1 MINUTE 1 HOUR 2 HOURS


TIME IN SECONDS

.005
500

.02
300

20
50
200
1000
2000
3000

.002
.003
.05
.2
.5
2
10
100
10,000

.03
.3
5
5000

.1
1

.01

.001
.5 .5
.6 .6
.7 Catalog Instantaneous Pickup Setting   (Amperes) Use With Limiter .7
.8 Number A B C D E F G H Catalog Number .8
.9 HMCP003A0 9 12 15 18 21 24 27 30 ELC3003R .9
1 1
HMCP007C0 21 28 35 42 49 56 63 70 ELC3007R
HMCP015E0 45 60 75 90 105 120 135 150 ELC3015R
HMCP030H1 90 120 150 180 210 240 270 300 ELC3030R
HMCP050K2 150 200 250 300 350 400 450 500 ELC3050R
HMCP070M2 210 280 350 420 490 560 630 700 ELC3070R
2 HMCP100R3 300 400 500 600 700 800 900 1000 ELC3100R 2
HMCP150T4 450 600 750 900 1050 1200 1350 1500 ELC3150R
HMCP150U4 750 1200 1250 1500 1750 2000 2250 2500 ELC3150R
3 3
PICK-UP

Notes:
4 HMCPS has same instantaneous pickup as HMCP. 4
Motor Circuit Protectors are for use only in combination motor controllers.
ADJUSTMENT

5 For additional information, see IL 29C-401. 5

HMCP150T4
HMCP015E0

HMCP100R3
HMCP050K2
HMCP007C0

HMCP030H1

HMCP150U4
HMCP003A0

HMCP070M2
6  For DC applications, pickup settings are approximately 40% higher. 6
Eaton Series C type GMCP, HMCP, 

 Tolerance –20%, +30% of setting.


H
G

7 7
F

8
A

8
and HMCPS motor circuit protectors 

9 9
To Set:

E
B

10 10
D
C
Press & Rotate

NAMEPLATE
TYPICAL HMCP

20 20
H–
G–
F –
E –
D–
C–
B–
A–
Instantaneous Trip Setting – Amps

30 30

40 40
AMP

Maximum
50 50
60 60
RATINGS

Interrupting Time

CURRENT IN AMPERES
70 70
80 80
90 90
100 100
250 Vdc
CURRENT IN AMPERES

200 200
600 Vac (50/60 Hz)
Maximum Voltage

ELC3007R
ELC3003R
300 300

400 400

500 500
3–150A

600 600

ELC3015R
700 700

Figure 2. Type HMCP and HMCPS 150A Motor Circuit Protector—Curve No. SC-4121-87B
800 800
900 900
1000 1000
Maximum Current
Motor Circuit Protector Time/Current Curves

ELC3030R
2000 2000

ELC3050R
Series C—Type HMCP and HMCPS , Two- and Three-Pole

3000 3000

ELC3100R
4000 4000
5000 5000

ELC3150R
6000 6000
7000 7000
8000 8000
9000 9000
10000 10000
1
2
3
5

.2

.1
.3
.5
20
30

10
50

.05

.02

.01
.03
100
200
500

300

.003
.005

.002

.001
1000
2000
3000
5000

TIME IN SECONDS
10,000

1 MINUTE
1 HOUR 2 HOURS

eaton www.eaton.com
3
Effective June 2013
Trip Curves 29-167H