INDOOR UNITS TC

INDOOR UNITS
Technical Catalog
Technical Data

Series

Qingdao Hisense Hitachi Air-conditioning Systems Co.,Ltd. <Indoor Units>


Add: Hisense Information Industry Park 218,Qianwangang
• Ceiling Ducted Type (Low Static Pressure)
Road, Qingdao Economic Development Zone,China • Ceiling Ducted Type (High Static Pressure)
Tel:+86-532-80879968 Fax:+86-532-80875929 • Low-Height Ceiling Ducted Type
Http: //www.hisensehitachi.com
E-mail: export@hisensehitachi.com • DC Low Height Ducted Type
• Slim Ceiling Ducted Type
TC2 2017003C

Specifications in this catalogue are subject to change without notice,in order that Hisense may bring the latest innovations to their customers. • 4-Way Cassette Type
• Compact 4-Way Cassette Type
• Ceiling & Floor Type
• Wall Mounted Type
• Floor Concealed Type
• All Fresh Air Indoor Unit
TC2 2017003C • 2-Way Cassette Type
TC2 2017003C
• 1-Way Cassette Type
Hisense

Hisense

Hisense
IMPORTANT NOTICE

Correct Disposal of this product


This marking indicates that this product should not be disposed with other
household wastes. To prevent possible harm to the environment or human
health from uncontrolled waste disposal, recycle it responsibly to promote the
sustainable reuse of material resources. To return your used device, please use
the return and collection systems or contact the retailer where the product was
purchased. They can take this product for environmental safe recycling.

Hisense's
Hisense's
l The appliance is not to be used by children or person with reduced physical, sensory or mental
capabilities,or lack of experience and knowledge, unless they have been given supervision or
instruction concerning use of the appliance by a person responsible for their safety.

l Children should be supervised that they do not play with the appliance.
l The appliance should not be installed in the laundry.


-CONTENTS-
1. Connectable Outdoor Units and Working Range ............................................................ 1
1.1 Connectable Outdoor Units .......................................................................................... 1
1.2 Working Range.............................................................................................................. 1
2.Necessary Tools.................................................................................................................. 2
3.Transportation and Handling ............................................................................................... 2
3.1 Transportation .............................................................................................................. 2
3.2 Handing of Indoor Unit ................................................................................................ 2
4. Indoor Unit Installation ...................................................................................................... 2
5.Celling ducted type (Low/High Static Pressure AVD) ......................................................... 3
5.1 General Data ............................................................................................................... 3
5.2 Dimensional Data ....................................................................................................... 10
5.3 Selection Data ............................................................................................................ 12
5.4 Component Data ........................................................................................................ 29
5.5 Control System ........................................................................................................... 33
5.6 Electrical Data ............................................................................................................. 35
5.7 Electrical Wiring Diagram ......................................................................................... 38
5.8 Indoor Unit Optional Parts ....................................................................................... 41
5.9 Factory-Supplied Accessories .................................................................................. 42
5.10 Installation................................................................................................................ 43
5.10.1 Initial Check ....................................................................................................... 43
5.10.2 Installation.......................................................................................................... 43
5.10.3 Refrigerant Piping Work .................................................................................... 46
5.10.4 Drain Piping........................................................................................................ 48
5.10.5 Electrical Wiring ................................................................................................. 49
5.10.6 Test Run............................................................................................................. 51
5.10.7 Common ............................................................................................................ 52
6. Low-Height / Slim Low-Height / DC Low Height Ducted Type (AVE)............................ 54
6.1 General Data ............................................................................................................. 54
6.2 Dimensional Data...................................................................................................... 59
6.3 Selection Data........................................................................................................... 62
6.4 Component Data ...................................................................................................... 72
6.5 Refrigeration Cycle ................................................................................................... 75
6.6 Electrical Data .......................................................................................................... 76
6.7 Electrical Wiring Diagram ...................................................................................... 78
6.8 Indoor Unit Optional Parts ..................................................................................... 81
6.9 Factory-Supplied Accessories ................................................................................ 82
6.10 Install ..................................................................................................................... 83
6.10.1 Initial Check .................................................................................................... 83
6.10.2 Installation ...................................................................................................... 83
6.11 Refrigerant Piping Work ....................................................................................... 86
6.11.1 Piping Materials ................................................................................................. 86
6.11.2 Piping Connection .............................................................................................. 86
6.12 Drain Piping .............................................................................................................. 87
6.13 Electrical Wiring ........................................................................................................ 88
6.13.1 General Check .................................................................................................... 89
6.13.2 Electrical Wiring Connection .............................................................................. 89
6.14 Test Run .................................................................................................................. 91
6.15 Common ................................................................................................................... 91
6.15.1 Field Minimum Wire Sizes For Power Source ................................................... 91
6.15.2 Setting of Dip Switches ..................................................................................... 92
6.15.3 FILTER SIGN RESET .......................................................................................... 93
7. 4-Way Cassette Type ...................................................................................................... 94
7.1 General Data ............................................................................................................... 94
7.2 Dimensional Data ....................................................................................................... 97
7.3 Selection Data ............................................................................................................ 99
7.4 Component Data ........................................................................................................ 103
7.5 Refrigeration Cycle ..................................................................................................... 105
7.6 Electrical Data ............................................................................................................. 106
7.7 Electrical Wiring Diagram .......................................................................................... 108
7.8 Indoor Unit Optional Parts ........................................................................................ 109
7.9 Factory-Supplied Accessories ................................................................................... 110
7.10 Install ........................................................................................................................ 111
7.10.1 Initial Check ....................................................................................................... 111
7.10.2 Installation .......................................................................................................... 112
7.11 Refrigerant Piping Work ........................................................................................... 114
7.11.1 Piping Materials ................................................................................................. 114
7.11.2 Piping Connection .............................................................................................. 114
7.12 Drain Piping .............................................................................................................. 115
7.13 Electrical Wiring ........................................................................................................ 116
7.13.1 General Check ................................................................................................... 116
7.13.2 Electrical Wiring Connection .............................................................................. 116
7.14 Test Run .................................................................................................................... 117
7.15 Common..................................................................................................................... 117
7.15.1 Field Minimum Wire Sizes For Power Source.................................................... 117
7.15.2 Setting of Dip Switches ...................................................................................... 118
7.16 Setting of Automatic Swing Louver ........................................................................... 119
7.17 Filter Cleaning ............................................................................................................ 119
7.17.1 Taking Out the Filter ......................................................................................... 119
7.17.2 Clean The Filter ................................................................................................ 119
7.17.3 Reset of Filter Indicaltion ................................................................................. 119
7.18 Troubleshooting ........................................................................................................ 120
7.18.1 If Troble Still Remains ........................................................................................ 120
7.18.2 No Operation ...................................................................................................... 120
7.18.3 Not Cooling or Heating Well .............................................................................. 120
7.18.4 This is Not Abnormal ......................................................................................... 120
8. Compact 4-Way Cassette Type ...................................................................................... 121
8.1 General Data ............................................................................................................... 121
8.2 Dimensional Data ....................................................................................................... 122
8.3 Selection Data ............................................................................................................ 123
8.4 Component Data ........................................................................................................ 125
8.5 Refrigeration Cycle ..................................................................................................... 126
8.6 Electrical Data ............................................................................................................. 127
8.7 Electrical Wiring Diagram .......................................................................................... 128
8.8 Indoor Unit Optional Parts ........................................................................................ 129
8.9 Factory-Supplied Accessories ................................................................................... 130
8.10 Install ........................................................................................................................ 131
8.10.1 Initial Check ....................................................................................................... 131
8.10.2 Installation .......................................................................................................... 132
8.11 Refrigerant Piping Work ........................................................................................... 135
8.11.1 Piping Materials ................................................................................................. 135
8.11.2 Piping Connection .............................................................................................. 135
8.12 Drain Piping .............................................................................................................. 137
8.13 Electrical Wiring ........................................................................................................ 137
8.13.1 General Check ................................................................................................... 138
8.13.2 Electrical Wiring Connection .............................................................................. 138
8.13.3 Fan Motor Speed-up Setting(SHi) .................................................................... 138
8.14 Test Run .................................................................................................................... 139
8.15 Common .................................................................................................................... 139
8.15.1 Field Minimum Wire Sizes For Power Source................................................... 139
8.15.2 Setting of Dip Switches ..................................................................................... 140
8.16 Setting of Automatic Swing Louver .......................................................................... 141
8.17 Filter Cleaning ............................................................................................................ 141
8.17.1 Taking Out the Filter ......................................................................................... 141
8.17.2 Clean The Filter ................................................................................................ 141
8.17.3 Reset of Filter Indicaltion ................................................................................. 141
8.18 Troubleshooting ........................................................................................................ 142
8.18.1 If Troble Still Remains ........................................................................................ 142
8.18.2 No Operation ...................................................................................................... 142
8.18.3 Not Cooling or Heating Well .............................................................................. 142
8.18.4 This is Not Abnormal ......................................................................................... 142
9. Ceiling & Floor Type(AVV) ............................................................................................ 143
9.1 General Data ............................................................................................................... 143
9.2 Dimensional Data ....................................................................................................... 145
9.3 Selection Data ............................................................................................................ 146
9.4 Component Data ........................................................................................................ 149
9.5 Refrigeration Cycle ..................................................................................................... 150
9.6 Electrical Data ............................................................................................................. 151
9.7 Electrical Wiring Diagram .......................................................................................... 152
9.8 Indoor Unit Optional Parts ........................................................................................ 153
9.9 Factory-Supplied Accessories ................................................................................... 154
9.10 Install ........................................................................................................................ 156
9.10.1 Initial Check ....................................................................................................... 156
9.10.2 Installation .......................................................................................................... 157
9.11 Refrigerant Piping Work ........................................................................................... 159
9.11.1 Piping Materials ................................................................................................. 159
9.11.2 Piping Connection .............................................................................................. 159
9.12 Drain Piping .............................................................................................................. 160
9.13 Electrical Wiring ........................................................................................................ 162
9.13.1 General Check ................................................................................................... 162
9.13.2 Electrical Wiring Connection .............................................................................. 162
9.14 Test Run .................................................................................................................. 163
9.15 Common .................................................................................................................. 164
9.15.1 Field Minimum Wire Sizes For Power Source................................................... 164
9.15.2 Setting of Dip Switches ..................................................................................... 164
9.16 Setting of Automatic Swing Louver ........................................................................ 165
9.17 Filter Cleaning .......................................................................................................... 165
9.17.1 Taking Out the Filter ......................................................................................... 165
9.17.2 Clean The Filter ................................................................................................ 166
9.17.3 Reset of Filter Indicaltion ................................................................................. 166
9.18 Troubleshooting ...................................................................................................... 166
9.18.1 If Troble Still Remains ........................................................................................ 166
9.18.2 No Operation ...................................................................................................... 166
9.18.3 Not Cooling or Heating Well .............................................................................. 166
9.18.4 This is Not Abnormal ......................................................................................... 166
10. Wall Mounted Type ........................................................................................................ 167
10.1 General Data ............................................................................................................. 167
10.2 Dimensional Data ..................................................................................................... 169
10.3 Selection Data .......................................................................................................... 171
10.4 Component Data ...................................................................................................... 174
10.5 Refrigeration Cycle ................................................................................................... 176
10.6 Electrical Data ........................................................................................................... 177
10.7 Electrical Wiring Diagram ........................................................................................ 178
10.8 Indoor Unit Optional Parts ...................................................................................... 179
10.9 Factory-Supplied Accessories ................................................................................. 180
10.10 Install ...................................................................................................................... 180
10.10.1 Initial Check ..................................................................................................... 180
10.10.2 Installation ........................................................................................................ 181
10.10.3 Mounting the Indoor Units .............................................................................. 183
10.10.4 Removing Flat Panel ........................................................................................ 183
10.11 Refrigerant Piping Work ......................................................................................... 184
10.11.1 Piping Materials ............................................................................................... 184
10.11.2 Piping Connection ............................................................................................ 185
10.12 Drain Piping ............................................................................................................ 186
10.13 Electrical Wiring ...................................................................................................... 187
10.13.1 General Check ................................................................................................. 188
10.13.2 Electrical Wiring Connection ............................................................................ 188
10.14 Test Run ................................................................................................................ 189
10.15 Common ................................................................................................................ 189
10.15.1 Field Minimum Wire Sizes For Power Source................................................. 189
10.15.2 Setting of Dip Switches ................................................................................... 190
10.15.3 Setting the Filter Indication Interval ................................................................. 191
10.15.4 Indoor Unit Address ......................................................................................... 192
10.16 Setting of Automatic Swing Louver ....................................................................... 194
10.17 Automatic Control .................................................................................................. 194
10.18 Filter Cleaning ........................................................................................................ 195
10.18.1 Taking Out the Filter ....................................................................................... 195
10.18.2 Clean The Filter .............................................................................................. 195
10.18.3 Reset of Filter Indicaltion ............................................................................... 195
10.19 Troubleshooting .................................................................................................... 195
10.19.1 If Troble Still Remains ...................................................................................... 195
10.19.2 No Operation .................................................................................................... 195
10.19.3 Not Cooling or Heating Well ............................................................................ 195
10.19.4 This is Not Abnormal ....................................................................................... 195
11. Floor Concealed Type(AVH) ........................................................................................... 196
11.1 General Data ............................................................................................................. 196
11.2 Dimensional Data ..................................................................................................... 197
11.3 Selection Data .......................................................................................................... 198
11.4 Component Data ...................................................................................................... 200
11.5 Refrigeration Cycle ................................................................................................... 201
11.6 Electrical Data ........................................................................................................... 202
11.7 Electrical Wiring Diagram ........................................................................................ 203
11.8 Indoor Unit Optional Parts ...................................................................................... 204
11.9 Factory-Supplied Accessories ................................................................................. 205
10.10 Installation Check ................................................................................................... 206
11.11 Installation.............................................................................................................. 206
11.11.1 Suspension Bolts ............................................................................................. 206
11.11.2 Hanging the IndoorUnit................................................................................... 207
11.11.3 Connecting Supply Duct ................................................................................. 207
11.12 Refrigerant Piping Work ......................................................................................... 207
11.12.1 Piping Materials ............................................................................................... 207
11.12.2 Piping Connection ............................................................................................ 208
11.13 Drain Piping ............................................................................................................ 209
11.14 Electrical Wiring ...................................................................................................... 209
11.14.1 General Check ................................................................................................. 210
11.14.2 Electrical Wiring Connection ............................................................................ 210
11.15 Test Run ................................................................................................................ 210
11.16 Common ................................................................................................................ 211
11.16.1 Field Minimum Wire Sizes For Power Source................................................. 211
11.16.2 Setting of Dip Switches ................................................................................... 211
11.16.3 FILTER SIGN RESET ....................................................................................... 212
11.17 Troubleshooting .................................................................................................... 212
11.17.1 If Troble Still Remains ...................................................................................... 212
11.17.2 No Operation .................................................................................................... 213
11.17.3 Not Cooling or Heating Well ............................................................................ 213
11.17.4 This is Not Abnormal ....................................................................................... 213
12. All Fresh Air Indoor Unit(AVA) ........................................................................................ 214
12.1 General Data ............................................................................................................. 214
12.2 Dimensional Data ..................................................................................................... 216
12.3 Selection Data .......................................................................................................... 218
12.4 Component Data ...................................................................................................... 224
12.5 Refrigeration Cycle ................................................................................................... 225
12.6 Electrical Data ........................................................................................................... 227
12.7 Electrical Wiring Diagram ........................................................................................ 228
12.8 Indoor Unit Optional Parts ...................................................................................... 233
12.9 Factory-Supplied Accessories ................................................................................. 234
12. 10 Installation For Model(30~114) ........................................................................... 235
12.10.1 Initial Check ..................................................................................................... 235
12.10.2 Installation ........................................................................................................ 235
12.11 Refrigerant Piping Work For Model(30~114) ........................................................ 239
12.11.1 Piping Materials ............................................................................................... 239
12.11.2 Piping Connection ............................................................................................ 239
12.12 Drain Piping For Model(30~114) ........................................................................... 240
12.13 Electrical Wiring For Model(30~114) ..................................................................... 241
12.13.1 General Check ................................................................................................. 241
12.13.2 Electrical Wiring Connection ............................................................................ 241
12.14 Common (For Model 30~114) ............................................................................. 243
12.14.1 Field Minimum Wire Sizes For Power Source................................................. 243
12.15 Factory-Supplied Accessories(For Model 154~190) ............................................ 244
12.16 Installation (For Model 154~190) ......................................................................... 244
12.16.1 Initial Check ..................................................................................................... 244
12.16.2 Installation ........................................................................................................ 245
12.17 Refrigerant PipingWork (For Model 154~190) ...................................................... 247
12.17.1 Piping Materials ............................................................................................... 247
12.17.2 Piping Connection ............................................................................................ 248
12.18 Drain Piping ............................................................................................................ 249
12.19 Electrical Wiring ...................................................................................................... 250
12.19.1 General Check ................................................................................................. 250
12.19.2 Electrical Wiring Connection ............................................................................ 250
12.20 Test Run(For Model:154~190)............................................................................... 252
12.20.1 Setting of Dip Switches .................................................................................. 253
13. 2-Way Cassette Type(AVL) ........................................................................................... 254
13.1 General Data ............................................................................................................. 254
13.2 Dimensional Data ..................................................................................................... 257
13.3 Selection Data .......................................................................................................... 258
13.4 Component Data ...................................................................................................... 261
13.5 Refrigeration Cycle ................................................................................................... 263
13.6 Electrical Data ........................................................................................................... 264
13.7 Electrical Wiring Diagram ........................................................................................ 265
13.8 Indoor Unit Optional Parts ...................................................................................... 266
13.9 Factory-Supplied Accessories ................................................................................. 267
13.10 Installation ............................................................................................................. 268
13.10.1 Initial Check ..................................................................................................... 268
13.10.2 Installation ........................................................................................................ 269
13.10.3 Mounting the Indoor Units .............................................................................. 269
13.11 Refrigerant Piping Work ......................................................................................... 271
13.11.1 Piping Materials ............................................................................................... 271
13.11.2 Piping Connection ............................................................................................ 271
13.12 Drain Piping ............................................................................................................ 272
13.13 Electrical Wiring ...................................................................................................... 273
13.13.1 General Check ................................................................................................. 273
13.13.2 Electrical Wiring Connection ............................................................................ 273
13.14 Test Run ................................................................................................................ 274
13.15 Common ................................................................................................................ 275
13.15.1 Field Minimum Wire Sizes For Power Source................................................. 275
13.15.2 Setting of Dip Switches ................................................................................... 275
13.16 Setting of Automatic Swing Louver ...................................................................... 276
13.17 Filter Cleaning ........................................................................................................ 276
13.17.1 Taking Out the Filter ....................................................................................... 276
13.17.2 Clean The Filter .............................................................................................. 277
13.17.3 Reset of Filter Indicaltion ............................................................................... 277
13.18 Troubleshooting .................................................................................................... 277
13.18.1 If Troble Still Remains ...................................................................................... 277
13.18.2 No Operation .................................................................................................... 277
13.18.3 Not Cooling or Heating Well ............................................................................ 277
13.18.4 This is Not Abnormal ....................................................................................... 277
14. 1-Way Cassette Type(AVL) ........................................................................................... 278
14.1 General Data ............................................................................................................. 278
14.2 Dimensional Data ..................................................................................................... 280
14.3 Selection Data .......................................................................................................... 281
14.4 Component Data ...................................................................................................... 283
14.5 Refrigeration Cycle ................................................................................................... 284
14.6 Electrical Data ........................................................................................................... 285
14.7 Electrical Wiring Diagram ........................................................................................ 286
14.8 Indoor Unit Optional Parts ...................................................................................... 287
14.9 Factory-Supplied Accessories ................................................................................. 288
14.10 Installation ............................................................................................................. 289
14.10.1 Initial Check ..................................................................................................... 289
14.10.2 Installation ........................................................................................................ 290
14.10.3 Mounting the Indoor Units .............................................................................. 290
14.11 Refrigerant Piping Work ......................................................................................... 292
14.11.1 Piping Materials ............................................................................................... 292
14.11.2 Piping Connection ............................................................................................ 292
14.12 Drain Piping ............................................................................................................ 293
14.13 Electrical Wiring ...................................................................................................... 294
14.13.1 General Check ................................................................................................. 294
14.13.2 Electrical Wiring Connection ............................................................................ 294
14.14 Test Run ................................................................................................................ 295
14.15 Common ................................................................................................................ 296
14.15.1 Field Minimum Wire Sizes For Power Source................................................. 296
14.15.2 Setting of Dip Switches ................................................................................... 296
14.16 Setting of Automatic Swing Louver ...................................................................... 297
14.17 Filter Cleaning ........................................................................................................ 298
14.17.1 Taking Out the Filter ....................................................................................... 298
14.17.2 Clean The Filter .............................................................................................. 298
14.17.3 Reset of Filter Indicaltion ............................................................................... 298
14.18 Troubleshooting .................................................................................................... 298
14.18.1 If Troble Still Remains ...................................................................................... 299
14.18.2 No Operation .................................................................................................... 299
14.18.3 Not Cooling or Heating Well ............................................................................ 299
14.18.4 This is Not Abnormal ....................................................................................... 299
Technical Data
1. Connectable Outdoor Units and Working Range

1.1 Connectable Outdoor Units

AVWT-86/96/114U(6/7/9)SR AVWT-76/96UESRX
Hi-Flexi M Series Hi-Flexi X Series
AVWT-136/154U(6/7/9)SS AVWT-114/136/154UESSX
-Heat Pump System
AVWT-182~460U(6/7/9)SZ AVWT-172~460UESZX
AVWT-76/96/114FE(7/9)SR Multi-Function System AFW-38/48/54U4SC
Hi-Flexi R Series AVWT-136/154/170FE(7/9)SS AVW-76/96/114UESR
AVWT-1190~510FE(7/9)SZ Hi-Flexi C Series AVW-76/96/114U7SR
AVWT-76/96TESRX AVW-76/96/114U9SR
Hi-Flexi X Series AVWT-114/136/154TESSX AVWT-76~114UK/8SNA
-Cooling only System
AVWT-172/460TESZX AVWT-136~170UK/8STA
Hi-Flexi G+ Series
Hi-Flexi M Series AVWW-28/38/48/54UC(2)SA AVWT-190~212UK/8S1A
-Water Source AVWW-76~190UE(7)SB AVWT-232~840UK/8SZA
AVW-38/48/54UC(2)SC AVWT-76/96/114UE(7)SRG
Hi-Flexi L Series
AVW-48/54UE(7)SC AVWT-136/154/170UE(7)SSG
Hi-Flexi G Series
AVW-28/34/43UC(2)SB AVWT-190~510UE(7)SZG
Hi-Flexi E Series
AVW-43UE(7)SB

1.2 Working Range

Power Supply
Working Voltage: 90% to 110% of the Rated Voltage
Voltage Imbalance: Within a 3% Deviation from Each Voltage at the Main Terminal of Iutdoor Unit Starting
Voltage: Higher than 85% of the Rated Voltage

Temperature Range
The temperature range are given in the following table (Except for All Fresh Air Indoor Unit).

Cooling Operation Heating Operation


Indoor Temperature: Minimum 21℃ DB/15.0℃ WB 15℃ DB
Maximum 32℃ DB/23.0℃ WB 27℃ DB
Outdoor Temperature: Minimum -20℃ WB *
-5℃ DB *
Maximum 43℃ DB * 15℃ WB *

For All Fresh Air Indoor Unit

Cooling Operation Heating Operation


Outdoor Temperature: Minimum 20℃ DB * -7℃ WB *
Maximum 43℃ DB * 15℃ WB *

*: The temperature may change depending on the outdoor units.

1
Necessary Tools

21 Wrench

R410A

2.5

2
5. Celling ducted type(AVD)

5.1 General Data

Indoor Unit Type Ceiling Ducted Type (Low Static Pressure)


Model AC 1 , 220-240V/50Hz AVD-07UXCSAL AVD-09UXCSAL AVD-12UXCSAL AVD-14UXCSAL AVD-17UXCSBL
Power Supply AC 1 , 220V/60Hz AVD-07UX2SAL AVD-09UXC2AL AVD-12UX2SAL AVD-14UX2SAL AVD-17UX2SBL
Nominal Cooling kW 2.3 2.9 3.8 4.4 5.2
Capacity *1) kcal/h 2,000 2,500 3,300 3,800 4,500
Btu/h 7,800 9,900 13,000 15,000 17,700
Nominal Cooling kW 2.2 2.8 3.6 4.3 5.0
Capacity *2) kcal/h 1,900 2,400 3,100 3,700 4,300
Btu/h 7,500 9,600 12,300 14,700 17,100

Cooling Power Consumption kW 0.11 0.11 0.15 0.15 0.15


Nominal Heating kW 2.8 3.3 4.2 4.9 5.6
Capacity kcal/h 2,400 2,800 3,600 4,200 4,800
Btu/h 9,600 11,300 14,300 16,700 19,100

Heating Power Consumption kW 0.11 0.11 0.15 0.15 0.15


Sound Pressure Level
(Overall A Scale) dB 30-26-24 30-26-24 32-30-28 32-30-28 33-31-29
Outer Dimensions
Height mm 270 270 270 270 270
(in.) (10-5/8) (10-5/8) (10-5/8) (10-5/8) (10-5/8)
Width mm 650+75 650+75 650+75 650+75 900+75
(in.) (25-9/16+2-15/16) (25-9/16+2-15/16) (25-9/16+2-15/16) (25-9/16+2-15/16) (35-7/16+2-15/16)
Depth mm 720 720 720 720 720
(in.) (28-3/8) (28-3/8) (28-3/8) (28-3/8) (28-3/8)
Net Weight kg 25 25 25 25 34
(lbs.) (55) (55) (55) (55) (75)
Refrigerant — R410A(Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 480/420/360 480/420/360 780/660/540 780/660/540 900/780/660
(Hi/Me/Lo) (cfm) (283/247/212) (283/247/212) (459/388/212) (459/388/212) (530/459/358)

External Pressure *3) Pa 30 30 30 30 30


Connections Flare-Nut Connection (with Flare Nuts)
Refrigerant Piping
Liquid Line mm Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ6.35
(in.) (1/4) (1/4) (1/4) (1/4) (1/4)
Gas Line mm Φ12.7 Φ12.7 Φ12.7 Φ12.7 Φ15.88
(in.) (1/2) (1/2) (1/2) (1/2) (5/8)
Condensate Drain — VP25 VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.21 0.21 0.21 0.21 0.27

NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meter Beneath the Unit.
With Discharge Duct (2.0m) and Return Duct (1.0m).
Voltage of the power source for the indoor fan motor is 220V.
In case of the power source of 240V, the sound pressure level increases by about 1 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3. The data for external pressure *3) indicates "Standard Pressure Setting values when a filter is not used.

3
Indoor Unit Type Ceiling Ducted Type (Low Static Pressure)
Model AC 1 , 220-240V/50Hz AVD-18UXCSBL AVD-22UXCSBL AVD-24UXCSBL AVD-27UXCSCL AVD-30UXCSCL
Power Supply AC 1 , 220V/60Hz AVD-18UX2SBL AVD-22UX2SBL AVD-24UX2SBL AVD-27UX2SCL AVD-30UX2SCL
Nominal Cooling kW 5.8 6.5 7.3 8.7 9.3
Capacity *1) kcal/h 5,000 5,600 6,300 7,500 8,000
Btu/h 19,800 22,200 24,900 29,700 31,700
Nominal Cooling kW 5.6 6.3 7.1 8.4 9.0
Capacity *2) kcal/h 4,800 5,400 6,100 7,200 7,700
Btu/h 19,100 21,500 24,200 28,700 30,700

Cooling Power Consumption kW 0.15 0.15 0.19 0.30 0.30


Nominal Heating kW 6.5 7.5 8.5 9.6 10.0
Capacity kcal/h 5,600 6,500 7,300 8,300 8,600
Btu/h 22,200 25,600 29,000 32,800 34,100

Heating Power Consumption kW 0.15 0.15 0.19 0.30 0.30


Sound Pressure Level
(Overall A Scale) dB 33-31-29 34-32-30 34-32-30 38-34-30 38-34-30
Outer Dimensions
Height mm 270 270 270 350 350
(in.) (10-5/8) (10-5/8) (10-5/8) (13-3/4) (13-3/4)
Width mm 900+75 900+75 900+75 900+75 900+75
(in.) (35-7/16+2-15/16) (35-7/16+2-15/16) (35-7/16+2-15/16) (35-7/16+2-15/16) (35-7/16+2-15/16)
Depth mm 720 720 720 800 800
(in.) (28-3/8) (28-3/8) (28-3/8) (31-1/2) (31-1/2)
Net Weight kg 34 34 34 44 44
(lbs.) (75) (75) (75) (97) (97)
Refrigerant — R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 900/780/660 960/840/720 960/840/720 1550/1350/1150 1550/1350/1150
(Hi/Me/Lo) (cfm) (530/459/388) (565/494/424) (565/494/424) (911/794/676) (911/794/676)

External Pressure *3) Pa 30 30 30 60 60


Connections Flare-Nut Connection (with Flare Nuts)
Refrigerant Piping
Liquid Line mm Φ6.35 Φ9.53 Φ9.53 Φ9.53 Φ9.53
(in.) (1/4) (3/8) (3/8) (3/8) (3/8)
Gas Line mm Φ15.88 Φ15.88 Φ15.88 Φ15.88 Φ15.88
(in.) (5/8) (5/8) (5/8) (5/8) (5/8)
Condensate Drain — VP25 VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.27 0.27 0.27 0.38 0.38
NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meter Beneath the Unit.
With Discharge Duct (2.0m) and Return Duct (1.0m).
Voltage of the power source for the indoor fan motor is 220V.
In case of the power source of 240V, the sound pressure level increases by about 1 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3. The data for external pressure *3) indicates "Standard Pressure Setting values when a filter is not used.

4
Indoor Unit Type Ceiling Ducted Type (Low Static Pressure)
Model AC 1 , 220-240V/50Hz AVD-38UXCSCL AVD-48UXCSDL AVD-54UXCSDL AVD-76UX6SEL *4) AVD-96UX6SFL *4)
Power Supply AC 1 , 220V/60Hz AVD-38UX2SCL AVD-48UX2SDL AVD-54UX2SDL AVD-76UX7SEL *5) AVD-96UX7SFL *5)
Nominal Cooling kW 11.6 14.5 16.5 23.2 28.6
Capacity *1) kcal/h 10,000 12,500 14,200 20,000 24,600
Btu/h 39,600 49,500 56,300 79,200 97,600
Nominal Cooling kW 11.2 14.2 16.0 22.4 28.0
Capacity *2) kcal/h 9,600 12,200 13,800 19,300 24,100
Btu/h 38,200 48,500 54,600 76,500 95,600

Cooling Power Consumption kW 0.30 0.43 0.43 0.95 1.12


Nominal Heating kW 13.0 16.3 18.0 25.0 31.5
Capacity kcal/h 11,200 14,000 15,500 21,500 27,100
Btu/h 44,400 55,600 61,400 85,300 107,500

Heating Power Consumption kW 0.30 0.43 0.43 0.95 1.12


Sound Pressure Level
(Overall A Scale) dB 39-35-31 41-38-33 43-39-34 50 52
Outer Dimensions
Height mm 350 350 350 470 470
(in.) (13-3/4) (13-3/4) (13-3/4) (18-1/2) (18-1/2)
Width mm 900+75 1,300+75 1,300+75 1,060 1,250
(in.) (35-7/16+2-15/16) (51-3/16+2-15/16) (51-3/16+2-15/16) (41-3/4) (49-1/4)
Depth mm 800 800 800 1,120 1,120
(in.) (31-1/2) (31-1/2) (31-1/2) (44-1/12) (44-1/12)
Net Weight kg 44 56 56 94 106
(lbs.) (97) (123) (123) (207) (234)
Refrigerant — R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 1550/1350/1150 2150/1800/1500 2200/1900/1500 3480 4320
(Hi/Me/Lo) (cfm) (911/794/676) (1,264/1,058/882) (1,294/1,117/882) (2048) (2542)

External Pressure *3) Pa 60 60 60 100 100


Connections Flare-Nut Connection (with Flare Nuts) Brazing
Refrigerant Piping
Liquid Line mm Φ9.53 Φ9.53 Φ9.53 Φ9.53 Φ9.53
(in.) (3/8) (3/8) (3/8) (3/8) (3/8)
Gas Line mm Φ15.88 Φ15.88 Φ15.88 Φ19.05 Φ22.2
(in.) (5/8) (5/8) (5/8) (3/4) (7/8)
Condensate Drain — VP25 VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.38 0.52 0.52 0.90 1.06
NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meter Beneath the Unit.
With Discharge Duct (2.0m) and Return Duct (1.0m).
Voltage of the power source for the indoor fan motor is 220V.
In case of the power source of 240V, the sound pressure level increases by about 1 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3. The data for external pressure *3) indicates "Standard Pressure Setting values when a filter is not used.
4. *4) AC 3 , 380~415V/50Hz, *5) AC 3 , 380V/60Hz

5
Indoor Unit Type Ceiling Ducted Type (High Static Pressure)
Model AC 1 , 220-240V/50Hz AVD-07UXCSAH AVD-09UXCSAH AVD-12UXCSAH AVD-14UXCSAH AVD-17UXCSBH
Power Supply AC 1 , 220V/60Hz AVD-07UX2SAH AVD-09UXC2AH AVD-12UX2SAH AVD-14UX2SAH AVD-17UX2SBH
Nominal Cooling kW 2.3 2.9 3.8 4.4 5.2
Capacity *1) kcal/h 2,000 2,500 3,300 3,800 4,500
Btu/h 7,800 9,900 13,000 15,000 17,700
Nominal Cooling kW 2.2 2.8 3.6 4.3 5.0
Capacity *2) kcal/h 1,900 2,400 3,100 3,700 4,300
Btu/h 7,500 9,600 12,300 14,700 17,100

Cooling Power Consumption kW 0.11 0.11 0.15 0.15 0.15


Nominal Heating kW 2.8 3.3 4.2 4.9 5.6
Capacity kcal/h 2,400 2,800 3,600 4,200 4,800
Btu/h 9,600 11,300 14,300 16,700 19,100

Heating Power Consumption kW 0.11 0.11 0.15 0.15 0.15


Sound Pressure Level
(Overall A Scale) dB 33-31-29 33-31-29 33-31-29 33-31-29 34-32-30
Outer Dimensions
Height mm 270 270 270 270 270
(in.) (10-5/8) (10-5/8) (10-5/8) (10-5/8) (10-5/8)
Width mm 650+75 650+75 650+75 650+75 900+75
(in.) (25-9/16+2-15/16) (25-9/16+2-15/16) (25-9/16+2-15/16) (25-9/16+2-15/16) (35-7/16+2-15/16)
Depth mm 720 720 720 720 720
(in.) (28-3/8) (28-3/8) (28-3/8) (28-3/8) (28-3/8)
Net Weight kg 25 25 25 25 34
(lbs.) (55) (55) (55) (55) (75)
Refrigerant — R410A(Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 480/420/360 480/420/360 780/660/540 780/660/540 900/780/660
(Hi/Me/Lo) (cfm) (283/247/212) (283/247/212) (459/388/212) (459/388/212) (530/459/358)

External Pressure *3) Pa 50(80) 50(80) 50(80) 50(80) 50(80)


Connections Flare-Nut Connection (with Flare Nuts)
Refrigerant Piping
Liquid Line mm Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ6.35
(in.) (1/4) (1/4) (1/4) (1/4) (1/4)
Gas Line mm Φ12.7 Φ12.7 Φ12.7 Φ12.7 Φ15.88
(in.) (1/2) (1/2) (1/2) (1/2) (5/8)
Condensate Drain — VP25 VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.21 0.21 0.21 0.21 0.27
NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meter Beneath the Unit.
With Discharge Duct (2.0m) and Return Duct (1.0m).
Voltage of the power source for the indoor fan motor is 220V.
In case of the power source of 240V, the sound pressure level increases by about 1 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3. The data for external pressure *3) indicates "Standard Pressure Setting values when a filter is not used.

6
Indoor Unit Type Ceiling Ducted Type (High Static Pressure)
Model AC 1 , 220-240V/50Hz AVD-18UXCSBH AVD-22UXCSBH AVD-24UXCSBH AVD-27UXCSCH AVD-30UXCSCH
Power Supply AC 1 , 220V/60Hz AVD-18UX2SBH AVD-22UX2SBH AVD-24UX2SBH AVD-27UX2SCH AVD-30UX2SCH
Nominal Cooling kW 5.8 6.5 7.3 8.7 9.3
Capacity *1) kcal/h 5,000 5,600 6,300 7,500 8,000
Btu/h 19,800 22,200 24,900 29,700 31,700
Nominal Cooling kW 5.6 6.3 7.1 8.4 9.0
Capacity *2) kcal/h 4,800 5,400 6,100 7,200 7,700
Btu/h 19,100 21,500 24,200 28,700 30,700

Cooling Power Consumption kW 0.15 0.15 0.19 0.30 0.30


Nominal Heating kW 6.5 7.5 8.5 9.6 10.0
Capacity kcal/h 5,600 6,500 7,300 8,300 8,600
Btu/h 22,200 25,600 29,000 32,800 34,100

Heating Power Consumption kW 0.15 0.15 0.19 0.30 0.30


Sound Pressure Level
(Overall A Scale) dB 34-32-30 36-34-32 36-34-32 41-39-34 41-39-34
Outer Dimensions
Height mm 270 270 270 350 350
(in.) (10-5/8) (10-5/8) (10-5/8) (13-3/4) (13-3/4)
Width mm 900+75 900+75 900+75 900+75 900+75
(in.) (35-7/16+2-15/16) (35-7/16+2-15/16) (35-7/16+2-15/16) (35-7/16+2-15/16) (35-7/16+2-15/16)
Depth mm 720 720 720 800 800
(in.) (28-3/8) (28-3/8) (28-3/8) (31-1/2) (31-1/2)
Net Weight kg 34 34 34 44 44
(lbs.) (75) (75) (75) (97) (97)
Refrigerant — R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 900/780/660 960/840/720 960/840/720 1600/1400/1150 1600/1400/1150
(Hi/Me/Lo) (cfm) (530/459/388) (565/494/424) (565/494/424) (941/823/676) (941/823/676)

External Pressure *3) Pa 50(80) 50(80) 50(80) 120(90) 120(90)


Connections Flare-Nut Connection (with Flare Nuts)
Refrigerant Piping
Liquid Line mm Φ6.35 Φ9.53 Φ9.53 Φ9.53 Φ9.53
(in.) (1/4) (3/8) (3/8) (3/8) (3/8)
Gas Line mm Φ15.88 Φ15.88 Φ15.88 Φ15.88 Φ15.88
(in.) (5/8) (5/8) (5/8) (5/8) (5/8)
Condensate Drain — VP25 VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.27 0.27 0.27 0.38 0.38
NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meter Beneath the Unit.
With Discharge Duct (2.0m) and Return Duct (1.0m).
Voltage of the power source for the indoor fan motor is 220V.
In case of the power source of 240V, the sound pressure level increases by about 1 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3. The data for external pressure *3) indicates "Standard Pressure Setting values when a filter is not used.

