L-mag D Electromagnetic flow meter Converter

User Manual Version 1.0


L-mag D

1
Content
1.SIGNAL LINES....................................................................................................................................................... 4

1.1LABELS AND CONNECTION OF SIGNAL LINES......................................................................................................4


1.2TERMINAL WIRING............................................................................................................................................... 4
1.3 CONVERTER INSTALLATION GROUNDING REQUIREMENT....................................................................................5
2. PARAMETER SETTING............................................................................................................................................6
2.1FLOW SETUP......................................................................................................................................................... 6
USER USE MORE THAN 3 BYTE CODE TO ENTER ,THEN SET THIS PASSWORD IN CLEAR TOTAL KEY..........................6
2.2 ALARM SETUP......................................................................................................................................................7
2.3 OUTPUT SETUP.................................................................................................................................................... 9
2.4 SENSOR SETUP.................................................................................................................................................. 10
2.5 COMMUNICATION.............................................................................................................................................. 11
2.6 METER PARAMETERS......................................................................................................................................... 11

3. DISPLAY AND OPERATION.............................................................................................................................11

3.1 KEYS FUNCTION................................................................................................................................................12


3.2FUNCTIONS SELECT MENU..................................................................................................................................13

4. CONVERTER PICTURE.....................................................................................................................................14

5. THE PRODUCT FUNCTION INTRODUCTION............................................................................................ 14

5.1 BASIC FUNCTION...............................................................................................................................................14


5.2 NORMAL WORKING CIRCUMSTANCE.................................................................................................................14
5.5 DIMENSION........................................................................................................................................................15
5.6 MEASUREMENT ACCURACY.............................................................................................................................. 15
5.7 SIMULATED CURRENT OUTPUT.........................................................................................................................15
5.8 DIGITAL FREQUENCY OUTPUT.......................................................................................................................... 16
5.9 DIGITAL PULSE OUTPUT....................................................................................................................................16
5.10 ALARM OUTPUT.............................................................................................................................................. 16
5.11 DIGITAL COMMUNICATION PORT AND PROTOCOL............................................................................................16
HART INTERFACE:DESIGNED BY STANDARD OF HART , IF YOU CHOOSE OUR HAND HELD UNIT , YOU CAN
DISPLAY THE MEASURE VALUE ON LINE,AND SETTING THE PARAMETERS............................................................... 16
5.12 ELECTRICAL ISOLATION.................................................................................................................................. 16
5.13 DIGITAL OUTPUT AND CALCULATE..................................................................................................................17
5.14 SIMULATION SIGNAL OUTPUT AND CALCULATE.............................................................................................. 19

6. ALARM INFORMATION...................................................................................................................................20

7. TROUBLESHOOTING.............................................................................................................................................21
7.1 NO DISPLAY...................................................................................................................................................... 21
7.2 EXCITING ALARM.............................................................................................................................................. 21
7.3 EMPTY PIPE ALARM........................................................................................................................................... 21
7.4 FLOW MEASUREMENT INACCURACIES...............................................................................................................22

APPENDIX 1.............................................................................................................................................................22

NONLINEAR AMENDMENT FUNCTION ADDITIONAL INSTRUCTION.................................................. 22

2
APPENDIX 2 MENU CHART............................................................................................................................. 23

SETTING PARAMETERS IN MENU................................................................................................................... 23

3
L-mag D Electromagnetic flow meter Converter Operation

1.Signal Lines
1.1Labels and connection of signal lines

1.1.Labels and connection of signal lines

Signal Line:

Twisted-pair cable: Black-white12 Conductor


for exciting current
Black 12 Conductor

Gray shielded twisted-pair cable:

10 Conductors (Red) connected to “Signals 1”

13 Conductors (White) connected to “Signals 2”

Shielded Conductor connected to “Signal Ground”

1.2Terminal Wiring

4
1.2 Terminal Wiring

K:

ON: Connect with RS485 communication terminal resistance(standard resistance :120Ω)

OFF:Not connect

Noted:Terminal Resistance is used for long distance communication only. If for short distance,do not connect.

