up to ten years (Munters, 1986). With this system,
The performance of such systems can be improved by employing air is allowed to pass through the wetted medium (media pad)
indirect evaporative cooling such that no moisture is added to the before entering the condenser. Hence water droplets do not reach
supply air stream. This can be achieved by evaporative cooling the heat transfer surfaces of the condenser coil, thus avoiding
of the outside air before it passes over the condenser coil, re- mineral deposits on the coil. The mineral deposits occur on the
sulting in a larger overall temperature difference across the heat inexpensive media pads, which can be replaced periodically as
exchanger and thus greater cooling effect. The process requires needed. The present investigation was conducted to demonstrate
very little additional energy input for the condenser fan and for the practicality of this concept for new air conditioning units as
water pumping, resulting in higher coefficient of performance. well as retrofits of existing units and to evaluate the actual savings
Increased cooling effect allows the equipment to be downsized by employing this concept. This paper presents the results of per-
resulting in lower peak demand and energy usage. This can result formance improvement of a residential air conditioner retrofitted
in significant energy and demand savings overall since there are with a media pad evaporative cooler.
millions of air conditioners in the residential sector that can be
easily retrofitted. A simple retrofit on the condenser of an air
conditioning unit can save enough energy to pay for itself in as
little as one to two years. Indirect evaporative cooling has rarely Literature Review
been used for the residential and small commercial air-to-air va-
por compression air conditioning systems due to the following Evaporative cooling has been investigated by a number of in-
reasons: vestigators in many different combinations and configurations
(Brown, 1990; Meckler, 1990). Different types of heat ex-
(1) spray of water on the coil causes mineral deposits on the heat change systems have been investigated by integrating the evapora-
transfer surfaces which decreases the performance of the system tive coolers: heat-pipe heat exchangers (Scofield, 1986; Scofield
and and Taylor, 1984; Mathur, 1990a); plate-type heat exchangers
(2) spray of water on the coil makes it essential to have an ex- (Scofield and DesChamp, 1984; Wu and Yellott, 1987); rotary
pensive water treatment system to prevent scale buildup on the regenerative heat exchangers (Woolridge et al., 1976); and two-
heat transfer surfaces. phase thermosiphon loop heat exchangers (Mathur, 1990b), etc.
Because of the importance of evaporative cooling in reducing the
Contributed by the Solar Energy Division of THE AMERICAN SOCIETY OF energy needs for cooling, the U.S. Department of Energy's (DOE)
MECHANICAL ENGINEERS for publication in the ASME JOURNAL OF SOLAR ENERGY
ENGINEERING. Manuscript received by the ASME Solar Energy Division, Jan. 1993; major computer program for building energy analysis (DOE 2.1d)
final revision, Mar. 1993. Associate Technical Editor: J. Mitchell. has been modified to model and analyze a variety of direct, indi-
rect, and multiple-stage evaporative cooling systems (McDonald recirculating pump. The face area of the media pad is larger than
et al., 1990). Evaporative cooling with a mechanical refrigera- the opening on the sides of the condenser coil. This resulted in
tion system as a backup has been designed (Scofield and Sterling, face velocities between 195 to 212 fpm (0.99 to 1.08 m/s) over
1992) for the arid areas. the media pads.
All of the work reported above on evaporative cooling primar- The face velocity over the evaporator coil was also measured.
ily deals with commercial and industrial applications where the Air flow measurements were done at nine points close to the
system capacities are very large. However, the same principle evaporator coil that resulted in an average air flow rate of 930
can be applied to the residential air conditioners also. cfm (0.44 m3/s). Dry and wet bulb temperatures were recorded
upstream and downstream of the evaporator coil.
System Set-Up and Instrumentation Individual power meters were used to monitor the power con-
The outdoor condensing unit of an existing 2.5 ton (8.8 kW) sumption of the compressor, fans (evaporator and condenser),
Trane Heat Pump was retrofitted with a media pad evaporative and the recirculating pump. The pressure drop across the media
cooler. The heat pump is being used for air conditioning of an pad was measured with an inclined manometer. A hygrometer
occupied test house at the University of Florida Energy Research was used to record the outside relative humidity during the day-
and Education Park. The manufacturer's specifications of the heat time. The conditioned space temperature was recorded from the
pump are: thermostat inside the building. A hygro-thermograph was used
inside the building to record the temperature and relative humid-
Condenser fan: 1/4 h.p. (187 W), Full load Amps = 2.7, 230
ity of the conditioned space. The pressure around the loop was
Volts
recorded with the help of Mamac transducers and the temperatures
Evaporator fan: 1/2 h.p. (373 W), Full load Amps = 3.3, 230
were measured with T-type (Copper-Constantan) thermocouples.