7
Indoor Unit Type Ceiling Ducted Type (High Static Pressure)
Model AC 1 , 220-240V/50Hz AVD-38UXCSCH AVD-48UXCSDH AVD-54UXCSDH AVD-76UX6SEH *4) AVD-96UX6SFH *4)
Power Supply AC 1 , 220V/60Hz AVD-38UX2SCH AVD-48UX2SDH AVD-54UX2SDH AVD-76UX7SEH *5) AVD-96UX7SFH *5)
Nominal Cooling kW 11.6 14.5 16.5 23.2 28.6
Capacity *1) kcal/h 10,000 12,500 14,200 20,000 24,600
Btu/h 39,600 49,500 56,300 79,200 97,600
Nominal Cooling kW 11.2 14.2 16.0 22.4 28.0
Capacity *2) kcal/h 9,600 12,200 13,800 19,300 24,100
Btu/h 38,200 48,500 54,600 76,500 95,600

Cooling Power Consumption kW 0.30 0.43 0.43 1.08 1.34


Nominal Heating kW 13.0 16.3 18.0 25.0 31.5
Capacity kcal/h 11,200 14,000 15,500 21,500 27,100
Btu/h 44,400 55,600 61,400 85,300 107,500

Heating Power Consumption kW 0.30 0.43 0.43 1.08 1.34


Sound Pressure Level
(Overall A Scale) dB 43-40-36 44-41-36 45-42-48 52 54
Outer Dimensions
Height mm 350 350 350 470 470
(in.) (13-3/4) (13-3/4) (13-3/4) (18-1/2) (18-1/2)
Width mm 900+75 1,300+75 1,300+75 1,060 1,250
(in.) (35-7/16+2-15/16) (51-3/16+2-15/16) (51-3/16+2-15/16) (41-3/4) (49-1/4)
Depth mm 800 800 800 1,120 1,120
(in.) (31-1/2) (31-1/2) (31-1/2) (44-1/12) (44-1/12)
Net Weight kg 44 56 56 94 106
(lbs.) (97) (123) (123) (207) (234)
Refrigerant — R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 1600/1400/1150 2100/1750/1450 2150/1900/1620 3480 4320
(Hi/Me/Lo) (cfm) (941/823/676) (1,235/1,029/853) (1,264/1,117/953) (2048) (2542)

External Pressure *3) Pa 120(90) 120(90) 120(90) 220 220


Connections Flare-Nut Connection (with Flare Nuts) Brazing
Refrigerant Piping
Liquid Line mm Φ9.53 Φ9.53 Φ9.53 Φ9.53 Φ9.53
(in.) (3/8) (3/8) (3/8) (3/8) (3/8)
Gas Line mm Φ15.88 Φ15.88 Φ15.88 Φ19.05 Φ22.2
(in.) (5/8) (5/8) (5/8) (3/4) (7/8)
Condensate Drain — VP25 VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.38 0.52 0.52 0.90 1.06
NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meter Beneath the Unit.
With Discharge Duct (2.0m) and Return Duct (1.0m).
Voltage of the power source for the indoor fan motor is 220V.
In case of the power source of 240V, the sound pressure level increases by about 1 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3. The data for external pressure *3) indicates "Standard Pressure Setting values when a filter is not used.
4. *4) AC 3 , 380~415V/50Hz, *5) AC 3 , 380V/60Hz

8
Indoor Unit Type Ceiling Ducted Type (High Static Pressure)
Model
AC 1 , 208~230V/60Hz AVD-76UX2SFH AVD-96UX2SFH
Power Supply
Nominal Cooling kW 23.2 28.6
Capacity *1) kcal/h 20,000 24,600
Btu/h 79,200 97,600
Nominal Cooling kW 22.4 28.0
Capacity *2) kcal/h 19,300 24,100
Btu/h 76,500 95,600

Cooling Power Consumption kW 1.42 1.46


Nominal Heating kW 25.0 31.5
Capacity kcal/h 21,500 27,100
Btu/h 85,300 107,500

Heating Power Consumption kW 1.42 1.46


Sound Pressure Level
(Overall A Scale) dB 52 54
Outer Dimensions
Height mm 470 470
(in.) (18-1/2) (18-1/2)
Width mm 1,250 1,250
(in.) (49-1/4) (49-1/4)
Depth mm 1,120 1,120
(in.) (44-1/12) (44-1/12)
Net Weight kg 118 118
(lbs.) (259) (259)
Refrigerant — R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 4000 4320
(Hi/Me/Lo) (cfm) (2353) (2541)

External Pressure *3) Pa 240 200


Connections Brazing
Refrigerant Piping
Liquid Line mm Φ9.53 Φ9.53
(in.) (3/8) (3/8)
Gas Line mm Φ19.05 Φ22.2
(in.) (3/4) (7/8)
Condensate Drain — VP25 VP25
Approximate
Packing Measurement m3 1.06 1.06
NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meter Beneath the Unit.
With Discharge Duct (2.0m) and Return Duct (1.0m).
Voltage of the power source for the indoor fan motor is 220V.
In case of the power source of 240V, the sound pressure level increases by about 1 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3. The data for external pressure *3) indicates "Standard Pressure Setting values when a filter is not used.

9
5.2 Dimensional Data

Models: AVD- 07~54*

l -φ 6
b (Around the Flange)
40 a Unit:mm
e c x 300 = d
300 4 - 40 x 12
20

(for Suspension Bolt)


Air Inlet
30
22

x
m

22
n

Remote Control Switch g


33.5

Viewed from A
22
30

120
20

300 l - φ6
e c x 300 = d (Around the Flange) Drain Pipe Connection Drain Pipe Connection
(Standard Position) (VP25) (Optional Drain-Up Mechanism)

Refrigerant Gas Pipe Connection


(With φi Flare Nut)
Air Outlet
Refrigerant Liquid Pipe Connection
a u

2xv=w
75(Electrical Control Box) (With φh Flare Nut) 45
2x90=180
220

A
q

90

v
r
97
p

23

35
s
t

48.5 f j (Refrigerant Gas Pipe Connection) 246(Refrigerant Liquid Pipe Connection)


90(Drain Pipe Connection) 321(Refrigerant Gas Pipe Connection)
k (Refrigerant Liquid Pipe Connection) 377
402

Dimension
Model a b c d e f g h i j k l
07~14 650 730 1 300 215 553 583 6.35 12.7 70 92 10
17/18 900 980 2 600 190 803 833 6.35 15.88 77 92 12
22/24 900 980 2 600 190 803 833 9.53 15.88 77 95 12
27/30 900 980 2 600 190 803 833 9.53 15.88 78 95 12
38 900 980 2 600 190 803 833 9.53 15.88 81 95 12
48/54 1300 1380 3 900 240 1203 1233 9.53 15.88 81 95 14

Dimension
Model m n p q r s t u v w x
07~24 676 720 23 270 182 222 43 220 100 200 226
27~54 756 800 103 350 204 244 123 300 140 280 306

10
Models: AVD-76/96*, AVD-76UX 2SFH, AVD-96UX 2SFH

Air Outlet

Unit:mm
(Around the Flange)
Viewed from A
(for Suspension Bolt)

916

Air Outlet

(Around the Flange)


Air Inlet
Refrigerant Liquid Pipe
9.53 Brazing
Drain Piping Refrigerant Gas Pipe
Air Inlet
22.2(19.05)Brazing
470

NOTES: Data in the bracket is for AVD-76* model.

Data of AVD-76UX2SFH ,AVD-96UX2SFH and AVD-96* is the same.

11
5.3 Selection Data
● Operation Space
Models:AVD-07~54*

Electrical Box Service Access


Door (Min. 450)
Service Space
100 Rear Side of False Ceiling 600
In case that the

1000
ceiling board can

Min.
not be detected

400
Rear Side
for servicing,
prepare a service
access door
below the indoor
275

unit for removing


the indoor unit.
Front Side
Front Side (130)
35

1000
Min.
View from Bottom Min.
Min. 600
600
View from Top

Models: AVD-76/96*

Service Space

Min. 20
730

800
0
~20
200 150
~30
0

Min. 20
600 50
50
Service Access Panel Ceiling
Secure the service space
600 of false ceiling for cleaning
the heat exchanger. * Prepare the Service Access Panel for service.
Service Access Panel * In case that the ceiling board is not be detachable
for servicing, prepare a service access panel below
the indoor unit for removing the indoor unit.

12
● Sensible Heat Factor (SHF)
The sensible heat factor of indoor units at each fan speed (Hi, Me, Lo) is given in the below.
SHF
Indoor Unit Model
Hi Me Lo
AVD-07* 0.81 0.69 0.68
AVD-09* 0.81 0.69 0.68
AVD-12* 0.73 0.69 0.65
AVD-14* 0.73 0.69 0.65
AVD-17* 0.75 0.71 0.68
AVD-18* 0.74 0.70 0.67
AVD-22* 0.71 0.69 0.67
AVD-24* 0.70 0.68 0.66
AVD-27* 0.70 0.68 0.66
AVD-30* 0.70 0.68 0.66
AVD-38* 0.72 0.69 0.62
AVD-48* 0.71 0.68 0.62
AVD-54* 0.70 0.68 0.63
AVD-76* (76UX2SFH) 0.71 (0.80 ) ─ ─
AVD-96*( 96UX2SFH) 0.70 ( 0.82 ) ─ ─

13
● Fan Performance
Ceiling Ducted Type (Low Static Pressure)

AVD-07UX*AL AVD-09UX*AL
EXTERNAL STATIC PRESSURE (Pa)

EXTERNAL STATIC PRESSURE (Pa)


Me Hi Me Hi
Lo Lo

AIR VOLUME (m3/min) AIR VOLUME (m3/min)

AVD-12UX*AL AVD-14UX*AL
EXTERNAL STATIC PRESSURE (Pa)

EXTERNAL STATIC PRESSURE (Pa)

Me Hi Me Hi
Lo Lo

AIR VOLUME (m3/min) AIR VOLUME (m3/min)

14
AVD-17UX*BL AVD-18UX*BL

EXTERNAL STATIC PRESSURE (Pa)


EXTERNAL STATIC PRESSURE (Pa)

Me Hi
Me Hi
Lo
Lo

AIR VOLUME (m3/min) AIR VOLUME (m3/min)

AVD-22UX*BL AVD-24UX*BL
EXTERNAL STATIC PRESSURE (Pa)

EXTERNAL STATIC PRESSURE (Pa)

Me Hi
Me Hi
Lo
Lo

AIR VOLUME (m3/min) AIR VOLUME (m3/min)

15
AVD-27UX*CL AVD-30UX*CL
EXTERNAL STATIC PRESSURE (Pa)

EXTERNAL STATIC PRESSURE (Pa)


Me Hi Me Hi
Lo Lo

AIR VOLUME (m3/min) AIR VOLUME (m3/min)

AVD-38UX*CL AVD-48UX*DL
EXTERNAL STATIC PRESSURE (Pa)
EXTERNAL STATIC PRESSURE (Pa)

Me Hi Hi
Me
Lo Lo

AIR VOLUME (m3/min) AIR VOLUME (m3/min)

16
AVD-54UX*DL

120

100
EXTERNAL STATIC PRESSURE (Pa)

80

60 Me Hi
Lo

40

20

0
20 26 32 38 44
AIR VOLUME (m3/min)

AVD-76UX6(7)SEL AVD-96UX6(7)SFL

140 140

130 130

120 120
EXTERNAL STATIC PRESSURE (Pa)

EXTERNAL STATIC PRESSURE (Pa)

110 110

100 100

90 90

80 80

70 70

60 60

50 50
54 56 58 60 62 60 65 70 75 80

AIR VOLUME (m3/min) AIR VOLUME (m3/min)

17
Ceiling Ducted Type (High Static Pressure)

AVD-07UX*AH AVD-09UX*AH
EXTERNAL STATIC PRESSURE (Pa)

EXTERNAL STATIC PRESSURE (Pa)


Hi (Optional Hi (Optional
Pressure Setting) Pressure Setting)

Hi (Standard Hi (Standard
Pressure Setting) Pressure Setting)

Me Me

Lo Lo

AIR VOLUME (m3/min) AIR VOLUME (m3/min)

AVD-12UX*AH AVD-14UX*AH
EXTERNAL STATIC PRESSURE (Pa)
EXTERNAL STATIC PRESSURE (Pa)

Hi (Optional Hi (Optional
Pressure Setting) Pressure Setting)

Hi (Standard Hi (Standard
Pressure Setting) Pressure Setting)

Me Me

Lo Lo

AIR VOLUME (m3/min) AIR VOLUME (m3/min)

18
AVD-17UX*BH AVD-18UX*BH

EXTERNAL STATIC PRESSURE (Pa)


EXTERNAL STATIC PRESSURE (Pa)

Hi (Optional Hi (Optional
Pressure Setting) Pressure Setting)

Hi (Standard Hi (Standard
Pressure Setting) Pressure Setting)

Me Me

Lo Lo

AIR VOLUME (m3/min) AIR VOLUME (m3/min)

AVD-22UX*BH AVD-24UX*BH
EXTERNAL STATIC PRESSURE (Pa)

EXTERNAL STATIC PRESSURE (Pa)

Hi (Optional Hi (Optional
Pressure Setting) Pressure Setting)

Hi (Standard Hi (Standard
Pressure Setting) Pressure Setting)

Me Me

Lo Lo

AIR VOLUME (m3/min) AIR VOLUME (m3/min)

19
AVD-27/30UX*CH AVD-38UX*CH
EXTERNAL STATIC PRESSURE (Pa)

EXTERNAL STATIC PRESSURE (Pa)


Hi (Standard Hi (Standard
Pressure Setting) Pressure Setting)

Hi (Optional
Pressure Setting) Hi (Optional
Pressure Setting)

Me
Me

Lo
Lo

AIR VOLUME (m3/min) AIR VOLUME (m3/min)

AVD-48UX*DH AVD-54UX*DH
EXTERNAL STATIC PRESSURE (Pa)

EXTERNAL STATIC PRESSURE (Pa)

Hi (Standard
Hi (Standard Pressure Setting)
Pressure Setting)

Hi (Optional Hi (Optional
Pressure Setting) Pressure Setting)

Me Me

Lo
Lo

AIR VOLUME (m3/min)

AIR VOLUME (m3/min)

20
AVD-76UX*FH AVD-96UX*FH
320 320

300 300

280 280

EXTERNAL STATIC PRESSURE (Pa)


EXTERNAL STATIC PRESSURE (Pa)

260 260

240 240

220 220

200 200

180 180

160 160

140 140
61 63 65 67 69 71 73 61 63 65 67 69 71 73

AIR VOLUME (m3/min) AIR VOLUME (m3/min)

AVD-76UX(6/7)SEH AVD-96UX(6/7)SFH
280 280

260 260

240 240
EXTERNAL STATIC PRESSURE (Pa)

EXTERNAL STATIC PRESSURE (Pa)

220 220

200 200

180 180

160 160

140 140

120 120

100 100
50 55 60 65 70 75 60 65 70 75 80 85
AIR VOLUME (m3/min) AIR VOLUME (m3/min)

21
Sound Data

Ceiling Ducted Type (Low Static Pressure)

Model: AVD-07/09UX*AL Power Supply: 220-240V/50Hz,220V/60Hz Model: AVD-12UX*AL Power Supply: 220-240V/50Hz,220V/60Hz

Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit

Noise Criteria Curve Noise Criteria Curve


Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)


Hi
Me
Hi
Me
Lo

Approximate Lo Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model: AVD-14UX*AL Power Supply: 220-240V/50Hz,220V/60Hz Model: AVD-17UX*BL Power Supply: 220-240V/50Hz,220V/60Hz

Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit

Noise Criteria Curve Noise Criteria Curve


Octave Sound Pressure Level(dB: Overall C Scale)
Octave Sound Pressure Level(dB: Overall C Scale)

Hi
Hi
Me
Me

Lo Lo

Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

22
Model: AVD-18UX*BL Power Supply: 220-240V/50Hz,220V/60Hz Model:AVD-22/24UX*BL Power Supply: 220-240V/50Hz,220V/60Hz

Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit

Noise Criteria Curve Noise Criteria Curve


Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)


Hi
Hi
Me Me

Lo Lo

Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model: AVD-27/30UX*CL Power Supply: 220-240V/50Hz,220V/60Hz Model: AVD-38UX*CL Power Supply: 220-240V/50Hz,220V/60Hz

Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit

Noise Criteria Curve Noise Criteria Curve


Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)

Hi
Hi
Me
Me

Lo
Lo

Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

23
Model: AVD-48UX*DL Power Supply: 220-240V/50Hz,220V/60Hz Model: AVD-54UX*DL Power Supply: 220-240V/50Hz,220V/60Hz

Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit

Noise Criteria Curve Noise Criteria Curve

Octave Sound Pressure Level(dB: Overall C Scale)


Octave Sound Pressure Level(dB: Overall C Scale)

Hi Hi
Me Me

Lo
Lo

Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model: AVD-76UX(6/7)SEL Power Supply: 380~415V/50Hz, 380V/60Hz Model: AVD-96UX(6/7)SFL Power Supply: 380~415V/50Hz, 380V/60Hz
Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit

Noise Criteria Curve Noise Criteria Curve


Octave Sound Pressure Level(dB: Overall C Scale)
Octave Sound Pressure Level(dB: Overall C Scale)

Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

24
Ceiling Ducted Type (High Static Pressure)

Model:AVD-07/09UX*AH Power Supply: 220-240V/50Hz,220V/60Hz Model: AVD-12UX*AH Power Supply: 220-240V/50Hz,220V/60Hz

Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit

Noise Criteria Curve Noise Criteria Curve


Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)


Hi
Hi
Me
Me

Lo Lo

Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model: AVD-14UX*AH Power Supply: 220-240V/50Hz,220V/60Hz Model: AVD-17UX*BH Power Supply: 220-240V/50Hz,220V/60Hz

Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit

Noise Criteria Curve Noise Criteria Curve


Octave Sound Pressure Level(dB: Overall C Scale)
Octave Sound Pressure Level(dB: Overall C Scale)

Hi Hi
Me Me

Lo Lo

Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

25
Model: AVD-18UX*BH Power Supply: 220-240V/50Hz,220V/60Hz Model:AVD-22/24UX*BH Power Supply: 220-240V/50Hz,220V/60Hz

Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit

Noise Criteria Curve Noise Criteria Curve


Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)


Hi Hi
Me Me

Lo Lo

Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model:AVD-27/30UX*CH Power Supply: 220-240V/50Hz,220V/60Hz Model: AVD-38UX*CH Power Supply: 220-240V/50Hz,220V/60Hz

Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
Octave Sound Pressure Level(dB: Overall C Scale)
Octave Sound Pressure Level(dB: Overall C Scale)

Hi
Hi
Me
Me

Lo
Lo

Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

26
Model: AVD-48UX*DH Power Supply: 220-240V/50Hz,220V/60Hz Model: AVD-54UX*DH Power Supply: 220-240V/50Hz,220V/60Hz

Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit

Noise Criteria Curve Noise Criteria Curve


Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)


Hi Hi

Me Me

Lo Lo

Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model: AVD-76UX(6/7)SEH Power Supply: 380~415V/50Hz, 380V/60Hz Model: AVD-96UX(6/7)SFH Power Supply: 380~415V/50Hz, 380V/60Hz
Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit

Noise Criteria Curve Noise Criteria Curve


Octave Sound Pressure Level(dB: Overall C Scale)
Octave Sound Pressure Level(dB: Overall C Scale)

Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

27
Model: AVD-76UX*FH Power Supply: 208~230V/60Hz Model: AVD-96UX*FH Power Supply: 208~230V/60Hz

Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit

Noise Criteria Curve Noise Criteria Curve

Octave Sound Pressure Level(dB: Overall C Scale)


Octave Sound Pressure Level(dB: Overall C Scale)

Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

28
5.4 Component Data

Indoor Heat Exchanger and Fan


Model AVD-07UX*AL AVD-09UX*AL AVD-12UX*AL AVD-14UX*AL AVD-17UX*BL
Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0 7.0
Rows - 2 2 3 3 2
Fin Material Aluminum
Pitch mm 1.8 1.8 1.8 1.8 1.8
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15 4.15
Total Face Area m2 0.14 0.14 0.14 0.14 0.21
Number of Coil/Unit - 1 1 1 1 1
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 1 1 1 1 2
Outer Diameter mm 186 186 186 186 186
Revolution (220V) rpm 890/755/635 890/755/635 1,050/900/750 1,050/900/750 990/835/700
Nominal Air Flow m /h
3
480/420/360 480/420/360 780/660/540 780/660/540 900/780/660
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - PSC (Permanent Split Capacitor)
Nominal Output W 20 20 40 40 45
Quantity - 1 1 1 1 1
Insulation Class - B B B B B

Model AVD-18UX*BL AVD-22UX*BL AVD-24UX*BL AVD-27UX*CL AVD-30UX*CL


Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0 7.0
Rows - 2 3 3 2 2
Fin Material Aluminum
Pitch mm 1.8 1.8 1.8 1.8 1.8
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15 4.15
Total Face Area m2 0.21 0.21 0.21 0.29 0.29
Number of Coil/Unit - 1 1 1 1 1
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 2 2 2 2 2
Outer Diameter mm 186 186 186 204 204
Revolution (220V) rpm 990/835/700 990/835/700 990/835/700 1,170/1,000/8251,170/1,000/825
Nominal Air Flow m3/h 900/780/660 960/840/720 960/840/720 1550/1350/11501550/1350/1150
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - PSC (Permanent Split Capacitor)
Nominal Output W 45 45 45 100 100
Quantity - 1 1 1 1 1
Insulation Class - B B B B B

29
Indoor Heat Exchanger and Fan

Model AVD-38UX*CL AVD-48UX*DL AVD-54UX*DL AVD-76UX*EL AVD-96UX*FL


Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 9.53 9.53
Rows - 3 3 3 3 3
Fin Material Aluminum
Pitch mm 1.8 1.8 1.6 1.9 1.9
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15 4.15
Total Face Area m2 0.29 0.46 0.46 0.51 0.62
Number of Coil/Unit - 1 1 1 1 1
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 2 2 2 2 2
Outer Diameter mm 204 204 204 280 280
Revolution (220V) rpm 1,170/1,000/825 1,190/1,005/835 1,200/980/850 1,250 1,270
Nominal Air Flow m3/h 1550/1350/1150 2150/1800/1500 2200/1900/1500 3480 4320
Indoor Fan Motor Drip-Proof Type Enclosure PSC
Starting Method - (Permanent Split Capacitor)
Nominal Output W 100 140 180 500 630
Quantity - 1 1 1 1 1
Insulation Class - B F F F F

Model AVD-07UX*AH AVD-09UX*AH AVD-12UX*AH AVD-14UX*AH AVD-17UX*BH


Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0 7.0
Rows - 2 2 3 3 2
Fin Material Aluminum
Pitch mm 1.8 1.8 1.8 1.8 1.8
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15 4.15
Total Face Area m2 0.14 0.14 0.14 0.14 0.21
Number of Coil/Unit - 1 1 1 1 1
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 1 1 1 1 2
Outer Diameter mm 186 186 186 186 186
Revolution (220V) rpm 890/755/635 890/755/635 1050/900/750 1050/900/750 990/835/700
Nominal Air Flow m3/h 480/420/360 480/420/360 780/660/540 780/660/540 900/780/660
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - PSC (Permanent Split Capacitor)
Nominal Output W 35 35 80 80 75
Quantity - 1 1 1 1 1
Insulation Class - B B B B B

30
Indoor Heat Exchanger and Fan
Model AVD-18UX*BH AVD-22UX*BH AVD-24UX*BH AVD-27UX*CH AVD-30UX*CH
Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0 7.0
Rows - 2 3 3 2 2
Fin Material Aluminum
Pitch mm 1.8 1.8 1.8 1.8 1.8
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15 4.15
Total Face Area m2 0.21 0.21 0.21 0.29 0.29
Number of Coil/Unit - 1 1 1 1 1
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 2 2 2 2 2
Outer Diameter mm 186 186 186 204 204
Revolution (220V) rpm 990/835/700 990/835/700 990/835/700 1170/1000/825 1170/1000/825
Nominal Air Flow m3 /h 900/780/660 960/840/720 960/840/720 1600/1400/1150 1600/1400/1150
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - PSC (Permanent Split Capacitor)
Nominal Output W 75 75 75 120 120
Quantity - 1 1 1 1 1
Insulation Class - B B B F F

Model AVD-38UX*CH AVD-48UX*DH AVD-54UX*DH AVD-76UX*EH AVD-96UX*FH


Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 9.53 9.53
Rows - 3 3 3 3 3
Fin Material Aluminum
Pitch mm 1.8 1.8 1.6 1.9 1.9
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15 4.15
Total Face Area m2 0.29 0.46 0.46 0.51 0.62
Number of Coil/Unit - 1 1 1 1 1
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 2 2 2 2 2
Outer Diameter mm 204 204 204 280 280
Revolution (220V) rpm 1170/1000/825 1190/1005/835 1200/980/850 1250* 1270*
Nominal Air Flow m3/h 1600/1400/1150 2100/1750/1450 2150/1800/1550 3480 4320
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - PSC (Permanent Split Capacitor)
Nominal Output W 120 200 250 650 990
Quantity - 1 1 1 1 1
Insulation Class - F F F F F

*: For 380V

31
Model AVD-76UX2SFH AVD-96UX2SFH
Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 9.53 9.53
Rows - 3 3
Fin Material Aluminum
Pitch mm 1.8 1.9
Maximum Operating Pressure MPa 4.15 4.15
Total Face Area m2 0.56 0.62
Number of Coil/Unit - 1 1
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 2 2
Outer Diameter mm 250 250
Revolution (220V) rpm 1320 1320
Nominal Air Flow m3/h 4000 4320
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - PSC (Permanent Split Capacitor)
Nominal Output W 530+530 530+530
Quantity - 2 2
Insulation Class - F F

32
5.5 Control System
Refrigeration Cycle

For Ceiling Ducted Type (05~54 Model)

Indoor Unit

2
: Refrigerant Flow Direction (Cooling)
: Refrigerant Flow Direction (Heating)
: Field Refrigerant Piping
3 : Flare Connection

4
b

Refrigerant Liquid Pipe Connection


S

3 a

Refrigerant Gas Pipe Connection

Mark Part Name


1 Heat Exchanger
2 Distributor
3 Strainer
4 Micro-Computer Control Expansion Valve

33
For Ceiling Ducted Type (76 and 96 Model)

Indoor Unit

: Refrigerant Flow Direction (Cooling)


: Refrigerant Flow Direction (Heating)
: Field Refrigerant Piping
: Brazing
2

3
1

S
4
b

4
Refrigerant Liquid Pipe Connection
S
3 a

Refrigerant Gas Pipe Connection

Mark Part Name


1 Heat Exchanger
2 Distributor
3 Strainer
4 Micro-Computer Control Expansion Valve

34
5.6 Electrical Data

< 50 Hz >
Indoor Unit
Unit Main Power Applicable Voltage Indoor Fan Motor
Model
VOL PH HZ Maximum Minimum PH RNC IPT
AVD-07UXCSAL 0.53 0.11
AVD-09UXCSAL 0.53 0.11
AVD-12UXCSAL 0.75 0.15
AVD-14UXCSAL 0.75 0.15
AVD-17UXCSBL 0.77 0.15
AVD-18UXCSBL 0.77 0.15
Ceiling Ducted AVD-22UXCSBL 220~240 1 50 264 198 1 0.77 0.15
Type (Low Static AVD-24UXCSBL 0.96 0.19
Pressure) AVD-27UXCSCL 1.55 0.30
AVD-30UXCSCL 1.55 0.30
AVD-38UXCSCL 1.55 0.30
AVD-48UXCSDL 2.19 0.43
AVD-54UXCSDL 2.19 0.43
AVD-76UXCSEL 1.71 0.95
380~415 3 50 457 342 3
AVD-96UXCSFL 2.03 1.12
AVD-07UXCSAH 0.53 0.11
AVD-09UXCSAH 0.53 0.11
AVD-12UXCSAH 0.75 0.15
AVD-14UXCSAH 0.75 0.15
AVD-17UXCSBH 0.77 0.15
AVD-18UXCSBH 0.77 0.15
Ceiling Ducted AVD-22UXCSBH 220~240 1 50 264 198 1 0.77 0.15
Type (High Static AVD-24UXCSBH 0.96 0.19
Pressure) AVD-27UXCSCH 1.55 0.30
AVD-30UXCSCH 1.55 0.30
AVD-38UXCSCH 1.55 0.30
AVD-48UXCSDH 2.19 0.43
AVD-54UXCSDH 2.19 0.43
AVD-76UXCSEH 1.96 1.03
380~415 3 50 457 342 3
AVD-96UXCSFH 2.43 1.28

VOL: Rated Unit Power Supply Voltage (Plated)(V) RNC: Running Current (A)
PH: Phase (φ) IPT: Input (kW)
HZ: Frequency (Hz)

35
< 60 Hz >
Indoor Unit
Unit Main Power Applicable Voltage Indoor Fan Motor
Model
VOL PH HZ Maximum Minimum PH RNC IPT
AVD-07UX2SAL 0.53 0.1
AVD-09UX2SAL 0.53 0.1
AVD-12UX2SAL 0.75 0.14
AVD-14UX2SAL 0.75 0.14
AVD-17UX2SBL 0.77 0.14
AVD-18UX2SBL 0.77 0.14
Ceiling Ducted AVD-22UX2SBL 0.77 0.14
Type (Low Static AVD-24UX2SBL 220 1 60 242 198 1 0.96 0.18
Pressure) AVD-27UX2SCL 1.55 0.29
AVD-30UX2SCL 1.55 0.29
AVD-38UX2SCL 1.55 0.29
AVD-48UX2SDL 2.19 0.41
AVD-54UX2SDL 2.19 0.41
AVD-76UX7SEL 1.71 0.9
380 3 60 418 342 3
AVD-96UX7SFL 2.03 1.07
AVD-07UX2SAH 0.53 0.1
AVD-09UX2SAH 0.53 0.1
AVD-12UX2SAH 0.75 0.14
AVD-14UX2SAH 0.75 0.14
AVD-17UX2SBH 0.77 0.14
AVD-18UX2SBH 0.77 0.14
Ceiling Ducted AVD-22UX2SBH 0.77 0.14
Type (High Static AVD-24UX2SBH 220 1 60 242 198 1 0.96 0.18
Pressure) AVD-27UX2SCH 1.55 0.29
AVD-30UX2SCH 1.55 0.29
AVD-38UX2SCH 1.55 0.29
AVD-48UX2SDH 2.19 0.41
AVD-54UX2SDH 2.19 0.41
AVD-76UX7SEH 1.96 1.03
380 3 60 418 342 3
AVD-96UX7SFH 2.43 1.28
AVD-76UX2SFH 6.62 1.42
220 1 60 242 198 1
AVD-96UX2SFH 6.8 1.46

VOL: Rated Unit Power Supply Voltage (Plated)(V) RNC: Running Current (A)
PH: Phase (φ) IPT: Input (kW)
HZ: Frequency (Hz)

36
Safety and Control Device Setting
Indoor Unit

AVD-07~96*
Model

For Evaporator Fan


℃ 130±5
Motor Thermostat Cut-Out
Cut-In ℃ 83±15
For Control Circuit
Fuse Capacity A 5

Freeze Protection
Thermostat ℃ 0
Cut-Out
Cut-In ℃ 14

Thermostat
Differential ℃ 2

37
5.7 Electrical Wiring Diagram Model: AVD-07~54*L

07~24

27~54

38
Electrical Wiring Diagram Model: AVD-76~96*

39
Electrical Wiring Diagram Model: AVD-07~54*H

07~24

07~24
27~54
27~54

40
5.8 Indoor Unit Optional Parts

Optional Parts Applied Indoor Unit Type


Ceiling Ducted Type Ceiling Ducted Type
Type Model
(Low Static Pressure) (High Static Pressure)
HYXE-F01H ● ●
HYXE-G01H ● ●
Wire Remote Control
Switch HYXE-A01H#01 ● ●
HYXE-J01H ● ●
HYXE-M01H ● ●
HYE-Q01 ● ●
Wireless Remote Control
HYE-L01 ● ●
Switch
HYE-W01 ● ●
HYRE-V01H ● ●
HYRE-T01H
Wireless Receiver Kit
HYRE-V02H
HYRE-X01H
7 Day Timer HYDE-E01H ● ●
HYJE-H01H ● ●
HYJE-D02H ● ●
HYJ-J01H ● ●
Centrol Station HCCS-H128H2C1YM ● ●
HCCS-H128H2C1NM ● ●
HCCS-H247R4C1E
HCCS-H128H2C2NM ● ●
Interface for Building HC-A64BNP ● ●
Control HCPC-H2M1C ● ●
HCH-160D ● ●
Switch Box
HCH-280D ● ●
HZX-2.0AEC
HZX-4.0AEC
AHU Kits HZX-6.0AEC
HZX-10.0AEC
HZX-20.0AEC
HPS-162#E ● ●
Drain Pump HPS-132#E ● ●
HPS-151#E ● ●
HF-224L-FE ●8-10HP
Long Life filter HF-280L-FE ●8-10HP
HF-40L-ZFE
HP-DB-NK
3D Air Swing
HP-EB-NK

41
5.9

For Model:AVD-07~54*

For Model:AVD-76~96*

42
5.10 Installation
5.10.1 Initial Check

AVD-07~54*

AVD-76~96*

600
5.10.2
600

43
● AVD-76~96*

below

AVD-07~54*

07 14

17 24

Fig. Suspension Bolts


27 38
AVD-76~96UX2SFH
Model(103 Btu/h) a b c d e f g h

76
1250 1288 1106 1100 20 1000 21 1050
96
48 54
AVD-76~96UX(6/7)S(E/F)(L/H)
Model3(10 Btu/h) a b c d e f g h

76 1060 1098 916 910 16 800 17 850

96 1250 1288 1106 1100 20 1000 21 1050

44

below Fig

45
Fig. Connecting Supply Duct

5.10.3

10A
AVD-07~54*

07 14
17 18
22 24
27 38
48 54

07 14
17 18
An excess or a shortage of refrigerant is the
22 30
main cause of trouble to the units.
Charge the correct refrigerant quantity. 38 54

46
AVD-76~96* AVD-07~54*

B-
C- A- below.

mm(in.)
(10 3 Btu/h) A B C

76 19.05(3/4) 9.53(3/8)
VP 25 ●
96 22.2(7/8) 9.53(3/8)

below.

Flaring Dimension
Perform the flaring work as shown below.

+0
Diameter A -0.4
R410A R407C
6.35 9.1 9.0
9.53 13.2 13.0
12.7 16.6 16.2
15.88 19.7 19.4
19.05 (*) 23.3
A +0
-0.4

(*)It is impossible to perform the flaring work with
1/2H material. In this case, use an accessory
pipe(with a flare).

AVD-76~96*

47
● 5.10.4

below.

07-14 10 3 Btu/h

17-54 10 3 Btu/h

76-96 103Btu/h

48
5.10.5

below.

49

17~24
27~38
07~14 48~54

Cord Clamp

below.

220-240V~ 50Hz
220V~60Hz

AVD-07~54*

Model Static/Pressure(Pa)
AVD-07~24*L 30(*)
AVD-07~54*L 60(*)
50(*)80
AVD-07~24*H
Printed 1(*)/2
120(*)/90
AVD-27~54*H
Printed 1(*)/2
AVD-76~96UX(6/7)SFL 100(*)
AVD-76~96UX(6/7)SFH 220(*)
AVD-76UX2SFH 240(*)
AVD-96UX2SFH 200(*)

50
AVD-76~96UX2SFH

Printed"2"
Fig. Static Pressure of Change

AVD-76~96UX2SFH,AVD-76~96UX6SE/FL/H

Cord Clamp
Cord Clamp

1PH, 208-230 V 60Hz

AVD-76~96UX(6/7)S(E/F)(L/H)

5.10.6

Cord Clamp

380-415V 3N 50Hz 380V 3N~60Hz

51

3 1.0~2.5
3 6 1.0~2.5
6 10 1.0~2.5
10 16 1.5~4.0
16 25 2.5~6.0
25 32 4.0~10.0
32 50 6.0~16.0
50 63 10.0~25.0
63 *2
2
5.10.7

Use an ELB (Electric Leakage Breaker).If not used ,it


will cause an electric shock or a fire.
Run through the cables using conduit tube, and
Completely seal the end of conduit tube with sealing
materials.with sealing materials.

