The Health & Safety Executive operates the ‘Gas Safe Register’,
a self-certification scheme for gas heating appliances.
The Benchmark Scheme This company is a member of the Benchmark initiative and fully
Benchmark places responsibilities on both manufacturers and installers. The supports the aims of the programme. Its aim is to improve the
purpose is to ensure that customers are provided with the correct equipment for standards of installation and commissioning of central heating
their needs, that it is installed, commissioned and serviced in accordance with the
systems in the UK and to encourage the regular servicing of all
manufacturer’s instructions by competent persons and that it meets the
requirements of the appropriate Building Regulations. The Benchmark Checklist central heating systems to ensure safety and efficiency.
can be used to demonstrate compliance with Building Regulations and should be
provided to the customer for future reference.
Building Regulations require that installations should comply
Installers are required to carry out installation, commissioning and servicing work with manufacturer's instructions. It is therefore important that
in accordance with the Benchmark Code of Practice which is available from the
Heating and Hotwater Industry Council who manage and promote the Scheme. the commissioning checklist is completed by the installer. The
Visit www.centralheating.co.uk for more information. relevant section of Building Regulations only relates to
dwellings. Therefore the checklist only applies if the appliance is
being installed in a dwelling or some related structure.
© Baxi Heating UK Ltd 2015 All rights reserved. No part of this publication may
be reproduced or transmitted in any form or by any means, or stored in any The flowchart opposite gives guidance for installers on the
retrieval system of any nature (including in any database), in each case whether process necessary to ensure compliance with Building
electronic, mechanical, recording or otherwise, without the prior written
permission of the copyright owner, except for permitted fair dealing under Regulations.
Copyrights, Designs and Patents Act 1988.
0086
ISO 9001
FM 00866
Choose Building
Regulations Notification
Route
Warning - Check the information on the data plate is compatible with local supply Where no specific instructions are given, reference should be
conditions. made to the relevant British Standard Code of Practice.
by the United Kingdom Competent Authority, and carrying the Notified Body
Number 0086.
General
The following advice should be adhered to, from when first handling the boiler to the final stages of installation, and also during maintenance.
Most injuries as a result of inappropriate handling and lifting are to the back, but all other parts of the body are vulnerable, particularly shoulders, arms and hands.
Health & Safety is the responsibility of EVERYONE.
There is no ‘safe’ limit for one man - each person has different capabilities. The boiler should be handled and lifted by TWO PEOPLE.
Wear appropriate Personal Protection Equipment e.g. protective gloves, safety footwear etc.
Preparation
Co-ordinate movements - know where, and when, you are both going.
Minimise the number of times needed to move the boiler - plan ahead.
Always ensure when handling or lifting the route is clear and unobstructed. If possible avoid steps, wet or slippery surfaces, unlit areas etc. and take special care
on ladders/into lofts.
Technique
When handling or lifting always use safe techniques - keep your back straight, bend your knees. Don’t twist - move your feet, avoid bending forwards and
sideways and keep the load as close to your body as possible.
Where possible transport the boiler using a sack truck or other suitable trolley.
Always grip the boiler firmly, and before lifting feel where the weight is concentrated to establish the centre of gravity, repositioning yourself as necessary. See the
‘Installation’ section of these instructions for recommended lift points.
Remember
The circumstances of each installation are different. Always asses the risks associated with handling and lifting according to the individual conditions.
If at any time when installing the boiler you feel that you may have injured yourself STOP !!
DO NOT ‘work through’ the pain - you may cause further injury.
IF IN ANY DOUBT DO NOT HANDLE OR LIFT THE BOILER - OBTAIN ADVICE OR ASSISTANCE BEFORE PROCEEDING !!
1.0 Introduction 7
9.0 Installation 23
10.0 Commissioning 28
11.0 Completion 31
12.0 Servicing 32
15.0 Electrical 44
18.0 Notes 52
Benchmark Checklist 54
1.1 Description
1. The Main Eco Elite Combi is a fully automatic gas fired wall
mounted condensing combination boiler. It is room sealed and
fan assisted, and will serve central heating and mains fed
Case Front Panel domestic hot water.