Symbols and Description of Terminals(Diagram 1)


TRX- RS485-B
TRX+ RS485-A
Frequency/Pulse/Current Common
ICOM:
Terminal (Ground)
Current Output for Flow
IOUT:
Measurement
DINP Reserve
Bi-directional flow frequency/Pulse
POUT:
output
DOUT: Alarm Output
DCOM Alarm Output(Ground)
N: 220V Power Supply
L: 220V Power Supply

1.3 Converter Installation Grounding Requirement

Contact area of copper Connector PE on Converter Cabinet for grounding should be larger than

1.6mm2.Contact resistance should be less than 10Ω.


Firstly,please cut red copper tube as length 1700mm(can be even longer if need),make it as a tent peg and put
into ground 1500mm. ( Noted:when put into the tent peg,please put some broken charcoal on the bottom of
the tent peg, and then irrigate salt water).

Secondly,weld the red copper wire to the tent peg, and finally connect the grounding wire to the sensor
flange,ground ring,pipe flange. Please check Chart 1.3.

Noted:Please use stainless steel material to fix the screw,spring washer,flat gasket.

5
Chart 1.3 Converter Grounding Diagram

2. Parameter Setting
2.1Flow setup
2.1.1 Flow Unit Flow Unit is selectable in flow parameter:L/s、L/m、L/h、m3/s、m3/m、m3/h;
2.1.2 Flow Total Unit
Converter display is counter with 9 bits, and the max is 999999999.

Flow integrator value: 0.001L、 0.010L、 0.100L、 1.000L

0.001m3、 0.010m3、 0.100m3、 1.000m3 ;

2.1.3 Clear Total Key


User use more than 3 byte code to enter ,Then set this password in Clear total key
2.1.4 Meter Factor
This fact is the special one of sensor-made-factory and the factory use this fact to unite L_Mag D

electromagnetic flow meters converters to make sure all the instruments can interchange by 0.1%.

2.1.5 Zero correction


Make sure the sensor is full of flow, and the flow is stillness. Flow zero is shown as velocity of flow, mm/s.

Converter’s zero-flow correction displays like this:

Upper small words: FS means measure value of zero;

Lower large words: correction value of zero.

When FS is not “0”, make FS = 0. Note: if change the value on next line and FS increases, please change the

6
“+, -” to correct FS to zero.

Flow zero is the compound value of the sensor, and should be recorded in sensor list and band. The unit will

be mm/s, and the sign will be opposite with correction value.

2.1.6 Low Flow cutoff


Flow cutoff is set in percentage of Upper Limit Range of flow, and users can delete all Negligible Small

Signals of flow volume, velocity and percentage out of displaying and outputting them. Sometimes user can

delete output of current output signal and frequency (pulse) output signal only to have flow, velocity and

percentage being displayed.

2.1.7 Flow Direction

If users think the direct and design are differ, just change the direct parameter is OK, but not change exciting

or signal.
2.1.8 Flow Filter Time
It means time of filter measure value. The long one can enhance the stability of flow display and output

digital, and fits for gross add up of pulse flow; the short one means fast respond rate, and fits for production

control. It is selectable 1S、2S、3S、4S、6S、8S、10S、15S、30S、60S.


2.1.9 Flow Range
Flow range means upper limit value, and lower limit value is set “0” automatically. So, it makes the range,

and makes the relation of percent display, frequency output and current output with flow:

percent display = ( flow measure / measure range) * 100 %;

frequency output = ( flow measure / measure range) * frequency full;

current output = ( flow measure / measure range) * current full + base point;

pulse output will not affect.


2.1.10 Reverse Flow En.
When “Reverse Flow En” is “enable”, if the flow flows, the sensor will export pulse and current。When it is

“disable”, the sensor will export pulse as “0” and current as “0”(4mA or 0mA) for the flow flows reversals.

2.2 Alarm setup


2.2.1 High alarm Ena.
Users can choose “Enable” or “Disable”
2.2.2 High alarm Val.
The parameter of upper limit alarm is percentage of flow range and can be set in the way of setting one

numerical value.When the value of flow percentage is larger than the value of setting value, the converter

7
outputs the alarm signal.
2.2.3 Snsr MT Range
When actual MT value is too small, user can adjust the empty pipe range. While doing this,please make sure

no liquid in the pipe.

