You are on page 1of 25

DENSIFICATION HANDBOOK AT&T Densification

V.4 – 9/9/16

HUB LOCATION ERICSSON NOKIA NODE LOCATION

RACK SIAD SIAD DFS DEMARC

POWER & GROUND OPN500 TERMINATIONS


6601 BBU

FIBER PANELS
CLEARFIELD FIBER
GPS GPS
CO TIE CABLE SET UP GROUNDING ON UTILITY
POLE
RADIOS RADIOS
ERICSSON GPS LAYOUT
POLE MISC. HARDWARE

NOKIA GPS LAYOUT ERICSSON RACK LAYOUT NOKIA RACK LAYOUT


POLE GROUNDING
EXAMPLE

FUSE PANEL LAYOUT FUSE PANEL LAYOUT Ericsson


2203/2205 Layout

AT&T Proprietary (Internal Use Only) Not for use or disclosure outside the AT&T companies except under written agreement
RACK AT&T Densification

 HXWXD – 84" X 21.94" X 9.63" (43U)


 EMPTY WEIGHT – 105 LBS.
 WEIGHT CAPACITY – 450 LBS.
 19" Relay Rack , Gray - NEQ.16094  MOUNTING HOLES – TAPPED FOR 12-24 HARDWARE
 ISO PAD & CONCRETE ANCHORS INCLUDED

 Vertical Cable Manager – SEQ.16386  HXWXD – 7'X6"X5"

 Middle Atlantic Lacing Bar – CEQ.10957  ONE PER SIAD/BBU/FUSE PANEL


 PACK OF 10

 6" LONG
 Stand Off Bracket – NEQ.15207  ZINC PLATED

 HXWXD – 1.75" X 17" X 19.69" (1U)


 19" Slide Out Shelf – NEQ.19268  WEIGHT – 25 LBS.
 ONE PER ROW OF RACKS
 PLACED AT RU POSITION 21

 Manufacturer – Upsite HotLok  Manufacturer: Telect or Equivalent


 Part # - 10009  Part #: TBD
 Description – Temperature Strip  Description: 22 Position w/diagonal holes
 Placed on each rack at 59"  19" Horizontal Rack Ground Bar
POWER & GROUND AT&T Densification

 HXWXD – 3.5" X 19" X 12" (2U)


 WEIGHT – 9 LBS.
 Telect Fuse Panel - NEQ.15111  FUSE POSITIONS – 20 GMT/PANEL, 10 GMT/BUS (DUAL BUS)
 CURRENT RATING – 200 AMPS/PANEL, 100 AMPS/BUS
 DC FEED – 100 AMP BREAKER PER BUS (DUAL BUS)

 Manufacturer: TelcoFlex IV  Manufacturer - TelcoFlex IV


 Part #: 57145801  Part # - 57192501
 Description: #2 Gray  Description - #2 Green
 BAT & RET for Fuse Panel  Ground for Rack Line Up

 Manufacturer - TelcoFlex IV  Manufacturer - TelcoFlex III


 Part # - 57150401  Part # - 57133601
 Description - #6 Green  Description - #14 Gray
 Grounding SIAD, BBU, Fuse Panel & Rack  BAT & RET for 6601 & SAR-8

 Manufacturer: T&B or Equivalent


 Manufacturer – ElectoWire or Equivalent  Part #: TV14-6R-L
 Part # - FXE1929030  Description: Narrow #16-14 Ring Terminal
 Description - #16 Dark Gray  #6 Stud Size
 BAT & RET for 901 SIAD  BAT & RET Fuse Panel Lug for SIAD & 6601

 Manufacturer: T&B or Equivalent  Manufacturer: T&B or Equivalent


 Part #: 54207NT  Part #: TV10-6R-L
 Description: #2 Narrow Tongue, Two Hole, Standard Barrel  Description: Narrow #12-10 Ring Terminal
 ¼” Stud Size  #6 Stud Size
 BAT & RET Input Lug for Fuse Panel  BAT & RET Fuse Panel Lug for 9926

 Manufacturer: T&B or Equivalent  Manufacturer: T&B or Equivalent


 Part #: 54135  Part #: 54205
 Description: #6, One Hole, Standard Barrel  Description: #6, Two Hole, Standard Barrel
 5/16” Stud Size  ¼” Stud Size
 Ground Lug for 6601  Ground Lug for Rack Ground Bar & Fuse Panel
AT&T Densification
SIAD

 HXWXD – 1.7" X 17.5" X 8.3" (1U)