6. The boiler model name and serial number are also shown on
the information label on the back of the facia door. This is for
user reference.
Data Badge
Fig. 1 9. All systems must be thoroughly flushed and treated with
inhibitor (see section 6.2).
Information Label
1. Boiler Unit
2. Wall Plate (inc. taps)
3. Set of Pipes (inc. nuts)
4. Template
5. Literature Pack
7. Filling Loop
8. 24 hr. Electro - Mechanical Timer
2.1 Layout
1. Expansion Vessel
1
2. Automatic Air Vent
22
3. DHW Plate Heat Exchanger
14
4. Circulation Pump
9
21. Gas/Air Inlet
8
22. Burner Mounting Panel
23. Igniter
24. Burner On Light
25. Central Heating Mode Light
26. Domestic Hot Water Mode Light
12
27. Display
28. Position for Integral Timer
3
2
11
4
5
25 26 6
2
Reset
1 3
0 4
bar
17 27 24 18 19 8 28
8 © Baxi Heating UK Ltd 2015
3.0 Appliance Operation
1
Central Heating Circuit 3.1 Central Heating Mode (Fig. 2)
27
1. With a demand for heating, the pump circulates water
through the primary circuit.
2 2. Once main burner ignites the fan speed controls the gas
3 4 rate to maintain the heating temperature measured by the
26 7 temperature sensor.
20
5 6 3. When the flow temperature exceeds the setting
temperature, a 3 minute delay occurs before the burner
relights automatically (anti-cycling). The pump continues to
run during this period.
25
8 4. When the demand is satisfied the burner is extinguished
24
18
and the pump continues to run for a period of 3 minutes
22 (Pump Overrun).
9
11
23
21 10
3.2 Domestic Hot Water Mode (Fig. 3)
Fig. 2 2. The flow of water will operate the Hall Effect Sensor
which requests the 3 way valve to change position. This will
Key allow the pump to circulate the primary water through the
1 Primary Heat Exchanger DHW plate heat exchanger.
15 Domestic Hot Water Outlet
2 Burner
16 Heating Flow
3 Ignition Electrodes 3. The burner will light automatically and the temperature of
17 Pressure Gauge
4 Flame Sensing Electrode
5 Gas Valve
18 Water Pressure Sensor the domestic hot water is controlled by the temperature
20 Fan sensor.
6 Pump
21 Diverter Valve Assembly
7 Automatic Air Vent
22 Diverter Valve Motor
8 Plate Heat Exchanger/Automatic By-Pass 4. When the domestic hot water demand ceases the burner
23 Domestic Hot Water Flow Temperature Sensor
9 Flow Sensor with Filter & Regulator
10 Pressure Relief Valve
24 Safety Thermostat will extinguish and the diverter valve will remain in the
25 Central Heating Temperature Sensor domestic hot water mode, unless there is a demand for
11 Boiler Drain Point
26 Expansion Vessel
12 Heating Return central heating.
27 Heat Exchanger Air Vent
13 Cold Water Inlet On/Off Valve and Filter
14 Gas Inlet
IMPORTANT: When the selector switch is in the ‘0’
(Off) position the electrical supply to the boiler is isolated.
The boiler will not operate and the integral timer will
1 require resetting once the selector switch is set to either
Domestic Hot Water Circuit Position ( ) or Position ( ).
27
25
24 8 3.4 Pump Protection
18
1. With the selector switch (see Section 2.1) in either the
22
9 central heating or central heating and domestic hot water
11 position, the pump will automatically operate for 1 minute in
23
21 10 every 24 hours to prevent sticking.