AVD-07~54*
5

MCA EN60 335-1 EN60 335-1


1 1
AVD-07~09* 1.1A

AVD-12~14* 1.5A

AVD-17~22* 1.6A

AVD-24* 1.9A
m2
2.5m 0.75mm2
AVD-27~38* 3.0A

AVD-48~54* 4.2A Ex.) Set at No.16 Unit


Setting Set by inserting DSW6
Position Slotted screwdriver
AVD-76~96UX(6/7)* 10A into the groove

2
AVD-76~96UX2SFH 11A 4.0mm 2 0.75mm
Set No.1 Pin ON
Before shipment. DSW6 and RSW1 are set to "0".
RSW1
Max.64 units are available to set when all the equipment
to be connected are corresponding to Hi-NET.
Max.16 units when the units corresponding/
non-corresponding to Hi-NET are combined. Set at "6"
The wire sizes marked with *1 in the above table are selected
at the maximum current of the unit according to the European
Standard, EN60 335-1.Use the wires which are not lighter than
the ordinary polyvinyl chloride sheathed flexible cord
(code designation H05VV-F).
3

52
② Setting of (DSW3&DSW4)

AVD-07~54*

AVD-76~96*

Capacity 07 09 12 14 17 18 22

Capacity 24 27 30 38 48 54 76

Capacity 96

53
6. Low-Height Celling Ducted Type(AVE)
6.1 General Data
Indoor Unit Type Low-Height Ceiling Ducted Type
Model AC 1 , 220-240V/50Hz AVE-05UXCSAL AVE-07UXCSAL AVE-09UXCSAL AVE-12UXCSAL AVE-14UXCSAL
Power Supply AC 1 , 220V/60Hz - AVE-07UX2SAL AVE-09UX2SAL AVE-12UX2SAL AVE-14UX2SAL
Nominal Cooling kW 1.8 2.3 2.9 3.8 4.4
Capacity *1) kcal/h 1,500 2,000 2,500 3,300 3,800
Btu/h 6,100 7,800 9,900 13,000 15,000
Nominal Cooling kW 1.7 2.2 2.8 3.6 4.3
Capacity *2) kcal/h 1,500 1,900 2,400 3,100 3,700
Btu/h 5,800 7,500 9,600 12,300 14,700

Cooling Power Consumption kW 0.019 0.05 0.05 0.07 0.07


Nominal Heating kW 1.9 2.8 3.3 4.2 4.9
Capacity kcal/h 1,700 2,400 2,800 3,600 4,200
Btu/h 6,500 9,600 11,300 14,300 16,700

Heating Power Consumption kW 0.019 0.05 0.05 0.07 0.07


Sound Pressure Level
(Overall A Scale) dB 30-29-28-27-26-25 27-24-21 27-24-21 32-30-27 32-30-27
Outer Dimensions
Height mm 192 192 192 192 192
(in.) (7-9/16) (7-9/16) (7-9/16) (7-9/16) (7-9/16)
Width mm 697 900 900 900 900
(in.) (27-7/16) (35-7/16) (35-7/16) (35-7/16) (35-7/16)
Depth mm 447 447 447 447 447
(in.) (17-19/32) (17-19/32) (17-19/32) (17-19/32) (17-19/32)
Net Weight kg 16 20 20 21 21
(lbs.) (35.2) (44) (44) (46) (46)
Refrigerant — R410A(Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 390/372/354/ 500/440/350 500/440/350 640/590/520 640/590/520
(Hi/Me/Lo) (cfm) 336/318/300 (294/259/206) (294/259/206) (376/347/306) (376/347/306)

External Pressure *3) Pa 10(0-10-30) 10(30) 10(30) 10(30) 10(30)


Connections Flare-Nut Connection (with Flare Nuts)
Refrigerant Piping
Liquid Line mm Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ6.35
(in.) (1/4) (1/4) (1/4) (1/4) (1/4)
Gas Line mm Φ12.7 Φ12.7 Φ12.7 Φ12.7 Φ12.7
(in.) (1/2) (1/2) (1/2) (1/2) (1/2)
Condensate Drain — VP25 VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.14 0.15 0.15 0.15 0.15
NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meter Beneath the Unit.
With Discharge Duct (2.0m) and Return Duct (1.0m).
Voltage of the power source for the indoor fan motor is 220V.
In case of the power source of 240V, the sound pressure level increases by about 1 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3. The data for external pressure *3) indicates "Standard Pressure Setting values when a filter is not used.

54
Indoor Unit Type Low-Height Ceiling Ducted Type
Model AC 1 , 220-240V/50Hz AVE-17UXCSBL AVE-18UXCSBL AVE-22UXCSBL AVE-24UXCSBL
Power Supply AC 1 , 220V/60Hz AVE-17UX2SBL AVE-18UX2SBL AVE-22UX2SBL AVE-24UX2SBL
Nominal Cooling kW 5.2 5.8 6.5 7.3
Capacity *1) kcal/h 4,500 5,000 5,600 6,300
Btu/h 17,700 19,800 22,200 24,900
Nominal Cooling kW 5.0 5.6 6.3 7.1
Capacity *2) kcal/h 4,300 4,800 5,400 6,100
Btu/h 17,100 19,100 21,500 24,200

Cooling Power Consumption kW 0.10 0.10 0.11 0.11


Nominal Heating kW 5.8 6.5 7.5 8.5
Capacity kcal/h 5,000 5,600 6,500 7,300
Btu/h 19,800 22,200 25,600 29,000

Heating Power Consumption kW 0.10 0.10 0.11 0.11


Sound Pressure Level
(Overall A Scale) dB 34-30-28 34-30-28 36-32-29 36-32-29
Outer Dimensions
Height mm 192 192 192 192
(in.) (7-9/16) (7-9/16) (7-9/16) (7-9/16)
Width mm 1,170 1,170 1,170 1,170
(in.) (46-1/16) (46-1/16) (46-1/16) (46-1/16)
Depth mm 447 447 447 447
(in.) (17-19/32) (17-19/32) (17-19/32) (17-19/32)
Net Weight kg 26 26 26 26
(lbs.) (57) (57) (57) (57)
Refrigerant — R410A(Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 870/750/630 870/750/630 950/820/710 950/820/710
(Hi/Me/Lo) (cfm) (512/442/371) (512/442/371) (559/482/417) (559/482/417)

External Pressure *3) Pa 10(30) 10(30) 10(30) 10(30)


Connections Flare-Nut Connection (with Flare Nuts)
Refrigerant Piping
Liquid Line mm Φ6.35 Φ6.35 Φ9.53 Φ9.53
(in.) (1/4) (1/4) (3/8) (3/8)
Gas Line mm Φ15.88 Φ15.88 Φ15.88 Φ15.88
(in.) (5/8) (5/8) (5/8) (5/8)
Condensate Drain — VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.18 0.18 0.18 0.18
NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meter Beneath the Unit.
With Discharge Duct (2.0m) and Return Duct (1.0m).
Voltage of the power source for the indoor fan motor is 220V.
In case of the power source of 240V, the sound pressure level increases by about 1 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3. The data for external pressure *3) indicates "Standard Pressure Setting values when a filter is not used.

55
Indoor Unit Type Slim Ceiling Ducted Type
Model AC 1 , 220-240V/50Hz AVE-07UXCSGL AVE-09UXCSGL AVE-12UXCSGL AVE-14UXCSGL
Power Supply AC 1 , 220V/60Hz AVE-07UX2SGL AVE-09UX2SGL AVE-12UX2SGL AVE-14UX2SGL
Nominal Cooling kW 2.3 2.9 3.8 4.4
Capacity *1) kcal/h 2,000 2,500 3,300 3,800
Btu/h 7,800 9,900 13,000 15,000
Nominal Cooling kW 2.2 2.8 3.6 4.3
Capacity *2) kcal/h 1,900 2,400 3,100 3,700
Btu/h 7,500 9,600 12,300 14,700

Cooling Power Consumption kW 0.05 0.05 0.06 0.06


Nominal Heating kW 2.8 3.3 4.2 4.9
Capacity kcal/h 2,400 2,800 3,600 4,200
Btu/h 9,600 11,300 14,300 16,700

Heating Power Consumption kW 0.05 0.05 0.06 0.06


Sound Pressure Level
(Overall A Scale) dB 27-23-21 27-23-21 31-29-27 31-29-27
Outer Dimensions
Height mm 192 192 192 192
(in.) (7-9/16) (7-9/16) (7-9/16) (7-9/16)
Width mm 700 700 700 700
(in.) (27-14/25) (27-14/25) (27-14/25) (27-14/25)
Depth mm 602 602 602 602
(in.) (23-7/10) (23-7/10) (23-7/10) (23-7/10)
Net Weight kg 21 21 21 21
(lbs.) (46) (46) (46) (46)
Refrigerant — R410A(Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 450/380/335 450/380/335 590/510/470 590/510/470
(Hi/Me/Lo) (cfm) (265/223/197) (265/223/197) (347/300/276) (347/300/276)

External Pressure *3) Pa 10(30) 10(30) 10(30) 10(30)


Connections Flare-Nut Connection (with Flare Nuts)
Refrigerant Piping
Liquid Line mm Φ6.35 Φ6.35 Φ6.35 Φ6.35
(in.) (1/4) (1/4) (1/4) (1/4)
Gas Line mm Φ12.7 Φ12.7 Φ12.7 Φ12.7
(in.) (1/2) (1/2) (1/2) (1/2)
Condensate Drain — VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.15 0.15 0.15 0.15
NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meter Beneath the Unit.
With Discharge Duct (2.0m) and Return Duct (1.0m).
Voltage of the power source for the indoor fan motor is 220V.
In case of the power source of 240V, the sound pressure level increases by about 1 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3. The data for external pressure *3) indicates "Standard Pressure Setting values when a filter is not used.

56
Indoor Unit Type DC Low Height Ducted Type
Model AC 1 , 220-240V/50Hz
AVE-07UXJSCL AVE-09UXJSCL AVE-12UXJSCL AVE-14UXJSCL AVE-17UXJSDL
Power Supply AC 1 , 220V/60Hz
Nominal Cooling kW 2.3 2.9 3.8 4.6 5.2
Capacity *1) kcal/h 2,000 2,500 3,300 4,000 4,500
Btu/h 7,800 9,900 13,000 15,600 17,700
Nominal Cooling kW 2.2 2.8 3.6 4.3 5.0
Capacity *2) kcal/h 1,900 2,400 3,100 3,900 4,300
Btu/h 7,500 9,600 12,300 14,700 17,100

Cooling Power Consumption kW 0.03 0.03 0.05 0.05 0.08


Nominal Heating kW 2.8 3.3 4.2 4.9 5.6
Capacity kcal/h 2,400 2,800 3,600 4,300 4,800
Btu/h 9,600 11,300 14,300 16,700 19,100

Heating Power Consumption kW 0.03 0.03 0.05 0.05 0.08


Sound Pressure Level
(Overall A Scale) dB 29-27-26-24-23-22 31-30-29-27-25-24 33-32-30-29-26-25 33-32-30-29-26-25 36-34-33-32-30-27
Outer Dimensions
Height mm 192 192 192 192 192
(in.) (7-9/16) (7-9/16) (7-9/16) (7-9/16) (7-9/16)
Width mm 910 910 910 910 1180
(in.) (35-13/16) (35-13/16) (35-13/16) (35-13/16) (46-7/16)
Depth mm 447 447 447 447 447
(in.) (17-5/8) (17-5/8) (17-5/8) (17-5/8) (17-5/8)
Net Weight kg 20 20 21 21 26
(lbs.) (44) (44) (46) (46) (57)
Refrigerant — R410A(Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
450/420/390/360/330/312 540/492/444/402/360/312 588/540/510/480/450/420 588/540/510/480/450/420 870/810/750/690/630/600
Air Flow Rate m3/h
(cfm) (265/247/230/194/194/176) (318/290/237/226/205/194) (346/332/300/265/212/194) (346/332/300/265/212/194) (512/477/442/406/371/282)

External Pressure *3) Pa 10(0-10-30) 10(0-10-30) 10(0-10-30) 10(0-10-30) 10(0-10-50)


Connections Flare-Nut Connection (with Flare Nuts)
Refrigerant Piping
Liquid Line mm Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ6.35
(in.) (1/4) (1/4) (1/4) (1/4) (1/4)
Gas Line mm Φ12.7 Φ12.7 Φ12.7 Φ12.7 Φ15.88
(in.) (1/2) (1/2) (1/2) (1/2) (5/8)
Condensate Drain — VP25 VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.17 0.17 0.17 0.17 0.21
NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meter Beneath the Unit.
With Discharge Duct (2.0m) and Return Duct (1.0m).
Voltage of the power source for the indoor fan motor is 220V.
In case of the power source of 240V, the sound pressure level increases by about 1 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

3. The data for external pressure *3) indicates "Standard Pressure Setting values when a filter is not used.

57
Indoor Unit Type DC Low Height Ducted Type
Model AC 1 , 220-240V/50Hz
AVE-18UXJSDL AVE-22UXJSDL AVE-24UXJSDL
Power Supply AC 1 , 220V/60Hz
Nominal Cooling kW 5.8 6.5 7.3
Capacity *1) kcal/h 5,000 5,600 6,300
Btu/h 19,800 22,200 24,900
Nominal Cooling kW 5.6 6.3 7.1
Capacity *2) kcal/h 4,800 5,400 6,100
Btu/h 19,100 21,500 24,200

Cooling Power Consumption kW 0.08 0.10 0.10


Nominal Heating kW 6.5 7.5 8.5
Capacity kcal/h 5,600 6,500 7,300
Btu/h 22,200 25,600 29,000

Heating Power Consumption kW 0.08 0.10 0.10


Sound Pressure Level
(Overall A Scale) dB 36-34-33-32-30-27 37-36-34-32-31-29 37-36-34-32-31-29
Outer Dimensions
Height mm 192 192 192
(in.) (7-9/16) (7-9/16) (7-9/16)
Width mm 1180 1180 1180
(in.) (46-7/16) (46-7/16) (46-7/16)
Depth mm 447 447 447
(in.) (17-5/8) (17-5/8) (17-5/8)
Net Weight kg 26 26 26
(lbs.) (57) (57) (57)
Refrigerant — R410A(Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 870/810/750/690/630/600 990/900/840/780/720/660 990/900/840/780/720/660
(cfm) (512/477/442/406/371/282) (583/530/494/459/424/389) (583/530/494/459/424/389)

External Pressure *3) Pa 10(0-10-50) 10(0-10-50) 10(0-10-50)


Connections Flare-Nut Connection (with Flare Nuts)
Refrigerant Piping
Liquid Line mm Φ6.35 Φ9.53 Φ9.53
(in.) (1/4) (3/8) (3/8)
Gas Line mm Φ15.88 Φ15.88 Φ15.88
(in.) (5/8) (5/8) (5/8)
Condensate Drain — VP25 VP25 VP25
Approximate
Packing Measurement m3 0.21 0.21 0.21
NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meter Beneath the Unit.
With Discharge Duct (2.0m) and Return Duct (1.0m).
Voltage of the power source for the indoor fan motor is 220V.
In case of the power source of 240V, the sound pressure level increases by about 1 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

3. The data for external pressure *3) indicates "Standard Pressure Setting values when a filter is not used.

58
6.2 Dimensional Data
■ Low-Height Ceiling Ducted Type

Models: AVE-07~14*AL

Electrical Box Gas Pipe Liquid Pipe Water Outlet


(Pump)

Models: AVE-17~24*BL

Unit:mm

Model Gas Pipe Diameter Liquid Pipe Diameter


Model 17~18
Model 22~24

Electrical Box Gas Pipe Liquid Pipe Water Outlet


(Pump)

59
■ Slim Ceiling Ducted Type
Models: AVE-07~14*GL

Unit:mm

Liquid Pipe Gas Pipe Water Outlet Electrical Box Return Air Inlet
(Pump)

Air Outlet

60
■ DC Low Height Ducted Type

Models: AVE-05UXCSAL , AVE-07~24UXJS(C/D)L


mm

Dimensional Data
Model

05 740 700

07 14 950 910

17 24 1220 1180

Air Outlet

(Standard)

Drain Pump(optional)

61
6.3 Selection Data

Models: AVE-07~24*A(B)L

Models: AVE-07~14*GL

Installation Width 1010

Models: AVE-05*AL,AVE-07~24*(C/D)L

62
● Sensible Heat Factor (SHF)
The sensible heat factor of indoor units at each fan speed (Hi, Me, Lo) is given in the below.

SHF
Indoor Unit Model
Hi Me Lo
AVE-05*AL 0.82 0.72 0.70
AVE-07*AL 0.82 0.72 0.70
AVE-09*AL 0.81 0.69 0.68
AVE-12*AL 0.77 0.72 0.68
AVE-14*AL 0.75 0.71 0.67
AVE-17*BL 0.75 0.71 0.67
AVE-18*BL 0.74 0.70 0.67
AVE-22*BL 0.72 0.70 0.68
AVE-24*BL 0.70 0.68 0.66
AVE-07*GL 0.82 0.72 0.70
AVE-09*GL 0.81 0.69 0.68
AVE-12*GL 0.81 0.69 0.68
AVE-14*GL 0.77 0.72 0.68
AVE-07*CL 0.82 0.72 0.70
AVE-09*CL 0.81 0.69 0.68
AVE-12*CL 0.77 0.72 0.68
AVE-14*CL 0.75 0.71 0.67
AVE-17*DL 0.75 0.71 0.67
AVE-18*DL 0.74 0.70 0.67
AVE-22*DL 0.72 0.70 0.68
AVE-24*DL 0.70 0.68 0.66

63
● Fan Performance
AVE-05*AL
EXTERNAL STATIC PRESSURE (Pa)

Hi

Me
Lo

HH

S-lo

Night Shift

AIR VOLUME (m3/min)

AVE-07/09*AL AVE-12/14*AL
AVE-07/09*GL AVE-12/14*GL
EXTERNAL STATIC PRESSURE (Pa)

EXTERNAL STATIC PRESSURE (Pa)

Hi (Optional) Hi (Optional)

Hi (Standard) Hi (Standard)
Me (Optional)

Me (Standard) Me (Optional)
Me (Standard)
Lo (Optional) Lo (Optional)

Lo (Standard) Lo (Standard)

AIR VOLUME (m3/min) AIR VOLUME (m3/min)

64
AVE-17/18*BL AVE-22/24*BL

EXTERNAL STATIC PRESSURE (Pa)


EXTERNAL STATIC PRESSURE (Pa)

Hi (Optional)
Hi (Optional)

Hi (Standard)
Hi (Standard)

Me (Optional)
Me (Optional)
Lo (Optional) Lo (Optional)
Me (Standard)
Me (Standard)
Lo (Standard)
Lo (Standard)

AIR VOLUME (m3/min) AIR VOLUME (m3/min)

65
AVE-07*CL AVE-09*CL
EXTERNAL STATIC PRESSURE (Pa)

EXTERNAL STATIC PRESSURE (Pa)


HH

Hi
Me Hi
HH
Me
Lo

S-lo Lo

S-lo
Night Shift

Night Shift

AIR VOLUME (m3/min) AIR VOLUME (m3/min)

AVE-12*CL AVE-14*CL
EXTERNAL STATIC PRESSURE (Pa)

EXTERNAL STATIC PRESSURE (Pa)

Hi HH HH
Hi

Me
Lo
Me
Lo
S-lo
S-lo

Night Shift Night Shift

AIR VOLUME (m3/min) AIR VOLUME (m3/min)

66
AVE-17*DL AVE-18*DL

HH HH

EXTERNAL STATIC PRESSURE (Pa)


EXTERNAL STATIC PRESSURE (Pa)

Hi Hi

Me Me

Lo Lo

S-lo S-lo

Night Shift Night Shift

AIR VOLUME (m3/min) AIR VOLUME (m3/min)

AVE-22*DL AVE-24*DL

HH
HH
EXTERNAL STATIC PRESSURE (Pa)

EXTERNAL STATIC PRESSURE (Pa)

Hi Hi

Me Me

Lo Lo

S-lo
S-lo

Night Shift
Night Shift

AIR VOLUME (m3/min) AIR VOLUME (m3/min)

67
● Sound Data

Low-height Ceiling Duct Type

Power Supply: 220-240V/50Hz,220V/60Hz Model: AVE-07/09*AL Power Supply: 220-240V/50Hz,220V/60Hz


Model: AVE-05*AL

Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit

Noise Criteria Curve Noise Criteria Curve

Octave Sound Pressure Level(dB: Overall C Scale)


Octave Sound Pressure Level(dB: Overall C Scale)

Low Noise
Hi
Me

Lo
Approximate
Threshold of
Hearing for
Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model: AVE-12/14*AL Power Supply: 220-240V/50Hz,220V/60Hz Model: AVE-17/18*BL Power Supply: 220-240V/50Hz,220V/60Hz

Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit

Noise Criteria Curve Noise Criteria Curve


Octave Sound Pressure Level(dB: Overall C Scale)
Octave Sound Pressure Level(dB: Overall C Scale)

Hi
Hi
Me Me

Lo Lo

Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

68
Model: AVE-22/24*BL Power Supply: 220-240V/50Hz,220V/60Hz

Measurement Point: 1.5 Meters Beneath the Unit

Noise Criteria Curve


Octave Sound Pressure Level(dB: Overall C Scale)

Hi
Me

Lo

Approximate
Threshold of
Hearing for
Continuous Noise

Central Frequency(Cycle per Second)

Model: AVE-07/09*GL Power Supply: 220~240V/50Hz, 220V/60Hz Model: AVE-12/14*GL Power Supply: 220~240V/50Hz, 220V/60Hz

Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit

Noise Criteria Curve Noise Criteria Curve


Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)

Hi
Me
Hi
Me

Lo
Lo
Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

69
Model: AVE-07*CL Power Supply: 220-240V/50Hz,220V/60Hz Model: AVE-09*CL Power Supply: 220-240V/50Hz,220V/60Hz

Measurement Point: 1.4 Meters Beneath the Unit Measurement Point: 1.4 Meters Beneath the Unit

Noise Criteria Curve Noise Criteria Curve


Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)


night shift
night shift

Approximate
Approximate
Threshold of
Hearing for Threshold of
Continuous Noise Hearing for
Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model: AVE-12*CL Power Supply: 220-240V/50Hz,220V/60Hz Model: AVE-14*CL Power Supply: 220-240V/50Hz,220V/60Hz

Measurement Point: 1.4 Meters Beneath the Unit Measurement Point: 1.4 Meters Beneath the Unit

Noise Criteria Curve Noise Criteria Curve


Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)

night shift
night shift

Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

70
Model: AVE-17*DL Power Supply: 220-240V/50Hz,220V/60Hz Model: AVE-18*DL Power Supply: 220-240V/50Hz,220V/60Hz

Measurement Point: 1.4 Meters Beneath the Unit Measurement Point: 1.4 Meters Beneath the Unit

Noise Criteria Curve Noise Criteria Curve


Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)


night shift night shift

Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model: AVE-22*DL Power Supply: 220-240V/50Hz,220V/60Hz Model: AVE-24*DL Power Supply: 220-240V/50Hz,220V/60Hz

Measurement Point: 1.4 Meters Beneath the Unit Measurement Point: 1.4 Meters Beneath the Unit

Noise Criteria Curve Noise Criteria Curve


Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)

night shift night shift

Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

71
6.4 Component Data

Indoor Heat Exchanger and Fan


Model AVE-05*AL AVE-07*AL AVE-09*AL AVE-12*AL AVE-14*AL
Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0 7.0
Rows - 2 2 2 3 3
Fin Material Aluminum
Pitch mm 1.6 1.8 1.8 1.8 1.8
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15 4.15
Total Face Area m2 0.14 0.13 0.13 0.13 0.13
Number of Coil/Unit - 1 1 1 1 1
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 2 2 2 2 2
Outer Diameter mm 130 130 130 130 130
889/853/818/
Revolution (220V) rpm 782/ 747/715 1,055/960/850 1,055/960/850 1,198/1,068/994 1,198/1,068/994

390/372/354/
Nominal Air Flow m3/h 500/440/350 500/440/350 640/590/520 640/590/520
336/318/300
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - PSC (Permanent Split Capacitor)
Nominal Output W 40 20 20 35 35
Quantity - 1 1 1 1 1
Insulation Class - B B B B B

Model AVE-17*BL AVE-18*BL AVE-22*BL AVE-24*BL


Heat Exchanger Type - M ult i- Pa ss C r o ss Fin ne d Tu b e
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0
Rows - 3 3 3 3
Fin Material Aluminum
Pitch mm 1.8 1.8 1.8 1.8
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15
Total Face Area m2 0.18 0.18 0.18 0.18
Number of Coil/Unit - 1 1 1 1
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 3 3 3 3
Outer Diameter mm 130 130 130 130
Revolution (220V) rpm 1,210/1,106/1,002 1,210/1,106/1,002 1,293/1,220/1,106 1,293/1,220/1,106
Nominal Air Flow m3/h 870/750/630 870/750/630 950/820/710 950/820/710
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - PSC (Permanent Split Capacitor)
Nominal Output W 45 45 50 50
Quantity - 1 1 1 1
Insulation Class - B B F F

72
Indoor Heat Exchanger and Fan
Model AVE-07*GL AVE-09*GL AVE-12*GL AVE-14*GL
Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0
Rows - 2 2 2 2
Fin Material Aluminum
Pitch mm 1.6 1.6 1.6 1.6
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15
Total Face Area m2 0.14 0.14 0.14 0.14
Number of Coil/Unit - 1 1 1 1
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 3 3 3 3
Outer Diameter mm 130 130 130 130
Revolution (220V) rpm 1,210/1,106/1,002 1,210/1,106/1,002 1,293/1,220/1,106 1,293/1,220/1,106
Nominal Air Flow m3/h 450/380/335 450/380/335 590/510/470 590/510/470
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - PSC (Permanent Split Capacitor)
Nominal Output W 15 15 25 25
Quantity - 1 1 1 1
Insulation Class - B B B B

73
Indoor Heat Exchanger and Fan
Model AVE-07*CL AVE-09*CL AVE-12*CL AVE-14*CL
Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0
Rows - 2 2 2 2
Fin Material Aluminum
Pitch mm 1.6 1.6 1.6 1.6
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15
Total Face Area m2 0.15 0.15 0.15 0.15
Number of Coil/Unit - 1 1 1 2
Indoor Fan Centrifugal Fan
Number/Unit - 2 2 2 2
Outer Diameter mm 130 130 130 130
Revolution 820/781/729/ 930/857/788/ 1059/982/934/ 1059/982/934/
rpm 687/633/612 712/652/586 887/843/786 887/843/786

Nominal Air Flow 450/420/390/ 540/492/402/ 588/564/510/ 588/564/510/


m3/h
330/330/300 384/348/330 450/360/330 450/360/330
Indoor Fan Motor IP40
Starting Method - Control software
Nominal Output W 40 40 40 40
Quantity - 1 1 1 1
Insulation Class - E E E E

Model AVE-17*DL AVE-18*DL AVE-22*DL AVE-24*DL


Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0
Rows - 3 3 3 3
Fin Material Aluminum
Pitch mm 1.6 1.6 1.6 1.6
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15
Total Face Area m2 0.2 0.2 0.2 0.2
Number of Coil/Unit - 1 1 1 1
Indoor Fan Centrifugal Fan
Number/Unit - 3 3 3 3
Outer Diameter mm 130 130 130 130
Revolution 1096/1031/974/ 1096/1031/974/ 1192/1108/1043/ 1192/1108/1043/
rpm 908/843/803 908/843/803 980/918/855 980/918/855

Nominal Air Flow 870/810/750 870/810/750/ 990/900/840/ 990/900/840/


m3/h
690/630/480 690/630/480 780/720/600 780/720/600
Indoor Fan Motor IP40
Starting Method - Control software
Nominal Output W 60 60 60 60
Quantity - 1 1 1 1
Insulation Class - E E E E

74
6.5 Refrigeration Cycle

05~24Model

Indoor Unit

2
: Refrigerant Flow Direction (Cooling)
: Refrigerant Flow Direction (Heating)
: Field Refrigerant Piping
3 : Flare Connection

4
b

Refrigerant Liquid Pipe Connection


S

3 a

Refrigerant Gas Pipe Connection

Mark Part Name


1 Heat Exchanger
2 Distributor
3 Strainer
4 Micro-Computer Control Expansion Valve

75
6.6 Electrical Data

< 50 Hz >
Unit Main Power Applicable Voltage Indoor Fan Motor
Model
VOL PH HZ Maximum Minimum PH RNC IPT
AVE-05UXCSAL 0.18 0.013
AVE-07UXCSAL 0.27 0.05
AVE-09UXCSAL 0.27 0.05
AVE-12UXCSAL 0.37 0.07
Low-Height
AVE-14UXCSAL 0.37 0.07
Ceiling Ducted 220~240 1 50 264 198 1
AVE-17UXCSBL 0.48 0.1
Type
AVE-18UXCSBL 0.48 0.1
AVE-22UXCSBL 0.52 0.11
AVE-24UXCSBL 0.52 0.11
AVE-07UXCSGL 0.25 0.05
Slim Ceiling AVE-09UXCSGL 0.25 0.05
220~240 1 50 264 198 1
Ducted Type AVE-12UXCSGL 0.27 0.06
AVE-14UXCSGL 0.27 0.06

< 60 Hz >

Unit Main Power Applicable Voltage Indoor Fan Motor


Model
VOL PH HZ Maximum Minimum PH RNC IPT
AVE-07UX2SAL 0.27 0.05
AVE-09UX2SAL 0.27 0.05
Low-Height AVE-12UX2SAL 0.37 0.07
Ceiling Ducted AVE-14UX2SAL 220 1 60 242 198 1 0.37 0.07
Type AVE-17UX2SBL 0.48 0.09
AVE-18UX2SBL 0.48 0.09
AVE-22UX2SBL 0.52 0.10
AVE-24UX2SBL 0.52 0.10
AVE-07UX2SGL 0.25 0.05
Slim Ceiling AVE-09UX2SGL 0.25 0.05
220 1 60 242 198 1
Ducted Type AVE-12UX2SGL 0.27 0.06
AVE-14UX2SGL 0.27 0.06

< 50 Hz >,< 60 Hz >


Unit Main Power Applicable Voltage Indoor Fan Motor
Model
VOL PH Hz Maximum Minimum PH RNC IPT

AVE-07UXJSCL 0.31/0.31 0.024/0.024


AVE-09UXJSCL 0.31/0.31 0.024/0.024
AVE-12UXJSCL 0.40/0.40 0.044/0.044
DC Low Height
Ducted Type AVE-14UXJSCL 0.40/0.40 0.044/0.044
50 242 198 1
AVE-17UXJSCL 220 1 0.66/0.66 0.074/0.074
60
AVE-18UXJSDL 0.66/0.66 0.074/0.074
AVE-22UXJSDL 0.78/0.78 0.094/0.094
AVE-24UXJSDL 0.78/0.78 0.094/0.094

VOL: Rated Unit Power Supply Voltage (Plated)(V) RNC: Running Current (A)
PH: Phase (φ) IPT: Input (kW)
HZ: Frequency (Hz)

76
Safety and Control Device Setting

Indoor Unit

AVE-05~24*
Model

For Evaporator Fan


℃ 130±5
Motor Thermostat Cut-Out
Cut-In ℃ 83±15
For Control Circuit
Fuse Capacity A 5
Freeze Protection
Thermostat ℃ 0
Cut-Out
Cut-In ℃ 14

Thermostat
Differential ℃ 2

77
6.7 Electrical Wiring Diagram
Model: AVE-05*

PCB2
TB1
Electrical Control Box of Indoor Unit

: Factory Wiring
: Earth Wiring
: Field Wiring
: Optional Parts

PCB1
PCB2

PCB1

1 2

Remote Control
Switch(HYXE-J01H)
MV1
Operation Line
DC5V

TB1,2
PCB
MIF Note :
MV 1. All the field wiring and equipment
FS must comply with local codes.

78
Electrical Wiring Diagram
Model: AVE-07~14*

79
Electrical Wiring Diagram
Model: AVE-07~24UXJ*

(EVI)

80
6.8 Indoor Unit Optional Parts

Optional Parts Applied Indoor Unit Type

Low-Height Ceiling Slim Ceiling DC Low Height


Type Model
Ducted Type Ducted Type Ducted Type

HYXE-F01H ● ●
HYXE-G01H ● ●
Wire Remote Control Switch HYXE-A01H#01 ● ●
HYXE-J01H ● ●
HYXE-M01H ● ● ●
HYE-Q01 ● ●
Wireless Remote Control Switch HYE-L01 ● ●
HYE-W01 ● ● ●
HYRE-V01H ● ●
HYRE-T01H
Wireless Receiver Kit
HYRE-V02H
HYRE-X01H
7 Day Timer HYDE-E01H ● ●
HYJE-H01H ● ●
HYJE-D02H ● ●
HYJ-J01H ● ●
Centrol Station HCCS-H128H2C1YM ● ●
HCCS-H128H2C1NM
HCCS-H247R4C1E
HCCS-H128H2C2NM ● ●
HC-A64BNP ● ●
Interface for Building Control
HCPC-H2M1C ● ●
HCH-160D ● ●
Switch Box
HCH-280D ● ●
HZX-2.0AEC
HZX-4.0AEC
AHU Kits HZX-6.0AEC
HZX-10.0AEC
HZX-20.0AEC
HPS-162#E
Drain Pump HPS-132#E
HPS-151#E
HF-224L-FE
Long Life filter HF-280L-FE
HF-40L-ZFE ●
HP-DB-NK ●
3D Air Swing
HP-EB-NK ●

81
6.9

AVE-05~24UX(C/2)S(A/B)L

(Only 07-24)

(Only 07-24)

AVE-07~14UX(C/2)SGL

AVE-07~24UXJS(C/D)L

Cable Clamp (big) For Power Wiring

Cable Clamp (small) For Transmission Wiring

82
6.10 Install
6.10.1

Section 6.3 Selection Data

below.

Model: AVE-05UXCSAL,AVE-07~24UXJS(C/D)L

(for Suspension Bolt)


for Suspension Bolt
411

6.10.2
Suspension Bolts

below.

83
Model: AVE-07-24UX(C/2)S(A/B)L ●
for Suspension Bolt below.
for Suspension Bolt

Model

05

07~14

17~24
below.

Model: AVE-05~24UX(C/2)S(A/B)L
Model: AVE-07~14UX(C/2)SGL

for Suspension Bolt


for Suspension Bolt

View from Top

Model: AVE-07~14UX(C/2)SGL

84
Model:AVE-07~24UXJS(C/D)L ●

5mm
Nut
Approx.
50mm

192 opening

Indoor Unit
Washer
Nut
sizes)

Model: AVE-05~24UX(C/2)S(A/B)L
AVE-07~24UXJS(C/D)L

Below

Model: AVE-07~14UX(C/2)SGL

85
6.11
Drain Pump(optional)
60
Refrigerant Liquid
1 A Pipe Connection
Refrigerant Gas
Pipe Connection
Drain Pipe
Connection

76
83
98
25

43 145
192 Drainage outlet was plugged
65
249 by rubber boss.
63 250

6.11.1
Model: AVE-07-24UX(C/2)S(A/B)L

Refrigerant Gas Refrigerant Liquid Drain Pipe


Pipe Connection Pipe Connection Connection

g
a
c
6.11.2 h m
b k
d 63

Model: AVE-05UXCSAL,AVE-07~24UXJS(C/D)L Piping Position


Refrigerant Liquid
Pipe Connection
Refrigerant Gas
Pipe Connection

Model a b c d g h k m
05 35 166 86 220 97 129 90 65

07~24 76 101 106 144 45 53 71 47


63
Drain Pipe
Connection
Model

05~14

Model: AVE-07~14UX(C/2)SGL 17~18

22~24
Standard

65
Refrigerant Liquid
Flaring Dimension
43 Refrigerant Gas
Pipe Connection Pipe Connection
Perform the flaring work as shown below.
83

98

25
ΦD
Φa
145
R410A R407C
60

92
192 Drain Pipe 6.35 9.1 9.0
Connection
249
9.53 13.2 13.0
12.7 16.6 16.2
15.88 19.7 19.4
19.05 (*) 23.3

(*)It is impossible to perform the flaring work with


1/2H material. In this case, use an accessory
pipe(with a flare).

86
below.

12

below.

field-

below.

Drain Pump(optional)
Optional Optional

Optional

Standard

installation

87
6.13

Avoid any wire from contacting with coolant


tube, edge of metal plate and electrical
part in the equipment, or otherwise the
below. wire may be damaged or even thereby cause
fire.
ELB with intermediate induction rate (with
shorter than 0.1 second or fewer) shall be
used, or otherwise electric shock or fire may
be caused.
Wire shall be fixed securely, since external
force imposed to the connecting terminal
may make it loose and thereby cause fire.
Do not use the power terminal strip
used for the air conditioner to sub-connect
any power cable, but use power branch box
to sub-connect power wire at indoor unit
side instead, and be sure to calculate
wire capacity, or otherwise too low
capacity may cause fire.
The system shall not be started until all
inspections have been performed properly.

Tighten screws using the following torque.

M4: 1.0~1.3 N▪m


M5: 2.0~2.4 N▪m
M6: 4.0~5.0 N▪m
M8: 9.0~11.0 N▪m
M10: 18.0~23.0 N ▪ m

88
6.13.1
(6)

(7)

a) Model: AVE-05UXCSAL,AVE-07~24UXJS(C/D)L
Setting the external static pressure for the
Romote Controller.
Please refer to the operation inatallation and
maintenance manual of the Romote Controller.

List of External Static Pressure


Model Static Pressure Setting of Romote
Controller
AVE-05* 0Pa 02
AVE-07~24*(C/D)L 10Pa 00
AVE-05~14UX(C/2)SGL 30Pa
01
AVE-17~24UXJS(C/D)L 50Pa

*:Factory set value


6.13.2 b) Model: AVE-07~24UX(C/2)S(A/B)L,AVE-07~14UX(C/2)SGL

(1) Wiring Connecting

For AVE-05~24UX(C/2)S(A/B)L,AVE-07~14UX(C/2)SGL

Cable Clamp (big) For Power Wiring

Cable Clamp (small) For Transmission Wiring


For AVE-07~24UXJS(C/D)L

Fig. Wiring Connecting

(2)

(3)
Model: AVE-05UXCSAL,AVE-07~24UXJS(C/D)L
(4)
Electrical Box Cover

(5)

89
Remove the fixing screws for electrical box cover
Model:AVE-07~14UX(C/2)SGL

Standard
Electrical Box Cover

Air Outlet Air lnlet

Remove the fixing screws for electrical box cover

Drain Pump(optional)
Electrical Box Cover
220-240V~ 50Hz
220V~ 60Hz
Air Outlet Air lnlet

Model: AVE-07~24UX(C/2)S(A/B)L Remove the fixing screws for electrical box cover

Electrical Box Cover

Air Outlet Air lnlet


PCB1

Cord Clamp
Remove the fixing screws for electrical box cover

PCB2

PCB2 PCB1

Cord Clamp

TB

220-240V~ 50Hz
220V~ 60Hz

Fig.

220-240V~ 50Hz
220V~ 60Hz

90
6.14

6.15
6.15.1

Use an ELB (Electric Leakage Breaker).If not used ,it will cause an electric shock or a fire.

Run through the cables using conduit tube, and Completely seal the end of conduit tube.with sealing materials.

