Bul.

140G
Time-Current Curves for Bulletin 140G-N (-NS) Molded Case Circuit Breaker Available Rating Plugs: (In):
400; 600; 800; 1000; 1200;
Electronic Trip Unit. LSIG 1250A (IEC)
10000
t [s] 0,4..1
0,4 1
L 1

1000 t [s]

0,6..10
0.1

100
0.01

10 I2t ON
0.001
1 10 100
I [kA]

S
1
I2t OFF I
1.5...15xIn
0.1

0.01

0.001
0.1 1 10 100

Disa Current in Multiples of In Trip Threshlold Trip Time


Protection Trip Threshhold Trip Time (2) (2)
ble Tollerance Tollerance
L I1 = 0.4-0.425-0.45-0.475-0.5-…- t1 = 3-12-24-36-48-72-108- Release between
2
(t=k/I ) 1 x In 144 s (1) @3I1 1.05 and 1.2 x I1 ± 10% Ig ≤ 6xIn
with I > I2
I2 = 0.6-0.8-1.2-1.8-2.4-3-3.6- The best of:
S √ t2 = 0.1-0.2-0.3-0.4-0.5-0.6- ± 7% Ig ≤ 6xIn ± 10% or ± 40 ms
4.2-5-5.8-6.6-7.4-8.2-9-10 x In
(t=k) 0.7-0.8 s ± 10% Ig > 6xIn

I2 = 0.6-0.8-1.2-1.8-2.4-3-3.6- t2 = 0.1-0.2-0.3-0.4-0.5-0.6- ± 7% Ig ≤ 6xIn ± 15% Ig ≤ 6xIn


S √
2 4.2-5-5.8-6.6-7.4-8.2-9-10 x In 0.7-0.8 s @10In ± 10% Ig > 6xIn ± 20% Ig > 6xIn
(t=k/I )

I3 = 1.5-2-3-4-5-6-7-8-9-10-11-
I √ ≤ 30ms ± 10%
12-13-14-15 x In
(t=k)

Notes: For all cases not covereed by the above


1. The minimum value of this trip is 1s regardless of curve type (self-protection) assumptions, the following tolerance values
2. These tolerances apply under the following conditions: apply:
- self-powered relay at full power (without start-up)
- presence of auxiliary power supply Protection Trip Threshhold Trip Time
- two-phase or three-phase power supply
L 1.05 ≤ x I1 ≤ 1.25 ± 20%
- preset trip time ≥ 100ms
3. Curve accuracy applies from -20 C to +55 C ambient. S ± 10% ± 20%
For possible continuous ampere derating for ambient above 40 C, consult 140G-TD100. I ± 15% ≤ 60 ms
4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.
Others ± 20%
5. Total clearing times shown include the response times of the trip unit, the breaker opening, and the
interruption of the current.
6. For high fault current levels an additional fixed instantaneous hardware override is provided at 22 kA.

10000861841 (Version 01)


Pub. 140G-TD032B-EN-P (1)
Bul.140G
Time-Current Curves for Bulletin 140G-N (-NS) Molded Case Circuit Breaker
Ground Fault Protection Curve for LSIG MCCBs
10000
t [s]

1000

100

10

1
I4= 0.2-0.3-0.4 In disabled at 4 In
I4= 0.6 In disabled at 6 In
I4= 0.8-0.9-1 In disabled at 8 In

0.1

0.01

0.001
0.1 1 Current in Multiples of In10 100

Disa Trip Threshlold Trip Time


Protection Trip Threshhold Trip Time
ble Tollerance Tollerance

I4 = 0.2-0.3-0.4-0.6-0.8-0.9-1 with I > I4 t4 = 0.1- The best of:


G √ ± 7%
x In 0.2-0.4-0.8 s ± 10% or ± 40 ms
(t=k)

t4 = 0.1 @4.47 I4 t4 = 0.2


I4 = 0.2-0.3-0.4-0.6-0.8-0.9-1
√ @3.16 I4 t4 = 0.4 @2.24 I4 ± 7% ± 15%
x In
G t4 = 0.8 @1.58 I4
2
(t=k/I )

For all cases not covereed by the above


assumptions, the following tolerance values
apply:

Protection Trip Threshhold Trip Time

G ± 10% ± 20%
Others ± 20%