 WEIGHT – 8.15 LBS.
 BTU’S – 2048 PER HOUR
 Cisco ASR901 – NEQ.16126  WATTS – 40 MAX
 DC FEED – TWO 3 AMP FUSES
 BBU’S – 5 MAX

Fiber SFP’s  For LTE & backhaul


 <10k Backhaul Circuit - SEQ.12859  1310nm
 >10k to <40k Backhaul Circuit – SEQ.11234

 Port 0/7 is used for backhaul only


 eNodeB’s start from port 0/11

0/5 0/7 0/9 0/11


0/4 0/6 0/8 0/10

SFP GE Ports
DC Power
AT&T Densification
6601

 HXWXD – 2.6" X 19" X 14" (1.5U)


 DUS41 6601 - CEQ.16693  WEIGHT – 23 LBS. FULLY LOADED
 5216 6601 – Coming Soon  POWER CONSUMPTION – 400 WATTS MAX
 MAX DC FEED – 20 AMP FUSE

 XMU - CEQ.TBD  NOT FOR USE WITH CRAN AT THIS TIME

 ONLY NEEDED IF DRY CONTACT IS REQUIRED


 SAU 02 01 - CEQ.11664
AT&T Densification
GPS

 HXD – 8.6" X 3.2"


 GPS Antenna – ANT.12191  RF CONNECTOR – N FEMALE
 GPS Mounting Kit – CEQ.11118  ONE EACH PER 16 BBU’S

 WXLXH – 4" X 6.3" X 1.25"


 GPS Splitter 1:8 - ANT.14135  WEIGHT – 1.65 LBS.
 RF CONNECTOR – N FEMALE

 ONE FOR EACH OPEN PORT


 GPS Splitter Terminator - ANT.10093  RF CONNECTOR – N MALE
 2 WATTS

 DIAMETER – 1.24"
 LENGTH – 4.26"
 WEIGHT – 1 LB.
 GPS Line Amplifier – ANT.13448  RF CONNECTOR – N FEMALE
 GPS DISTANCE – 0 = 375'/ 1 = 750'/ 2 = 1150'
AT&T Densification
Radios

mRBS 6501 mRRUS12 2203


 B2 (PCS) – CEQ.15423  B2 (PCS) – CEQ.15431  B66A (AWS) – CEQ.17265
 B4 (AWS) – CEQ.14645  B4 (AWS) – CEQ.15436
 B12 (700) – CEQ.14644  B12 (700) – CEQ.15433

 HXWXD – 20" X 12" X 5"  HXWXD – 18.1" X 10.5" X 5.5"  HXWXD – 7.87" X 7.87" X 3.94"
 WEIGHT – 35 LBS.  WEIGHT – 22 LBS.  WEIGHT – 11 LBS.
 RF – N TYPE FEMALE  RF – N TYPE FEMALE  RF – 4.3-10 FEMALE
 POWER CONSUMPTION – 218 WATTS MAX  POWER CONSUMPTION – 86 WATTS MAX  POWER CONSUMPTION – 97 WATTS MAX
 MINIMUM AC FUSE RATING – 9 AMP  MINIMUM AC FUSE RATING – 4 AMP  MINIMUM AC FUSE RATING – 6 AMP
 MAX HEAT DISSIPATION – 250 WATTS  MAX HEAT DISSIPATION – 140 WATTS  MAX HEAT DISSIPATION – 90 WATTS
AT&T Densification
SIAD

 HXWXD – 3.5" X 17.5" X 9.8" (2U)


 WEIGHT – 16 LBS.
ALU 7705 SAR-8 v.2  BTU’S – 2730 PER HOUR
(1 Ethernet Card + 2 Fiber/1 Copper SFP)  WATTS – 800 MAX
 +24/-48VDC - NEQ.19190  DC FEED - TWO 15 AMP FUSES
 BBU’S - 5 MAX

 8 GIGABIT ETHERNET SFP PORTS


 8 Port Ethernet Card – NEQ.17282  UP TO SIX MODULES PER SAR-8
 2 SFP’S PER CARD MAX

Fiber SFP’s
 SM/LX/1310nM - NEQ.11786
BBU’s AT&T Densification

 HXWXD – 3.5" X 19" X 12" (2U)


 9926 BBU - CEQ.16672  WEIGHT – 26 LBS. FULLY LOADED
 POWER CONSUMPTION – 360 WATTS MAX
(v5 -1 bCEM & eCCM2)  DC FEED – 20 AMP FUSE
 WIRE SIZE – 12 AWG

 Rate 5 SFP – CEQ.14449

 bCEM2 Card – CEQ.16476

 HXWXD – 5.05" X 19" X 15.75" (3U)