Power
Model Source MCA EN60 335-1 EN60 335-1

AVE-05UXCSAL 0.26A
AVE-07~09UX(C/2)S(A/B)L 0.6A

AVE-12~14UX(C/2)A(A/B)L 0.8A
AVE-17~18UX(C/2)S(A/B)L ~ 1.0A 2.5
220V~60Hz
AVE-22~24UX(C/2)S(A/B)L 1.1A
AVE-07~09UX(C/2)SGL 0.28A
AVE-12~14UX(C/2)SGL 0.29A
AVE-07~24UXJS(C/D)L 1.86A

The wire sizes marked with *1 in the above table are selected 3 1.0~2.5
at the maximum current of the unit according to the European 3 6 1.0~2.5
Standard, EN60335-1.Use the wires which are not lighter than 6 10 1.0~2.5
the ordinary polyvinyl chloride sheathed flexible cord 10 16 1.5~4.0
(code designation H05VV-F). 16 25 2.5~6.0
25 32 4.0~10.0
3
32 50 6.0~16.0
50 63 10.0~25.0
63 *2
2

91
6.15.2
Model:AVE-05UXCSAL,AVE-07~24UXJS(C/D)L
Capacity 05
Setting
Position
Model:AVE-05UXCSAL,AVE-07~24UXJS(C/D)L

Capacity 07 Capacity 09
Setting Setting
Position Position

Capacity 12 Capacity 14
Setting Setting
Model:AVE-07~24UX(C/2)S(A/B)L,AVE-07~14UX(C/2)SGL Position Position

Capacity 17 Capacity 18
Setting Setting
Position Position

Capacity 22 Capacity 24
Setting Setting
Position Position

Setting Set by inserting


Ex.) Set at No.16 Unit
DSW6
Model:AVE-05* Model: AVE-07-24*(A/B)L
Position Slotted screwdriver
into the groove
AVE-07~24*(C/D)L AVE-07~14*GL

Set No.1 Pin ON


Before shipment. DSW6 and RSW1 are set to "0".
RSW1
Max.64 units are available to set when all the equipment
to be connected are corresponding to Hi-NET.
Max.16 units when the units corresponding/
non-corresponding to Hi-NET are combined. Set at "6"

Ex.) Set at No.5 Cycle


Setting Set by inserting DSW5
Position Slotted screwdriver
(Model:AVE-07~24UX(C/2)S(A/B)L, AVE-07~14UX(C/2)SGL) into the groove

Set All Pins OFF


Before shipment. DSW5 and RSW2 are set to "0".
RSW2
Max.64 cycles are available to set when all the equipment
to be connected are corresponding to Hi-NET.
Max.16 cycles when the units corresponding/
non-corresponding to Hi-NET are combined. Set at "5"
Capacity 07 09 12 14 17
Setting
Position

Capacity 18 22 24
Setting
Position

92
(f) Humidity Sensor Setting(DSW8)
( For AVE-05UXCSAL,AVE-07~24UXJS(C/D)L)

No setting is required.
Setting position before
shipment are all have.

6.15.3

93
7. 4-Way Cassette Type
7.1 General Data
Indoor Unit Type 4-Way Cassette Type
Model AC 1 , 220-240V/50Hz AVC-09UXCSEB AVC-12UXCSEB AVC-14UXCSEB AVC-17UXCSEB
Power Supply AC 1 , 220V/60Hz AVC-09UX2SEB AVC-12UX2SEB AVC-14UX2SEB AVC-17UX2SEB
Nominal Cooling kW 2.9 3.8 4.4 5.2
Capacity *1) kcal/h 2,500 3,300 3,800 4,500
Btu/h 9,900 13,000 15,000 17,700
Nominal Cooling kW 2.8 3.6 4.3 5.0
Capacity *2) kcal/h 2,400 3,100 3,700 4,300
Btu/h 9,600 12,300 14,700 17,100

Cooling Power Consumption kW 0.04 0.05 0.05 0.05


Nominal Heating kW 3.3 4.2 4.9 5.6
Capacity kcal/h 2,800 3,600 4,200 4,800
Btu/h 11,300 14,300 16,700 19,100

Heating Power Consumption kW 0.04 0.05 0.05 0.05


Sound Pressure Level
(Overall A Scale) dB 30-29-27 31-29-27 31-29-27 32-30-27
Outer Dimensions
Height mm 248 248 248 248
(in.) (9-3/4) (9-3/4) (9-3/4) (9-3/4)
Width mm 840 840 840 840
(in.) (33-1/16) (33-1/16) (33-1/16) (33-1/16)
Depth mm 840 840 840 840
(in.) (33-1/16) (33-1/16) (33-1/16) (33-1/16)
Net Weight kg 22 22 22 23
(lbs.) (48) (48) (48) (51)
Refrigerant — R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 780/720/660 900/810/720 900/810/720 960/840/720
(Hi/Me/Lo) (cfm) (459/424/388) (530/477/424) (530/477/424) (565/494/424)

Connections Flare-Nut Connection (with Flare Nuts)


Refrigerant Piping
Liquid Line mm Φ6.35 Φ6.35 Φ6.35 Φ6.35
(in.) (1/4) (1/4) (1/4) (1/4)
Gas Line mm Φ12.7 Φ12.7 Φ12.7 Φ15.88
(in.) (1/2) (1/2) (1/2) (5/8)
Condensate Drain — VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.22 0.22 0.22 0.22
Adaptable Panel Model — HPE-A-NA
Color — Neutral White
Outer Dimensions
Height mm 37 37 37 37
(in.) (1-7/16) (1-7/16) (1-7/16) (1-7/16)
Width mm 950 950 950 950
(in.) (37-3/8) (37-3/8) (37-3/8) (37-3/8)
Depth mm 950 950 950 950
(in.) (37-3/8) (37-3/8) (37-3/8) (37-3/8)
Net Weight kg 6 6 6 6
(lbs.) (13) (13) (13) (13)
Approximate
Packing Measurement m3 0.08 0.08 0.08 0.08
NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meters Beneath the Unit.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

94
Indoor Unit Type 4-Way Cassette Type
Model AC 1 , 220-240V/50Hz AVC-18UXCSEB AVC-22UXCSEB AVC-24UXCSEB AVC-27UXCSFB
Power Supply AC 1 , 220V/60Hz AVC-18UX2SEB AVC-22UX2SEB AVC-24UX2SEB AVC-27UX2SFB
Nominal Cooling kW 5.8 6.5 7.3 8.7
Capacity *1) kcal/h 5,000 5,600 6,300 7,500
Btu/h 19,800 22,200 24,900 29,700
Nominal Cooling kW 5.6 6.3 7.1 8.4
Capacity *2) kcal/h 4,800 5,400 6,100 7,200
Btu/h 19,100 21,500 24,200 28,700

Cooling Power Consumption kW 0.05 0.06 0.06 0.09


Nominal Heating kW 6.5 7.5 8.5 9.6
Capacity kcal/h 5,600 6,500 7,300 8,300
Btu/h 22,200 25,600 29,000 32,800

Heating Power Consumption kW 0.05 0.06 0.06 0.09


Sound Pressure Level
(Overall A Scale) dB 32-30-27 33-31-29 33-31-29 36-34-32
Outer Dimensions
Height mm 248 248 248 298
(in.) (9-3/4) (9-3/4) (9-3/4) (11-3/4)
Width mm 840 840 840 840
(in.) (33-1/16) (33-1/16) (33-1/16) (33-1/16)
Depth mm 840 840 840 840
(in.) (33-1/16) (33-1/16) (33-1/16) (33-1/16)
Net Weight kg 23 23 23 24
(lbs.) (51) (51) (51) (53)
Refrigerant — R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 960/840/720 1140/1020/840 1200/1020/900 1560/1380/1200
(Hi/Me/Lo) (cfm) (565/494/424) (671/600/494) (706/600/530) (918/812/706)

Connections Flare-Nut Connection (with Flare Nuts)


Refrigerant Piping
Liquid Line mm Φ6.35 Φ9.53 Φ9.53 Φ9.53
(in.) (1/4) (3/8) (3/8) (3/8)
Gas Line mm Φ15.88 Φ15.88 Φ15.88 Φ15.88
(in.) (5/8) (5/8) (5/8) (5/8)
Condensate Drain — VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.22 0.22 0.22 0.26
Adaptable Panel Model — HPE-A-NA
Color — Neutral White
Outer Dimensions
Height mm 37 37 37 37
(in.) (1-7/16) (1-7/16) (1-7/16) (1-7/16)
Width mm 950 950 950 950
(in.) (37-3/8) (37-3/8) (37-3/8) (37-3/8)
Depth mm 950 950 950 950
(in.) (37-3/8) (37-3/8) (37-3/8) (37-3/8)
Net Weight kg 6 6 6 6
(lbs.) (13) (13) (13) (13)
Approximate
Packing Measurement m3 0.08 0.08 0.08 0.08
NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meters Beneath the Unit.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

95
Indoor Unit Type 4-Way Cassette Type
Model AC 1 , 220-240V/50Hz AVC-30UXCSFB AVC-38UXCSFB AVC-48UXCSFB AVC-54UXCSFB
Power Supply AC 1 , 220V/60Hz AVC-30UX2SFB AVC-38UX2SFB AVC-48UX2SFB AVC-54UX2SFB
Nominal Cooling kW 9.3 11.6 14.5 16.5
Capacity *1) kcal/h 8,000 10,000 12,500 14,200
Btu/h 31,700 39,600 49,500 56,300
Nominal Cooling kW 9.0 11.2 14.2 16.0
Capacity *2) kcal/h 7,700 9,600 12,200 13,800
Btu/h 30,700 38,200 48,500 54,600

Cooling Power Consumption kW 0.09 0.12 0.15 0.16


Nominal Heating kW 10.0 13.0 16.3 18.0
Capacity kcal/h 8,600 11,200 14,000 15,500
Btu/h 34,100 44,400 55,600 61,400

Heating Power Consumption kW 0.09 0.12 0.15 0.16


Sound Pressure Level
(Overall A Scale) dB 36-34-32 41-38-35 44-39-36 44-42-38
Outer Dimensions
Height mm 298 298 298 298
(in.) (11-3/4) (11-3/4) (11-3/4) (11-3/4)
Width mm 840 840 840 840
(in.) (33-1/16) (33-1/16) (33-1/16) (33-1/16)
Depth mm 840 840 840 840
(in.) (33-1/16) (33-1/16) (33-1/16) (33-1/16)
Net Weight kg 24 27 27 27
(lbs.) (53) (59) (59) (59)
Refrigerant — R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 1560/1380/1200 1920/1680/1440 2040/1740/1500 2220/1920/1620
(Hi/Me/Lo) (cfm) (918/812/706) (1,130/989/847) (1,201/1,024/883) (1,307/1,130/954)

Connections Flare-Nut Connection (with Flare Nuts)


Refrigerant Piping
Liquid Line mm Φ9.53 Φ9.53 Φ9.53 Φ9.53
(in.) (3/8) (3/8) (3/8) (3/8)
Gas Line mm Φ15.88 Φ15.88 Φ15.88 Φ15.88
(in.) (5/8) (5/8) (5/8) (5/8)
Condensate Drain — VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.26 0.26 0.26 0.26
Adaptable Panel Model — HPE-A-NA
Color — Neutral White
Outer Dimensions
Height mm 37 37 37 37
(in.) (1-7/16) (1-7/16) (1-7/16) (1-7/16)
Width mm 950 950 950 950
(in.) (37-3/8) (37-3/8) (37-3/8) (37-3/8)
Depth mm 950 950 950 950
(in.) (37-3/8) (37-3/8) (37-3/8) (37-3/8)
Net Weight kg 6 6 6 6
(lbs.) (13) (13) (13) (13)
Approximate
Packing Measurement m3 0.08 0.08 0.08 0.08
NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meters Beneath the Unit.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

96
7.2 Dimensional Data
Models: AVC-09~24*EB

Unit: mm

Mark Name Remark


20 860~910 20 1 Air Outlet 4-Way
(Opening Hole for Ceiling)
840 4-14 x 26 Holes 2 Air Inlet
760 (for Suspension Bolt) 3 Refrigerant Gas Pipe Connection with φ a Flare Nut
(for Suspension Bolt) 4 Refrigerant Liquid Pipe Connection with φ b Flare Nut
14

20
5 Drain Pipe Connection VP25
6 Wiring Hole for Conduit Tube φ32.5 Knockout Hole
7 Wiring Hole 30 x 39 Hole
8 Suspension Bracket

(Opening Hole for Ceiling)


(for Suspension Bolt)
9 Suspension Bolt 4-M10 or W3/8
10 Supply Duct Connection 150 x 385 Knockout Hole

860~910
11 Supply Duct Connection 150 x 400 Knockout Hole
760

840
25 (Liquid Pipe)
24 (Drain Pipe)

12 Remote Control Switch without Cable


18 (Gas Pipe)

13 Shielded Twist-Pair Cable Min. 0.75mm2, Field-Supplied

Dimension a b
Model
09~14 12.7 6.35
B 17/18 15.88 6.35
20

110 (Gas Pipe)


22/24 15.88 9.53
180 (Liquid Pipe)
8 9 D
710 (Drain Pipe) Suspension Bolts M10 or W3/8
(Field-Supplied)

Duct Adapter Connection


3 4 5 Viewed from C
E E

C
248
36
31
127 (Liquid Pipe)

102
118 (Drain Pipe)
37
102 (Gas Pipe)

A
Air Inlet Grille
7 6 Optional Air Panel

Optional 12 13 (Field-Supplied) 10
In case of using this,
cut the insulation material 385 30
along to the line indicated 220 100

46
opening position.
2 1
120 7 6 In case of using this,
cut the insulation material
145

150
along to the line indicated
opening position.
5

25
10

25
9-M4 75 135 135 75
127 85
31

(for Self-Tapping Screw)


Viewed from B Enlarged View of D
950

In case of using this, 11


400 50
Switch Box cut the insulation material
JISC8336-1985 220 100
along to the line indicated
46

(Field-Supplied) opening position.


145

150

950
20 20
25
10

10
Viewed from A
Wall Mounting Embedding Cable 9-M4 75 135 135 75
in the Wall (for Self-Tapping Screw)
Mounting for Remote Control Switch (Optional) Enlarged View of E

Service Space
Min.

Min.

Min.
100

100

100

Min. Min. Min. Min. Min.


500 500 Surroundings 500 3000 500
in the Ceiling
NOTE:
Distance between the wall and panel edge must be
a min. 1500mm to prevent short circuiting.

Service Access Panel


Min.

Min.

Min.
100

100

100

Piping Connection Piping Connection Service Access Piping Connection


Service Access Panel Panel

Separated Installation Closed Installation

97
Models: AVC-27~54*FB
Unit: mm
20 860~910 20 Mark Name Remark
(Opening Hole for Ceiling) 1 Air Outlet 4-Way
840 4-14 x 26 Holes
(for Suspension Bolt)
2 Air Inlet
760
(for Suspension Bolt)
3 Refrigerant Gas Pipe Connection with φ a Flare Nut
14 4 Refrigerant Liquid Pipe Connection with φ b Flare Nut

20
5 Drain Pipe Connection VP25
6 Wiring Hole for Conduit Tube φ 32.5 Knockout Hole
7 Wiring Hole 30 x 39 Hole

(Opening Hole for Ceiling)


8 Suspension Bracket

(for Suspension Bolt)


9 Suspension Bolt 4-M10 or W3/8
10 Supply Duct Connection 150 x 385 Knockout Hole

860~910
760

840
11 Supply Duct Connection 150 x 400 Knockout Hole
25 (Liquid Pipe)
24 (Drain Pipe)
18 (Gas Pipe)

12 Remote Control Switch without Cable


13 Shielded Twist-Pair Cable Min. 0.75mm2, Field-Supplied

Dimension
a b
HP
27/30 15.88 9.53
B
38 15.88 9.53
20

110 (Gas Pipe)


180 (Liquid Pipe) 48/54 15.88 9.53
8 9 Suspension Bolts M10 or W3/8
710 (Drain Pipe)
(Field-Supplied)
D

Duct Adapter Connection


3 4 5 Viewed from C
E E

C
298
127 (Liquid Pipe)

36
31

102
118 (Drain Pipe)
102 (Gas Pipe)

37

A
Air Inlet Grille
7 6 Optional Air Panel

Optional 12 13 (Field-Supplied) 10
In case of using this, 385 30
cut the insulation material 220 100

96
along to the line indicated
opening position.
2 1
120 7 6 In case of using this,
cut the insulation material
145

150
along to the line indicated
opening position.
5

25
10

25
9-M4 75 135 135 75
127 85
31

(for Self-Tapping Screw)


Viewed from B Enlarged View of D
950

400 50
Switch Box In case of using this, 11
JISC8336-1985 220 100
cut the insulation material
96

(Field-Supplied)
along to the line indicated
opening position.
145

150

950
20 20
Viewed from A
25
10

Embedding Cable 10
Wall Mounting
in the Wall 9-M4 75 135 135 75
Mounting for Remote Control Switch (Optional) (for Self-Tapping Screw)
Enlarged View of E

Service Space
Min.

Min.

Min.
100

100

100

Min. Min. Min. Min. Min.


500 500 Surroundings 500 3000 500
in the Ceiling
NOTE:
Distance between the wall and panel edge must be
a min. 1500mm to prevent short circuiting.

Service Access Panel


Min.

Min.

Min.
100

100

100

Piping Connection Piping Connection Service Access Piping Connection


Service Access Panel Panel

Separated Installation Closed Installation

98
7.3 Selection Data

■ Service Space
Models: AVC-07~54*

Unit: mm

1500

1500
1500

Min.

Min.
Min.

Min. 500 Min. 100

Min. Min. Min. Min. Min. Piping


1500 1500 1500 3000 1500 Connection
Side

1500

1500
1500

Min.

Min.
Min.

Min. 100 Min. 500


Min. 1000
Piping Connection Piping Connection Piping Connection Service Space
Service Access Door Service Access Door Service Access Door
Separated Installation Closed Installation
Distance from Wall Side

● Sensible Heat Factor (SHF)


The sensible heat factor of indoor units at each fan speed (Hi, Me, Lo) is given in the below.

SHF
Indoor Unit Model
Hi Me Lo
AVC-09*EB 0.80 0.77 0.75
AVC-12*EB 0.78 0.76 0.74
AVC-14*EB 0.77 0.75 0.73
AVC-17*EB 0.79 0.77 0.76
AVC-18*EB 0.78 0.76 0.75
AVC-22*EB 0.74 0.72 0.70
AVC-24*EB 0.73 0.71 0.69
AVC-27*FB 0.79 0.76 0.72
AVC-30*FB 0.79 0.76 0.72
AVC-38*FB 0.78 0.75 0.72
AVC-48*FB 0.74 0.70 0.68
AVC-54*FB 0.73 0.69 0.67

99
Sound Data

Model: AVC-09UXC(2)SEB Power Supply: 220-240V/50Hz,220V/60Hz Model: AVC-12UXC(2)SEB Power Supply: 220-240V/50Hz,220V/60Hz
Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve

80 80
Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)


70 NC-70 70 NC-70

60 NC-6 60 NC-6
0 0

50 NC-5
0 50 NC-5
0

Hi
Hi
40 NC-4
0
40 NC-4
0

Me Me

30 NC-3
0
30 NC-3
0

20 Approximate NC- 20 Approximate NC-


Threshold of 20 Threshold of 20

Hearing for Hearing for Lo


Lo
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model: AVC-14UXC(2)SEB Power Supply: 220-240V/50Hz,220V/60Hz Model: AVC-17UXC(2)SEB Power Supply: 220-240V/50Hz,220V/60Hz
Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve

80 80
Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)

70 NC-70 70 NC-70

60 NC-6 60 NC-6
0 0

50 NC-5
0 50 NC-5
0

Hi Hi
40 NC-4
0
40 NC-4
0

Me Me

30 NC-3
0
30 NC-3
0

20 Approximate NC- 20 Approximate NC-


Threshold of 20 Threshold of 20

Hearing for Lo Hearing for


Lo
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

100
Model: AVC-18UXC(2)SEB Power Supply: 220-240V/50Hz,220V/60Hz Model: AVC-22UXC(2)SEB Power Supply: 220-240V/50Hz,220V/60Hz
Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve

80 80
Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)


70 NC-70 70 NC-70

60 NC-6 60 NC-6
0 0

50 NC-5
0 50 NC-5
0

Hi Hi

40 NC-4
0
40 NC-4
0

Me Me

30 NC-3
0
30 NC-3
0

20 Approximate NC- 20 Approximate NC-


Threshold of 20 Threshold of 20

Hearing for Hearing for


Lo Lo
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model: AVC-24UXC(2)SEB Power Supply: 220-240V/50Hz,220V/60Hz Model: AVC-27UXC(2)SFB Power Supply: 220-240V/50Hz,220V/60Hz
Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve

80 80
Octave Sound Pressure Level(dB: Overall C Scale)
Octave Sound Pressure Level(dB: Overall C Scale)

70 NC-70 70 NC-70

60 NC-6 60 NC-6
0 0

50 NC-5
0
50 NC-5
0

Hi Hi

40 NC-4
0
40 NC-4
0

Me Me

30 NC-3
0
30 NC-3
0

20 Approximate NC- 20 Approximate NC-


Threshold of 20 Threshold of 20

Hearing for Hearing for Lo


Continuous Noise Lo Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

101
Model: AVC-30UXC(2)SFB Power Supply: 220-240V/50Hz,220V/60Hz Model: AVC-38UXC(2)SFB Power Supply: 220-240V/50Hz,220V/60Hz
Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve

80 80
Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)


70 NC-70 70 NC-70

60 NC-6 60 NC-6
0 0

Hi
50 NC-5
0 50 NC-5
0

Hi

40 NC-4
0 40 NC-4
0
Me
Me

30 NC-3
0
30 NC-3
0

20 Approximate NC- 20 Approximate NC-


Threshold of 20 Threshold of 20
Hearing for Lo Hearing for
Continuous Noise Continuous Noise Lo
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model: AVC-48UXC(2)SFB Power Supply: 220-240V/50Hz,220V/60Hz Model: AVC-54UXC(2)SFB Power Supply: 220-240V/50Hz,220V/60Hz
Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve

80 80
Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)

70 NC-70 70 NC-70

60 NC-6 60 NC-6
0 0

Hi Hi
50 NC-5
0 50 NC-5
0

Me Me

40 NC-4
0 40 NC-4
0

30 NC-3
0 30 NC-3
0

Lo
Lo
20 Approximate NC- 20 Approximate NC-
Threshold of 20 Threshold of 20
Hearing for Hearing for
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

102
7.4 Component Data

Model AVC--09UX*EB AVC--12UX*EB AVC--14UX*EB AVC--17UX*EB


Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0
Rows - 1 1 1 2
Fin Material Aluminum
Pitch mm 1.5 1.5 1.5 1.5
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15
Total Face Area m2 0.39 0.39 0.39 0.39
Number of Coil/Unit - 1 1 1 1
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 1 1 1 1
Outer Diameter mm 490 490 490 490
Revolution (220V) rpm 290/270/250 335/285/250 335/285/250 340/295/245
Nominal Air Flow m /h
3
780/720/660 900/810/720 900/810/720 960/840/720
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - DC Driven
Nominal Output W 56 56 56 56
Quantity - 1 1 1 1
Insulation Class - E E E E

Indoor Heat Exchanger and Fan

Model AVC--18UX*EB AVC--22UX*EB AVC--24UX*EB AVC--27UX*FB


Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0
Rows - 2 2 2 2
Fin Material Aluminum
Pitch mm 1.5 1.5 1.5 1.5
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15
Total Face Area m2 0.39 0.39 0.39 0.49
Number of Coil/Unit - 1 1 1 1
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 1 1 1 1
Outer Diameter mm 490 490 490 490
Revolution (220V) rpm 340/295/245 380/340/290 380/340/290 475/420/340
Nominal Air Flow m /h
3
960/840/720 1140/1020/840 1200/1020/900 1560/1380/1200
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - DC Driven
Nominal Output W 56 56 56 56
Quantity - 1 1 1 1
Insulation Class - E E E E

103
Model AVC--30UX*FB AVC--38UX*FB AVC--48UX*FB AVC--54UX*FB
Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0
Rows - 2 3 3 3
Fin Material Aluminum
Pitch mm 1.5 1.5 1.5 1.5
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15
Total Face Area m2 0.49 0.49 0.49 0.49
Number of Coil/Unit - 1 1 1 1
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 1 1 1 1
Outer Diameter mm 490 490 490 490
Revolution (220V) rpm 475/420/340 585/485/440 630/515/450 640/525/460
Nominal Air Flow m3/h 1560/1380/1200 1920/1680/1440 2040/1740/1500 2220/1920/1620
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - DC Driven
Nominal Output W 56 124 124 124
Quantity - 1 1 1 1
Insulation Class - E E E E

104
7.5 Refrigeration Cycle

Indoor Unit

2
: Refrigerant Flow Direction (Cooling)
: Refrigerant Flow Direction (Heating)
: Field Refrigerant Piping
3 : Flare Connection

4
b

Refrigerant Liquid Pipe Connection


S

3 a

Refrigerant Gas Pipe Connection

Mark Part Name


1 Heat Exchanger
2 Distributor
3 Strainer
4 Micro-Computer Control Expansion Valve

105
7.6 Electrical Data

< 50 Hz >
Indoor Unit
Unit Main Power Applicable Voltage Indoor Fan Motor
Model
VOL PH HZ Maximum Minimum PH RNC IPT
AVC-09UXCSEB 0.21 0.04
AVC-12UXCSEB 0.27 0.05
AVC-14UXCSEB 0.27 0.05
AVC-17UXCSEB 0.27 0.05
AVC-18UXCSEB 0.27 0.05
4-Way AVC-22UXCSEB 0.32 0.06
220~240 1 50 264 198 1
Cassette Type AVC-24UXCSEB 0.32 0.06
AVC-27UXCSFB 0.48 0.09
AVC-30UXCSFB 0.48 0.09
AVC-38UXCSFB 0.59 0.12
AVC-48UXCSFB 0.75 0.15
AVC-54UXCSFB 0.80 0.16

VOL: Rated Unit Power Supply Voltage (Plated)(V) RNC: Running Current (A)
PH: Phase (φ) IPT: Input (kW)
HZ: Frequency (Hz)

< 60 Hz >
Indoor Unit
Unit Main Power Applicable Voltage Indoor Fan Motor
Model
VOL PH HZ Maximum Minimum PH RNC IPT
AVC-09UX2SEB 0.21 0.04
AVC-12UX2SEB 0.27 0.05
AVC-14UX2SEB 0.27 0.05
AVC-17UX2SEB 0.27 0.05
AVC-18UX2SEB 0.27 0.05
4-Way AVC-22UX2SEB 0.32 0.06
220 1 60 242 198 1
Cassette Type AVC-24UX2SEB 0.32 0.06
AVC-27UX2SFB 0.48 0.09
AVC-30UX2SFB 0.48 0.09
AVC-38UX2SFB 0.59 0.11
AVC-48UX2SFB 0.75 0.14
AVC-54UX2SFB 0.80 0.15

VOL: Rated Unit Power Supply Voltage (Plated)(V) RNC: Running Current (A)
PH: Phase (φ) IPT: Input (kW)
HZ: Frequency (Hz)

106
Safety and Control Device Setting
Indoor Unit

Model
AVC-09~54*

For Evaporator Fan


Motor Thermostat ℃ 130±5
Cut-Out
Cut-In ℃ 83±15
For Control Circuit
Fuse Capacity A 5
Freeze Protection
Thermostat ℃ 0
Cut-Out
Cut-In ℃ 14

Thermostat
℃ 2
Differential

107
7.7 Electrical Wiring Diagram
Model: AVC-09~54* WARNING Before inspecting the electrical parts
set the Operation Switch to OFF,
HEAT PUMP and cut OFF the power supply.

TB1 PCB2 MIF


L EFR1 DM
PCN203
Z1 Noise Air Panel
N Filter
Z2
DSA Supply
PCN201 Circuit
CN201

PCN202 CN202
Name
CN
CN38 CN
CN36
C
* Fiel
Connection DSW
EF
PCB1 FS
: Factory Wiri PCN7 PCN1 CN1 CN19 CN17 MD
: Earth Wiri CN11 MIF
Alarm MS
: Field Wiri
: Optional Par MV
PCB1,2
H2
PCN
RSW
TB1,2
TF
THM
YH2
MD

Electrical Control Box


Service Connector for Drain
Discharge Mechanism Note :
Operation Line Remote Control 1.All the field wiring and equipment
(DC5V)
must comply with local codes.

108
7.8 Indoor Unit Optional Parts

Optional Parts Applied Indoor Unit Type

Type Model 4-Way Cassette Type

HYXE-F01H ●
HYXE-G01H ●
Wire Remote Control Switch HYXE-A01H#01 ●
HYXE-J01H ●
HYXE-M01H ●
HYE-Q01 ●
Wireless Remote Control Switch HYE-L01 ●
HYE-W01 ●
HYRE-V01H
HYRE-T01H ●
Wireless Receiver Kit
HYRE-V02H
HYRE-X01H
7 Day Timer HYDE-E01H ●
HYJE-H01H ●
HYJE-D02H ●
HYJ-J01H ●
Centrol Station HCCS-H128H2C1YM ●
HCCS-H128H2C1NM
HCCS-H247R4C1E
HCCS-H128H2C2NM ●
HC-A64BNP ●
Interface for Building Control
HCPC-H2M1C ●
HCH-160D ●
Switch Box
HCH-280D ●
HZX-2.0AEC
HZX-4.0AEC
AHU Kits HZX-6.0AEC
HZX-10.0AEC
HZX-20.0AEC
HPS-162#E
Drain Pump HPS-132#E
HPS-151#E
HF-224L-FE
Long Life filter HF-280L-FE
HF-40L-ZFE
HP-DB-NK
3D Air Swing
HP-EB-NK

109
7.9

110
7.10 Install
7.10.1

below.

2.5

09 24
27 54

111
7.10.2 ●

below.

Model
09 24
27 54

below.

112

113
7.11 Flaring Dimension
Perform the flaring work as shown below.
+0
Diameter A -0.4
10A d R410A R407C
6.35 9.1 9.0
9.53 13.2 13.0
12.7 16.6 16.2
15.88 19.7 19.4
19.05 (*) 23.3

(*)It is impossible to perform the flaring work with


1/2H material. In this case, use an accessory
7.11.1 pipe(with a flare).

below.

09 14

17 18

22 27

30

38 54

below.

7.11.2

below.

114
7.12
below.

115
7.13

13.

below.

13.

116
7.14
7.15

TB1

220-240V 50Hz
220V 60Hz

7.15
7.15.1

Use an ELB (Electric Leakage Breaker).If not


used ,it will cause an electric shock or a fire.
Run through the cables using conduit tube,
and Completely seal the end of conduit tube
with sealing materials.

MCA
EN60 335-1 *1 EN60 335-1 *1

09 27 1.0A
2.5mm2 0.75mm2
30 54 1.8A

117
The wire sizes marked with *1 in the above table are selected
at the maximum current of the unit according to the European
Standard, EN60335-1.Use the wires which are not lighter than
the ordinary polyvinyl chloride sheathed flexible cord
(code designation H05VV-F).
3 Ex.) Set at No.16 Unit
Setting Set by inserting DSW6
Position Slotted screwdriver
into the groove

Set No.1 Pin ON


Before shipment. DSW6 and RSW1 are set to "0".
RSW1
Max.64 units are available to set when all the equipment
to be connected are corresponding to Hi-NET.
Max.16 units when the units corresponding/
non-corresponding to Hi-NET are combined.
3 1.0~2.5 Set at "6"

3 6 1.0~2.5
6 10 1.0~2.5 Capacity
22
×10 Btu/h
3 09 12 14 17 18
10 16 1.5~4.0
16 25 2.5~6.0
25 32 4.0~10.0
32 50 6.0~16.0 Capacity
×10 3Btu/h 24 27/30 38 48 54
50 63 10.0~25.0
63 *2
2

7.15.2

The indoor unit

118
7.16 7.17.1

outlet

Outlet

7.17.2

7.17

7.17.3

119
7.18

7.18.1

7.18.2

7.18.3

7.18.4

120
8. Compact 4-Way Cassette Type
8.1 General Data
Indoor Unit Type Compact 4-Way Cassette Type
Model AC 1 , 220-240V/50Hz AVC-05URCSAB AVC-07URCSAB AVC-09URCSAB AVC-12URCSAB AVC-14URCSAB AVC-17URCSAB
Power Supply AC 1 , 220V/60Hz - AVC-07UR2SAB AVC-09UR2SAB AVC-12UR2SAB AVC-14UR2SAB AVC-17UR2SAB
Nominal Cooling kW 1.8 2.3 2.9 3.8 4.4 5.2
Capacity *1) kcal/h 1,500 2,000 2,500 3,300 3,800 4,500
Btu/h 6,100 7,800 9,900 13,000 15,000 17,700
Nominal Cooling kW 1.7 2.2 2.8 3.6 4.3 5.0
Capacity *2) kcal/h 1,500 1,900 2,400 3,100 3,700 4,300
Btu/h 5,800 7,500 9,600 12,300 14,700 17,100

Cooling Power Consumption kW 0.63 0.63 0.63 0.63 0.71 0.89


Nominal Heating kW 1.9 2.8 3.3 4.2 4.9 5.6
Capacity kcal/h 1,700 2,400 2,800 3,600 4,200 4,800
Btu/h 6,500 9,600 11,300 14,300 16,700 19,100

Heating Power Consumption kW 0.63 0.63 0.63 0.63 0.71 0.89


Sound Pressure Level
(Overall A Scale) dB 39-34-30 39-34-30 39-34-30 39-34-30 41-38-33 44-41-37
Outer Dimensions
Height mm 270 270 270 270 270 270
(in.) (10-2/3) (10-2/3) (10-2/3) (10-2/3) (10-2/3) (10-2/3)
Width mm 570 570 570 570 570 570
(in.) (22-11/25) (22-11/25) (22-11/25) (22-11/25) (22-11/25) (22-11/25)
Depth mm 570 570 570 570 570 570
(in.) (22-11/25) (22-11/25) (22-11/25) (22-11/25) (22-11/25) (22-11/25)
Net Weight kg 20 20 20 20 20 20
(lbs.) (44) (44) (44) (44) (44) (44)
Refrigerant — R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 570/480/384 570/480/384 570/480/384 570/480/384 654/564/456 792/690/588
(Hi/Me/Lo) (cfm) (335/282/226) (335/282/226) (335/282/226) (335/282/226) (385/332/268) (466/406/346)

Connections Flare-Nut Connection (with Flare Nuts)


Refrigerant Piping
Liquid Line mm Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ6.35
(in.) (1/4) (1/4) (1/4) (1/4) (1/4) (1/4)
Gas Line mm Φ12.7 Φ12.7 Φ12.7 Φ12.7 Φ12.7 Φ12.7
(in.) (1/2) (1/2) (1/2) (1/2) (1/2) (1/2)
Condensate Drain — VP25 VP25 VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.18 0.18 0.18 0.18 0.18 0.18
Adaptable Panel Model — TBD
Color — Neutral White
Outer Dimensions
Height mm 30 30 30 30 30 30
(in.) (1-1/6) (1-1/6) (1-1/6) (1-1/6) (1-1/6) (1-1/6)
Width mm 650 650 650 650 650 650
(in.) (25-3/5) (25-3/5) (25-3/5) (25-3/5) (25-3/5) (25-3/5)
Depth mm 650 650 650 650 650 650
(in.) (25-3/5) (25-3/5) (25-3/5) (25-3/5) (25-3/5) (25-3/5)
Net Weight kg 2.4 2.4 2.4 2.4 2.4 2.4
(lbs.) (5.3) (5.3) (5.3) (5.3) (5.3) (5.3)
Approximate
Packing Measurement m3 0.06 0.06 0.06 0.06 0.06 0.06
NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meters Beneath the Unit.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

121
8.2 Dimensional Data
Models: AVC-05~17*AB

19 570 650 Dimension Of


Panel
610 Dimension Of
Suspension Bolts
600 Dimension Of
Opening 4-positions Of
Suspension Bolts
570
570
400

Suspension Bolts

Dimension Of

650 Dimension Of
400 Dimension Of

Unit Size

Opening
84

Panel
85

570

600
64

80
76
54 303
41 Drain Pipe

Wiring Hole
54
103
88
117

570
270

Gas Pipe 77
Liquid Pipe 55 292
42 Drain Pipe
40

Wiring Hole
230

Gas Pipe
180
167

Liquid Pipe
10 Min

Wiring Hole
285
196
7
18

650
650

122
8.3 Selection Data

● Service Space
Models: AVC-05~17*AB

● Sensible Heat Factor (SHF)


The sensible heat factor of indoor units at each fan speed (Hi, Me, Lo) is given in the below.