It will display as below:

Upper Line:MR stand for the measure value of the empty pipe range.

Below Line:stand for modified value of empty pipe range

If increase modified value on the below line, MR will increase; If decrease modified value on the below

line,MR will decrease. User can adjust MR to a suitable value( suggest to adjust to around MR=500),then

actual MTP near to actual modified MR.

2.2.4 Snsr MT Zero


When the pipe is full of liquid (whether flowing or not), the parameter of “Snsr MT” could be modified more

easily. The parameter displayed upper line is real MTP, and the parameter displayed bellow is the “Snsr MT

alarm” that should be set. When setting “Snsr MT alarm”, you could be according to the real MTP, the value

that should be set is usually three to five times of real MTP.


When the pipe is full of liquid,user can adjust empty pipe zero point. When doing this,please make sure the
sensor is full of liquid, and it will display as below:

Upper Line: MZ standard for the measure value of empty pipe zero point
Below Line: Modified value of empty pipe zero point

Firstly,according to the actual MT value,adjust the modified value to make MZ=5~10 around (Noted:If add
below line modified value,MZ value will be smaller).
2.2.5 Snsr MT alarm
When the pipe is full of liquid (whether flowing or not), the parameter displayed upper line is real MTP, and
the parameter displayed below is the “Snsr MT alarm” that should be set. When setting “Snsr MT alarm”, you
could be according to the real MTP, the value that should be set is usually three to five times of real MTP
2.2.6 .Snsr measure Ena.
The state of empty pipe can be detected with the function of converter and do not need additional electrode. If

user select System alarm enable,then when the fluid is lower than electrode, the flow meter can detect as

8
empty pipe state.If the pipe is empty, the signals of analog output and digital output would be zero and

displayed flow would be zero.


2.2.7 System Alarm Ena.
Selecting Enable will have the function, and selecting Disable will cancel the function.
2.2.8 Alarm Low Value
The same as upper limit alarm.

2.3 Output setup


2.3.1 Digital output
Frequency output range corresponding to upper limit flow:percent flow 100%. Frequency output upper limit

can be set between 1~10000Hz.


2.3.2 Analog Out.Test
After adjusting analog zero and analog range,user can use this parameter to test the linearity of the output
current. User can set 0,20.00,50.00,70.00,99.99 to check the output current linearity.

2.3.3 Analog Range CRC


When the converters is made in the factory, output current have been calibrated to full scale, that is, accurate

20mA output.
2.3.4 Analog Zero CRC
Adjust analog output zero point,to accurate at 4mA.
2.3.5 Analog Output
Analog Output type: 4~20mA.
2.3.6 Pulse Output
Two kinds of Pulse Outputs are can be chosen: Frequency Output and Pulse Output. Frequency Output is

continuous square waveform and Pulse output is a serial wave of square wave. Frequency output is mainly

used for instant flow and total integrated flow in short time measurement. Frequency output can be chosen in

equivalent frequency unit and volume of integrated flow can be displayed. Frequency Output can be used in

long time measurement for total integrated flow with volume units.

Frequency output and pulse output are usually from OC gates so that DC power supplies and load resistors

have to be required.
2.3.7 Pulse Width
Pulse output is active low. Pulse width:1---9999ms
Pulse Width—Max Output Pulse Number(Chart 2)
No. Pulse Width(ms) Max Output Pulse Number/hour(p/h)

9
1 1 1800000
2 5 360000
3 10 180000
4 50 36000
5 100 18000
6 500 3600
7 999 1801
8 9999 180

2.3.8 Pulse Fact


Equivalent pulse Unit is referred to one pulse for value of flow. Pulse fact need to set two parameters

setting:“Pulse Fact Unit” And “Pulse Fact”. Range is between 00.001 L~ 59.999 m3
Under the same flow, the smaller pulse, the higher frequency output, and the smaller error will be.

2.3.9 Pulse Unit


Two pulse unit:m3 and L

2.4 Sensor Setup


2.4.1 Sensor Size

L-mag electromagnetic flow meter converter supporting sensor diameter range: 3 to 3000 mm.