Volts
A strip chart recorder was used for recording all the variables for
Cooling Capacity = 29,800 Btu/hr (8.73 kW)
analysis. Table 1 shows the summary of the instruments used in
SEER = 9.0.
this investigation. Figure 2 shows the schematic view of the sys-
The condenser coil is rectangular in shape and is placed outside tem. It also shows the locations of the temperature and pressure
the building. It is a single row deep coil. The ambient air is drawn taps. The performance of the system was recorded without and
into it from all four sides and the hot air is exhausted from the with the media pad evaporative cooler on the condenser.
top of the condenser unit. The retrofit consisted of constructing a
sheetmetal structure around the condenser coil to hold the media
pad, a pan at the bottom of the media pad holder, a spray bar at Results and Discussions
the top of the media pad and a small pump to pump the water
from the pan to the spraybar, as shown in Fig. 1. At each side The air conditioning system was first monitored for four weeks
of the condenser coil, the opening (26 in. x 21 in.) was divided without the media pad evaporative cooler on the condenser coil.
into 16 equal elements. The air velocity was measured at the The condenser was then retrofitted and the system performance
center of the individual elements. The face velocity at the side was monitored for another four weeks. Figures 3 to 6 show the
of the condenser coil ranges between 280 to 700 fpm (1.42 to data without the evaporative cooler while Figs. 7 to 9 show the
3.6 m/s). The total air flow rate over the condenser coil was data with the condenser retrofitted with the evaporative cooler.
measured to be 2430 cfm (1.15 m3/s). The condenser fan has a Figure 10 shows the psychromatic process of the condenser per-
1/4 hp (187 W) motor installed. The condenser coil was retrofitted formance with and without evaporative cooler on the condenser
with 8-in. (20.32-cm) thick media pad (Munters, 1986), and a coil.
Nomenclature
COP coefficient of performance Hw = water pressure drop, feet W.C.
CFM air volumetric flow rate, SCFM P = peak demand charges (dollars kW)
E effectiveness of the system, percent SE = saturation efficiency, percent
Ec cooling equipment efficiency (0.95 kW/ton)
EER energy efficiency ratio Subscripts
GPM water flow rate, gallons per minute e = evaporator
Ha air pressure drop, inches W.C. c = condenser
Fig. 2 Refrigeration system showing the location of the pressure, temperature, and power measurements
COMPRESSOR COMPRESSOR
POWER ( kW) POWER ( kW)
—* kW/TON
8.00 9.00 10.00 11.00 12.00 13.00 14.00 15.00 16.00 17.00 18.00 19.00 20.00 21.00 10.00 11.00 12.00 13.00 14.00 15.00 16.00 17.00 18.00 19.00 20.00 21.00
TIME ( hrs ) TIME ( hrs )
Fig. 4 System performance without evaporative cooler (date 7/13/92) Fig. 6 System performance without evaporative cooler (date 7/14/92)
12-
11-
1 * EER
10-
AMBIENT TEMP (F)
(X10) 9- H AMBIENT TEMP (F)
EER (X 10)
8
7-
6- j*. RH (X 10)
5-
m COP
3-
COMPRESSOR
POWER ( kW) 2- (kW)
1-
Fig. 5 System performance without evaporative cooler (date 7/20/92) Fig. 7 System performance with evaporative cooler (date 8/19/92)
the storm moved into the test area, the ambient air temperature The following uncertainties were obtained:
dropped to 77°F (25°C) at 15.30 hours. A sudden reduction of compressor power 1.6 percent
the ambient air temperature resulted in a decrease of the con- COP 1.6 percent
denser pressure thus reducing the compressor power which in EER = 2.4 percent.