SHF
Indoor Unit Model
Hi Me Lo

AVC-05*AB 0.79 0.76 0.74


AVC-07*AB 0.79 0.76 0.74
AVC-09*AB 0.79 0.76 0.74
AVC-12*AB 0.78 0.75 0.72
AVC-14*AB 0.75 0.71 0.68
AVC-17*AB 0.73 0.70 0.67

123
● Sound Data

Model: AVC-05~12URC(2)SAB Power Supply: 220-240V/50Hz,220V/60Hz Model: AVC-14URC(2)SAB Power Supply: 220-240V/50Hz,220V/60Hz
Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve

80 80

Octave Sound Pressure Level(dB: Overall C Scale)


70 NC-70 70 NC-70

60 NC-6 60 NC-6
0 0

50 NC-5
0 50 NC-5
0
Hi
Hi
40 NC-4
0
40 Me NC-4
0

Me

30 NC-3
0
30 NC-3
0

Lo
20 Approximate NC- 20 Approximate NC-
Threshold of 20 Threshold of 20
Lo
Hearing for Hearing for
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model: AVC-17URC(2)SAB Power Supply: 220-240V/50Hz,220V/60Hz


Measurement Point: 1.5 Meters Beneath the Unit
90
Noise Criteria Curve

80
Octave Sound Pressure Level(dB: Overall C Scale)

70 NC-70

60 NC-6
0

50 Hi NC-5
0

Me
40 NC-4
0

30 NC-3
0

20 Approximate NC-
Threshold of 20

Hearing for Lo
Continuous Noise
10
63 125 250 500 1000 2000 4000 8000

Central Frequency(Cycle per Second)

124
8.4 Component Data

Indoor Heat Exchanger and Fan

Model AVC-05UR*AB AVC-07UR*AB AVC-09UR*AB AVC-12UR*AB AVC-14UR*AB AVC-17UR*AB


Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0 7.0 7.0
Rows - 2 2 2 2 2 2
Fin Material Aluminum
Pitch mm 1.5 1.5 1.5 1.5 1.5 1.5
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15 4.15 4.15
Total Face Area m2 0.27 0.27 0.27 0.27 0.27 0.27
Number of Coil/Unit - 1 1 1 1 1 1
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 1 1 1 1 1 1
Outer Diameter mm 283 283 283 283 283 283
Revolution (220V) rpm 760/640/520 760/640/520 760/640/520 760/640/520 810/700/580 890/790/685
Nominal Air Flow m3 /h 570/480/384 570/480/384 570/480/384 570/480/384 654/564/456 792/690/588
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - PSC (Permanent Split Capacitor)
Nominal Output W 18 18 18 18 25 38
Quantity - 1 1 1 1 1 1
Insulation Class - B B B B B B

125
8.5 Refrigeration Cycle

Indoor Unit

2
: Refrigerant Flow Direction
(Cooling) : Refrigerant Flow Direction
(Heating) : Field Refrigerant Piping :
3 Flare Connection

4
b

Refrigerant Liquid Pipe Connection


S

3 a

Refrigerant Gas Pipe Connection

Mark Part Name


1 Heat Exchanger
2 Distributor
3 Strainer
4 Micro-Computer Control Expansion Valve

126
8.6 Electrical Data

< 50 Hz >
Indoor Unit
Unit Main Power Applicable Voltage Indoor Fan Motor
Model
VOL PH HZ Maximum Minimum PH RNC IPT
AVC-05URCSAB 0.29 0.063
AVC-07URCSAB 0.29 0.063
Compact AVC-09URCSAB 0.29 0.063
4-Way AVC-12URCSAB 220~240 1 50 264 198 1 0.29 0.063
Cassette Type AVC-14URCSAB 0.32 0.071
AVC-17URCSAB 0.40 0.089

< 60 Hz >
Indoor Unit
Unit Main Power Applicable Voltage Indoor Fan Motor
Model
VOL PH HZ Maximum Minimum PH RNC IPT
AVC-07UR2SAB 0.29 0.063
Compact AVC-09UR2SAB 0.29 0.063
4-Way AVC-12UR2SAB 220 1 60 242 198 1 0.29 0.063
Cassette Type AVC-14UR2SAB 0.32 0.071
AVC-17UR2SAB 0.40 0.089

VOL: Rated Unit Power Supply Voltage (Plated)(V) RNC: Running Current (A)
PH: Phase (φ) IPT: Input (kW)
HZ: Frequency (Hz)

Safety and Control Device Setting


Indoor Unit
AVC-05~17*
Model

For Evaporator Fan


℃ 130±5
Motor Thermostat Cut-Out
Cut-In ℃ 83±15
For Control Circuit
Fuse Capacity A 5
Freeze Protection
Thermostat ℃ 0
Cut-Out
Cut-In ℃ 14

Thermostat
℃ 2
Differential

127
8.7 Electrical Wiring Diagram
Model: AVC-05~17UR(C/2)SAB

128
8.8 Indoor Unit Optional Parts

Optional Parts Applied Indoor Unit Type

Type Model Compact 4-Way Cassette Type

HYXE-F01H ●
HYXE-G01H ●
Wire Remote Control Switch HYXE-A01H#01 ●
HYXE-J01H ●
HYXE-M01H ●
HYE-Q01 ●Standard Option
Wireless Remote Control Switch HYE-L01
HYE-W01 ●
HYRE-V01H
HYRE-T01H
Wireless Receiver Kit
HYRE-V02H
HYRE-X01H
7 Day Timer HYDE-E01H ●
HYJE-H01H ●
HYJE-D02H ●
HYJ-J01H ●
Centrol Station HCCS-H128H2C1YM ●
HCCS-H128H2C1NM
HCCS-H247R4C1E
HCCS-H128H2C2NM ●
HC-A64BNP ●
Interface for Building Control
HCPC-H2M1C ●
HCH-160D ●
Switch Box
HCH-280D ●
HZX-2.0AEC
HZX-4.0AEC
AHU Kits HZX-6.0AEC
HZX-10.0AEC
HZX-20.0AEC
HPS-162#E
Drain Pump HPS-132#E
HPS-151#E
HF-224L-FE
Long Life filter HF-280L-FE
HF-40L-ZFE
HP-DB-NK
3D Air Swing
HP-EB-NK

129
8.9

(12ID)

(25ID)

130
8.10 Installtion
8.10.1

below.

2.5

Fan Motor Speed-up


Setting so that uniform air distribution is available.

285mm

131
8.10.2 ●

below.

below.

140

196

132
15 to 20
15 to 20 15 to 20

12
15 to 20
5

(1) Removing Air Intake Grille from Air Panel


Step 1
Open the air intake grille to an angle of approximately 45o
from the surface of the air panel as shown in Fig. below.

Air Panel

Air Intake Grille

45o

● Use the Pattern Board

is in the packing
carton of indoor unit.Take it and do not fold it. Knob

Use it to decide an installation location and * Slide the knobs toward the allow direction

direction of the unit.


Fig. Removing Method of Air Intake Grille
(2) Press the Pattern Board tightly onto the
surface of the roof, draw out the hole position
for suspension bolts with a pencil.
NOTE
(3) Cut an opening on the ceiling board with
assistance of the Pattern Board, make sure to * Do not touch the air louver during installation work.
follow the same direction of suspension bolts. * Do not try to remove the grille while it is at an angle of 90o
from the surface of the air panel.

Step 2
Lift the grille keeping it inclined.
Step 3
Draw the grille towards the open space after lifting.

133
(2) Installing Air Panel
Step 1
Four fixing positions will be seen after removing air l If the screws are tightened insuficiently, it may
intake grille from air panel. cause of the failure.
Set the corner of the electrical box of the indoor unit to
the position of wireless receiver corner of the air panel. Air Leakage
Otherwise wiring between indoor unit and air panel can
not be connected.

Air Panel Smudge

fixing position Dewing


wireless
receiver
corner l When there is still the gap even after tightening the
screws firmly enough, readjust the height of the
indoor unit.

No gap shall exist.

l The indoor unit height is adjustable by adjusting the


nut of suspension bolts for indoor unit .
fixing position
* Significant height adjustment will cause of dewing
Step 2 from the drain pan and lead to the limit switch failure.
Mount the air panel onto the air panel fixing position by using
the factory-supplied fixing screws (M5 screws). l Do not turn the air louver by hand.
If moved, the louver mechanism would be damaged.
Indoor Unit

Electrical
Box Motor Wiring for Auto Louver
(On the Unit Side)
(5-Pole Connector) Louver
ch

Wireless Receiver Wiring


u

(On the Unit Side)


To
ot
N

(10-Pole Connector)
o
D

wireless
receiver
corner Step 4
Air Panel Wiring Connection for Air Panel
The Motor Wiring for Auto Louver and Wireless Receiver
Wiring on the Panel Side and the Unit Side is shown in
Fig. Connect them carefully.
Then attach the air intake grille. This panel is available
to be installed from any 4 directions by rotating the air
Scre w (Q'ty 4) intake grille.
(factory-supplied
in air panel)

Motor Wiring for Auto Louver


(On the panel Side)
Before electrical wiring work, turn OFF the power source.
(5-Pole Connector) If the connectors are connected without turning OFF the
Wireless Receiver Wiring power source, the auto-swing louver can not activate.
(On the panel Side)
(10-Pole Connector)

Fig. Installing Air Panel

Step 3
Check to ensure that there is no gap around the contacting Wired Remote Control Switch and Wireless Remote Control
surface between the indoor unit and the air panel. Any gap Switch can not be used simultaneously .If Wired Remote
may cause air leakage or dewing. Control Switch is connected ,Disconnect Wireless Receiver
Wiring on the Panel Side and the Unit Side.

134
8.11
Check the wiring connections securely after wiring work.
If some problems are existing at the wiring connections,
it may cause a fire. 10A
Fix the cables near the wiring connections securely, if
not, it may cause a fire. Protect the wires or etc. from
rats or other animals. If not protected, rats may gnaw at
unprotected parts and at the worst, a fire will occur.

(3)Test Run of Air Panel


1) After completing the installation of the air panel, perform
the test run according to the “Installation & Maintenance
Manual” attached with outdoor unit. 8.11.1
2) Check the swing louvers’ operating conditions during the
test run.
The swing louvers are operated automatically. Never
move the swing louver by hand.

* Press the ”SWING LOUVER” switch on the remote control


switch.
07 17
* Every time pressing the switch, the horizontal deflectors
repeat swing and stop. The deflectors’ positions are shown
on the “SWING LOUVER” indicator on the remote control
switch LCD.

(When Swinging)

The mark " "


moves continuously.
8.11.2

Section 8.10.2
(When in Fixed Position)
Flaring Dimension

The mark " " Perform the flaring work as shown below.
indicates the position +0
of louvers. Diameter A -0.4
d R410A R407C
6.35 9.1 9.0
NOTE 9.53 13.2 13.0
1) The adequate air flow direction may be different depending 12.7 16.6 16.2
on the conditions such as:
15.88 19.7 19.4
• Air Conditioner’s Installation Position
• Room Structure 19.05 (*) 23.3
• Furniture Layout
If satisfied cooling/heating condition is not obtained, adjust
the air flow direction. (*)It is impossible to perform the flaring work with
2) Perform the louver position setting with observing the 1/2H material. In this case, use an accessory
“SWING LOUVER” Indicator on the remote control switch. pipe(with a flare).
(Louver position does not indicate the actual louver
operating position.)
3) SWING LOUVER
Even if the “SWING LOUVER” switch is pressed, the
louvers may not stop immediately and move up to one
swing at a maximum.
4) If cooling operation is performed under the condition with
over 80% humidity, dew condensation may occur at the
panel or the louvers.

135
below.

below.

136
8.12
900mm.

8.13

Section 8.10.2
740mm

230

137
8.13.1

TB1

220-240V
50Hz
220V 60Hz

8.13.2

below.

connected.

8.13.3 Fan Motor Speed-up Setting(SHi)


To be adapted for high ceiling installation
Speed-up Setting(SHi) is required .Before shipment normal
fan speed (Hi) is connected. To shift to SHi setting Connect
cable terminal of SHi to the power line of fan motor.

SHi setting: Enlarged View of P in Fig.below


Printed "SHi"

SHi

Hi

Printed "Hi"

Fig. Fan Motor Speed-up Setting

138
Noise level will increase 2-3db(A) by Speed-up
Power MCA
Setting(SHi) Source EN60 335-1 * 1 EN60 335-1 *1

14 07 12 220-240V 0.53A

50Hz
14 0.59A 2.5mm 2 0.75mm2
220V
17 60Hz 0.75A

The wire sizes marked with *1 in the above table are selected
at the maximum current of the unit according to the European
Standard, EN60335-1.Use the wires which are not lighter than
the ordinary polyvinyl chloride sheathed flexible cord
(code designation H05VV-F).
3

3 1.0~2.5
3 6 1.0~2.5
6 10 1.0~2.5
10 16 1.5~4.0
16 25 2.5~6.0
25 32 4.0~10.0
32 50 6.0~16.0
50 63 10.0~25.0
63 *2
2

8.15
8.15.1

Use an ELB (Electric Leakage Breaker).If not


used ,it will cause an electric shock or a fire.
Run through the cables using conduit tube,
and Completely seal the end of conduit tube
with sealing materials.

139
8.15.2

Ex.) Set at No.5 Cycle


Setting Set by inserting DSW5
Position Slotted screwdriver
into the groove

Set All Pins OFF


Before shipment. DSW5 and RSW2 are set to "0".
RSW2
Max.64 cycles are available to set when all the equipment
to be connected are corresponding to Hi-NET.
Max.16 cycles when the units corresponding/
non-corresponding to Hi-NET are combined. Set at "5"

Ex.) Set at No.16 Unit


Setting Set by inserting DSW6
Position Slotted screwdriver
into the groove

Set No.1 Pin ON


Before shipment. DSW6 and RSW1 are set to "0".
RSW1
Max.64 units are available to set when all the equipment
to be connected are corresponding to Hi-NET.
Max.16 units when the units corresponding/
non-corresponding to Hi-NET are combined. Set at "6"

Capacity 05 07 09 12 14 17

140
8.16 8.17.1

four clips

outlet air angle

Outlet air angle clips

clips

8.17.2

8.17

8.17.3

141
8.18

8.18.1

8.18.2

8.18.3

8.18.4

142
9. Ceiling & Floor Type(AVV)
9.1 General Data
Indoor Unit Type Ceiling & Floor Type
Model AC 1 , 220-240V/50Hz AVV-17URSCA AVV-18URSCA AVV-22URSCA AVV-24URSCA
Power Supply AC 1 , 220V/60Hz AVV-17UR2SA AVV-18UR2SA AVV-22UR2SA AVV-24UR2SA
Nominal Cooling kW 5.2 5.8 6.5 7.3
Capacity *1) kcal/h 4,500 5,000 5,600 6,300
Btu/h 17,700 19,800 22,200 24,900
Nominal Cooling kW 5.0 5.6 6.3 7.1
Capacity *2) kcal/h 4,300 4,800 5,400 6,100
Btu/h 17,100 19,100 21,500 24,200

Cooling Power Consumption kW 0.04 0.04 0.07 0.07


Nominal Heating kW 5.6 6.5 7.5 8.5
Capacity kcal/h 4,800 5,600 6,500 7,300
Btu/h 19,100 22,200 25,600 29,000

Heating Power Consumption kW 0.04 0.04 0.07 0.07


Sound Pressure Level
(Ceiling Type)
(Overall A Scale) dB 39-35-30 39-35-30 45-41-37 45-41-37

Sound Pressure Level


(Floor Type)
(Overall A Scale) dB 43-38-35 43-38-35 48-44-40 48-44-40
Outer Dimensions
Height mm 230 230 230 230
(in.) (9) (9) (9) (9)
Width mm 990 990 990 990
(in.) (39) (39) (39) (39)
Depth mm 680 680 680 680
(in.) (26-3/4) (26-3/4) (26-3/4) (26-3/4)
Net Weight kg 31 31 32 32
(lbs.) (68) (68) (70) (70)
Refrigerant — R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 780/660/540 780/660/540 966/840/678 966/840/678
(Hi/Me/Lo) (cfm) (459/389/318) (459/389/318) (569/495/399) (569/495/399)

Connections Flare-Nut Connection (with Flare Nuts)


Refrigerant Piping
Liquid Line mm Φ6.35 Φ6.35 Φ9.53 Φ9.53
(in.) (1/4) (1/4) (3/8) (3/8)
Gas Line mm Φ15.88 Φ15.88 Φ15.88 Φ15.88
(in.) (5/8) (5/8) (5/8) (5/8)
Condensate Drain — VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.31 0.31 0.31 0.31
NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.0 Meter Beneath the Unit. 1.0 Meter from Discharge Grille.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
When bottom air inlet is adopted, sound pressure will increase according to factors such as installation mode and the room structure.

143
Indoor Unit Type Ceiling & Floor Type
Model AC 1 , 220-240V/50Hz AVV-27URSCB AVV-30URSCB AVV-38URSCB AVV-48URSCC
Power Supply AC 1 , 220V/60Hz AVV-27UR2SB AVV-30UR2SB AVV-38UR2SB AVV-48UR2SC
Nominal Cooling kW 8.7 9.3 11.6 14.5
Capacity *1) kcal/h 7,500 8,000 10,000 12,500
Btu/h 29,700 31,700 39,600 49,500
Nominal Cooling kW 8.4 9.0 11.2 14.2
Capacity *2) kcal/h 7,200 7,700 9,600 12,200
Btu/h 28,700 30,700 38,200 48,500

Cooling Power Consumption kW 0.07 0.08 0.13 0.16


Nominal Heating kW 9.6 10.0 13.0 16.3
Capacity kcal/h 8,300 8,600 11,200 14,000
Btu/h 32,800 34,100 44,400 55,600

Heating Power Consumption kW 0.07 0.08 0.13 0.16


Sound Pressure Level
(Ceiling Type)
(Overall A Scale) dB 43-39-34 45-40-36 51-46-40 50-46-42

Sound Pressure Level


(Floor Type)
(Overall A Scale) dB 46-41-37 48-43-39 54-49-43 55-50-46

Outer Dimensions
Height mm 230 230 230 230
(in.) (9) (9) (9) (9)
Width mm 1285 1285 1285 1580
(in.) (50-3/5) (50-3/5) (50-3/5) (62-1/5)
Depth mm 680 680 680 680
(in.) (26-3/4) (26-3/4) (26-3/4) (26-3/4)
Net Weight kg 39 40 41 47
(lbs.) (86) (88) (90) (103)
Refrigerant — R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 1092/912/732 1164/978/798 1488/1230/978 1980/1680/1380
(Hi/Me/Lo) (cfm) (643/537/431) (685/576/470) (876/724/576) (1166/989/812)

Connections Flare-Nut Connection (with Flare Nuts)


Refrigerant Piping
Liquid Line mm Φ9.53 Φ9.53 Φ9.53 Φ9.53
(in.) (3/8) (3/8) (3/8) (3/8)
Gas Line mm Φ15.88 Φ15.88 Φ15.88 Φ15.88
(in.) (5/8) (5/8) (5/8) (5/8)
Condensate Drain — VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.40 0.40 0.40 0.48
NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.0 Meter Beneath the Unit. 1.0 Meter from Discharge Grille.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
When bottom air inlet is adopted, sound pressure will increase according to factors such as installation mode and the room structure.

144
9.2 Dimensional Data

Models: AVV-17~24*

Unit:mm

104
177
91 17

43
230 39 912 39
990

680

680

261
182

174
10 101

66 88 16 88
43

22
184

Models: AVV-27~38*

Unit:mm
41 108
177

95 16

1285 230
680

680

261
182

174
10 101

22

66 88
43

16 88
184

Models: AVV-48*

Unit:mm
44 101
177

92 16

230
1580
680
680

261
182

174
10 101

66 88
22
43

16 88
184

145
9.3 Selection Data
● Service Space
Models: AVV-17~48*

50
100

300 500

● Sensible Heat Factor (SHF)


The sensible heat factor of indoor units at each fan speed (Hi, Me, Lo) is given in the below.

SHF
Indoor Unit Model
Hi Me Lo

AVV-17* 0.71 0.68 0.64


AVV-18* 0.71 0.68 0.64
AVV-22* 0.73 0.69 0.66
AVV-24* 0.73 0.69 0.66
AVV-27* 0.74 0.69 0.65
AVV-30* 0.76 0.71 0.68
AVV-38* 0.75 0.70 0.66
AVV-48* 0.76 0.72 0.69

146
● Sound Data

Model: AVV-17* Power Supply: 220-240V/50Hz,220V/60Hz Model: AVV-18* Power Supply: 220-240V/50Hz,220V/60Hz
Measurement Point: 1.0 Meters Beneath the Unit Measurement Point: 1.0 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve

80 80
Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)


70 NC-70 70 NC-70

60 NC-6 60 NC-6
0 0

50 NC-5
0 50 NC-5
0

Hi Hi

40 Me NC-4
0
40 Me NC-4
0

30 NC-3
0
30 NC-3
0

20 Approximate NC- 20 Approximate NC-


Threshold of 20 Threshold of 20
Lo Lo
Hearing for Hearing for
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model: AVV-22* Power Supply: 220-240V/50Hz,220V/60Hz Model: AVV-24* Power Supply: 220-240V/50Hz,220V/60Hz

Measurement Point: 1.0 Meters Beneath the Unit Measurement Point: 1.0 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve

80 80
Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)

70 NC-70 70 NC-70

60 NC-6 60 NC-6
0 0

50 Hi NC-5
0 50 Hi NC-5
0

Me Me
40 NC-4
0
40 NC-4
0

30 NC-3
0
30 NC-3
0

20 Approximate NC- 20 Approximate NC-


Threshold of 20 Threshold of 20

Hearing for Lo Hearing for Lo


Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

147
Model: AVV-* Power Supply: 220-240V/50Hz,220V/60Hz Model: AVV-0* Power Supply: 220-240V/50Hz,220V/60Hz

Measurement Point: 1.0 Meters Beneath the Unit Measurement Point: 1.0 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve

80 80
Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)


70 NC-70 70 NC-70

60 NC-6 60 NC-6
0 0

Hi
50 Hi NC-5 50 NC-5
0 0

Me Me

40 NC-4
0 40 NC-4
0

30 NC-3
0 30 NC-3
0

Lo
20 Approximate Lo NC- 20 Approximate NC-
Threshold of 20 Threshold of 20
Hearing for Hearing for
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model: AVV-* Power Supply: 220-240V/50Hz,220V/60Hz Model: AVV-* Power Supply: 220-240V/50Hz,220V/60Hz
Measurement Point: 1.0 Meters Beneath the Unit Measurement Point: 1.0 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve

80 80
Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)

70 NC-70 70 NC-70

60 NC-6 60 NC-6
0 0
Hi
Hi

50 NC-5
0 50 NC-5
0
Me Me

40 NC-4
0 40 NC-4
0

30 NC-3
0
30 NC-3
0
Lo

Lo
20 Approximate NC- 20 Approximate NC-
Threshold of 20 Threshold of 20
Hearing for Hearing for
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

148
9.4 Component Data

Indoor Heat Exchanger and Fan

Model AVV-17* AVV-18* AVV-22* AVV-24*


Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0
Rows - 3 3 3 3
Fin Material Aluminum
Pitch mm 1.8 1.8 1.8 1.8
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15
Total Face Area m2 0.22 0.22 0.22 0.22
Number of Coil/Unit - 1 1 1 1
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 2 2 2 2
Outer Diameter mm 161 161 161 161
Revolution (220V) rpm 850/745/630 850/745/630 1035/910/800 1035/910/800
Nominal Air Flow m3/h 780/660/540 780/660/540 966/840/678 966/840/678
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - DC Driven
Nominal Output W 40 40 100 100
Quantity - 1 1 1 1
Insulation Class - E E E E

Indoor Heat Exchanger and Fan

Model AVV-27* AVV-30* AVV-38* AVV-48*


Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0
Rows - 3 3 3 3
Fin Material Aluminum
Pitch mm 1.8 1.8 1.8 1.8
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15
Total Face Area m2 0.30 0.30 0.30 0.39
Number of Coil/Unit - 1 1 1 1
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 3 3 3 4
Outer Diameter mm 161 161 161 161
Revolution (220V) rpm 920/790/660 980/835/720 1210/1010/835 1200/1045/890
Nominal Air Flow m /h
3
1092/912/732 1164/978/798 1488/1230/978 1980/1680/1380
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - DC Driven
Nominal Output W 140 140 140 181
Quantity - 1 1 1 1
Insulation Class - E E E E

149
9.5 Refrigeration Cycle

Indoor Unit

2
: Refrigerant Flow Direction (Cooling)
: Refrigerant Flow Direction (Heating)
: Field Refrigerant Piping
3 : Flare Connection

4
b

Refrigerant Liquid Pipe Connection


S

3 a

Refrigerant Gas Pipe Connection

Mark Part Name


1 Heat Exchanger
2 Distributor
3 Strainer
4 Micro-Computer Control Expansion Valve

150
9.6 Electrical Data

< 50 Hz >
Indoor Unit
Unit Main Power Applicable Voltage Indoor Fan Motor
Model
VOL PH HZ Maximum Minimum PH RNC IPT
AVV-17URSCA 0.18 0.04
AVV-18URSCA 0.18 0.04
AVV-22URSCA 0.32 0.07
Ceiling & AVV-24URSCA 0.32 0.07
220~240 1 50 264 198 1
Floor Type AVV-27URSCB 0.32 0.07
AVV-30URSCB 0.36 0.08
AVV-38URSCB 0.59 0.13
AVV-48URSCC 0.73 0.16

< 60 Hz >
Indoor Unit
Unit Main Power Applicable Voltage Indoor Fan Motor
Model
VOL PH HZ Maximum Minimum PH RNC IPT

AVV-17UR2SA 0.18 0.04


AVV-18UR2SA 0.18 0.04
AVV-22UR2SA 0.32 0.07
Ceiling & AVV-24UR2SA 0.32 0.07
220 1 60 242 198 1
Floor Type AVV-27UR2SB 0.32 0.07
AVV-30UR2SB 0.36 0.08
AVV-38UR2SB 0.59 0.13
AVV-48UR2SC 0.73 0.16

VOL: Rated Unit Power Supply Voltage (Plated)(V) RNC: Running Current (A)
PH: Phase (φ) IPT: Input (kW)
HZ: Frequency (Hz)

Safety and Control Device Setting


Indoor Unit

Model
AVV-17~48*

For Evaporator Fan


Motor Thermostat ℃ 130±5
Cut-Out
Cut-In ℃ 83±15
For Control Circuit
Fuse Capacity
A 5
Freeze Protection
Thermostat ℃ 0
Cut-Out
Cut-In ℃ 14

Thermostat
℃ 2
Differential

151
9.7 Electrical Wiring Diagram
Model: AVV-17~48*
HEAT PUMP

WARNING Before inspecting the electrical parts


PCB2
TB1 MIF set the Operation Switch to OFF,
L EFR1 DM PCN203 and cut OFF the power supply.
Z1 Noise ☆ Air Panel
N Filter
DCL Z2
DSA Supply Name
PCN201 Circuit
CN1~26,39~202
CN201 CN27~38
PCN202 CN202
C
* On y For DSW3,5
48K(5HP) CN38※ DCL
CN36
EF
MIF
PCB1 MS
MV
PCN7 PCN1 CN1 CN19 CN17
PCB1,2
CN11 Alarm
PCN1~203
RSW
H2 TB1,2
TF
YH2

PCB2 DCL Note :
TF
1.All the field wiring and equipment
PCB1 must comply with local codes.
TB2 TB1 2.※Optional,no impact on the performance
Receiver kit of air conditioning.

152
9.8 Indoor Unit Optional Parts

Optional Parts Applied Indoor Unit Type

Type Model Ceiling & Floor Type

HYXE-F01H ●
HYXE-G01H ●
Wire Remote Control Switch HYXE-A01H#01 ●
HYXE-J01H ●
HYXE-M01H ●
HYE-Q01 ●Standard Option
Wireless Remote Control Switch HYE-L01
HYE-W01 ●
HYRE-V01H
HYRE-T01H
Wireless Receiver Kit
HYRE-V02H
HYRE-X01H
7 Day Timer HYDE-E01H ●
HYJE-H01H ●
HYJE-D02H ●
HYJ-J01H ●
Centrol Station HCCS-H128H2C1YM ●
HCCS-H128H2C1NM
HCCS-H247R4C1E
HCCS-H128H2C2NM ●
HC-A64BNP ●
Interface for Building Control
HCPC-H2M1C ●
HCH-160D ●
Switch Box
HCH-280D ●
HZX-2.0AEC
HZX-4.0AEC
AHU Kits HZX-6.0AEC
HZX-10.0AEC
HZX-20.0AEC
HPS-162#E
Drain Pump HPS-132#E
HPS-151#E
HF-224L-FE
Long Life filter HF-280L-FE
HF-40L-ZFE
HP-DB-NK
3D Air Swing
HP-EB-NK

153
9.9 Factory-Supplied Accessories
#N,&19,'/&/1-1:*&%,&%0*&)*('.&+,9*)(;&3*8,)*
4'8%'.:&,)&-,9'.:&%0*&'./,,)&2.'%;&@2%&1&+4,%0&,. Fixing screw

%0*&)*('.&+,9*)(6 of side cover

kfflUWX^
mpno\
kfflUWX
mn[o
Inside of resin side cover
The three hooking parts and one hooking plate
should be mounted when recovering resin side cover

Fig. Removing the air inlet grille


and resin side cover

# Remove the fixing adhesive tape on the fan snail


shell and outer panel befor installation.The tape
is just used for fixing during transportation.

Fig. Side Covers

# Remove the air inlet grille and resin side cover


befor installation.

Remove the air inlet grille


(1) Open the air inlet grille after removing screw covers
and fixing screws as is shown in Fig. below.
(2) Remove fixing screws of air inlet grille .
(3) Carefully push the air inlet grille away from the.
mounting plate of indoor unit. Two tapes on
Each fan snail shell
(4) Remove the air inlet grille .

Remove the resin side cover Two tapes on


Each fan snail shell
(1) Remove fixing screw of side cover.

#N0*&-*+01.'(-&,8&%0*&12%,-1%'+&(I'.:&4,29*)
(2) Carefully push the side cover away from the
indoor unit approximately 10mm forward.
'(&2%'4'>*/6&&?,&.,%&-,9*&%0*&(I'.:&4,29*)&3C
(3) Remove the resin side cover .
01./&,)&,%0*)&,3S*+%(6&&N0'(&+1.&/1-1:*&%0*
-*+01.'(-&,8&%0*&12%,-1%'+&(I'.:&4,29*)6

Push Fixing screw


forward
of side cover
Fixing screws
Push forward
of air inlet grille

Removing the air inlet grille


and resin side cover

154
of Drain Pipe Connection

Drain Pipe Connection

Packing For Covering Clamp


(10T×38×165) of Drain Pipe Connection

Wireless Remote For Controlling the


Control Switch Unit

155
9.10 Installation
9.10.1 Initial Check
679 98778989  7 %$8"98 & 9 8
around the indoor unit with a proper clearance 8799 88 4
working space,as shown below. #79879 98778987  87&
abbc 897$ 88989
ceiling
99877894
'888979 9( 7
9"&87987789 7

Z[
7 & 78799" 
WXYZ[200 WXYZ[300 9 98 99877894
) & 997987998787979
877898879 87 89 9
88989 978 $
8 *87994
+%,#79879 9877899
9 798 $889&899
WXYZ[_]]

WXYZ[100
WXYZ[\]] 998 "(979"
979894
+-,679 987789 7779 
 98  9 9.9 9
9 798 $894
+,)  9"( 7879 99
For ceiling installation

WXYZ[200 WXYZ[300 798987894)  9789


9" 789979"87894
'7779978899"(
799"4
+#,679 788979&
89 784
' $8 7&8$ 98799 9
( 779879 98778987 7
8  877$87794
WXYZ[150

[
WXYZ[_]]

wall /012345641789:1450;54501479<=1:46>4=1?6@4A8
@A50A74BCD3EF2<DC44G501:@A814A54<;H42;981
WXYZ[\]]

I;7E1:48A59;5A674A>45014:1>:AE1:;754A74501
G95I66:4J7A54?1;384A75645014:66<4@01:1450A8
K7I66:4J7A54A84A785;??1IC
OP65;?4Q1>:AE1:;754R9;75A5H4S1:46714G95I66:4J7A5T
OU6?9<146>45014:66<4@01:1450A8 T VBCD3EF<
floor
WXYZ[150

D
K7I66:4J7A54A84A785;??1IC
For wall mounted installation K74I15;A?L4:1>1:45645014K785;??;5A674M;79;?4>6:
Fig. Operation and Maintenance Space 695I66:497A5C
or wall

 789 8898"987 987789


99 9 79 89"
9879 978 899879
 7""9874
#79879  " 9879$8
 9877894

156
9.10.2 Installtion ●
● Mounting of Suspension Bolts
Step1
Select final location and installation direction of
the indoor unit paying careful attention to the space
(The nut is unnecessary if the unit
for the piping,wiring and mantenance. is installed against the ceiling)
Step2
Mount suspension bolts,as shown in Fig.below.
*For Concrete Slab *For Steel Beam
ceiling or wall
UXV<HE<UYV@@ ;BL>FH
OUVV<HE<UXVZ[W

160

230
IEBCF>H>
JH>>G
ABCDEF<=EGH ;<=>?@ For ceiling installation
OPQRS<EF<TUVW
JKLM>BLNEB<=EGH
OPQRS<EF<TUVW
Fig. Mounting of Suspension Bolts
● Installation Pattern

is in the packing If expansible bolt used


deepen the bolt into
carton of indoor unit. concrete 50--60mm to
Use it to decide an installation location and prevent loose
direction of the unit. Keep distance
between bottom Install the unit
(2) Press the Pattern Board tightly onto the of the unit and floor against the wall
surface , draw out the hole position
for suspension bolts with a pencil. For wall mounted installation
Ceiling Pattern Board Wall Pattern Board

Wall the resin covers.


Floor

For ceiling installation For wall mounted installation

Fig. Pattern Board

9 i 
17-24 912 990

27-38 1207 1285

48 1502 1580

Air outlet side

15 7
(4) Adjusting of the Unit Level

For ceiling installation

(Min. 10mm)
Keep horizontal

The unit should be installed so that the drain View from front
piping connection side of the unit is slightly
Fig. Inclination of Unit for Drain
(Min. 10mm) lower than the other side ,in order
to avoid the incorrect position of the drain for wall mounted installation
dicharge.

(2)
(Min. 10mm)

completed.
< Lower

hN>f<F̀E@<_N[DH
(Min. 10mm)
<< Lower

drain piping
connection
side

hN>f<F̀E@<bFEBH
Fig. 6339 696: 369633
for ceiling installation

For wall mounted installation


The unit should be installed so that the bottom
of rear side inclines towards the wall slightly.
(Min. 10mm)
The unit should be installed horizontal viewed
from front.

<
Closer
(Min. 10mm)

hN>f<F̀E@<_N[DH

158
9.11 Refrigerant Piping Work 8H9+,-,./0C5:D0I2;JE25?0@,?4
Knock out
hole

68678968 5968678968 64


 86 6 66 6868
7!! "6 #9 $ 69 6
8678968 6%6 6878!9 6  6
68 98&964'6667 6 _V`Y aWbcWdY
86686!6# 68$ #  $6 piping piping

69 4(986!!6 #6#


!866#9898 6 88678968 "6
$6#78666764 Drain piping Drain Piping Connection
in drain pan

9.11.1 Piping Materials


8I9+,-,./0C5:D0K--450@,?4
809+54-25406:;266<=7>--6,4?0;:--450-,-47* Knock out

829@464;303A40-,-,./07,B40C5:D03A40C:66:E,./ hole

32F64*
Table Piping Size
aWbcWdY
DD08,.*9 piping
1:?46 Ž270+,-,./ ,>,?0+,-,./ _V`Y
0 17-18 ‡0)*ˆˆ 8)‰ˆ9 ‡Š*‹) 80‰Œ9 piping

22-30 ‡0)*ˆˆ 8)‰ˆ9 ‡*)‹ 8‹‰ˆ9


‡0)*ˆˆ 8)‰ˆ9 ‡*)‹ 8‹‰ˆ9
38-48
8L9+,-,./0C5:D0M,/A30@,?40L:N45
8‹9@464;30;642.0;:--450-,-47*0012J407>54 Knock out hole

3A4540,70.:0?>7302.?0D:,73>540,.7,?4*00I6:E
3A40,.7,?40:C03A40-,-470E,3A0.,35:/4.0:50?5<
2,5l03:054D:N402.<0?>730:50C:54,/.0D2345,267
F4C:540;:..4;3,./0-,-47* Right resin
side cover
Knock out
hole for drain piping
9.11.2 Piping Connection
809+:7,3,:.0:C0-,-,./0;:..4;3,:.0,707A:E.0,. 829+,-,./0E:5J07A:>6?0F40-45C:5D4?0C5:D03A4
Fig.
bottom side of the unit.Open the air inlet
_V`Y aWbcWdY grille and remove the resin side cover before
piping piping
the piping work.

P View
Drain Piping

Cut out the knock-out hole along the groove in the


Right Side Cover using saw blade to avoid sharp
edges if piping from right side.
Seal the clearance around pipes with seal material
to prevent ingress of dirt and protect wires from
damage by sharp edge after piping and wiring .

Air inlet grille


P View

Fig. Piping Connection of indoor Unit

159
9.12
(3)
below.