3、4、5、6、8、10、15、20、25、32、40、50、65、80、100、125、150、200、250、300、320、

350、400、450、500、600、700、800、900、1000、1100、1200、1300、1400、1500、1600、1700、

1800、1900、2000、2100、2200、2300、2400、2500、2600、2700、2800、2900、3000;
2.4.2 Sensor Code
It is referred to the produced date of sensor and the serial number of product that can keep the sensors

coefficient right and accurate.

2.4.3 Sensor Factor


“Sensor Coefficient” is printed on the Label of the sensor when it is made in factory. The “sensor coefficient”

has to be set into Sensor Coefficient Parameter when it runs with converter.
2.4.4 Exat. Frequency
L_Mag D affords six exciting frequency types(default setting is 6.25Hz,25Hz and 30Hz are High-frequency

excitation frequency ):3.125Hz,4.167Hz,6.25Hz,12.5Hz,25Hz,30Hz. The small size sensor should use 6.25

Hz, and large size sensor should use 3.12Hz or 4.16Hz. When using, please select low exciting frequency first,

if the zero of velocity is too high, select other lower exciting lower frequency in turn.

10
Note: Demarcate on which exciting type, working on it only. If use high frequency excitation,should choose

12.5Hz,25Hz,30Hz
2.4.5 Lineary correct
Please refer to Appendix 1.

2.5 Communication
2.5.1 Communication Mode
L-mag D converter can accomplish three communication mode: MODBUS,HART,PROFIBUS; This is

according to user’s choice.

2.5.2 Baud Rate


Baud Rate range: 300、600、1200、2400、4800、9600、19200、38400
2.5.3 Comm Address
When communicate,this instrument’s address can be selectable from range:01~250, holding the 0.

2.6 Meter parameters


2.6.1 Password 1~4
User can use 5 grade password to enter into then can change password
2.6.2 Rev. Total
User use 5 byte code to enter, and can modify the negative accumulating volume (∑-). Usually, it is
unsuitable to exceed the minimum the counter set(999999999).
2.6.3 Fwd Total
Positive total volume high byte and low byte can change forthcoming and reverse total value, and be used to

maintenance and instead.

User use 5 byte code to enter, and can modify the positive accumulating volume (∑+). Usually, it is

unsuitable to exceed the maximum the counter set(999999999).

2.6.4 Meter Code 1 and 2


Meter code can record converter ex-factory time and code

3. Display and Operation

11
Chart 3 Keys And Display

When power on,the flow meter will automatically come into measurement state. Under automatically

measurement state, the flow meter will complete measurement function automatically and display

measurement data. Under the parameter setting way,if user want to set the parameter must change the flow

meter from measurement state to parameter setting state first. In parameter setting state,user can use keys to

accomplish parameters setting.

3.1 Keys Function


3.1.1 Keys function under automatically measurement state

“Down” key:Cycle selection screen downward display

“Right”key:Press the “right”key,the flow meter will enter into function selection screen

3.1.2 Keys function under parameter setting state

“Down” key:Subtract 1 from the number at cursor area; Page Up

“Up”key:Plus 1 to the number at cursor area; Page Down.

Touch“Right” key, make the cursor move clockwise.

Touch“Left” key, make the cursor move counter-clockwise.

When cursor move to “Up” key,press “Up” to enter sub-menu.

When cursor move to “Down” key,press“Down” to back to previous menu.

12
3.2Functions select menu
Chart 3

Code Functions Notes


3.2.1 1 Parameters Set Select this function; It can enter the picture of parameter.
2 Cl r Total Rec Select this function,It can be gross reset operation

Parameters Set

Touch “Right”key,Flow meter will enter into the state“00000” of input password,Input the password(different

grade of password please refer to APPENDIX 3) and then make cursor move to “Enter” key, touch “Enter”

key. It displays “ parameter setting”,then touch “Left”or “Right” key make cursor move the below of

“Enter”key,touch the “Enter”key into main menu and set parameters.