turn resulted in an increase of the COP and EER. The system
performance decreased again when the ambient air temperature
increased in the late afternoon. Savings Analysis
System Performance With Evaporatively Cooled Con- This section gives an analysis of the savings due to an evap-
denser. Figures 7 to 9 show the variation of COP, EER, ambient orative cooler. The following data for 7/11/92 (11.30 a.m.) are
air temperature (°F) and relative humidity, kW/ton, and compres- used for the analysis:
sor power (kW) during the day with evaporatively cooled con- Ambient dry bulb temperature 92°F (33.3°C)
denser. The compressor power in this case, on the average, was Ambient wet bulb temperature 75°F (23.9°C)
approximately 2.4 kW in comparison to approximately 2.9 to 3.0 Conditioned space dry bulb
kW without evaporative cooling. This represents a decrease in temperature 75°F (23.9°C)
the compressor power by approximately 17 to 20 percent. Fig- Conditioned space wet bulb
ures also reveal that the EER of the system has gone up from an temperature 62.5°F (16.9°C)
average value of 9 (without evaporative cooling, Figs. 3, 4, 5, 6) Saturation efficiency of media pad 88 percent
to approximately 11 with evaporative cooling. This is an increase
[8 inches (20.32 cm) @ 200 fpm
of the system performance by approximately 22 percent.
(1.02 m/s)]
Figures 7 to 9 also show the variation of the kW/ton. This Pressure drop for the media pad 0.025" W.C. (6.2 Pa)
shows how the evaporative cooler has caused a reduction of the Evaporator air flow rate 930 scfm (0.44 m3/s)
electrical input to produce a ton of cooling. The value of kW/ton Condenser air flow rate 2430 scfm (1.15 m3/s)
went down to 0.8 from an average value of 0.95 for the system
kW/ton the system 0.95
without the evaporative cooling.
Condenser effectiveness (measured) 21 percent
Evaporator effectiveness (measured) 47 percent
Error Analysis. Error analysis for estimating uncertainty in
experimental results was done (Kline and McClintock, 1953). The dry bulb temperature of the air leaving the media pad evap-
Test data for 7/11/92 (11:30 a.m.) were used for the analysis. orative cooler (before entering the condenser) may be determined
STATE DBT(F)/WBT(F)
1 92/75
* COMPRESSOR
POWER (kW)
2 77/75
Dry Bulb Temperature 3 84.4/77
4 104.6/78
9.00 10.00 11.00 12.00 13.00 14.00 15.00 16.00 17.00 18.00 19.00 Process 1-2-3 C With evaporative Cooler)
TIME { hrs ) Process 1-4 < Without evaporative cooler)
Fig. 8 System performance with evaporative cooler (date 8/20/92) Fig. 10 Psychrometric process diagram
Assuming the supply air to be made up of 100 percent out- Peak demand savings/year= tons saved * Ec * P * 12
side air, the supply-side temperature drop across the evaporator = 0.69 * 0.95 * 7.5 * 12
is increased by 7.05°F (3.9°C) (difference between 92°F and = $59.00.
84.95°F). This additional recovery on the evaporator side re- The above analysis shows that if a media pad evaporative
sults in a decrease of the cooling load by 0.28 tons (0.99 kW) cooler is used with a 2.5 ton (8.8 kW) air conditioning unit,
[1.08 * 930 * 0.47 * 7.05/12000]. Figure 10 shows the process on the cooling load reduces by 0.28 tons (0.99 kW) and the con-
the psychrometric chart. denser load goes down by 0.69 tons (2.43 kW). This reduction in
the cooling tonnage results in a lower initial cost of the system
Cooling Savings. In order to calculate the energy and the by $448.50, net power savings of 0.618 kW, and peak demand
equipment savings for cooling, a cooling equipment efficiency of savings of $59.00/year.
0.95 kW/ton, and a cooling equipment cost of $650/ton (Mathur,
1990b) are used. The reduction in cooling equipment cost may Retrofit Payback Calculations. The following section gives
be determined by the following equation: the details of the retrofit payback analysis:
Tons saved = 1.08 * 2430 * 0.21 (92-77.0)/12000 2.5 ton unit: 14.8 Amps @ 230 Volts
= 0.69 tons (2.43 kW) Operation 12/day for 7 months