Flaring Dimension
Perform the flaring work as shown below.
+0
Diameter A -0.4
d R410A R407C
6.35 9.1 9.0
9.53 13.2 13.0
12.7 16.6 16.2
15.88 19.7 19.4
19.05 (*) 23.3

O>*(A,71/7'/(/.'*2,.&1(&+(/'7.1(?.?.13(2&11*2,.&1
(*)It is impossible to perform the flaring work with
.A('.3>,(A./*(7A(=.*C*/(+'&<(,>*(/.A2>7'3*(3'.99*A4
1/2H material. In this case, use an accessory
P&C*=*'J(.,(271(B*(?*'+&'<*/(+'&<(,>*(9*+,(A./*
pipe(with a flare).
C>*1(,>*(9*+,(A./*(2&11*2,.&1(.A('*Q:.'*/(/:*(,&
(4)
,>*(B:.9/.13(2&1A,':2,.&14
below. "0$%&'(;.3>,(-./*(0&11*2,.&1
(A ) Insert the Drain Pipe Connection into Drain
Boss with clamp until the connection reaches
the end of the drain pan.
(B ) Insert the Drain Hose and Drain Pipe with
clamps sequently until reaching the end.
"0$O.3>,*1(,>*(A2'*C(+&'(,>*(>&A*(297<?(.1
order to hold the hose around the drain
connection without any leakage of drain
water as shown below.
"6$Fclamp
1A:97,to*(,prevent
>*(/'7.1any
(>&Acondensation
*(7'&:1/(,>*(as>&A*
shown below.
Clamp of Drain
Pipe Connection

Drain Pipe

m`UWdn^Tlo Connection

Drain Hose cYT_XdZ`UU


m`UWdn^Tlo Thermal Insulation
for Clamp

jk t[kWU_hWd_UdX`dXWpWUUTYus
\XUW]Y^lT
TV_`^dX jkWYlT^d\XU]^TV_`X
c_YWpVdVkWdUpYWqd̀rdk`UW
p^Tlod]oqTY[dV̀doYWhWXV
VkWdUpYWqdrY`ldV̀]pk_Xb
VkWdr_^VWYs
cYT_Xda_oW t[kWU_hWd_UdX`dXWpWUUTYus
Bend Drain Pipe inside Side Cover
(5) For Side Cover Connection

Fig. Connecting Drain Piping

160
"#$%&'()*+,(-./*(0&11*2,.&1 /012344567849:;:<=;84:>8?849
cYT_XdZ`UU STXde]XXWY STXdg`V̀Y /@1>=5?;=5:;:?3ABC84BA:6DA3=8E5:/>F:GF:21
7HI5:J87D:;4:3H75=:E8;K575=:3L:0MKKF
(VP25)
cYT_Xda^]b /O1>;B:;77547834:73:7D5:?3P87834:3L:7D5:E=;84
?8?5F::Q55?:7D5:E3J4RPA3?5S:0TM2:73:0T
eWTYdf_[W 0NNF::<3:437:6=5;75:;4:H??5=:PA3?5:3=
=8P5:L3=:7D5:E=;84:?8?849F
/21U5;A:7D5:6344567849:?;=7:3L:7D5:E=;84
STUVWXWY ?8?5:IB:HP849:7D5:J;75=R?=33L:6DA3=8E5
ZTX[ 7B?5:P5;A849:K;75=8;AF
\a^
XU]]b^TV_`X /<1V=;?:7D5:84PHA;7834:K;75=8;A:;=3H4E:7D5
6344567849:?;=7:?5=L567ABF
cYT_Xda^]b /W1X;P754:7D5:E=;84:?8?5:73:7D5:6344567849
?;=7:J87D:7D5:L;673=BRPH??A85E:6A;K?F
hijklmnopq hi jklmnopq
rsttkjjiuvw
Fig. Drain Plug l
Clamp
rsttkjjiuvw r
st tkjjiuvw
Remove the drain plug of the left-side drain boss |}kuponl~zjno€yiz
xuoyzl{ijj rsttkj jiu
vw r‚yknƒ„qqnykw
as indicated in the following procedure
s}kjy†klyj
xuoyzl
hi jk „ktukliŠzŠou
zilzktkjjouv‹ jniqk‹
inv†yzvn
"D$0:,(,>*(+7A,*1*'4 m}niuyklyqk
rVP25
"E$;*<&=*(,>*(.1A:97,.&1(<7,*'.794 ‚yknƒ„qqnykw
"0$;*<&=*(,>*(/'7.1(?9:34 s
zil}zkkjtyk†kjjlyojuv‹
"6$F1A*',(,>*(/'7.1(?9:3(.1,&(,>*('.3>,@A./* rsttkjjiuvw
Drain Pipe Connection
|}kuponl~zjno€yiz
drain boss by using a driver as shown rsttkjjiuvw
below.

iX_Vdf_[W ~zjno€yiz
hijklmnopq
r‚ot€iuvƒ„qqnykw
cY_hWY cY
a^]Tb_Xd cYT_XdZ`UU Fig. Wrapping Insulation Material

/X1<3:437:6344567:7D5:E=;84:?8?5P:J87D
Fig. Inserting Drain Plug
P;487;=B:3=:P5J;95:3=:;4B:37D5=:E=;84;95
"I$D+,*'(.1A*',.13(,>*(/'7.1(?9:3(.1,&(,>* ?8?5F
'.3>,@A./*(/'7.1(B&AAJ(A*79(,>*(K&.1,*/(?7', /\1VD54:84P7;AA849:7D5:?8?5S:E3:437:785:7D5
BG(:A.13(7(C7,*'@?'&&+(2>9&'./*(,G?* E=;84:?8?5:;4E:=5L=895=;47:?8?5:73957D5=F
A*79.13(<7,*'.79(71/(A*2:'*(.,(C.,> /]1@L75=:63K?A57849:7D5:E=;84:?8?5:J3=^S
+7A,*1*'4 ?3H=:J;75=:8473:7D5:E=;84:?;4:;4E:6D56^
73:54PH=5:7D;7:J;75=:6;4:LA3J:PK337DABF
fWT^dgTVWY_T^

cYT_Xda^]b

Fig. Sealing Joint Part

"%$M'7?(,>*(.1A:97,.&1(<7,*'.79(7'&:1/(,>*
/'7.1(2&11*2,.&14
"N$0&11*2,(,>*(/'7.1(>&A*(,&(,>*(9*+,@A./*
/'7.1(2&11*2,.&1(7A(,>*(A7<*(7A(,>*
'.3>,(A./*(/'7.1(2&11*2,.&1(?'&2*/:'*4
Fig. Drain Piping

161
9.13 9.13.1

9.13.2

Fig below.

Hole for Power


Draw out the electrical Source
box cover toward the Hole for Transmission
arrow direction Wiring

Fig. Remove electrical box cover

162
The edge of electrical box cover should
be embeded in electrical box.
The edge should not cut Wired Remote Control Switch and Wireless Remote Control
wiring in electrical box.
Switch can not be used simultaneously .If Wired Remote
Electrical box cover
Control Switch is connected ,Disconnect Wireless Receiver
Wiring on the right side as viewed from the discharge grilles
(refrigerant piping connection side ).
Draw in the electrical
box cover toward the
arrow direction

Electrical box

Fig. Recover electrical box cover

Remove the right resin side cover and


DCL
Disconnect Wireless Receiver wiring
TF PCB2 (10-Pole Connector)

Fig. Disconnect Wireless Receiver wiring


PCB1
9.14

Cord clamp
for power
source
wires
Cord clamp
for transmission
wires
TB1

220-240V
50Hz
220V 60Hz

Fig.

Before electrical wiring work, turn OFF the power source.


If the connectors are connected without turning OFF the
power source, the auto-swing louver can not activate.

163
9.15
9.15.2
9.15.1

Use an ELB (Electric Leakage Breaker).If not


used ,it will cause an electric shock or a fire.
Run through the cables using conduit tube,
and Completely seal the end of conduit tube
with sealing materials.

5
Power MCA
Source EN60 335-1 *1 EN60 335-1 *1
17-18 0.75A
22-24 220-240V 1.00A
27 50Hz 1.00A 2.5mm 2 0.75mm2
30 220V 1.10A
38 60Hz 1.98A
48 2.25A

The wire sizes marked with *1 in the above table are selected
Ex.) Set at No.16 Unit
at the maximum current of the unit according to the European Set by inserting
Setting DSW6
Standard, EN60335-1.Use the wires which are not lighter than Position Slotted screwdriver
into the groove
the ordinary polyvinyl chloride sheathed flexible cord
(code designation H05VV-F).
Set No.1 Pin ON
3 Before shipment. DSW6 and RSW1 are set to "0".
RSW1
Max.64 units are available to set when all the equipment
to be connected are corresponding to Hi-net.
Max.16 units when the units corresponding/
non-corresponding to Hi-net are combined. Set at "6"

3 1.0~2.5
3 6 1.0~2.5
6 10 1.0~2.5 the indoor unit.
10 16 1.5~4.0
16 25 2.5~6.0
25 32 4.0~10.0
32 50 6.0~16.0
50 63 10.0~25.0
63 *2
2

164
Capacity
× 103 Btu/h 17 18 22 24 27 30

Capacity
48
outlet air angle
3
× 10 Btu/h 38

Ex.) Set at No.5 Cycle


Outlet air angle
Setting Set by inserting DSW5
Position Slotted screwdriver
into the groove

Set All Pins OFF


Before shipment. DSW5 and RSW2 are set to "0".
RSW2
Max.64 cycles are available to set when all the equipment
to be connected are corresponding to Hi-net.
Max.16 cycles when the units corresponding/
non-corresponding to Hi-net are combined. Set at "5"

9.17

9.17.1

9.16

Open the air inlet grille after removing screw


covers and fixing screws.

clips

16 5
screw covers Screw 9.18.1
and fixing screws

Pull screw cover

9.18.2

Pull screw 9.18.3


cover

Fig.9.17.2 Open the air inlet grille

.9.17.2

9.18.4

9.17.3

9.18

166
10. Wall Mounted Type
10.1 General Data
Indoor Unit Type Wall Mounted Type
Model AC 1 , 220-240V/50Hz AVS-07URCSAB(A/B) AVS-09URCSAB(A/B) AVS-12URCSAB(A/B) AVS-14URCSAB(A/B) AVS-17URCSAB(A/B)
Power Supply AC 1 , 220V/60Hz AVS-07UR2SAB(A/B) AVS-09UR2SAB(A/B) AVS-12UR2SAB(A/B) AVS-14UR2SAB(A/B) AVS-17UR2SAB(A/B)
Nominal Cooling kW 2.3 2.9 3.8 4.2 5.2
Capacity *1) kcal/h 2,000 2,500 3,300 3,600 4,500
Btu/h 7,800 9,900 13,300 14,400 17,700
Nominal Cooling kW 2.2 2.8 3.6 4.0 5.0
Capacity *2) kcal/h 1,900 2,400 3,100 3,400 4,300
Btu/h 7,500 9,600 12,300 13,700 17,100
Cooling Power Consumption
(50Hz/60Hz) kW 0.50/0.55 0.50/0.55 0.60/0.65 0.60/0.65 0.65/0.75
Nominal Heating kW 2.5 3.3 4.0 4.5 5.6
Capacity kcal/h 2,150 2,800 3,400 3,900 4,800
Btu/h 8,500 11,300 13,700 15,300 19,100

Heating Power Consumption 0.60/0.65 0.60/0.65 0.65/0.75


0.50/0.55 0.50/0.55
(50Hz/60Hz) kW
Sound Pressure Level
39-34-32-28 39-34-32-28 43-39-32-28 43-39-32-28 45-40-34-29
(Overall A Scale) dB
Cabinet Color — White
Outer Dimensions
Height mm 315 315 315 315 315
(in.) (12-2/5) (12-2/5) (12-2/5) (12-2/5) (12-2/5)
Width mm 960 960 960 960 960
(in.) (37-4/5) (37-4/5) (37-4/5) (37-4/5) (37-4/5)
Depth mm 230 230 230 230 230
(in.) (9) (9) (9) (9) (9)
Net Weight kg 13.5 13.5 13.5 13.5 13.5
(lbs.) (17) (17) (17) (17) (17)
Refrigerant — R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
660/590/520/460 660/590/520/460 830/660/520/460 830/660/520/460 900/750/590/460
Air Flow Rate m3/h
(388/347/306/271) (388/347/306/271) (488/388/306/271) (488/388/306/271) (529/441/347/271)
(Hi/Me/Lo) (cfm)

Connections Flare-Nut Connection (with Flare Nuts)


Refrigerant Piping
Liquid Line mm 6.35 6.35 6.35 6.35 6.35
(in.) (1/4) (1/4) (1/4) (1/4) (1/4)
Gas Line mm 12.7 12.7 12.7 12.7 12.7
(in.) (1/2) (1/2) (1/2) (1/2) (1/2)
Condensate Drain — VP16 VP16 VP16 VP16 VP16
Approximate
Packing Measurement m3 0.17 0.17 0.17 0.17 0.17
Standard Accessories — Wall Mounting Bracket

NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1 meter beneath the unit and 1 meter from inlet grille.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

167
Indoor Unit Type Wall Mounted Type
Model AC 1 , 220-240V/50Hz AVS-18URCSBB(A/B) AVS-22URCSBB(A/B) AVS-24URCSBB(A/B)
Power Supply AC 1 , 220V/60Hz AVS-18UR2SBB(A/B) AVS-22UR2SBB(A/B) AVS-24UR2SBB(A/B)
Nominal Cooling kW 5.8 6.5 7.3
Capacity *1) kcal/h 5,000 5,600 6,300
Btu/h 19,800 22,200 24,900
Nominal Cooling kW 5.6 6.3 7.1
Capacity *2) kcal/h 4,800 5,400 6,100
Btu/h 19,100 21,500 24,200
Cooling Power Consumption
(50Hz/60Hz) kW 0.54/0.65 0.62/0.74 0.72/0.83
Nominal Heating kW 6.3 7.1 8.0
Capacity kcal/h 5,400 6,100 6,900
Btu/h 21,500 24,200 27,300
Heating Power Consumption
(50Hz/60Hz) 0.62/0.75 0.72/0.83 0.82/0.91
kW
Sound Pressure Level
41-37-34-30 44-41-36-31 46-43-38-33
(Overall A Scale) dB
Cabinet Color — White
Outer Dimensions
Height mm 315 315 315
(in.) (12-2/5) (12-2/5) (12-2/5)
Width mm 1120 1120 1120
(in.) (44) (44) (44)
Depth mm 230 230 230
(in.) (9) (9) (9)
Net Weight kg 16.0 16.0 16.0
(lbs.) (20) (20) (20)
Refrigerant — R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
893/782/671/582 1006/893/716/621 1122/984/804/649
Air Flow Rate m3/h
525/460/395/342) (592/525/421/365) (660/579/473/382)
(Hi/Me/ Lo /SLo) (cfm)

Connections Flare-Nut Connection (with Flare Nuts)


Refrigerant Piping
Liquid Line mm 9.53 9.53 9.53
(in.) (3/8) (3/8) (3/8)
Gas Line mm 15.88 15.88 15.88
(in.) (5/8) (5/8) 5/8)
Condensate Drain — VP16 VP16 VP16
Approximate
Packing Measurement m3 0.19 0.19 0.19
Standard Accessories — Wall Mounting Bracket

NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1 meter beneath the unit and 1 meter from inlet grille.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

168
10.2 Dimensional Data
Models:AVS-07~17*

Unit: mm

169
Models:AVS-18~24* Unit: mm

170
10.3 Selection Data
● Service Space
Models:AVS-07~24*

150 (unit:mm)

100 100

1000
Operation and Maintenance Space

● Sensible Heat Factor (SHF)


The sensible heat factor of indoor units at each fan speed (Hi, Me, Lo) is given in the below.

SHF
Indoor Unit Model
Hi Me Lo
AVS-07* 0.78 0.74 0.71
AVS-09* 0.78 0.74 0.71
AVS-12* 0.73 0.72 0.70
AVS-14* 0.73 0.72 0.70
AVS-17* 0.69 0.68 0.67
AVS-18* 0.69 0.68 0.67
AVS-22* 0.71 0.69 0.68
AVS-24* 0.73 0.71 0.69

171
● Sound Data
Model: AVS-07* Power Supply: 220~240V/50Hz,220V/60Hz Model: AVS-09* Power Supply: 220~240V/50Hz,220V/60Hz
Measurement Point: 1 Meter Beneath the Unit and Measurement Point: 1 Meter Beneath the Unit and
1 Meter From Discharge Grille 1 Meter From Discharge Grille
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)


Hi Hi

Me Me

Lo Lo

Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise SLo Continuous Noise SLo

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model: AVS-12* Power Supply: 220~240V/50Hz,220V/60Hz Model: AVS-14* Power Supply: 220~240V/50Hz,220V/60Hz
Measurement Point: 1 Meter Beneath the Unit and Measurement Point: 1 Meter Beneath the Unit and
1 Meter From Discharge Grille 1 Meter From Discharge Grille
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)

Hi Hi

Me Me

Lo Lo

Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise SLo Continuous Noise SLo

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

172
Model: AVS-17* Power Supply: 220~240V/50Hz,220V/60Hz Model: AVS-18* Power Supply: 220~240V/50Hz,220V/60Hz
Measurement Point: 1 Meter Beneath the Unit and Measurement Point: 1 Meter Beneath the Unit and
1 Meter From Discharge Grille 1 Meter From Discharge Grille
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)


Hi

Me
Hi

Me

Lo
Lo

Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise SLo
SLo

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model: AVS-22* Power Supply: 220~240V/50Hz,220V/60Hz Model: AVS-24* Power Supply: 220~240V/50Hz,220V/60Hz
Measurement Point: 1 Meter Beneath the Unit and Measurement Point: 1 Meter Beneath the Unit and
1 Meter From Discharge Grille 1 Meter From Discharge Grille
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)

Hi

Hi
Me
Me

Lo

Lo

Approximate SLo Approximate SLo


Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

173
10.4 Component Data

Indoor Heat Exchanger and Fan


Model AVS-07UR*BA(B) AVS-09UR*BA(B) AVS-12UR*BA(B) AVS-14UR*BA(B) AVS-17UR*BA(B)
Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0 7.0
Rows - 2 2 2 2 2
Fin Material Aluminum
Pitch mm 1.65 1.65 1.65 1.65 1.65
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15 4.15
Total Face Area m2 0.24 0.24 0.24 0.24 0.24
Number of Coil/Unit - 1 1 1 1 1
Indoor Fan Tubular Fan
Number/Unit - 1 1 1 1 1
Outer Diameter mm 107 107 107 107 107
Revolution (220V) rpm 1000/900/800/700 1000/900/800/700 1160/1000/800/700 1160/1000/800/700 1240/1060/900/700
Nominal Air Flow m3/h 660/590/520/460 660/590/520/460 830/660/520/460 830/660/520/460 900/750/590/460
Indoor Fan Motor Drip-Proof Type Enclosure PSC
-
Starting Method (Permanent Split Capacitor)
Nominal Output W 35 35 35 35 35
Quantity 1 1 1 1 1
Insulation Class
- E E E E E

Indoor Heat Exchanger and Fan

Model AVS--18URC* AVS--22URC* AVS--24URC*


Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0
Rows - 2 2 2
Fin Material Aluminum
Pitch mm 1.65 1.65 1.65
Maximum Operating Pressure MPa 4.15 4.15 4.15
Total Face Area m2 0.33 0.33 0.33
Number of Coil/Unit - 1 1 1
Indoor Fan Tubular Fan
Number/Unit - 1 1 1
Outer Diameter mm 100 100 100
Revolution (220V) rpm 1000/910/820/750 1100/1000/840/750 1200/1080/920/780
Nominal Air Flow m /h3
893/782/671/582 1006/893/716/621 1122/984/804/649
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - PSC (Permanent Split Capacitor)
Nominal Output W 50 50 50
Quantity - 1 1 1
Insulation Class - E E E

174
Indoor Heat Exchanger and Fan

Model AVS--18UR2* AVS--22UR2* AVS--24UR2*


Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0
Rows - 2 2 2
Fin Material Aluminum
Pitch mm 1.65 1.65 1.65
Maximum Operating Pressure MPa 4.15 4.15 4.15
Total Face Area m2 0.33 0.33 0.33
Number of Coil/Unit - 1 1 1
Indoor Fan Tubular Fan
Number/Unit - 1 1 1
Outer Diameter mm 100 100 100
Revolution (220V) rpm 1000/910/820/750 1100/1000/840/750 1200/1080/920/780
Nominal Air Flow m /h
3
893/782/671/582 1006/893/716/621 1122/984/804/649
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - PSC (Permanent Split Capacitor)
Nominal Output W 50 50 50
Quantity - 1 1 1
Insulation Class - E E E

Indoor Heat Exchanger and Fan

175
10.5 Refrigeration Cycle

Indoor Unit

2
: Refrigerant Flow Direction (Cooling)
: Refrigerant Flow Direction (Heating)
: Field Refrigerant Piping
3 : Flare Connection

4 b

Refrigerant Liquid Pipe Connection


S

3 a

Refrigerant Gas Pipe Connection

Mark Part Name


1 Heat Exchanger
2 Distributor
3 Strainer
4 Micro-Computer Control Expansion Valve

176
10.6 Electrical Data

< 50 Hz >
Indoor Unit

Unit Main Power Applicable Voltage Indoor Fan Motor


Model
VOL PH HZ Maximum Minimum PH RNC IPT
AVS-07URCSAB(A/B) 0.4 0.05
Wall Mounted
AVS-09URCSAB(A/B) 0.4 0.05
Type
AVS-12URCSAB(A/B) 0.45 0.06
AVS-14URCSAB(A/B) 0.45 0.06
220~240 1 50 264 198 1
AVS-17URCSAB(A/B) 0.5 0.065
AVS-18URCSBB(A/B) 0.41 0.062
AVS-22URCSBB(A/B) 0.41 0.072
AVS-24URCSBB(A/B) 0.41 0.082

< 60 Hz >
Indoor Unit
Unit Main Power Applicable Voltage Indoor Fan Motor
Model
VOL PH HZ Maximum Minimum PH RNC IPT
AVS-07UR2SAB(A/B) 0.4 0.05
Wall Mounted
AVS-09UR2SAB(A/B) 0.4 0.05
Type
AVS-12UR2SAB(A/B) 0.45 0.06
AVS-14UR2SAB(A/B) 0.45 0.06
220 1 60 264 198 1
AVS-17UR2SAB(A/B) 0.5 0.065
AVS-18UR2SBB(A/B) 0.41 0.062
AVS-22UR2SBB(A/B) 0.41 0.072
AVS-24UR2SBB(A/B) 0.41 0.082

VOL: Rated Unit Power Supply Voltage (Plated)(V) RNC: Running Current (A)
PH: Phase (φ) IPT: Input (kW)
HZ: Frequency (Hz)

Safety and Control Device Setting

Model AVS-07~24*

For Evaporator Fan


Motor Thermostat ℃ 130±5
Cut-Out
Cut-In ℃ 83±15
For Control Circuit
Fuse Capacity A 5
Freeze Protection
Thermostat ℃ 0
Cut-Out
Cut-In ℃ 14

Thermostat
℃ 2
Differential

177
10.7 Electrical Wiring Diagram
Model: AVS-09~24*

178
10.8 Indoor Unit Optional Parts
Optional Parts Applied Indoor Unit Type

Type Model Wall Mounted Type

HYXE-F01H ●
HYXE-G01H ●
Wire Remote Control Switch HYXE-A01H#01 ●
HYXE-J01H ●
HYXE-M01H ●
HYE-Q01
Wireless Remote Control Switch HYE-L01 ●Standard Option
HYE-W01 ●
HYRE-V01H
HYRE-T01H
Wireless Receiver Kit
HYRE-V02H
HYRE-X01H
7 Day Timer HYDE-E01H ●
HYJE-H01H ●
HYJE-D02H ●
HYJ-J01H ●
Centrol Station HCCS-H128H2C1YM ●
HCCS-H128H2C1NM
HCCS-H247R4C1E
HCCS-H128H2C2NM ●
HC-A64BNP ●
Interface for Building Control
HCPC-H2M1C ●
HCH-160D ●
Switch Box
HCH-280D ●
HZX-2.0AEC
HZX-4.0AEC
AHU Kits HZX-6.0AEC
HZX-10.0AEC
HZX-20.0AEC
HPS-162#E
Drain Pump HPS-132#E
HPS-151#E
HF-224L-FE
Long Life filter HF-280L-FE
HF-40L-ZFE
HP-DB-NK
3D Air Swing
HP-EB-NK

179
10.9

10.10 Installation
10.10.1

180
10.10.2

below.

181
182
10.10.3 10.10.4

183
10.11

10.11.1
10.10

184
10.11.2

below.

185
10.12
below.

below.

below.

186
10.13

187
10.13.1

10.13.2

Wiring Connection).

188
10.15
10.15.1

10.14

220V~60Hz

189
3 1.0~2.5
3 6 1.0~2.5
6 10 1.0~2.5
10 16 1.5~4.0
16 25 2.5~6.0
25 32 4.0~10.0
32 50 6.0~16.0
50 63 10.0~25.0
63 *2
2

10.15.2

190
10.15.3

191
10.15.4

192
193
10.16 10.17

194
10.18 10.19

10.18.1

10.19.1

10.19.2

10.19.3

10.18.2
10.19.4

10.18.3

195
11. Floor Concealed Type(AVH)
11.1 General Data
Indoor Unit Type Floor Concealed Type
Model AC 1 , 220-240V/50Hz AVH-09UXCSAA AVH-14UXCSAA AVH-18UXCSBA AVH-24UXCSBA
Power Supply AC 1 , 220V/60Hz AVH-09UX2SAA AVH-14UX2SAA AVH-18UX2SBA AVH-24UX2SBA
Nominal Cooling kW 2.9 4.1 5.8 7.3
Capacity *1) kcal/h 2,500 3,500 5,000 6,300
Btu/h 9,900 14,000 19,800 24,900
Nominal Cooling kW 2.8 4.3 5.6 7.1
Capacity *2) kcal/h 2,400 3,700 4,800 6,100
Btu/h 9,600 14,700 19,100 24,200

Cooling Power Consumption kW 0.05 0.08 0.09 0.12


Nominal Heating kW 3.3 4.9 6.5 8.5
Capacity kcal/h 2,800 4,200 5,600 7,300
Btu/h 11,300 16,700 22,200 29,000

Heating Power Consumption kW 0.05 0.08 0.09 0.12


Sound Pressure Level
(Overall A Scale) dB 34-31-27 40-36-34 41-36-32 44-40-36
Cabinet Color — --
Outer Dimensions
Height mm 620 620 620 620
(in.) (24-7/16) (24-7/16) (24-7/16) (24-7/16)
Width mm 900 900 1170 1170
(in.) (35-2/5) (35-2/5) (46) (46)
Depth mm 202 202 202 202
(in.) (8) (8) (8) (8)
Net Weight kg 18 22 26 27
(lbs.) (40) (48) (57) (59)
Refrigerant — R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 510/450/380 620/540/480 890/740/630 980/830/710
(Hi/Me/Lo) (cfm) (300/265/223) (365/318/282) (523/435/370) (576/488/417)

Connections Flare-Nut Connection (with Flare Nuts)


Refrigerant Piping
Liquid Line mm 6.35 6.35 6.35 9.53
(in.) (1/4) (1/4) (1/4) (3/8)
Gas Line mm 12.7 12.7 15.88 15.88
(in.) (1/2) (1/2) (5/8) (5/8)
Condensate Drain — VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.19 0.19 0.23 0.23
NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1 meter beneath the unit and 1 meter from inlet grille.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

196
11.2 Dimensional Data
Models: AVH-09~24*

Refrigerant Gas Line


09 and 14 Model: φ 12.7 with Flare Nut
18 and 24 Model: φ 15.88 with Flare Nut

Air Outlet Refrigerant Liquid Line


09 and 18 Model: φ 6.35 with Flare Nut
24 Model: φ 9.53 with Flare Nut

202
a
168

61 72 109
b
Connection Flange 113
c
33
619

397
394
258
157

Fan Motor
Fan
Return Air Inlet
25 d 39 120

99

99
194
120

e f
b b

Fixing Hole on Floor

Screw Hole (2-M10)

(4-M6)

Unit
Dimension
Model
AVH-09*
AVH-14*
AVH-18*
AVH-24*

197
11.3 Selection Data
● Service Space
Models: AVH-09~24*

Ceiling Ceiling

Upward Air Outlet


Short

1000
Front Air Outlet

Min.
Flexible Duct

620
640
Floor Floor
Min. Min. Min. Min.
240 240 240 240

Service Space
● Sensible Heat Factor (SHF)
The sensible heat factor of indoor units at each fan speed (Hi, Me, Lo) is given in the below.

SHF
Indoor Unit Model
Hi Me Lo
AVH-09* 0.81 0.69 0.68
AVH-14* 0.75 0.71 0.67
AVH-18* 0.70 0.70 0.67
AVH-24* 0.68 0.68 0.66

198
● Sound Data

Model: AVH-09* Power Supply: 220~240V/50Hz,220V/60Hz Model: AVH-14* Power Supply: 220~240V/50Hz,220V/60Hz
Measurement Point: 1.5 Meter from the Unit Measurement Point: 1.5 Meter from the Unit
1.5 Meter from Floor Level 1.5 Meter from Floor Level
Noise Criteria Curve Noise Criteria Curve

80 80
Octave Sound Pressure Level (dB: Overall C Scale)

Octave Sound Pressure Level (dB: Overall C Scale)


70 70

60
60

50 50

40 40

30 30

20 20
Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)

Model: AVH-18* Power Supply: 220~240V/50Hz,220V/60Hz Model: AVH-24* Power Supply: 220~240V/50Hz,220V/60Hz
Measurement Point: 1.5 Meter from the Unit Measurement Point: 1.5 Meter from the Unit
1.5 Meter from Floor Level 1.5 Meter from Floor Level
Noise Criteria Curve Noise Criteria Curve

80 80
Octave Sound Pressure Level (dB: Overall C Scale)

Octave Sound Pressure Level (dB: Overall C Scale)

70 70

60
60

50 50

40 40

30 30

20 20
Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)

199
11.4 Component Data
Indoor Heat Exchanger and Fan

Model AVH--09* AVH--14* AVH--18* AVH--24*


Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0
Rows - 2 3 3 3
Fin Material Aluminum
Pitch mm 1.8 1.8 1.8 1.8
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15
Total Face Area m2 0.13 0.13 0.18 0.18
Number of Coil/Unit - 1 1 1 1
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 1 1 1 1
Outer Diameter mm 130 130 130 130
Revolution (220V) rpm 475/420/340 585/485/440 630/515/450 640/525/460
Nominal Air Flow m /h
3
1560/1380/1200 1920/1680/1440 2040/1740/1500 2220/1920/1620
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - PSC (Permanent Split Capacitor)
Nominal Output W 20 35 40 50
Quantity - 1 1 1 1
Insulation Class - B B B B

200
11.5 Refrigeration Cycle

Floor Concealed Type

Indoor Unit

2
: Refrigerant Flow Direction (Cooling)
: Refrigerant Flow Direction (Heating)
: Field Refrigerant Piping
3 : Flare Connection

4
b

Refrigerant Liquid Pipe Connection


S

3 a

Refrigerant Gas Pipe Connection

Mark Part Name


1 Heat Exchanger
2 Distributor
3 Strainer
4 Micro-Computer Control Expansion Valve

201
11.6 Electrical Data
< 50 Hz >
Indoor Unit
Unit Main Power Applicable Voltage Indoor Fan Motor
Model
VOL PH HZ Maximum Minimum PH RNC IPT
AVH-09UXCSAA 0.25 0.05
Floor
AVH-14UXCSAA 0.40 0.08
Concealed 220~240 1 50 264 198 1
AVH-18UXCSBA 0.43 0.09
Type
AVH-24UXCSBA 0.55 0.12

< 60 Hz >
Indoor Unit
Unit Main Power Applicable Voltage Indoor Fan Motor
Model
VOL PH HZ Maximum Minimum PH RNC IPT
AVH-09UX2SAA 0.25 0.05
Floor AVH-14UX2SAA 0.40 0.08
220 1 60 242 198 1
Concealed Type AVH-18UX2SBA 0.43 0.09
AVH-24UX2SBA 0.55 0.11

VOL: Rated Unit Power Supply Voltage (Plated)(V) RNC: Running Current (A)
PH: Phase (φ) IPT: Input (kW)
HZ: Frequency (Hz)

09~24

202
Model: AVH-09~24*
11.7 Electrical Wiring Diagram

203
11.8 Indoor Unit Optional Parts

Optional Parts Applied Indoor Unit Type

Type Model Floor Concealed Type

HYXE-F01H ●
HYXE-G01H ●
Wire Remote Control Switch HYXE-A01H#01 ●
HYXE-J01H ●
HYXE-M01H ●
HYE-Q01 ●
Wireless Remote Control Switch HYE-L01 ●
HYE-W01 ●
HYRE-V01H ●
HYRE-T01H
Wireless Receiver Kit
HYRE-V02H
HYRE-X01H
7 Day Timer HYDE-E01H ●
HYJE-H01H ●
HYJE-D02H ●
HYJ-J01H ●
Centrol Station HCCS-H128H2C1YM ●
HCCS-H128H2C1NM
HCCS-H247R4C1E
HCCS-H128H2C2NM ●
HC-A64BNP ●
Interface for Building Control
HCPC-H2M1C ●
HCH-160D ●
Switch Box
HCH-280D ●
HZX-2.0AEC
HZX-4.0AEC
AHU Kits HZX-6.0AEC
HZX-10.0AEC
HZX-20.0AEC
HPS-162#E
Drain Pump HPS-132#E
HPS-151#E
HF-224L-FE
Long Life filter HF-280L-FE
HF-40L-ZFE
HP-DB-NK
3D Air Swing
HP-EB-NK

204
11.9

205
11.11
11.10 Installation Check
11.11.1

Ceiling

Outlet

At least 1000
619
At least 250 At least 250

Wall

At least 800
At least 50 (Maintenance space)

Size

09~14

18~24

Fig. Suspension Bolts

206
11.11.2 Hanging the IndoorUnit 11.11.3 Connecting Supply Duct
Prevent the subversion of the machine. The supply duct should be inserted onto the root of
The method for ground installation is shown below. the unit outlet. Thermal insulation should be done
Fix the unit with bolt in the specified location as and the junction with the unit should be sealed
shown below. with aluminum foil tape.
Insulation materials should be attached all around
the outlet preventing the condensation, when there
is no duct connected.
Bolt adjustment hole Anchor bolt fixed position Duct

Insulation materials
Tape Outlet

Size Insulation materials Outlet


Attached all around
09~14 (At least 10mm)

18~24

11.12

Nut
Anchor M10
Washer 1 A
Concrete
Filling Motar

Fig. Installation Method

11.12.1

207
11.12.2
below.

202
168
72 109 58

113 50
33

Gas pipe
Liquid pipe
394

Water tray
397
258

below.

09~14

18

24

Flaring Dimension
Perform the flaring work as shown below.

ΦD
Φa
R 410A R 407C
6.35 9.1 9.0
9.53 13.2 13.0
12.7 16.6 16.2
15.88 19.7 19.4
19.05 (* ) 23.3

installation
(*)It is impossible to perform the flaring work with
1/2H material. In this case, use an accessory
pipe(with a flare).

208
11.13

below.

11.14

209
11.14.1

11.14.2

below.
As below
220-240V~ 50Hz
220V~60Hz

11.15

210
3 1.0~2.5
3 6 1.0~2.5
6 10 1.0~2.5
10 16 1.5~4.0
16 25 2.5~6.0
25 32 4.0~10.0
32 50 6.0~16.0
50 63 10.0~25.0
63 *2
2

11.16.2

11.16
11.16.1

Use an ELB (Electric Leakage Breaker).If not


used ,it will cause an electric shock or a fire.
Run through the cables using conduit tube,
and Completely seal the end of conduit tube
with sealing materials.
5

Model MCA EN 60335-1 EN 60335-1


1 1
a
09 0.46A

14 0.56A
2.5 0.75
18 0.70A

24 0.83A Ex.) Set at No.16 Unit


Setting Set by inserting DSW6
Position Slotted screwdriver
into the groove

Set No.1 Pin ON


Before shipment. DSW6 and RSW1 are set to "0".
The wire sizes marked with *1 in the above table are selected Max.64 units are available to set when all the equipment
RSW1
at the maximum current of the unit according to the European to be connected are corresponding to Hi-NET.
Standard, EN 60335-1.Use the wires which are not lighter than Max.16 units when the units corresponding/
non-corresponding to Hi-NET are combined. Set at "6"
the ordinary polyvinyl chloride sheathed flexible cord
(code designation H05VV-F).
3

211
Capacity 09 14 18 24

11.16.3 FILTER SIGN RESET

Ex.) Set at No.5 Cycle


Setting Set by inserting DSW5
Position Slotted screwdriver
into the groove

Set All Pins OFF


Before shipment. DSW5 and RSW2 are set to "0".
RSW2
Max.64 cycles are available to set when all the equipment
to be connected are corresponding to Hi-NET.
Max.16 cycles when the units corresponding/
non-corresponding to Hi-NET are combined. Set at "5"

11.17 Troubleshooting

11.17.1

212
11.17.2

11.17.3

11.17.4

213
12. All Fresh Air Indoor Unit(AVA)
12.1 General Data
Indoor Unit Type All Fresh Air Indoor Unit
Model AC 1 , 220-240V/50Hz AVA-30UXCSCH-70 AVA-48UXCSQH-108 AVA-76UXCSRH-168 AVA-96UXCSRH-210
Power Supply AC 1 , 220V/60Hz AVA-30UX2SCH-70 AVA-48UX2SQH-108 AVA-76UX2SRH-168 AVA-96UX2SRH-210
Nominal Cooling kW 9.0 14.0 22.4 28.0
Capacity kcal/h 7,700 12,000 19,300 24,100
Btu/h 30,700 47,800 76,500 95,600

Cooling Power Consumption kW 0.15 0.33 0.49 0.51


Nominal Heating kW 8.6 13.7 21.9 24.5
Capacity kcal/h 7,400 11,800 18,800 21,100
Btu/h 29,400 46,800 74,700 83,600

Heating Power Consumption kW 0.15 0.33 0.49 0.51


Sound Pressure Level
(Overall A Scale) dB 32 43 45 46
Outer Dimensions
Height mm 370 370 486 486
(in.) (14-1/2) (14-1/2) (19-1/7) (19-1/7)
Width mm 920 1,320 1,270 1,270
(in.) (36-1/5) (52) (50) (50)
Depth mm 800 800 1,069 1,069
(in.) (31-1/2) (31-1/2) (42) (42)
Net Weight kg 46 60 97 97
(lbs.) (101) (132) (213) (213)
Refrigerant — R410A(Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 660 1080 1680 2100
(Hi/Me/Lo) (cfm) (388) (635) (988) (1235)
External Pressure Pa 60(120) 200 220 220

Connections Flare-Nut Connection (with Flare Nuts) Brazing


Refrigerant Piping
Liquid Line mm Φ9.53 Φ9.53 Φ9.53 Φ9.53
(in.) (3/8) (3/8) (3/8) (3/8)
Gas Line mm Φ15.88 Φ15.88 Φ19.05 Φ22.2
(in.) (5/8) (5/8) (3/4) (7/8)
Condensate Drain — VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.38 0.52 1.09 1.09
NOTES:
1. The nominal cooling capacity and heating capacity are based on following conditions:
Cooling Operation Conditions
Outdoor Air Inlet Temperature: 33oC DB 28oC WB
Heating Operation Conditions
Outdoor Air Inlet Temperature: 0 oC DB -2.9oC WB
Piping Length: 7.5 Meters Piping Lift: 0 Meter
(Heating capacity is tested when defrosting is not available)
2. The sound pressure level is based on following conditions.
1.5 Meter Beneath the Unit.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3. An air filter with dust collection efficiency more than 50% needs to be attached to the duct system of the suction side at site.
4. When the resistance of the field-supplied duct is small, it may cause abnormal stoppage, malfunction, spraying water, etc. due to excessive air flow.
And the duct, which is to be connected to this unit, shall be insulated for dew protection.
5. All fresh air indoor unit is for processing fresh air load and not for stabilizing the room temperaure. For adjusting the air conditioning load of the room,
the additional air conditioner is required.
6. This unit shall be connected to Hi-Flexi outdoor unit. In case of connecting this unit with other indoor units in the same refrigerant cycle, calculate the
capacity of this unit as 13.5kW(3HP), 21.0kW(5HP), 33.6kW(8HP), 42.0kW(10HP).
7. When outdoor unit is connected only with all fresh air indoor unit, the configuration rate is 100%.
8. Under cooling mode, when outdoor temperature is lower than 20 ℃, the system will automatically shift to ventilation operation;
Under heating mode, when outdoor temperature is higher than 15℃, the system will automatically shift to ventilation operation;
In case inlet temperature is below -5℃, All Fresh Air Indoor Unit will stop.