3.2.2 Cl r Total Rec

Touch “ Right” key, flow meter will enter into the state “00000” of input password, Input the

password(different grade of password please refer to APPENDIX 3) and then make cursor move to to

“Enter” key, touch “Enter” key. It displays“parameter setting”,then press“Up” or “ Down” key to find the

function of “Cl r Total Rec”. Input the password of Cl r Total Rec ,touch “Left” or “ Right” key to make the

cursor move to “Enter”key, Press“Enter” key. When the Cl r Total Rec password back to “00000”,the clear

total function is finished.

13
4.Converter Picture

5.

Chart 4.1 Converter Picture

5. The product function introduction


5.1 Basic Function
■ Flow Rate :0.1 --- 15m/s,current speed resolution:0.5mm/s

■ AC high frequency switching power,range of voltage:185VAC --- 250VAC

■ DC24V switching power,range of voltage:20VDC --- 36VDC

■ Function(Option):MODBUS、HART、 GPRS、PROFIBUS;

■ Two integrator gross inside,respective register:Forward gross,reverse gross

5.2 Normal Working Circumstance


Ambient Temperature Ranges: fission –10~+60℃;

Relative Humidity:5%~90%;

Power Supply: 85~250V,45~63Hz;

Dissipation Power:< 20W(After connecting sensor)

14
5.5 Dimension

Chart 8.6 Dimension Drawing

5.6 Measurement Accuracy

VS:Setting measurement range(m/s)

Diameter mm Range m/s Accuracy

3~20 ≤0.3 ±0.25%FS


0.3~1 ±1.0%R
1~15 ±0.5%R
25~600 0.1~0.3 ±0.25%FS
0.3~1 ±0.5%R
1~15 ±0.3%R
700~3000 ≤0.3 ±0.25%FS
0.3~1 ±1.0%R
1~15 ±0.5%R
%FS:for relative ranges;%R:for relative value

5.7 Simulated Current Output


Load resistor: 0~750Ω。

Basic Errors: 0.1%±10μA。

15
5.8 Digital Frequency Output
Frequency output range:1~10000Hz;

Output electric isolate:Photoelectric isolate. Isolate voltage:> 1000VDC;

Frequency output drive : output by field-effect transistors,the highest subjected voltage is

36VDC,maximum of output current is 250mA.

5.9 Digital Pulse Output


Pulse output value:0.001~59.999 m3 / cp、

0.001~59.999 Ltr / cp、

Pulse output width:1~500ms adjustable;

Pulse output isolate:photoelectric isolate,Isolate voltage: > 1000VDC;

Pulse output drive:output by field-effect transistors,the highest subjected voltage is 36VDC,maximum

of output current is 250mA.

5.10 Alarm Output


Alarm output junction:DOUT --- upper,lower limit and empty pipe alarm common output point;If there’s

alarm,output low level signal. If there’s no alarm,output high level signal.

Output isolate:Photo electricity isolate. Isolate voltage:> 1000VDC;

Alarm output drive:output by Darlington pipe,the highest subjected voltage is 36VDC,maximum of output

current is 250mA.

5.11 Digital communication port and protocol


MODBUS interface:format of RTU, physical interface RS-485,electrical separation 1000V;

HART interface:designed by standard of HART , if you choose our hand held unit , you can display the

measure value on line,and setting the parameters

5.12 Electrical Isolation


Insulated voltage between simulated input and simulated output should be higher than 500V;

Insulated voltage between simulated input and alarm power supply should be higher than 500V;

Insulated voltage between simulated input and AC power supply should be higher than 500V;

Insulated voltage between simulated output and AC power supply should be higher than 500V;

Insulated voltage between simulated output and earth should be higher than 500V;

16
Insulated voltage between pulse output and AC power supply should be higher than 500V;

Insulated voltage between pulse output and earth should be higher than 500V;

Insulated voltage between alarm output and AC power supply should be higher than 500V;

Insulated voltage between alarm output and earth should be higher than 500V;

5.13 Digital output and calculate


Digital output means frequency output and pulse output, and both of them use the same output point, so user

can choose only one type of them but not both.

5.13.1 Frequency output:

Frequency output range is 0~5000HZ, and corresponding the percent of flux.