 FSM4 – Coming Soon  WEIGHT – 50 LBS. FULLY LOADED
 POWER CONSUMPTION – 839 WATTS MAX
 DC FEED – TBD

 HXWXD – 1.72" X 19" X 5" (1U)


 GPS Splitter 1:16 - ANT.TBD  RF CONNECTOR – N FEMALE
Radios AT&T Densification

cMRO 9768 LP RRH


 B2 (PCS) – Coming Soon  Coming Soon
 B66 (AWS) – Coming Soon

 HXWXD – 10.4" X 7.09" X 5.3"  HXWXD – TBD


 WEIGHT – 15 LBS.  WEIGHT – TBD
 RF – 4.3-10 FEMALE  RF - TBD
 POWER CONSUMPTION – 100 WATTS MAX  POWER CONSUMPTION – TBD
 MINIMUM AC FUSE RATING – AMP  MINIMUM AC FUSE RATING – TBD
 MAX HEAT DISSIPATION – WATTS  MAX HEAT DISSIPATION – TBD
AT&T Densification
FIBER PANELS

 FPX 144 Fiber Patch Panel – NEQ.18941  HXWXD – 5.15" X 17" X 12" (3U)
 LC/UPC (BLUE)
 ADAPTERS ONLY

 HXWXD – 8.75" X 17" X 12" (5U)


 LC/UPC (BLUE)
 FPX 288 Fiber Patch Panel – NEQ.19521  RIBBON PIGTAIL
AT&T Densification
ERICSSON RACK LAYOUT

ACTIVE RACK PASSIVE RACK

43 Ground Busbar 43
42 42 BACKHAUL Commscope 144 LC/UPC
41 41
40 40
39
38 Telect Fuse Panel
39
38
DESIGN NOTES
37 37 FRONTHAUL
36 36  Two Nodes per BBU (PICO)
35
34
35
34  Three Nodes per BBU (MICRO)
33
32
33
32
 One BBU per 6601
31 Cisco 901 SIAD 31  Five BBU’s per 901 SIAD
30 30 Commscope 288 LC/UPC
29 29
28 28
27 27
26
25
26
25
C&E NOTES
24 24
23 23  Ten 6601's per rack max
22 22
21 21  Two 901 SIAD’s per rack max
20 Ericsson 6601 20
 Blanking panels required
19 19
18 18 Computer Shelf  Temperature Sensing strip required at 59"
17 17
16 16
15 15
14 14
13 13
12 12
11 11
10 10
9 9
8 8 Commscope 288 LC/UPC
7 7
6 6
5 5
4
Ericsson GPS 03 01 4
3 3
2 2
1 1

AT&T Proprietary (Internal Use Only) Not for use or disclosure outside the AT&T companies except under written agreement
RACK LAYOUT AT&T Densification

ACTIVE RACK PASSIVE RACK

43 Ground Busbar 43
42 42 BACKHAUL Commscope 144 LC/UPC
41 41
40 40
Telect Fuse Panel
39
38
39
38
DESIGN NOTES
37 37 FRONTHAUL
36 36  2 Nodes per BBU (PICO)
35
34
35
34  3 Nodes per BBU (MICRO)
33
32 Nokia 7705
33
32
 5 BBU’s per SIAD
31 31
30 30 Commscope 288 LC/UPC
29 29
28 28
27 27
26
25
26
25
C&E NOTES
24 24
23 23  Ten 9926's per rack max
22 22
21 21  Two SIAD’s per rack max
20
19
20
19
 Blanking panels required
18
Nokia 9926 18 Computer Shelf  Temperature Sensing strip required at 59"
17 17
16 16
15 15
14 14
13 13
12 12
11 11
10 10
9 9
8 8 Commscope 288 LC/UPC
7 7
6 6
5 GPS Splitter 5
4 4
3 3
2 2
1 1

AT&T Proprietary (Internal Use Only) Not for use or disclosure outside the AT&T companies except under written agreement
AT&T Densification
FUSE PANEL LAYOUT

INPUT BUS A INPUT BUS B


VOLTAGE BREAKER SIZE Cable Size FEED VOLTAGE BREAKER SIZE Cable Size FEED
-48 VDC 100 AMP 2 AWG BDFB -48 VDC 100 AMP 2 AWG BDFB
Output BUS A OUTPUT BUS B
Equipment Fuse Size Cable Size Equipment Fuse Position Fuse Size Cable Size Equipment
1 3 Amp 16 AWG ASR901 -1 1 3 Amp 16 AWG ASR901 -1
2 Vacant 2 Vacant
3 3 Amp 16 AWG ASR901 -2 3 3 Amp 16 AWG ASR901 -2
4 Vacant 4 Vacant
5 15 Amp 14 AWG 6601-1 5 15 Amp 14 AWG 6601-2
6 15 Amp 14 AWG 6601-3 6 15 Amp 14 AWG 6601-4
7 15 Amp 14 AWG 6601-5 7 15 Amp 14 AWG 6601-6
8 15 Amp 14 AWG 6601-7 8 15 Amp 14 AWG 6601-8
9 15 Amp 14 AWG 6601-9 9 15 Amp 14 AWG 6601-10
10 Vacant 10 Vacant