214
Indoor Unit Type All Fresh Air Indoor Unit
Model AC 3 , 380-415V/50Hz AVA-114UX6SRH-300 AVA-154UX6SSH-400 AVA-190UX6STH-500 AVA-190UX6STH-600
Power Supply AC 3 , 380V/60Hz AVA-114UX7SRH-300 AVA-154UX7SSH-400 AVA-190UX7STH-500 AVA-190UX7STH-600
Nominal Cooling kW 33.5 45.0 56.0 56.0
Capacity kcal/h 28,800 38,700 48,200 48,200
Btu/h 114,300 153,600 191,100 191,100

Cooling Power Consumption kW 0.74 1.12 1.33 1.62


Nominal Heating kW 26.8 36.0 44.8 44.8
Capacity kcal/h 23,000 31,000 38,500 38,500
Btu/h 91,500 122,900 152,900 152,900

Heating Power Consumption kW 0.74 1.12 1.33 1.62


Sound Pressure Level
(Overall A Scale) dB 56 61 64 66
Outer Dimensions
Height mm 486 635 735 735
(in.) (19-1/7) (25) (29) (29)
Width mm 1,270 1,950 1,950 1,950
(in.) (50) (76-4/5) (76-4/5) (76-4/5)
Depth mm 1,069 805 805 805
(in.) (42) (31-7/10) (31-7/10) (31-7/10)
Net Weight kg 97 196 222 222
(lbs.) (213) (431) (488) (488)
Refrigerant — R410A(Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 3000 4000 5000 6000
(Hi/Me/Lo) (cfm) (1764) (635) (2940) (3528)
External Pressure Pa 220 300 300 300

Connections Brazing
Refrigerant Piping
Liquid Line mm Φ12.7 Φ12.7 Φ15.88 Φ15.88
(in.) (1/2) (1/2) (5/8) (5/8)
Gas Line mm Φ25.4 Φ25.4 Φ28.6 Φ28.6
(in.) (1) (1) (1-1/8) (1-1/8)
Condensate Drain — VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 1.09 1.84 2.06 2.06
NOTES:
1. The nominal cooling capacity and heating capacity are based on following conditions:
Cooling Operation Conditions
Outdoor Air Inlet Temperature: 33oC DB 28oC WB
Heating Operation Conditions
Outdoor Air Inlet Temperature: 0 oC DB -2.9oC WB
Piping Length: 7.5 Meters Piping Lift: 0 Meter
(Heating capacity is tested when defrosting is not available)
2. The sound pressure level is based on following conditions.
1.5 Meter Beneath the Unit.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3. An air filter with dust collection efficiency more than 50% needs to be attached to the duct system of the suction side at site.
4. When the resistance of the field-supplied duct is small, it may cause abnormal stoppage, malfunction, spraying water, etc. due to excessive air flow.
And the duct, which is to be connected to this unit, shall be insulated for dew protection.
5. All fresh air indoor unit is for processing fresh air load and not for stabilizing the room temperaure. For adjusting the air conditioning load of the room,
the additional air conditioner is required.
6. All fresh air indoor unit (12HP~20HP) only can be connected with Hi-Flexi outdoor unit one to one.
7. Under cooling mode, when outdoor temperature is lower than 20 ℃, the system will automatically shift to ventilation operation;
Under heating mode, when outdoor temperature is higher than 15℃, the system will automatically shift to ventilation operation;
In case inlet temperature is below -5℃, All Fresh Air Indoor Unit will stop.

215
12.2 Dimensional Data
Models: AVA-30~48*

1320(920)
1380(980)

1203(803) 1233(833)

NOTE: Data in bracket is for Model: AVA-30*

Models: AVA-76~114*

216
Models: AVA-154~190*

AVA-154
AVA-190

217
12.3 Selection Data
● Service Space
Models: AVA-30~190*

● Sensible Heat Factor (SHF)


The sensible heat factor of indoor units at each fan speed (Hi, Me, Lo) is given in the below.

SHF
Indoor Unit Model
Hi Me Lo
AVA-30* 0.43 ─ ─
AVA-48* 0.42 ─ ─
AVA-76* 0.41 ─ ─
AVA-96* 0.40 ─ ─
AVA-114* 0.40 ─ ─
AVA-154* 0.42 ─ ─
AVA-190*-500 0.41 ─ ─
AVA-190*-600 0.41 ─ ─

218
● Fan Performance

AVA-30UXCSCH-70(60Pa)

100

80

60

40

20
585 693.6 844.3

AVA-30UXCSCH-70(120Pa)

160

140

120

100

80
518 656.4 771

AVA-48UXCSQH-108

219
AVA-76UXCSRH-168

AVA-96UXCSRH-210

AVA-114UX6SRH-300

220
AVA-154UX6SSH-400

AVA-190UX6STH-500

AVA-190UX6STH-600

221
● Sound Data

Model: AVA-30* Power Supply: 220~240V/50Hz,220V~60Hz Model:AVA-48* Power Supply: 220~240V/50Hz,220V~60Hz


Measurement Point: 1.5 Meters Beneath the Unit

Noise Criteria Curve Noise Criteria Curve


Octave Sound Pressure Level(dB: Overall C Scale)

Approximate
Threshold of
Hearing for
Continuous Noise

Central Frequency(Cycle per Second)

Model:AVA-76* Power Supply: 220~240V/50Hz,220V~60Hz Model:AVA-96* Power Supply: 220~240V/50Hz,220V~60Hz

222
Model: AVA-114* Power Supply: 380V~415V 380V~60Hz Model: AVA-154* Power Supply: 380V~415V 380V~60Hz

Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)


Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model: AVA-190-500* Power Supply: 380V~415V 380V~60Hz


Model: AVA-190-600* Power Supply: 380V~415V 380V~60Hz

Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)

Approximate
Threshold of Approximate
Hearing for Threshold of
Continuous Noise Hearing for
Continuous Noise

Central Frequency(Cycle per Second)


Central Frequency(Cycle per Second)

223
12.4 Component Data
Indoor Heat Exchanger and Fan

Model AVA-30* AVA-48* AVA-76* AVA-96*


Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 9.53 9.53
Rows - 2 3 3 3
Fin Material Aluminum
Pitch mm 1.8 1.8 1.8 1.8
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15
Total Face Area m2 0.294 0.46 0.56 0.62
Number of Coil/Unit - 1 1 1 1
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 1 1 2 2
Outer Diameter mm 200.4 200.4 227.4 227.4
Revolution (220V) rpm 800 1,310 1,220 1,270
Nominal Air Flow m3/h 660 1080 1,680 2,100
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - PSC (Permanent Split Capacitor)
Nominal Output W 60 180 140 180
Quantity - 1 1 2 2
Insulation Class - F F F F

Model AVA-114* AVA-154* AVA-190* AVA-190*


Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 9.53 9.53 9.53 9.53
Rows - 3 3 3 3
Fin Material Aluminum
Pitch mm 1.8 1.8 1.8 1.8
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15
Total Face Area m2 0.62 0.94 1.11 1.11
Number of Coil/Unit - 1 1 1 1
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 1 1 1 1
Outer Diameter mm 254.5 387 387 387
Revolution (380V) rpm 1,200 1,400 1,400 1,420
Nominal Air Flow m3/h 3,000 4,000 5,000 6,000
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - PSC (Permanent Split Capacitor)
Nominal Output W 600 1100 1500 2200
Quantity - 1 1 1 1
Insulation Class - F F F F

224
12.5 Refrigeration Cycle

AVA-30~114*

Indoor Unit

2
: Refrigerant Flow Direction (Cooling)
: Refrigerant Flow Direction (Heating)
: Field Refrigerant Piping
3 : Flare Connection

4
b

Refrigerant Liquid Pipe Connection


S

3 a

Refrigerant Gas Pipe Connection

Mark Part Name


1 Heat Exchanger
2 Distributor
3 Strainer
4 Micro-Computer Control Expansion Valve

225
AVA-154~190*

Refrigerant Gas Pipe


Connection (A)

2
3
Refrigerant Liquid Pipe
Connection (B)

: Refrigerant Flow Direction (Cooling)


: Refrigerant Flow Direction (Heating)
: Field Refrigerant Piping
: Brazing or Flare-nut Connection

Mark Part Name


1 Heat Exchanger
2 Distributor
3 Strainer
4 Micro-Computer Control Expansion Valve

226
12.6 Electrical Data

Indoor Unit
< 50 Hz >
Unit Main Power Applicable Voltage Indoor Fan Motor
Model
VOL PH HZ Maximum Minimum PH RNC IPT
AVA-30UXCSCH-70 0.65 0.15
AVA-48UXCSQH-108 1.45 0.33
220~240 1 50 264 198 1
AVA-76UXCSRH-168 2.25 0.49
All Fresh Air AVA-96UXCSRH-210 2.35 0.51
Indoor Unit AVA-114UX6SRH-300 1.47 0.74
AVA-154UX6SSH-400 1.92 1.12
380~415 3 50 456 342 3
AVA-190UX6STH-500 2.45 1.33
AVA-190UX6STH-600 2.96 1.62

Indoor Unit
< 60 Hz >
Unit Main Power Applicable Voltage Indoor Fan Motor
Model
VOL PH HZ Maximum Minimum PH RNC IPT
AVA-30UXCSCH-70 0.14 0.65
AVA-48UXCSQH-108 0.31 1.45
220 1 60 242 198 1
AVA-76UXCSRH-168 0.61 2.79
All Fresh Air AVA-96UXCSRH-210 0.71 3.25
Indoor Unit AVA-114UX6SRH-300 0.70 1.47
AVA-154UX6SSH-400 1.07 1.92
380 3 60 418 342 3
AVA-190UX6STH-500 1.27 2.45
AVA-190UX6STH-600 1.54 2.96

VOL: Rated Unit Power Supply Voltage (Plated)(V) RNC: Running Current (A)
PH: Phase (φ) IPT: Input (kW)
HZ: Frequency (Hz)

AVA-30~96* AVA-114~190*

130±5 145±5
83±15 80±15

5 5

0 0
14 14

2 2

227
12.7 Electrical Wiring Diagram
Model: AVA-30*

228
Electrical Wiring Diagram
Model: AVA-48*

229
Model: AVA-76~96*
Electrical Wiring Diagram

230
Electrical Wiring Diagram Model: AVA-114*

231
Electrical Wiring Diagram Model: AVA-154*~190*

232
12.8 Indoor Unit Optional Parts

Optional Parts Applied Indoor Unit Type

Type Model All Fresh Air Indoor Unit

HYXE-F01H ●
HYXE-G01H
Wire Remote Control Switch HYXE-A01H#01 ●
HYXE-J01H ●
HYXE-M01H ●
HYE-Q01 ●
Wireless Remote Control Switch HYE-L01 ●
HYE-W01 ●
HYRE-V01H ●
HYRE-T01H
Wireless Receiver Kit
HYRE-V02H
HYRE-X01H
7 Day Timer HYDE-E01H ●
HYJE-H01H ●
HYJE-D02H ●
HYJ-J01H ●
Centrol Station HCCS-H128H2C1YM ●
HCCS-H128H2C1NM
HCCS-H247R4C1E
HCCS-H128H2C2NM ●
HC-A64BNP ●
Interface for Building Control
HCPC-H2M1C ●
HCH-160D ●
Switch Box
HCH-280D ●
HZX-2.0AEC
HZX-4.0AEC
AHU Kits HZX-6.0AEC
HZX-10.0AEC
HZX-20.0AEC
HPS-162#E
Drain Pump HPS-132#E
HPS-151#E
HF-224L-FE
Long Life filter HF-280L-FE
HF-40L-ZFE
HP-DB-NK
3D Air Swing
HP-EB-NK

233
12.9 Factory-Supplied Accessories

Model: AVA-30*~114*

2QO\IRU30~48N%WXK 5
2QO\IRU76~114N%WXK

2QO\IRU30~48N%WXK 5

2QO\IRU76~114N%WXK 6

M 1

2QO\IRU30~48N%WXK
M 16

234
12.10 Installation For Model(30~114)
12.10.1

below.
Model:30~48 unit:mm
Model:76~114

12.10.2

235
● Model:48 unit:mm

32
306
370
1233

30
22
unit:mm
Model:30

800
756
833

22
30
30 1320
1380

58 1203

220
110
(2)

unit:mm
Model:76~114
920
980 1100

34
803

415
486
21×50=1050

Φ3 26
(1)
1021
1069

Φ3
29

4-40×12 20×50=1000
1270
1288 40

1106
110
30
338

(3)

236

below.

below.

237
● ●

238
12.11 Refrigerant Piping Work For Model(30~114) Model:76~114 B-
unit:mm
C- A-

Air inlet Air Outlet

mm(in.)
MODEL A B C

12.11.1 30 15.88(5/8) 9.53(3/8)

48 15.88(5/8) 9.53(3/8)

19.05(3/4) 9.53(3/8) VP 25
76
96 22.2(7/8) 9.53(3/8)

114 25.4(1) 12.7(1/2)

12.11.2

An excess or a shortage of refrigerant is the


main cause of trouble to the units.
Charge the correct refrigerant quantity.

unit:mm
Model:30~48 A-Refrigerant Gas C-Drain Pipe
Pipe Connection Connection
B-Refrigerant Liquid
Pipe Connection
244
202

81

95

239
12.12 Drain Piping For Model(30~114)

below.

below.

240
12.13.1

12.13.2
12.13 Electrical Wiring For Model(30~114)
below.

Model:30~48

Air outlet
Air inlet

Electrical Box Cover


Model:76~114

241
Cord Clamp

Cord Clamp
Operating Wires Power Supply

Cable of Remote Cable of


Control Switch Cord Clamp Remote
Cord Clamp Control
Power Supply Switch

Power Supply Operating Wires


220-240V 220-240V
~ 50Hz
 ̄/50Hz
220V~/60Hz
)
Power Supply Model:76~96
Operating Cable of Remote
220-240V
Wires Control Switch ~ 50Hz

Wiring Connection TerminalBoard(TB)


Enlarged View of P

Model:30~48

Cord Clamp Cable of


Remote
Control
Switch
Power Supply
380-415V Operating Wires
3N~ 50Hz

Model:114

242
12.14 Common (For Model 30~114)
12.14.1

Use an ELB(Electric Leakage Breaker).If not used,


it will cause an electric shock or a fire.

Run through the cables using conduit tube,and


Completely seal the end of conduit tube with
sealing materials.

Model Power MCA


Source EN60335-1 EN60335-1
1 1

30 1.2A 0.75mm2
2.5mm 2

48 220- 240V 2.5A 2.5mm 2 0.75mm2


~ 50Hz
220V~60Hz
76 5.2A 2.5mm 2 0.75mm2

96 6.0A 2.5mm 2 0.75mm2

380-415V
3N~ 50Hz
114 2.7A 2.5mm 2 0.75mm2
380V~60Hz

12.15 Factory-Supplied Accessories(For Model 154~190)

Model: AVA-154*~190*

(In c lu d in g Tw o R em o te Tem p eratu re Sen s o rs)

243
12.16 Installation (For Model 154~190)
12.16.1

below.

unit:mm
800 or more

Working
Keep enough distance between the indoor unit and
Space
800 or more the walls around to avoid contacting each other
Air Inlet Piping
Surface of the ceiling

50 or more
Vent-pipe

Air Passage
50 or more

Air Strainer
500 or more

(Field Supply)
100

Electrical Box
Support Board
Service Access Panel (Field Supply)
(600)
500 or more

The indoor unit is not designed for the places that (B)Install the indoor unit and components as far as
need quiet environment .Install the indoor unit in practical or at least 3meters from the electromagnetic
the places like equipment rooms that do not bring wave radiator.
noise problems.
(C)Prepare a steel box and install the remote control
Avoid bostacles which m ay hamper the air intake switch in it.Prepare a steel conduit tube and wire
or the air discharge flow. the remote control cable in it.Then,connect the
Do not install the indoor unit in a machine shop or ground wire with the box and the tube.
kitchen where vapor from oil or its mist flows to (D) Install a noise filter when the power supply emits
the indoor unit. harmful noises.
The oil will deposit on the heat exchanger,
To avoid any corrosive action to the heat
thereby reducing the indoor unit
exchangers,do not install the indoor unit in an acid or
performance,and may deform and in the worst alkaline environment.
case,break the plasticparts of the indoor unit.
Install the service access panel at the same side with
Pay attention to the following points when the indoor the electrical box in order to maintain and service
unit is installed in a hospital or other facilities where
conveniently.
there are electronic waves from medical equipment.
( A)Do not i nstall the indoo r unit whe re the electromagetic The indoor unit can not control the tempreture.
wave is directly radiated to the electrical box,remote Do not install the indoor Unit in places like the plage or
control cable or remote control switch. hotspring where the environment is saliferous and
corrodent.

244
unit:mm

Air Inlet
12.16.2 1520
1520

● Suspension bolts
(1)Select final location and installation direction of the
indoor unit paying careful attention to the space for

A
the piping, wiring and maintenance.

B
(2)Using suspendion bolts to install the indoor
unit.Check the celing whether is strong enough
to support the indoor unit.Plase reinforce the
ceiling before installation if it is not safe.
160×9=1440
(3)Install the indoor unit 2.5 meters higher from 69
69
the floor level,when exposed outdoor.
(4)Strainer(Field Supply)must be installed in the Ø17
pipeline.Make sure the the outdoor air through
the strainer
805
530

200×4=800
1950
2090
Ceiling

Anchor Bolt Air Outlet


850
Long Nut or Thread Take-up

C
Suspension Bolts
270

Indoor Unit
550

Fig. Sling Bolts

● MODEL A B C

154 520 635 130


190 620 735 230

245
● Hanging Indoor Unit
Install the indoor unit and the support
board using bolts (M12)as shown below.
Adjust the indoor unit installed to the
preconcerted height.
Hook the suspendion bracket to the nut
and washer of rach hanging bolt.
Check to ensure the indoor unit is
horizontally.
If the indoor unit is not horizontal,it may
cause a leakage.
Adjust theangle of the indoor unit using the
gradienter or polyethylene pipe .
Screw down the nuts.
Tighten the bolts of the sling nuts with the
suspension brackets after Adjustment is
completed.
Special plastic paint must be applied to the
bolts in order to prevent them from
loosening.

Setscrew (M12)
(Field Supply) Nut (Field Supply)

Support Board
Polyethylene Pipe
Polyethylene Pipe (Field Supply)
Drain Pipe Sleeve
Washer (Field Supply)

Nut×2 (Field Supply)


Sling Bolt
Bolt: M12
Drain Pipe
Sleeve

A:0~14mm B 0~36mm Fig Hanging Methods

Fig Installation Methods

246
● 12.17 Refrigerant PipingWork
Connect the duct as follows. (For Model 154~190)
<Air Inlet>
Connect the duct with flange inlet
together.
Seal the pontes between the flange inlet
and duct using the aluminous adhesive
tape.
<Air Outlet>
Connect the duct with flange o utlet
together.
Seal the pontes between the flange
outletand duct using the aluminous
adhesive tape. 12.17.1
Connect the flange outlet with the
indoor unit together using screws.

Flange Inlet Flange Outlet


Thermal Insulation
The Wall Thermal Insulation
Outside
The Indoor
(Downward Slop) Unit Air Outlet
Canvas Duct
Air Inlet Canvas Duct (Field Supply)
The Cover (Field Supply) 3
(Field Supply)

Air Inlet
Air Outlet
Refrigerant Gas Pipe
The strainer is not standard,install it in Refrigerant Liquid Pipe
the air inlet piping.
Ensure the air inlet piping downwardto Drain Pipe
avoid a seeper.
Ensure the air outside can be inhaled ,or
the indoor unit will not work.
Perform the heat insulation work over the
duct for dew protection.
When metal lic duct and other wire
netting are used,ensure the duct
insulative from thewalls.
When welding the duct,do not leave
residue on the indoor unit. Gas Pipe Liquid Pipe Drain Pipe

154
R p1
screw thread
190

247
Discharge gas inside
And remove the cap

Gas Pipe Cool by a wet cloth

Liquid
Pipe
Drain P
ipe

12.17.2

An excess or a shortage of refrigerant is


the main cause of trouble to the units.
Charge the correct refrigerant quantity.

248
12.18 Drain Piping

The drain pipe must be installed as the following Do not connect the drain pipe with
figure to avoid bring scales due to the congeal and Sanitary or sewage piping or any other
leakage. drainage piping.
The positon of the drain piping When the comm on drain piping is
connection is shown below. connected with other indoor units
please install as follows .
The drain pipe can be installed at the left or
right side of the exit of the drain pipe.The Pour some water into the drain pan in
plug can be removed to invert into any side. order to test wether the water flows
sm oothly.
Open the cover ,pour about one litre of
The drain pipe should be as short as
water,test the draining status.
possible for the best effect.The pipe must
be performed with a DOWN-SLOP PITCH
to ensure that water flows smoothly.
Make sure the drain pipe thermal
insulated.
Install a trap at the drain outlet,because it below.
will bring splash or smell without it.
Keep the drain pipe flat in order to clean
the sediment.
Seal another drain pipe ,do up it using
thermal insulation .

Indoor Unit

The Bottom

Drain Plug
100 or more

Auxiliary Drain Pan Trap


(Field Supply) Common Drain Pipe
100 or more
100 or more

(1/100 Down-Slop at least)


(Do not lay into the water)

249
12.19
● All the materials and components Don not connect cable of remote control
should comply with local statutes. switch and operating wires with power
supplyand earth wires together.Keep
● Only brass wires are allowed. 50MM away from each other .
● Connect eletrical wires refering to the
Use appointed wires,and ensure the
circuit diagram.
terminal fixed.
● All the connection must be operated by
professionals.
● Install a breaker that can cut off the 12.19.1
wholesysterm.
● Grounded resistance must be less
Than100Ω .
● Connect the ground wire.
● If the fan reverse,adjust the phase.

12.19.2

below.

Cut out the center of the rubber bushing in the


wiring connection hole,as shown below.

Connect the cable of the remote control


switch to the connectors inside the
electrical box through the connecting hole in
the cabinet.

Connect th e power supply and earth wires to


the terminals in the electrical box.

Tightly clamp the sires using the cord clamp


inside the electrical box.
The elecrtrical wires should not contact with
gas pipe or liquid pipe.Make sure the pipe Seal the wiring connection hole after running
systerm insulated completely the cables with the seal meterial to protect
. the unit from condensate water or insects.
Make sure that the electrical wires are not
¡ñnipped into the electrical box or maintance
Connect the wires between the indoor unit
cover.
and outdoor unit to the terminals in the
¡ñ Do not connect the remote control unit electrical box.
wires with the power supply wires
together,or it may cause an abnormity.
¡ñ Do not connect diffent standard wires to
the same terminal.

250
Cut Inside
Rubber Bushing

Eletrical Box
Power Supply
Eletrical Box Cover 380-415V 3N~ 50Hz
ELB

Bolts Cable of Remote


Control Switch
Operating Wires

Cord Clamp

Maximum Power Source Cable Size Transmitting Cable Size


Model
Current EN60 335-1*1 EN60 335-1*1
2 2
AVA-154UX6SSH-400 3.48A 2.5mm 0.75mm
2 2
AVA-190UX6STH-500 4.46A 2.5mm 0.75mm
2 2
AVA-190UX6STH-600 5.46A 2.5mm 0.75mm

251
12.20 Test Run(For Model:154~190)

The wire sizes marked with *1 in the above table are selected
at the maximum current of the unit according to the European
Standard, EN60335-1.Use the wires which are not lighter than
the ordinary polyvinyl chloride sheathed flexible cord
(code designation H05VV-F).
3

EN60335-1

6 2.5
6 10 2.5
10 16 2.5~4
16 25 2.5~6
25 32 4~10
32 40 6~16
40 63 10~25
63 *2

*2

252
12.20.1
c 4
1

3 4

d DSW5&RSW2

2
8

a DSW6&RSW1

e Fuse Recover (DSW7)

f Optional Function Setting (DSW8)

Model 30 48

Model 76、154 96~114、190

253
13. 2-Way Cassette Type(AVL)
13.1 General Data
Indoor Unit Type 2-Way Cassette Type
Model AVL-07UXJSGA AVL-09UXJSGA AVL-12UXJSGA AVL-14UXJSGA
Power Supply AC 1 , 220-240V/50Hz AC 1 , 220V/60Hz
Nominal Cooling kW 2.2 2.8 3.6 4.5
Capacity kcal/h 1,900 2,400 3,100 3,900
Btu/h 7,500 9,600 12,300 15,400

Cooling Power Consumption kW 0.02 0.02 0.02 0.03


Nominal Heating kW 2.8 3.3 4.0 5.0
Capacity kcal/h 2,400 2,800 3,400 4,300
Btu/h 9,600 11,300 13,700 17,100

Heating Power Consumption kW 0.02 0.02 0.02 0.03


Sound Pressure Level
(Overall A Scale) dB 32--30-29-27 33-30-29-28 34-31-30-28 40-37-34-32
Outer Dimensions
Height mm 298 298 298 298
(in.) (11-3/4) (11-3/4) (11-3/4) 11-3/4)
Width mm 860 860 860 860
(in.) (33-7/8) (33-7/8) (33-7/8) (33-7/8)
Depth mm 630 630 630 630
(in.) (24-13/16) (24-13/16) (24-13/16) (24-13/16)
Net Weight kg 22 22 22 24
(lbs.) (48) (48) (48) (53)
Refrigerant — R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 600/510/432/360 660/564/492/396 720/630/534/450 900/792/690/594
(cfm) (353/300/254/212) (388/332/289/233) (424/371/314/265) (530/466/406/350)

Connections Flare-Nut Connection (with Flare Nuts)


Refrigerant Piping
Liquid Line mm Φ6.35 Φ6.35 Φ6.35 Φ6.35
(in.) (1/4) (1/4) (1/4) (1/4)
Gas Line mm Φ12.7 Φ12.7 Φ12.7 Φ12.7
(in.) (1/2) (1/2) (1/2) (1/2)
Condensate Drain — VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.27 0.27 0.27 0.27
Adaptable Panel Model — HP-C-NA
Color — Silk White
Outer Dimensions
Height mm 30 30 30 30
(in.) (1-3/16) (1-3/16) (1-3/16) (1-3/16)
Width mm 1100 1100 1100 1100
(in.) (43-5/16) (43-5/16) (43-5/16) (43-5/16)
Depth mm 710 710 710 710
(in.) (27-15/16) (27-15/16) (27-15/16) (27-15/16)
Net Weight kg 7.5 7.5 7.5 7.5
(lbs.) (17) (17) (17) (17)
Approximate
Packing Measurement m3 0.10 0.10 0.10 0.10

NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
19.0oC WB (66.2oF WB)

Outdoor Air Inlet Temperature: 35oC DB (95oF DB)


Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meters Beneath the Unit.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

254
Indoor Unit Type 2-Way Cassette Type
Model AVL-18UXJSGA AVL-24UXJSGA AVL-27UXJSGA AVL-30UXJSGA
Power Supply AC 1 , 220-240V/50Hz AC 1 , 220V/60Hz
Nominal Cooling kW 5.6 7.1 8.4 9.0
Capacity kcal/h 4,800 6,100 7,200 7,700
Btu/h 19,100 24,200 28,700 30,700

Cooling Power Consumption kW 0.04 0.05 0.07 0.08


Nominal Heating kW 6.5 8.0 9.0 10.0
Capacity kcal/h 5,600 6,800 7,700 8,600
Btu/h 22,200 27,300 30,700 34,100

Heating Power Consumption kW 0.04 0.05 0.07 0.08


Sound Pressure Level
(Overall A Scale) dB 42-39-36-33 45-42-39-36 47-44-40-36 49-46-42-37
Outer Dimensions
Height mm 298 298 298 298
(in.) (11-3/4) (11-3/4) (11-3/4) 11-3/4)
Width mm 860 860 860 860
(in.) (33-7/8) (33-7/8) (33-7/8) (33-7/8)
Depth mm 630 630 630 630
(in.) (24-13/16) (24-13/16) (24-13/16) (24-13/16)
Net Weight kg 24 24 24 24
(lbs.) (53) (53) (53) (53)
Refrigerant — R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 1020/894/780/672 1140/984/858/738 1260/1104/936/756 1320/1158/978/786
(cfm) (601/526/459/594) (671/579/505/435) (742/650/551/445) (777/682/576/463)

Connections Flare-Nut Connection (with Flare Nuts)


Refrigerant Piping
Liquid Line mm Φ6.35 Φ9.53 Φ9.53 Φ9.53
(in.) (1/4) (3/8) (3/8) (3/8)
Gas Line mm Φ12.7 Φ15.88 Φ15.88 Φ15.88
(in.) (1/2) (5/8) (5/8) (5/8)
Condensate Drain — VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.27 0.27 0.27 0.27
Adaptable Panel Model — HP-C-NA
Color — Silk White
Outer Dimensions
Height mm 30 30 30 30
(in.) (1-3/16) (1-3/16) (1-3/16) (1-3/16)
Width mm 1100 1100 1100 1100
(in.) (43-5/16) (43-5/16) (43-5/16) (43-5/16)
Depth mm 710 710 710 710
(in.) (27-15/16) (27-15/16) (27-15/16) (27-15/16)
Net Weight kg 7.5 7.5 7.5 7.5
(lbs.) (17) (17) (17) (17)
Approximate
Packing Measurement m3 0.10 0.10 0.10 0.10

NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
19.0oC WB (66.2oF WB)

Outdoor Air Inlet Temperature: 35oC DB (95oF DB)


Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meters Beneath the Unit.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

255
Indoor Unit Type 2-Way Cassette Type
Model AVL-38UXJSHA AVL-48UXJSHA AVL-54UXJSHA
Power Supply AC 1 , 220-240V/50Hz AC 1 , 220V/60Hz
Nominal Cooling kW 11.2 14.0 16.0
Capacity kcal/h 9,600 12,000 13,800
Btu/h 38,000 47,700 54,600

Cooling Power Consumption kW 0.09 0.11 0.12


Nominal Heating kW 13.0 16.0 18.0
Capacity kcal/h 11,200 13,800 15,500
Btu/h 44,000 54,600 61,400

Heating Power Consumption kW 0.09 0.11 0.12


Sound Pressure Level
(Overall A Scale) dB 46-44-40-38 48-45-42-38 49-46-43-40
Outer Dimensions
Height mm 298 298 298
(in.) (11-3/4) (11-3/4) (11-3/4)
Width mm 1420 1420 1420
(in.) (55-7/8) (55-7/8) (55-7/8)
Depth mm 630 630 630
(in.) (24-13/16) (24-13/16) (24-13/16)
Net Weight kg 39 39 39
(lbs.) (86) (86) (86)
Refrigerant — R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 1800/1584/1386/1188 2100/1848/1614/1266 2220/1950/1704/1446
(cfm) (1060/933/816/670) (1237/1088/950/746) (1307/1148/1003/852)

Connections Flare-Nut Connection (with Flare Nuts)


Refrigerant Piping
Liquid Line mm Φ9.53 Φ9.53 Φ9.53
(in.) (3/8) (3/8) (3/8)
Gas Line mm Φ15.88 Φ15.88 Φ15.88
(in.) (5/8) (5/8) (5/8)
Condensate Drain — VP25 VP25 VP25
Approximate
Packing Measurement m3 0.41 0.41 0.41
Adaptable Panel Model — HP-F-NA
Color — Silk White
Outer Dimensions
Height mm 30 30 30
(in.) (1-3/16) (1-3/16) (1-3/16)
Width mm 1660 1660 1660
(in.) (65-3/8) (65-3/8) (65-3/8)
Depth mm 710 710 710
(in.) (27-15/16) (27-15/16) (27-15/16)
Net Weight kg 10.5 10.5 10.5
(lbs.) (23) (23) (23)
Approximate
Packing Measurement m3 0.15 0.15 0.15

NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
19.0oC WB (66.2oF WB)

Outdoor Air Inlet Temperature: 35oC DB (95oF DB)


Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meters Beneath the Unit.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

256
13.2 Dimensional Data
● AVL07_30*



Unit:mm


 






 
















 



● AVL38_54*





    














 

 

No. Name Remark


1 Turbo Fan
2
3
Motor
Heat exchanger

Model a b
4 Distributor 07 12.7 6.35
5 Filter
09 12.7 6.35
6 EXP. VALVE
12 12.7 6.35
7 Power souce
14 12.7 6.35
8 Refrigerant Gas Pipe Connection with φ a Flare Nut
18 12.7 6.35
9 Refrigerant Liquid Pipe Connection with φ b Flare Nut
10 24 15.88 9.53
Drain Pipe Connection VP25
11 Pump 27 15.88 9.53
12 Float SW 30 15.88 9.53
13 Water conncting plate 38 15.88 9.53
Panel P-AP90DNA with Model 07~30 Optional 48 15.88 9.53
14
P-AP160DNA with Model 38~54 54 15.88 9.53
15 Air Inlet grille
16 Air filter
17 Air Outlet
18 Air Inlet
257
13.3 Selection Data
● Service Space

AVL-07~54* Unit:mm

Min.
Min. 

Min. Min.
Min. Min.  
1 

Min. Piping Min.


 Connection


Min. Min.
Separated Installation  

Min. Piping
Connection
distance from wall side 

10 -20mm Closed Installation


298mm
Unit Hight in
False Celling
Unit Hight in False Celling

Min. Min.

Piping Connection Side

Min. Min.

Min.