Measure value
F=  frequency range
Full scale value
The upper limit of frequency output can be adjusted. It can be chosen from 0 ~ 10000HZ, and also can be

chosen low frequency: such as 0 ~ 1000HZ or 0 ~ 5000HZ.

Frequency output mode general can be used in control application, because it responses the percent flux.

Users can choose pulse output when the equipment is applied to count.

5.13.2 Pulse output mode

Pulse output mainly applies in count mode. A pulse output delegates a unit flux, such as 1L or 1M3 etc.

Pulse output unit can be set from range 0.001L~59.999m3 .When users choose the pulse unit, they should

notice the match of the flux range of flow meter and pulse unit. For volume flux, count formula as follows:

QL = 0.0007854 × D2 × V (L/S)

QM = 0.0007854 × D2 × V × 10-3(M3/S)

D-nozzle(mm) V-velocity(m/s)

The oversize flux and too small pulse unit will be made the pulse output over the up limit. Generally, pulse

output should be controlled below 500Hz. However, the too small flux and too large pulse unit will be made

the instrument exports a pulse long time. Detailed setting can refer to the chart of “Pulse width-Maximum

output pulse number”.

Otherwise, pulse output is different from frequency output. When pulse output cumulates a pulse unit, it

exports a pulse. Therefore, pulse output is not equality. Generally, measure pulse output should choose to

count instrument, but not frequent instrument.

17
5.13.3 The connection of digital output

Digital output has two connected points: digital output connected point, digital ground point, and symbol as

follows:

POUT ----- digital output point;

ICOM ----- digital ground point;

POUT is open collector output, user may refer to next circuit to connect.

5.13.4 The connection of digital voltage output

5.13.5 Digital output connect photo electricity coupling (PLC etc.)

Commonly user’s photo electricity coupling current is about 10mA, so about E/R=10mA, E=5~24V

5.13.6 Digital output connect relay

18
Commonly relay needs E as 12V or 24V. D is extend diode, now most middle relays has this diode inside. If

not have, user can connect one outside.

Table of digital output parameter:

POUT
Parameter Test condition Min Typical Max Unit

Vo l t a g e IC=100 mA 5 24 36 V

C u r r e n t Vol≤1.4V 0 300 350 mA

IC=100mA
Frequency 0 5000 7500 HZ
Vcc=24V

High voltage IC=100mA Vcc Vcc Vcc V

Low voltage IC=100mA 0.9 1.0 1.4 V

5.14 Simulation signal output and calculate


5.14.1 Simulation signal output

Simulation signal output:4~20mA signal.

Simulation signal output inner is 24V , it can drive 750Ω resistance.

The percent flux of simulation signal output:


Measure value
I0 =  the scale of current + the zero point of current
Full scale value

For 4~20mA signal,current zero is 4mA

It can be advanced simulation signal output distinguish. User can select the range of measure.

Parameters before ex-factory, manufacturer have already set the suitable parameters. In normal case,there’s

no need to adjust anymore.If have abnormity, it can consult as below:

5.14.2 Simulation Signal Output Adjust

(1)The Converter adjust preparative

hen the converter is running 15 minutes, the inner of converter becomes stabilization. Preparative 0.1%

ampere meter or 250Ω、 0.1% voltage instrument.

19
1.000
IOUT
DC20V
Converter

ICOM

(2)Current zero correct

When the converter getting into parameter setting, selecting to “Analog Zero” and enter to it. The standard

of signal fountain getting to “0”.Adjust parameter make ampere meter is 4mA(±0.004mA).

(3)The full scale current correct

To select “Analog Range” to enter.Adjust the converter parameter make ampere meter is

20mA(±0.004mA)

Adjust the current zero and the full range, the current function of the converter reached exactness.The

line degree of current output of conversion should be controlled within the scope of 0.1%

(4)Current line degree checking

You can place the standard signal source in 75%、50%、25%,and check the line degree of current output

※ Note : After L-mag D Electromagnetic flow meter converter 、 sensor be connected to fluid

pipeline(whatever for calibration or normal use),Please follow below steps first:

 Use copper line to connect the pipeline before the sensor and pipeline after the sensor tightly.