AT&T Proprietary (Internal Use Only) Not for use or disclosure outside the AT&T companies except under written agreement
FUSE PANEL LAYOUT AT&T Densification

INPUT BUS A INPUT BUS B


VOLTAGE BREAKER SIZE Cable Size FEED VOLTAGE BREAKER SIZE Cable Size FEED
-48 VDC 100 AMP 2 AWG BDFB -48 VDC 100 AMP 2 AWG BDFB
Output BUS A OUTPUT BUS B
Equipment Fuse Size Cable Size Equipment Fuse Position Fuse Size Cable Size Equipment
1 15 Amp 14 AWG SAR-8v.2 -1 1 15 Amp 14 AWG SAR-8v.2 -1
2 15 Amp 14 AWG SAR-8v.2 -2 2 15 Amp 14 AWG SAR-8v.2 -2
3 Vacant 3 Vacant
4 15 Amp 12 AWG 9926 -1 4 15 Amp 12 AWG 9926 -2
5 15 Amp 12 AWG 9926 -3 5 15 Amp 12 AWG 9926 -4
6 15 Amp 12 AWG 9926 -5 6 15 Amp 12 AWG 9926 -6
7 15 Amp 12 AWG 9926 -7 7 15 Amp 12 AWG 9926 -8
8 15 Amp 12 AWG 9926 -9 8 15 Amp 12 AWG 9926 -10
9 Vacant 9 Vacant
10 Vacant 10 Vacant

AT&T Proprietary (Internal Use Only) Not for use or disclosure outside the AT&T companies except under written agreement
CENTRAL OFFICE SET UP AT&T Densification

Affiliate Space Telco Space Node Location

FRONTHAUL LGX FRONTHAUL LGX DMARC

BACKHAUL LGX BACKHAUL LGX RRU

SIAD NTE

BLUE = Mobility Provided & Owned


BBU ORANGE = Telco Provided & Owned
(Telco space will typically have multiple LGX panels)
AT&T Densification
GPS LAYOUT

BBU
GPS
BBU 03 01 GPS Antenna
ANT.12191
BBU
GPS
Mounting Kit
BBU 03 01 CEQ.11118
BBU
GPS
BBU 03 01

BBU
GPS
BBU 03 01
8:1 Splitter
ANT.14135 Poly
BBU
GPS Phaser
BBU 03 01

BBU
GPS BLUE = Included with CEQ.16693
BBU 03 01 BLACK = Purchased Separately
= ½” Coax NM to NM
BBU
GPS
BBU 03 01 Terminator
ANT.14135
= for any unused splitter ports
BBU
GPS
BBU 03 01
RACK LAYOUT AT&T Densification

eCCM2

eCCM2 GPS Antenna

eCCM2
Mounting Kit
eCCM2

eCCM2

eCCM2

eCCM2

eCCM2 16:1
Splitter
eCCM2 ANT.TBD Lightening
Arrestor
eCCM2

eCCM2
BLUE = Included with CEQ.16672
eCCM2 BLACK = Purchased Separately

eCCM2 = ½” Coax NM to NM

eCCM2

eCCM2

eCCM2
DFS DMARC AT&T Densification

Existing DMARC Terminal Options With LC/UPC


Wireline Splice (placed & owned by Wireline)

OPN-500 FOSC450-C6

or

Innerduct & Fiber Innerduct & Fiber Drops


(placed & owned by Wireline) (placed & owned by Mobility)

AT&T Proprietary (Internal Use Only) Not for use or disclosure outside the AT&T companies except under written agreement
OPN-500 Terminations AT&T Densification
Port #1 Options
Port Layout

¾” Conduit Adapter (included)


Port #1 Port #3 For use with SCH 40 Rigid Nonmetallic Conduit.
¾” Conduit adapter ½” Compression Fitting

Port #2
Rubber Grommet

Port #1 – Mobility port for conduit/Microduct.


Heyco M3234
Port #2 – Wireline port for #6 ground cable. AFL Part # DM001171

Port #3 – Wireline port for fiber drop.