Service Space

„ Sensible Heat Factor (SHF)

SHF
Indoor Unit Model
 AVL-07*
Hi

Me

Lo

AVL-09*   

 AVL-12* 
AVL-14* 






AVL-18*   

 AVL-24*
AVL-27*






AVL-30*   

 AVL-38*
AVL-48*






AVL-54*   

258
● Sound Data

Model:AVL-07* Power Supply: 220-240V/50Hz,220V/60Hz Model:AVL-09* Power Supply: 220-240V/50Hz,220V/60Hz


Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)


80 80

NC--70 NC--70
70 70
NC--65 NC--65

60 NC--60 60 NC--60
NC--55 NC--55

50 NC--50 NC--50
50

HH NC--45
HH NC--45
40 NC--40 NC--40
Hi 40
Hi
NC--35 NC--35
30 Me NC--30
30 Me NC--30
NC--25 NC--25
20 NC--20 NC--20
20
Lo NC--15 Lo NC--15
10
63 125 250 500 1000 2000 4000 8000 10
63 125 250 500 1000 2000 4000 8000
Central Frequency(Cycle per Second)
Central Frequency(Cycle per Second)

Model:AVL-12* Power Supply: 220-240V/50Hz,220V/60Hz Model:AVL-14* Power Supply: 220-240V/50Hz,220V/60Hz


Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)

80 80

NC--70 NC--70
70 70
NC--65 NC--65

60 NC--60 60 NC--60

NC--55 NC--55
HH Hi NC--50
50 NC--50 50
HH NC--45 Me NC--45
Hi NC--40 NC--40
40 40

Me NC--35 NC--35

30 NC--30 30 NC--30

NC--25 Lo NC--25

20 NC--20 20 NC--20
Lo
NC--15 NC--15

10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model:AVL-18* Power Supply: 220-240V/50Hz,220V/60Hz Model:AVL24* Power Supply: 220-240V/50Hz,220V/60Hz


Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)

80 80

NC--70 NC--70
70 70
NC--65 NC--65

60 NC--60 60 NC--60

NC--55 HH NC--55
HH Hi Hi
50 NC--50 50 NC--50
Me
Me NC--45 NC--45

40 NC--40 40 NC--40

NC--35 NC--35

NC--30
30 NC--30 30
Lo
Lo NC--25
NC--25

20 NC--20 20 NC--20

NC--15 NC--15

10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

259
Model:AVL-27* Power Supply: 220-240V/50Hz,220V/60Hz Model:AVL-30* Power Supply: 220-240V/50Hz,220V/60Hz
Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve

Octave Sound Pressure Level(dB: Overall C Scale)


Octave Sound Pressure Level(dB: Overall C Scale)

80 80

NC--70 NC--70
70 70
NC--65 NC--65

60 NC--60 60 NC--60
HH HH
Hi NC--55 Hi NC--55
Me Me
50 NC--50 50 NC--50

NC--45 NC--45

40 NC--40 40 NC--40

NC--35 NC--35

30 NC--30 NC--30
Lo 30
Lo
NC--25 NC--25

20 NC--20 20 NC--20

NC--15 NC--15

10 10 8000
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model:AVL-38* Power Supply: 220-240V/50Hz,220V/60Hz Model:AVL-48* Power Supply: 220-240V/50Hz,220V/60Hz

Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90
90
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level(dB: Overall C Scale)

80
80
Octave Sound Pressure Level(dB: Overall C Scale)

NC--70
NC--70 70
70
NC--65
NC--65

60 NC--60
60 NC--60 HH Hi
HH NC--55
Hi NC--55 Me
Me 50 NC--50
50 NC--50
NC--45
NC--45
40 NC--40
40 NC--40
NC--35
NC--35

NC--30
30 Lo NC--30
30
Lo NC--25
NC--25
20 NC--20
20 NC--20
NC--15
NC--15
10
10 63 125 250 500 1000 2000 4000 8000
63 125 250 500 1000 2000 4000 8000
Central Frequency(Cycle per Second)
Central Frequency(Cycle per Second)

Model:AVL-54* Power Supply: 220-240V/50Hz,220V/60Hz


Measurement Point: 1.5 Meters Beneath the Unit
90
Noise Criteria Curve
Octave Sound Pressure Level(dB: Overall C Scale)

80

NC--70
70
NC--65
HH
60 NC--60
Hi
NC--55
Me
50 NC--50

NC--45

40 NC--40

NC--35

NC--30
30
Lo
NC--25

20 NC--20

NC--15

10
63 125 250 500 1000 2000 4000 8000

Central Frequency(Cycle per Second)

260
13.4 Component Data

Model AVL-07* AVL-09* AVL-12* AVL-14*


Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0
Rows - 10 10 10 12
Fin Material Aluminum
Pitch mm 1.6 1.6 1.6 1.6
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15
Total Face Area m2 0.30 0.30 0.30 0.36
Number of Coil/Unit - 1 1 1 2
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 1 1 1 1
Outer Diameter mm 360 360 360 360
Revolution rpm 384/342/304/265 419/370/328/286 454/402/356/311 584/522/463/408
Nominal Air Flow m3/h 600/528/432/360 660/576/504/396 720/630/552/450 900/792/690/594
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - PSC (Permanent Split Capacitor)
Nominal Output W 57 57 57 57
Quantity - 1 1 1 1
Insulation Class - E E E E

Model AVL-18* AVL-24* AVL-27* AVL-30*


Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0
Rows - 12 12 12 12
Fin Material Aluminum
Pitch mm 1.6 1.6 1.6 1.6
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15
Total Face Area m2 0.36 0.36 0.36 0.36
Number of Coil/Unit - 2 2 2 2
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 2 1 1 1
Outer Diameter mm 360 360 360 360
Revolution rpm 636/567/505/439 713/633/560/491 792/702/605/501 827/733/629/519
Nominal Air Flow m3/h 1020/870/780/672 1140/984/858/738 1260/1104/936/756 1320/1158/978/786
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - PSC (Permanent Split Capacitor)
Nominal Output W 57 57 57 57
Quantity - 1 1 1 1
Insulation Class - E E E E

261
Model AVL-38* AVL-48* AVL-54*
Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0
Rows - 12 12 12
Fin Material Aluminum
Pitch mm 1.6 1.6 1.6
Maximum Operating Pressure MPa 4.15 4.15 4.15
Total Face Area m2 0.61 0.61 0.61
Number of Coil/Unit - 4 4 4
Indoor Fan Multi-Blade Centrifugal Fan
Number/Unit - 2 2 2
Outer Diameter mm 360 360 360
Revolution rpm 675(/607)/ 771(/694)/ 809(/728)/
606(/545)/ 690(/621)/ 723(/651)/
543(/488)/ 615(/554)/ 644(/580)/
479(/431) 504(/454) 562(/506)
Nominal Air Flow m3/h 1800/1584/1386/1188 2100/1848/1614/1266 2220/1950/1704/1446
Indoor Fan Motor Drip-Proof Type Enclosure
Starting Method - PSC (Permanent Split Capacitor)
Nominal Output W 57+57 57+57 57+57
Quantity - 2 2 2
Insulation Class - E E E

262
13.5 Refrigeration Cycle

Indoor Unit

2
: Refrigerant Flow Direction (Cooling)
: Refrigerant Flow Direction (Heating)
: Field Refrigerant Piping
3 : Flare Connection

b
Refrigerant Liquid Pipe Connection
S

3 a

Refrigerant Gas Pipe Connection

Mark Part Name


1 Heat Exchanger
2 Distributor
3 Strainer
4 Micro-Computer Control Expansion Valve

263
13.6 Electrical Data

Indoor Unit
Unit Main Power Applicable Voltage Indoor Fan Motor
Model
VOL PH HZ Maximum Minimum PH RNC IPT

AVL-07* 0.17/0.17 0.014/0.014


AVL-09* 0.17/0.17 0.014/0.014
AVL-12* 0.17/0.17 0.014/0.014
AVL-14* 0.27/0.27 0.024/0.024
2-Way
AVL-18* 220~ 1 50 264 198 1 0.37/0.37 0.034/0.034
Cassette
AVL-24* 240V 0.47/0.47 0.044/0.044
Type
AVL-27* 0.67/0.67 0.064/0.064
AVL-30* 0.67/0.67 0.074/0.074
AVL-38* 0.77/0.77 0.084/0.084
AVL-48* 0.97/0.97 0.104/0.104
AVL-54* 1.07/1.07 0.114/0.114

VOL: Rated Unit Power Supply Voltage (Plated)(V) RNC: Running Current (A)
PH: Phase (φ) IPT: Input (kW)
HZ: Frequency (Hz)

Safety and Control Device Setting

Model AVL-07~54*

For Control Circuit


Fuse Capacity A 5
Freeze Protection
Thermostat ºC 0
Cut-Out
Cut-In ºC 14

Thermostat
Differential ºC 2

264
13.7 Electrical Wiring Diagram

Models: AVL-07~54*

265
13.8 Indoor Unit Optional Parts

Optional Parts Applied Indoor Unit Type

Type Model 2-Way Cassette Type

HYXE-F01H
HYXE-G01H
Wire Remote Control Switch HYXE-A01H#01
HYXE-J01H
HYXE-M01H ●
HYE-Q01
Wireless Remote Control Switch HYE-L01
HYE-W01 ●
HYRE-V01H
HYRE-T01H
Wireless Receiver Kit
HYRE-V02H ●
HYRE-X01H
7 Day Timer HYDE-E01H
HYJE-H01H
HYJE-D02H
HYJ-J01H
Centrol Station HCCS-H128H2C1YM
HCCS-H128H2C1NM
HCCS-H247R4C1E
HCCS-H128H2C2NM
HC-A64BNP
Interface for Building Control
HCPC-H2M1C
HCH-160D
Switch Box
HCH-280D
HZX-2.0AEC
HZX-4.0AEC
AHU Kits HZX-6.0AEC
HZX-10.0AEC
HZX-20.0AEC
HPS-162#E
Drain Pump HPS-132#E
HPS-151#E
HF-224L-FE
Long Life filter HF-280L-FE
HF-40L-ZFE
HP-DB-NK
3D Air Swing
HP-EB-NK

266
13.9 Factory-Supplied Accessories

2.3

Air Panel(optional)
Indoor Unit Panel Selected
07~30 HP-C-NA
38~54 HP-F-NA

(small)

(big)

(small)

(big)

(big)

(small)

For Power Wiring and


Cable Clamp
Transmission Wiring

267
13.10 Installation
13.10.1 Instal Check

below.

500mm Min.

500mm
100mm Min.
Min.

Piping
500mm Min. Connection

500mm Min.

100mm 500mm
Min. Min.

3000mm Min.

500mm
100mm Min.
Min.

Piping
500mm Min.
Connection

Distance from Wall Side

100mm Min. 1,500mm Min.

Piping
Connection Side

500mm Min.
1500mm Min.
1,000mm Min.

Service Space

Clearance 10 -20mm
298mm
Unit Hight in False
Ceiling

268
13.10.2 ●

10 Min.
4-Suspension Bolts
M10 or W3/8(Field-Supplied)

347
Nut(Field Supplied)
Washer(Accessory)

115

*47
30
Surface
of Ceiling
below.
*indicates the dimension between lower face of
A(Dimension of Opening)
Optional Panel (mm) indoor unit and surface of ceiling.
B(Dimension of Suspension Bolts)

Gas Pipe Connection 359

Suspension Bolts)
668(Dimension of

291

(Dimension of
Liquid Pipe Connection
211
Opening)

540
Drain Pipe Connection

347
260

50
208
Position of Piping
Suspension Bolts Connection Side
Panel

30
Position of Optical Sensor (if optical
sensor component is selected Air Inlet Grille

Unit: mm
70(Gas Pipe)
Model A B
70(Liquid Pipe)
07~30 1048 910 65 (Drain Pipe)

38~54 1608 1470


115

13.10.3

below.
Approx. 50

(mm)
For Concrete Slab For Steel Beam

Insert
150 to 160mm (100 to150kg)

Concrete
*
Steel
Anchor Bolt l Beam
(W3/8 or M10) Bracket
Suspension Bolt
(W3/8 or M10)
Approx. 65
115

For Wooden Beam

Wooden Rib
(60 to 90mm square timber)
Nut Square Washer

Square Washer
Nut
Wooden Beam Suspension Bolt

269
Drain Pipe
Fixing Bracket of Panel
Adjust four corners of
the system with a
plastic hose filled with
water

Suspension Bolt

Transparent
Plastic Hose

Bottom View

Suspension
Piping
Bracket
Connection Side

Drain Pan

Indoor Unit

Suspension Bolt

Ceiling

47
The fixing bracket is panel

● Connected to Ceiling

Indoor Unit

Connected to Indoor Unit


Ceiling

Dimension
of Opening
32

Adjustment Range
3-4mm

Fixing Bracket of Panel

Bolt M6
(Panel Accessories)

Pattern Board

270
13.11

10A Pipe Diameter (a)

Flaring
Diameter
(D)

13.11.1 below.

12.7mm 60
07 18

24~54

below.

13.11.2

below.

(mm)
Gas Pipe 359
Liquid Pipe 291
Drain Pipe 211
347
260
208

Panel(optional)

70 Gas Pipe
70 Liquid Pipe
65 Drain Pipe

Flaring Dimension
Perform the flaring work as shown below.

271
13.12 P Drain Hose

Horizontal or Upward Slope


Drain pipe must be installed horizontally or in upward slope
to prevent occurrence of air column, or otherwise water will
flow from rear of the equipment to cause leakage or
abnormal noise when the equipment is shut down.

(a) Use the drain pipe and hose clamp provided


by the manufacture.
(b) Do not impose too much force on the pipe
joint to prevent damage to it.
(c) Do not use any bent or twisted pipe, which
may cause leakage.
(d) Complete insert the drain pipe provided by
the manufacturer, or otherwise leakage may
be caused.
Drain Hose(Accessory)
Hose Band(Accessory)
Tightening Torque 2.5~3.4(N.m)
Elbow or Polyvinyl Chloride VP25
Drain Pipe
Connection

1.5or2.5
20+5
Insert Drain Pipe Completely to No Adhesive Agent Polyvinyl Chloride-based
End of The Hose Connection to be Adhesive Agent
(Correct)

1.5or2.5
(Incorrect) Twisted and Incomplete Insertion

section 13.11.2.

Ceiling
1- 1.5m Suspension
Bracket
a c
b

≤ 300) ( ≤50 )
≤ 850

1/25 to 1/100
Down-Slope
P
260

(mm)

Drain Hose
(Accessory)

950mm.

272
13.13
13.13.1

● Turn OFF the main power switch to the indoor


unit and the outdoor unit and wait for at least 3
minutes before electrical wiring work or a
periodical check is performed.
● Check to ensure that the indoor fan and the
outdoor fan have stopped before electrical
wiring work or a periodical check is performed.
● Protect the wires,drain pipe, electrical parts,
etc. from rats or other small animals.
If not protected, rats may gnaw at unprotected
parts and at the worst, a fire will occur.
● Avoid any wire from contacting with
Refrigerant tube, edge of metal plate and
electrical part in the equipment, or otherwise
the wire may be damaged or even thereby
cause fire.
● ELB with intermediate induction rate (with
shorter than 0.1 second or fewer) shall be
used, or otherwise electric shock or fire may
be caused.
● Wire shall be fixed securely, since external
force imposed to the connecting terminal may 13.13.2
make it loose and thereby cause fire.
● Do not use the power terminal strip used for next page.
the air conditioner to sub-connect any power
cable, but use power branch box to sub-
connect power wire at indoor unit side instead,
and be sure to calculate wire capacity, or
otherwise too low capacity may cause fire.
● The system shall not be started until all
inspections have been performed properly.

● Wrap the accessory packing around the wires,


and plug the wiring connection hole with the
seal material to protect the product from any
condensate water or insects.
● Tightly secure the wires with the cord clamp
inside the indoor unit.
● Secure the cable of the remote control switch
using the cord clamp inside the electrical box.
● Tighten screws according to the following
torque.
13.15
M3.5:1.2 N.m
M6:2.0~2.4 N.m

273
(a) Remove electrical box cover (by loosening one
Pipe screw (A)).
Baffle
(b) Loosen two screws (B) on electrical box
Wiring component and pull out the component.
Port (c) Fix the wire harness from connecting port to
electrical box with cord clamp to prevent it from
scratched by edge of container of other
component.
Base Board
(d) Mount a magnetic ring to the communication wire,
Electrical Box
which shall be wound by three circles around the
Screw(for fixing of
electrical box cover)
wire and then fixed with cord clamp provided in the
Electrical Box Cover
accessory bag.
07~30 (e) Upon completion of wiring, mount electrical box,
and take care not to press any wire.

Pipe
Baffle
Wiring •After wire is connected to terminal board, be
Port
sure to fix it with cord clamp and lay the wire in
cable tray to prevent it from being squeezed and
fire caused thereby.
Base Board
Electrical Box
Screw(for fixing of
Electrical
13.14
electrical box cover)
Box Cover Base
Board
Electrical
Box Cover

38~54

Wiring Hole Transmission


Terminal Board

Earth
Transmission Wiring
Screw
Remote Control Switch Cable
Power Source
Wiring

Power Terminal
Board
Wiring Hole

Electrical Box Cover


Fixing Screw

Transmission Terminal
Wiring Hole Board

Transmission Wiring
Remote Control
Switch Cable Cord Clamp

Power Source
Wiring

Wiring Hole
Earth Screw
Electrical Power Terminal
Box Board

Zoom-in View of Part A

274
13.15
13.15.1 13.15.2

Use an ELB (Electric Leakage Breaker).If not


used ,it will cause an electric shock or a fire. DSW5(Refrigerant Cycle No. Setting)
RSW2(Refrigerant Cycle No. Setting)
Run through the cables using conduit tube,
and Completely seal the end of conduit tube DSW3(Capacity Code Setting)
with sealing materials.
DSW7(Fuse Recover)

DSW6(Unit
MCA No. Setting) RSW1(Unit No. Setting)
EN60 335-1 *1 EN60 335-1 *1
DSW9(Optional Function Setting)
DSW4(Unit Mode Code Setting)
07 30 0.9A
2.5mm2 0.75mm2
38 54 1.8A 5

The wire sizes marked with *1 in the above table are selected
at the maximum current of the unit according to the European
Standard, EN60335-1.Use the wires which are not lighter than
the ordinary polyvinyl chloride sheathed flexible cord
(code designation H05VV-F).
3

Ex.) Set at No.16 Unit


Setting Set by inserting DSW6
Position Slotted screwdriver
into the groove
3 2.5
3 6 2.5 Set No.1 Pin ON
6 10 2.5 Before shipment. DSW6 and RSW1 are set to "0".
RSW1
Max.64 units are available to set when all the equipment
10 16 4.0 to be connected are corresponding to Hi-NET.
16 25 6.0 Max.16 units when the units corresponding/
non-corresponding to Hi-NET are combined.
25 32 10.0 Set at "6"

32 50 16.0
50 63 25.0
2

275
outlet

Outlet

(6) Optional Function Setting(DSW9)


No setting is required
Setting positions before shipment are all OFF
Setting the model code

13.17

13.17.1

13.16

Step 1
Remove the air returning decorative plate with
both hands,as shown below.
Step 2
Turn the buttons along edges of filter screen to
make them parallel to the slot, and then remove
the screen.

276
13.1

13.18.2

13.18.3

13.17.2

13.18.4

13.17.3

13.18

277
14. 1-Way Cassette Type(AVY)

14.1 General Data


Indoor Unit Type 1-Way Cassette Type
Model AVY-07UXJSJA AVY-09UXJSJA AVY-12UXJSJA AVY-14UXJSJA
Power Supply AC 1 , 220-240V/50Hz AC 1 , 220V/60Hz
Nominal Cooling kW 2.2 2.8 3.6 4.5
Capacity kcal/h 1,900 2,400 3,100 3,900
Btu/h 7,500 9,600 12,300 15,400

Cooling Power Consumption kW 0.02 0.02 0.03 0.03


Nominal Heating kW 2.5 3.2 4.0 5.0
Capacity kcal/h 2,200 2,800 3,400 4,300
Btu/h 8,500 11,000 13,600 17,100

Heating Power Consumption kW 0.02 0.03 0.04 0.04


Sound Pressure Level

Nominal Cooling dB 30/29/28/27/27/26 32/31/30/29/28/27 37/35/34/32/30/28 41/37/34/33/31/30

Nominal Heating dB 33/32/31/30/29/28 35/34/32/31/29/28 40/36/35/33/30/29 43/39/35/33/31/29


Outer Dimensions
Height mm 192 192 192 192
(in.) (7-9/16) (7-9/16) (7-9/16) (7-9/16)
Width mm 910 910 910 910
(in.) (35-13/16) (35-13/16) (35-13/16) (35-13/16)
Depth mm 470 470 470 470
(in.) (18-1/2) (18-1/2) (18-1/2) (18-1/2)
Net Weight kg 19 19 20 20
(lbs.) (42) (42) (44) (44)
Refrigerant — R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 372/354/336/306/288/276 396/372/336/306/288/276 498/438/408/372/336/306 600/498/408/378/342/312
(cfm) (219/208/198/180/170/163) (233/219/198/180/170/163) (293/258/240/219/198/180) (353/293/240/223/201/184)

Connections Flare-Nut Connection (with Flare Nuts)


Refrigerant Piping
Liquid Line mm Φ6.35 Φ6.35 Φ6.35 Φ6.35
(in.) (1/4) (1/4) (1/4) (1/4)
Gas Line mm Φ12.7 Φ12.7 Φ12.7 Φ12.7
(in.) (1/2) (1/2) (1/2) (1/2)
Condensate Drain — VP25 VP25 VP25 VP25
Approximate
Packing Measurement m3 0.19 0.19 0.19 0.19
Adaptable Panel Model — HP-D-NA
Color — Neutral White
Outer Dimensions
Height mm 55 55 55 55
(in.) (2-3/16) (2-3/16) (2-3/16) (2-3/16)
Width mm 1100 1100 1100 1100
(in.) (43-5/16) (43-5/16) (43-5/16) (43-5/16)
Depth mm 550 550 550 550
(in.) (21-5/8) (21-5/8) (21-5/8) (21-5/8)
Net Weight kg 5 5 5 5
(lbs.) (11) (11) (11) (11)
Approximate
Packing Measurement m3 0.10 0.10 0.10 0.10
NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
19.0oC WB (66.2oF WB)

Outdoor Air Inlet Temperature: 35oC DB (95oF DB)


Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meters Beneath the Unit.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

278
Indoor Unit Type 1-Way Cassette Type
Model AVY-18UXJSKA AVY-24UXJSKA
Power Supply AC 1 , 220-240V/50Hz AC 1 , 220V/60Hz
Nominal Cooling kW 5.6 7.1
Capacity kcal/h 4,800 6,100
Btu/h 19,100 24,200

Cooling Power Consumption kW 0.04 0.08


Nominal Heating kW 6.3 8.0
Capacity kcal/h 5,400 6,900
Btu/h 21,500 27,300

Heating Power Consumption kW 0.05 0.10


Sound Pressure Level

Nominal Cooling dB 40/38/35/33/32/31 46/42/40/37/34/32

Nominal Heating dB 41/39/36/35/33/31 48/46/43/40/37/33


Outer Dimensions
Height mm 192 192
(in.) (7-9/16) (7-9/16)
Width mm 1180 1180
(in.) (46-7/16) (46-7/16)
Depth mm 470 470
(in.) (18-1/2) (18-1/2)
Net Weight kg 24 24
(lbs.) (53) (53)
Refrigerant — R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Air Flow Rate m3/h 726/594/528/492/468/396 936/756/672/594/504/426
(cfm) (427/350/311/290/275/233) (551/445/396/350/297251)

Connections Flare-Nut Connection (with Flare Nuts)


Refrigerant Piping
Liquid Line mm Φ6.35 Φ9.53
(in.) (1/4) (3/8)
Gas Line mm Φ15.88 Φ15.88
(in.) (5/8) (5/8)
Condensate Drain — VP25 VP25
Approximate
Packing Measurement m3 0.24 0.24
Adaptable Panel Model — HP-E-NA
Color — Neutral White
Outer Dimensions
Height mm 55 55
(in.) (2-3/16) (2-3/16)
Width mm 1370 1370
(in.) (53-15/16) (53-15/16)
Depth mm 550 550
(in.) (21-5/8) (21-5/8)
Net Weight kg 6 6
(lbs.) (13) (13
Approximate
Packing Measurement m3 0.12 0.12

NOTES:
1. The nominal cooling capacity is the combined capacity of the Hisense standard split system.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
19.0oC WB (66.2oF WB)

Outdoor Air Inlet Temperature: 35oC DB (95oF DB)


Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meters Beneath the Unit.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

279
14.2 Dimensional Data
Model:07~14 10
Unit:mm





   



 




 

5 
     

Model:18~24
80





   












5 
     

No. Name
1 Turbo Fan
Remark

2 Motor
3 Heat Exchanger Model a b
4 Distributor 07 12.7 6.35
5 Filter
09 12.7 6.35
6 EXP. VALVE
12 12.7 6.35
7 Power Souce
14 12.7 6.35
8 Refrigerant Gas Pipe Connection with φ a Flare Nut
18 15.88 6.35
9 Refrigerant Liquid Pipe Connection with φ b Flare Nut
10 24 15.88 9.53
Drain Pipe Connection VP25
11 Pump
12 Float SW
13 Water Conncting Plate
14 Panel P-N45SNKQA with Model 07~14 Optional
P-N71SNKQA with Model 18~24
15 Air Inlet Grille
16 Air Filter
17 Air Outlet
18 Air Inlet

280
14.3 Selection Data

● Service Space

Unit:mm

Min
50

Min Piping
50 Connection
Min
500 Min.230mm

Min
500

Unit Hight in False Celling


distance from wall side

Min
PP
Min
PP
Piping
Connection

Min
PP
Min
PP Min
PP

Service Space

● Sensible Heat Factor (SHF)

SHF
Indoor Unit Model
Hi Me Lo
AVY-07* 0.82 0.72 0.67
AVY-09* 0.81 0.69 0.60
AVY-12* 0.77 0.72 0.68
AVY-14* 0.75 0.71 0.67
AVY-18* 0.74 0.70 0.67
AVY-24* 0.70 0.68 0.68

281
● Sound Data

Model:AVY-07* Power Supply: 220-240V/50Hz,220V/60Hz Model:AVY-09* Power Supply: 220-240V/50Hz,220V/60Hz


Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
Noise Criteria Curve Noise Criteria Curve
90
90

Octave Sound Pressure Level(dB: Overall C Scale)


Octave Sound Pressure Level(dB: Overall C Scale)

80
80

70
NC-70 70
NC-70
NC-65
60 NC-65
NC-60 60
NC-60
NC-55
50 NC-55
NC-50 50
NC-50
HH NC-45 HH
40 Hi NC-45
NC-40 40 Hi
Me Me NC-40
Lo
NC-35 NC-35
30 30 Lo
NC-30 NC-30
20 NC-25 20 NC-25
S-Lo NC-20 S-Lo NC-20
night shift night shift
10 NC-15 10 NC-15
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k
Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model:AVY-12* Power Supply: 220-240V/50Hz,220V/60Hz Model:AVY-14* Power Supply: 220-240V/50Hz,220V/60Hz


Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
Noise Criteria Curve Noise Criteria Curve
90 90
Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)

80 80

70 70
NC-70 NC-70
NC-65 NC-65
60 60
NC-60 NC-60
HH
NC-55 NC-55
50 50
HH NC-50 NC-50
Hi
Hi NC-45 Me
40 Me
NC-45
40 Lo
NC-40 NC-40
Lo
NC-35 NC-35
30 30
NC-30 NC-30
20 NC-25 NC-25
20
S-Lo NC-20 S-Lo NC-20
night shift night shift
10 NC-15 NC-15
10
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k
Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

Model:AVY-18* Power Supply: 220-240V/50Hz,220V/60Hz Model:AVY-24* Power Supply: 220-240V/50Hz,220V/60Hz


Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
Noise Criteria Curve Noise Criteria Curve
90 90
Octave Sound Pressure Level(dB: Overall C Scale)

Octave Sound Pressure Level(dB: Overall C Scale)

80 80

70 70
NC-70 NC-70
NC-65 NC-65
60 60
NC-60 NC-60
HH
NC-55 NC-55
50 50
HH NC-50 Hi NC-50
Hi NC-45 Me
40 NC-45
Me 40
NC-40 Lo NC-40
Lo NC-35
30 NC-35
30
NC-30 NC-30
20 NC-25 20 NC-25
S-Lo NC-20 S-Lo NC-20
night shift NC-15 night shift
10 10 NC-15
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k
Central Frequency(Cycle per Second) Central Frequency(Cycle per Second)

282
14.4 Component Data
Indoor Heat Exchanger and Fan
Model AVY-07* AVY-09* AVY-12* AVY-14*
Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0 7.0 7.0
Rows - 2 2 3 3
Fin Material Aluminum
Pitch mm 1.6 1.6 1.6 1.6
Maximum Operating Pressure MPa 4.15 4.15 4.15 4.15
Total Face Area m2 0.15 0.15 0.15 0.15
Number of Coil/Unit - 1 1 1 2
Indoor Fan Centrifugal Fan
Number/Unit - 2 2 2 2
Outer Diameter mm 130 130 130 130
Revolution 705/687/660/ 786/740/687/ 1100/934/887/ 1250/1059/934/
rpm 633/608/586 633/608/586 820/750/687 887/820/750

Nominal Air Flow 372/354/336/ 396/372/336/ 498/438/408/ 600/498/408/


m3/h
306/288/276 306/288/276 372/336/306 378/342/312
Indoor Fan Motor IP20
Starting Method - Control software
Nominal Output W 40 40 40 40
Quantity - 1 1 1 1
Insulation Class - E E E E

Model AVY-18* AVY-24*


Heat Exchanger Type - Multi-Pass Cross Finned Tube
Tube Material Copper Tube
Outer Diameter mm 7.0 7.0
Rows - 3 3
Fin Material Aluminum
Pitch mm 1.6 1.6
Maximum Operating Pressure MPa 4.15 4.15
Total Face Area m2 0.2 0.2
Number of Coil/Unit - 1 1
Indoor Fan Centrifugal Fan
Number/Unit - 3 3
Outer Diameter mm 130 130
Revolution 1159/980/890/ 1440/1196/1080/
rpm 843/803/710 980/855/750

Nominal Air Flow 726/594/528/ 936/756/672/


m3/h
492/468/396 594/504/426
Indoor Fan Motor IP20
Starting Method - Control software
Nominal Output W 60 60
Quantity - 1 1
Insulation Class - E E

283
14.5 Refrigeration Cycle

05~24Model

Indoor Unit

2
: Refrigerant Flow Direction (Cooling)
: Refrigerant Flow Direction (Heating)
: Field Refrigerant Piping
3 : Flare Connection

4
b

Refrigerant Liquid Pipe Connection


S

3 a

Refrigerant Gas Pipe Connection

Mark Part Name


1 Heat Exchanger
2 Distributor
3 Strainer
4 Micro-Computer Control Expansion Valve

284
14.6 Electrical Data

< 50 Hz >
Indoor Unit
Unit Main Power Applicable Voltage Indoor Fan Motor
Model
VOL PH HZ Maximum Minimum PH RNC IPT

AVY-07* 0.17/0.17 0.014/0.014


AVY-09* 0.17/0.27 0.014/0.024
1-Way 220
AVY-12* 1 50/60 264 198 1 0.27/0.37 0.024/0.034
Cassette ~240/
Type AVY-14* 220V 0.37/0.47 0.034/0.044
AVY-18* 0.37/0.47 0.034/0.044
AVY-24* 0.57/0.67 0.074/0.094

VOL: Rated Unit Power Supply Voltage (Plated)(V) RNC: Running Current (A)
PH: Phase (φ) IPT: Input (kW)
HZ: Frequency (Hz)

Safety and Control Device Setting

Model AVY-07~24*

For Control Circuit


A 5
Fuse Capacity
Freeze Protection
Thermostat ºC 0
Cut-Out
Cut-In ºC 14
Thermostat ºC 2
Differential

285
AVY-07~24*

WARNING
14.7 Electrical Wiring Diagram
Before inspecting the electrical parts set the Operation Switch to
OFF, and cut OFF the power supply.

PCB1

TB1

Factory Wiring
Earth Wiring
Field Wiring
Optional Parts
Field Connection

CN19

MD
CN3 PCN12 CN1 MS1~3
FFC

PCB2
Field Connection

Air Panel

Alarm

Note :
1.. All the field wiring and equipme
must comply with local codes.

Operation Line

286
14.8 Indoor Unit Optional Parts

Optional Parts Applied Indoor Unit Type

Type Model 1-Way Cassette Type

HYXE-F01H
HYXE-G01H
Wire Remote Control Switch HYXE-A01H#01
HYXE-J01H
HYXE-M01H ●
HYE-Q01
Wireless Remote Control Switch HYE-L01
HYE-W01 ●
HYRE-V01H
HYRE-T01H
Wireless Receiver Kit
HYRE-V02H
HYRE-X01H ●
7 Day Timer HYDE-E01H
HYJE-H01H
HYJE-D02H
HYJ-J01H
Centrol Station HCCS-H128H2C1YM
HCCS-H128H2C1NM
HCCS-H247R4C1E
HCCS-H128H2C2NM

HC-A64BNP
Interface for Building Control
HCPC-H2M1C
HCH-160D
Switch Box
HCH-280D
HZX-2.0AEC
HZX-4.0AEC
AHU Kits HZX-6.0AEC
HZX-10.0AEC
HZX-20.0AEC
HPS-162#E
Drain Pump HPS-132#E
HPS-151#E
HF-224L-FE
Long Life filter HF-280L-FE
HF-40L-ZFE
HP-DB-NK
3D Air Swing
HP-EB-NK

287
14.9

Air Panel(optional)
Indoor Unit Panel Selected
07~14 HP-D-NA
18~24 HP-E-NA

Screw 8

Magnet Ring 1

1 For Fixing Magnet Ring

288
14.10 Installation
14.10.1

below.

150mm Min. Service Hole(450Min.)

150mm Min.

500mm
Min.
1500mm Min. Piping
Connection

Distance From Wall Side

1,500mm Min.
150mm Min.
Piping
Connection Side

500mm Min.
150mm Min.
1,000mm Min.

Service Space

230mm Min.

289
14.10.2
● 14.10.3

Approx. 50
(mm)

below.
Bracket

28+3
(mm)

217
Dimension of Panel D
Dimension of Suspension Bolts C
Unit Size B Refrigerant
Outlet Pipe

20
Dimension of Panel 550

Suspension Bolts 450

Air Outlet

Unit Size 470


Dimension of

Dimension of
Opening 500
Indoor Unit

Panel
10

+20
Dimension of Opening A 0

Unit: mm
6L]HV $ % & '
0RGHO
$9<8;-6-$
$9<8;-6-$
   
$9<8;-6-$ (3) Use a gradienter or transparent plastic hose
$9<8;-6-$ filled with water to level the two directions of
$9<8;-6K$ indoor unit, length and width sides.
   
$9<8;-6K$

Suspension Bolt Gradienter

Suspension
Bracket

Piping
Connection
below. Side

For Concrete Slab For Steel Beam

Insert
150 to 160mm (100 to150kg) Transparent
Plastic Hose
Concrete
Steel
Anchor Bolt l Beam
(W3/8 or M10)
Suspension Bolt
(W3/8 or M10)

For Wooden Beam

Wooden Rib
(60 to 90mm square timber)
Nut Square Washer

If indoor unit is installed in a position inclined to


Square Washer
Nut the reverse direction, it may cause false
Wooden Beam Suspension Bolt
operation of float switch and there result in
leakage.

290
(4)
Pattern Board for Installation

Checking Scale 02
Checking Scale 01

● (2) Adjust the distance between indoor unit


and ceiling.
Adjust the indoor unit to a proper position
with the checking scale provided by the
Bottom View factory
(mm)

Ceiling
Air Outlet
Refrigerant Indoor Unit
Indoor Unit Outlet Pipe

Supported by
Dimension of
Opening Surface of Ceiling
Dimension of Opening

Connected to Indoor Unit

Side View
Fig. Adjustment of Distance to Indoor Unit
Suspension Bolt

(3) Cutting the Ceiling

Mount ceiling opening to the indoor unit with


screws (four) by using Pattern Board. Cut
the ceiling based on opening dimension of
the pattern board and mount the panel.

Adjustment Range
3-4mm

Panel Fixing Screw

Pattern Board

Bolt M6
(Panel Accessories)

After installation is completed, remove


the pattern board off the ceiling.

(1) Pattern Board for Installation is


provided in the packing,please cut it
off.

291
14.11

Pipe Diameter (a)


10A

Flaring
Diameter
(D)

below.
14.11.1

12.7mm 60

07 14

18

24

below.

14.11.2

below.
Drain Pipe Connection Liquid Pipe Connection Gas Pipe Connection
(PVC, VP25)

Flaring Dimension
Perform the flaring work as shown below.

292
14.12 P Drain Hose

Horizontal or Upward Slope


Drain pipe must be installed horizontally or in upward slope
to prevent occurrence of air column, or otherwise water will
flow from rear of the equipment to cause leakage or
abnormal noise when the equipment is shut down.

(a) Use the drain pipe and hose clamp provided


by the manufacture.
(b) Do not impose too much force on the pipe
joint to prevent damage to it.
(c) Do not use any bent or twisted pipe, which
may cause leakage.
(d) Complete insert the drain pipe provided by
the manufacturer, or otherwise leakage may
be caused.
Drain Hose(Accessory)
Hose Band(Accessory)
Tightening Torque 2.5~3.4(N.m)
Elbow or Polyvinyl Chloride VP25
Drain Pipe
Connection

2or2.5
20+5
Insert Drain Pipe Completely to No Adhesive Agent Polyvinyl Chloride-based
End of The Hose Connection to be Adhesive Agent
(Correct)

2
(Incorrect) Twisted and Incomplete Insertion

below.

Ceiling
1- 1.5m Suspension
Bracket
a c
b

≤ 300) ( ≤50 )
≤ 850

1/25 to 1/100
Down-Slope
115±4

(mm)

Drain Hose
(Accessory)

950mm.

293
14.13

14.13.1
● Turn OFF the main power switch to the indoor
unit and the outdoor unit and wait for at least 3
minutes before electrical wiring work or a
periodical check is performed.
● Check to ensure that the indoor fan and the
outdoor fan have stopped before electrical
wiring work or a periodical check is performed.
● Protect the wires,drain pipe, electrical parts,
etc. from rats or other small animals.
If not protected, rats may gnaw at unprotected
parts and at the worst, a fire will occur.
● Avoid any wire from contacting with
Refrigerant tube, edge of metal plate and
electrical part in the equipment, or otherwise
the wire may be damaged or even thereby
cause fire.
● ELB with intermediate induction rate (with
shorter than 0.1 second or fewer) shall be
used, or otherwise electric shock or fire may
be caused.
● Wire shall be fixed securely, since external
force imposed to the connecting terminal may
make it loose and thereby cause fire.
● Do not use the power terminal strip used for 14.13.2
the air conditioner to sub-connect any power
cable, but use power branch box to sub- below.
connect power wire at indoor unit side instead,
and be sure to calculate wire capacity, or
otherwise too low capacity may cause fire.
● The system shall not be started until all
inspections have been performed properly.

● Wrap the accessory packing around the wires,


and plug the wiring connection hole with the
seal material to protect the product from any
condensate water or insects.
● Tightly secure the wires with the cord clamp
inside the indoor unit.
● Secure the cable of the remote control switch
using the cord clamp inside the electrical box.
● Tighten screws according to the following
torque.
M4:1.0~1.3 N.m
M5:2.0~2.4 N.m
M6:4.0~5.0 N.m 14.15
M8:9.0~11.0 N.m
M10:18.0~23.0 N.m

294
Screw A (a) Remove electrical box cover (by loosening one
Screw B screw (A)).
Screw B
(b) Loosen two screws (B) on electrical box
component and pull out the component.
(c) Fix the wire harness from connecting port to
electrical box with cable clamp to prevent it
from scratched by edge of container of other
P component.
Cord Clamp
(d) Mount a magnetic ring to the communication wire,
Wire Hole which shall be wound by three circles around the
Base Board(two-layer)
wire and then fixed with cord clamp provided in the
accessory bag.
(e) Upon completion of wiring, mount electrical box,
and take care not to press any wire.

Electrical Box
Component •After wire is connected to terminal board, be
sure to fix it with cord clamp and lay the wire in
Electrical Box cable tray to prevent it from being squeezed and
Cover fire caused thereby.

Transmission Wiring 14.14

Power Source Wiring

Transmission Wiring
(between Indoor
Unit and Outdoor Unit)
R.C.S. Transmission

Remote Control
Switch Cable

Earth Screw

Power Source Wiring

295
14.15
14.15.1 14.15.2

DSW4(Unit Mode Code Setting)

Use an ELB (Electric Leakage Breaker).If not DSW3(Capacity Code Setting)

used ,it will cause an electric shock or a fire. DSW6(Unit No. Setting)

Run through the cables using conduit tube, RSW1(Unit No. Setting)
and Completely seal the end of conduit tube
DSW7(Fuse Recover)
with sealing materials.

MCA
EN60 335-1 *1 EN60 335-1 *1
RSW2(Refrigerant Cycle No. Setting)
07~09 0.3A
DSW5(Refrigerant Cycle No. Setting)

12 14 0.4A
2.5mm2 0.75mm2
18 0.5A 5

24 0.8A

The wire sizes marked with *1 in the above table are selected
at the maximum current of the unit according to the European
Standard, EN60335-1.Use the wires which are not lighter than
the ordinary polyvinyl chloride sheathed flexible cord
(code designation H05VV-F).
3

Ex.) Set at No.16 Unit


Setting Set by inserting DSW6
Position Slotted screwdriver
into the groove

3 2.5
Set No.1 Pin ON
3 6 2.5 Before shipment. DSW6 and RSW1 are set to "0".
6 10 2.5 Max.64 units are available to set when all the equipment
RSW1
to be connected are corresponding to Hi-NET.
10 16 4.0 Max.16 units when the units corresponding/
16 25 6.0 non-corresponding to Hi-NET are combined. Set at "6"
25 32 10.0
32 50 16.0
50 63 25.0
ON
2 OFF
of the indoor unit.

296
Capacity
14.16
×10 Btu/h
3 07 09 12

Capacity
×10 3Btu/h 14 18 24

outlet

Outlet

297
14.17
Left Side

Knobs (two)

14.17.1
Zoom-in
View of Knob
Right side

Remove the other filter screen in the same way.

14.17.2

Left Side
Knob

Right Side

14.17.3

14.18

Note:
There are two grilles on the panel of
HP-E-NA, which should be removed
respectively.

298
14.18.1

14.18.2

14.18.3

14.18.4

299