 Make sure sensor grounding well

 When set the zero point,make sure the liquid in the pipeline is static

 Make sure the electrode oxidation film inside sensor is stable(Usually make the electrode and liquid

continuously connect more than 48hours is ok)

6. Alarm Information
PCB of electromagnetic flow meters converters uses SMT, so for user, it is unable to service, and cannot open

the shell of converter.

L-mag D Intelligent converters have self-diagnose function. Without trouble of power and hardware
circuit, the normal trouble can be alarmed correctly. This information displays on the left of LCD. The trouble

is like this:

SYS ---- System exciting alarm.; MTP ---- Flow empty pipe alarm;

CUT ---- Small signal Cut Alarm; REV ---- Reverse Flow Cut Alarm
20
HIG ---- Flow high limit alarm; LOW---- Flow low limit alarm

7. Troubleshooting
7.1 No display
a) Check the power supply connection;

b) Check the power fuse to see for OK;

c) Check the contrast of LCD and regulate it to working state;

7.2 Exciting alarm


a) Check if the exciting cables EX1 and EX2 did not connected;

b) Check if the total resistance of sensor’s exciting coil resistances less than 150Ω;

c) If a) and b) are OK, the converter is failed.

7.3 Empty pipe alarm


* If measured fluid full of testing pipe of sensor;

* When shorting circuit three connectors SIG +, SIG -, SGND of converter, and no “Empty Alarm”

displayed then the converter works OK. In this case, it is possible that conductivity of measured fluid

may be small or empty threshold of empty pipe and range of empty pipe are set wrongly.

* Check if the signal cable is OK;

* Check if the electrode-poles are OK or not.

Let the flow is zero, then the displayed conductivity should be less than 100%.

Resistances of SIG+ to SGND and SIG- to SGND are all less than 50kΩ (conductivity of water)

during measurement operation. (It is better to test the resistances by means of multimeter with pointer

to see the charging process well.)

* The DC voltage should be less than 1V between DRS+ and DRS- testing the voltage by means of

multimeter. If DC voltage is larger than 1V, the electrode poles of sensor were polluted that have to be

cleaned.

21
7.4 Flow measurement inaccuracies

*Measuring fluid sensor tubes are filled;

*Signal cable is connected properly;

*Check the sensor coefficient, whether the sensor zero calibration sensor plate or single factory settings

Appendix 1
Nonlinear Amendment function Additional Instruction
Nonlinear amendment function,in principle is used for line regulation of low flow which under 0.5m/s. The

function is designed to four amendments, and divided into four flow velocity points and four correction

factors.

Nonlinear amendment coefficient works on the basis of the original transducer calibration coefficient, so

please close nonlinear amendment function before calibrating the transducer coefficient, and open the

function to realize nonlinear amendment after calibrating. Set correction points and correction factors

according to the nonlinear segment of transducer, if be the appropriate settings, do not have to re-calibration.

As a rule, the flow velocity which calculated form transducer coefficient is called original flow velocity, and

the other which gained from non-linear amendment is called correction flow velocity. The relationship

between them is shown as following:

a. Correction point 1 > Original flow velocity ≥ Correction point 2:

Correction flow velocity = Correction coefficient 1 × Original flow velocity

b. Correction point 2 > Original flow velocity ≥ Correction point 3:

Correction flow velocity = Correction coefficient 2 × Original flow velocity

c. Correction point 3 > Original flow velocity ≥ Correction point 4:

Correction flow velocity = Correction coefficient 3 × Original flow velocity

d. Correction point 4 > Original flow velocity ≥ 0:

Correction flow velocity = Correction coefficient 4 × Original flow velocity

Notice: Correction points must satisfy the following relationship:

Correction point 1>Correction point 2>Correction point 3>Correction point 4

The intermediate value of correction coefficient is 1.0000,when bigger than it is considered as positive

22
coefficient (increase), and smaller is considered as negative coefficient (decrease).