¾” Compression Fitting (ordered separately)


For use with ClearField 14mm Microduct.

AT&T Proprietary (Internal Use Only) Not for use or disclosure outside the AT&T companies except under written agreement
AT&T Densification
Pushable Fiber

DMARC Terminal
(placed & owned by Wireline)
Pushable Fiber

or 14mm MicroDuct

 Part # - FS-DED-NT-214-PS-1500F
 QTY - 1500' Reel

FieldShield Patchcord

INSTALL ONE 14MM MICRODUCT


FROM DMARC TO RRU LOCATION  Connector Part # - FS-AA1-002-1ZZ-3ZZ-Base
(placed & owned by Mobility)  Cable Part # - FS-AA1-002-1ZZ-3ZZ-PPF
 QTY – Per Foot

 Purchased by AT&T or install vender from


Power & Tel at pass through pricing.
INSTALL ONE FIELDSHIELD PATCHCORD PER RRU - MAX 3 PER 14MM MICRODUCT  10 Day Lead Time on custom lengths.
(placed & owned by Mobility)

AT&T Proprietary (Internal Use Only) Not for use or disclosure outside the AT&T companies except under written agreement
GROUNDING ON UTILITY POLE AT&T Densification

MULTIPLE GROUND CONNECTIONS CONNECTION TO EQUIPMENT BRACKET

SINGLE LUG COMPRESSION DOUBLE LUG COMPRESSION


LONG BARREL CONNECTOR LONG BARREL CONNECTOR

GROUND BLOCK

BARE #6 SOLID GROUND WIRE BARE #6 SOLID GROUND WIRE

BARE #6 SOLID
GROUND WIRE CONNECTION TO GROUND ROD

BARE #6 SOLID GROUND WIRE


Ground Line

12" MIN.
5/8" GROUND ROD CLAMP
TO TOP OF
WITH SHEAR HEAD
ROD
24"-36"
5/8" GROUND ROD

5/8" X 8' IF A SINGLE GROUND ROD DOES NOT HAVE A


GROUND RESISTANCE TO GROUND OF 25 OHMS OR LESS, IT
ROD SHALL BE SUPPLEMENTED BY AN ADDITIONAL
GROUND ROD. SEPARATION BETWEEN GROUND
RODS MUST BE AT A MINIMUM DISTANCE OF 6’.

AT&T Proprietary (Internal Use Only) Not for use or disclosure outside the AT&T companies except under written agreement
POLE MISC. HARDWARE AT&T Densification

 Superior Essex: 12-901-04


 Bolt-A-Band
 Solid #6 Bare Ground Wire
 Type 201 Annealed Stainless Steel
 200' Box
 Various

 Electric Motion Co: EM2DB-BL-01


 5/8" Ground Rod Clamp with Shear Head  Electric Motion Co: EM4250-5-BOH-NS
 10 Pack  Brass Tin Plated w/brass hex head screws

 Erico: 615880
 Copper Clad 5/8" x 8' Ground Rod
 Hubbell: PSC208-0330
 16" Offset from Pole
 Finish: Hot Dip Galvanized

 Thomas & Betts: 54905BE


 Single Lug Long Barrel #6 w/o inspection window
 50 Pack

 Thomas & Betts: 54852BE  Amphenol: 505-173-5-003


 Double Lug Long Barrel #6 w/o inspection window  Universal Wall/Ceiling Mount Bracket
 50 Pack  Can mount two per PSC208-0330
UTILITY POLE GROUNDING EXAMPLE AT&T Densification

Antenna
Equipment Bracket
Ericsson AC Grounding
Radio

PSU Grounded through AC cable


N L/N PE
Do not ground lug

Power Shut Off

Conduit for shut off


Nokia AC Grounding
Power Meter
Ground Point

Conduit for earth ground Conduit for earth ground


to small cell bracket to power meter

Ground Rod

AT&T Proprietary (Internal Use Only) Not for use or disclosure outside the AT&T companies except under written agreement
AT&T Densification
ERICSSON 2203/2205 LAYOUT

8" 4" 8"


2" 2"

4" RRU

TOP VIEW
8" RRU 8" RRU

FRONT VIEW SIDE VIEW


2" 2"

Option 1 Option 2 Option 3

8"
12" 24"

RRU RRU
12" RRU RRU RRU 12" RRU RRU RRU

FRONT VIEW FRONT VIEW


1 SQ FT 2 SQ FT
32" RRU 32" RRU

8"

12" RRU
12" RRU RRU RRU

SIDE VIEW
SIDE FRONT VIEW SIDE
VIEW 2 SQ FT VIEW

You might also like