Appendix 2 Menu Chart

Setting Parameters in Menu

Setting Grad
Code Parameter words
Way
Range
es
Flow set up Select
1 Flow unit Select L/h、L/m、L/s、m3/h、m3/m、m3/s 2
2 Flow total unit Select 0.001m3~1m3 、0.001L~1L、 2
3 Clear total key Set count 0~99999 3
4 Meter Factor Set count 0.0000~5.9999 2
5 Zero correction Set count 0~±9999 2
6 Fluid density Set count 0~19.999T/m3 2
7 Low flow cutoff Set count 0~599.99% 2
8 Cutoff alarm en. Select Enable/Disable 2
9 Flow direction Select Plus/ Reverse 2
10 Noise limit tim. Set count 0s~20s 3
11 Noise limit val. Set count 0%~30% 3
12 Flow filter time Select 1~60S 2
13 Flow range Set count 0~99999 2
14 Reverse flow en. Select Enable/Disable 2
Alarm setup
1 High alarm ena. Select Enable/Disable 2
2 High alarm val. Set count 000.0~599.99% 2
3 Snsr MT range Set count 0~5.9999 5
4 Snsr MT zero Set count 0~59999 5
5 Snsr MT alarm Set count 0~59999 2
6 Snsr measure ena. Select Enable/Disable 2
7 System alarm ena. Select Enable/Disable 2
8 Low alarm value Set count 000.0~599.99% 2
9 Low alarm ena. Select Enable/Disable 2
Output setup
1 Digital output Set count 1~ 10000 Hz 2
2 Analog out.test Set count 0.0000~0.9999 2
3 Analog range CRC Set count 0.0000~3.9999 5
4 Analog zero CRC Set count 0.0000~1.9999 5
5 Analog output Select 4-20mA 2
6 Pulse output Select Frequency/pulse 2
7 Pulse width Select 1~9999ms 2
8 Pulse factor Set count 00.001~ 59.999 2
9 Pulse unit Select m3 、L 2
Sensor setup
1 Sensor size Select 3~3000 2
2 Sensor code 2 User set Product number(0-99999) 4
3 Sensor code 1 User set Finished Y M(0-99999) 4
4 Velocity point 5 User set Set Velocity 4
5 Velocity value 4 User set 0.0000~1.9999 4
6 Velocity point 4 User set Set Velocity 4
7 Velocity value 3 User set 0.0000~1.9999 4
8 Velocity point 3 User set Set Velocity 4
23
9 Velocity value 2 User set 0.0000~1.9999 4
10 Velocity point 2 User set Set Velocity 4
11 Velocity value 1 User set 0.0000~1.9999 4
12 Velocity point 1 User set Set Velocity 4
13 Lineary correct Selec Enable/Disable 4
14 Sensor factor Set count 0.0000~5.9999 4
15 Exat.frequency Select 3.125Hz~12.5Hz 4
Communication
1 Communication code Select MODBUS、HART、PROFIBUS 2
2 Check mode Set count 0~250 2
3 Baud rate Select 300~38400 2
Communication No Parity Check;
4 address
Select
Odd Parity Check;Even Parity Check
2
Meter parameters
1 Pass Word 1 User set 0~59999 5
2 Rev.total high User set 0~9999 5
3 Rev.total low User set 0~99999 5
4 Fwd. total high User set 0~9999 5
5 Fwd. total low User set 0~99999 5
6 Meter Code 2 Factory set Finished Y /M(0-99999)
7 Meter Code 1 Factory set Finished Y /M(0-99999)
8 Password 4 User set 0~59999 5
9 Password 3 User set 0~59999 5
10 Password 2 User set 0~59999 5
11 Password 1 User set 0~59999 5

Parameters of converters can decide the running status, process and output ways as well as state of output. Correct option and

setting of parameters can keep the converters running optimally and get higher accuracy of output bother in display and in

measurement.

There are 5 grades of passwords for setting parameters function. Grades 1 to grade 4of passwords are for users and grade 5

of password is for manufacturer. Users can reset their passwords of grades 1~4 in grade

Users can check converters parameters in any grade of password. However, if users want to change parameters pf converters,

different grade of parameters have to be used by the users.

Grade 1 of password (set by manufacturer as 00522): users can only read parameter;

Grade 2 of password (set by manufacturer as 03210);


Grade 3 of password (set by manufacturer as 06108);
Grade 4 of password (set by manufacturer as 07206);
Grade 5 of password (Fixed):users can change with reference above parameters.

24