17
16 15 14 13 12
Fig. 3
Appliance Type C13 C33 C53 Inlet Pressure (Natural Gas - G20) NOx Class 5
mbar 20
Appliance Category CAT I 2H Central Heating Primary Circuit
Injector (Natural Gas - G20) Pressures
Heat Input CH Qn Hs (Gross) 6.0mm bar
Max Min Safety Discharge 3
Electrical Supply 230V~ 50Hz Max Operating 2.5
25 model kW 28.92 8.68 (Appliance must be connected to an Min Operating 0.5
30 model kW 32.54 9.77 earthed supply) Recommended Operating Range 1-2
Heat Output CH Pn (Non-Condensing) Power Consumption DHW Circuit bar
Max Min 25 & 30 105W Pressures
25 model kW 25.94 7.61 Max Operating 8
Electrical Protection
Min Operating 0.15
30 model kW 28.63 8.56 IPX0D (with timer)
IPX4D (without timer) Flow Rates (25) (30)
Heat Output CH Pnc (Condensing) External Fuse Rating 3A l/min l/min
Max Min DHW Flow Rate
Internal Fuse Rating F2L @ 30o C Rise 11.9 14.3
25 model kW 26.95 8.37
Condensate Drain DHW Flow Rate
30 model kW 30.2 9.42 To accept 21.5mm (3/4 in) plastic waste pipe @ 35o C Rise 10.2 12.3
Flue Terminal Diameter 100mm Min Working
Heat Input DHW Qnw Hs (Gross)
Dimensions Projection 125mm DHW Flow Rate 2 2
Max
IMPORTANT: Where Low Flow Taps or Fittings are
25 model kW 28.92 Connections copper tails intended to be used in the DHW system connected it is
30 model kW 33.30 Gas Supply - 22mm strongly recommended that the DHW flow rate DOES
Central Heating Flow - 22mm NOT fall below 2.5l/min. This will ensure reliable
Central Heating Return - 22mm operation of the DHW function.
Heat Output DHW Max Cold Water Mains Inlet - 15mm
DHW Flow - 15mm Pump
25 model kW 24.88
Pressure Relief Discharge - 15mm Available Head See graph below
30 model kW 30.00
Expansion Vessel - (For Central Heating
Outercase Dimensions
only. Integral with appliance)
Max Gas Rate (Natural Gas - G20) Casing Height - 780mm
bar
(After 10 mins) Overall Height Inc Flue Elbow - 965mm
Min Pre-charge Pressure 0.5
Casing Width - 450mm
25 model m3/h 2.76
Casing Depth - 345mm
30 model 3
m /h 3.17 Max Capacity of litre
Clearances CH System 125
Above Casing 175 mm Min For greater system capacities an
300mm Min (80/125) additional expansion vessel MUST be fitted.
Product Characteristic Database Below Casing 200 mm Min Primary Water Content
(SEDBUK) Front 450 mm Min (For Servicing) of Boiler (unpressurised) 3.1
Front 5 mm Min (In Operation)
SAP 2009 Annual Efficiency Temperatures
L.H. Side 5 mm Min
C.H. Flow Temp (adjustable)
R.H. Side 5 mm Min (In Operation)
25 - 89.0 % 25°C to 80°C max (± 5°C)
30 - 88.7 % Weights 25 & 30
D.H.W. Flow Temp (adjustable)
This value is used in the UK Government’s Standard Packaged Boiler Carton 51.0 kg
35°C to 60°C max (± 5°C)
Assessment Procedure (SAP) for energy rating of Installation Lift Weight 45.0 kg
dependent upon flow rate
dwellings. The test data from which it has been
calculated has been certified by 0086.
Pump - Available Head
5.5
3.5
2.5
Metre (wg)
1.5
0.5
0
0 200 400 600 800 1000 1200 1400
10 © Baxi Heating UK Ltd 2015 Flow Rate (l/h)
4.0 Technical Data
See
The back cover for contact details.
Dimensions
A 780mm
At Least 1.5o G B 345mm
C 450mm
D 116mm Ø Min.
A
F 145mm
G 106mm
210mm (80/125)
H 225mm
B
360° Orientation
H
D
C
H
Tube Ø 100mm
F
Tap Rail
127 mm
Condensate
Drain
65 mm 65 mm 65 mm 65 mm 65 mm
6.1 Information
6.3 Bypass
1. The boiler utilises the primary side of the DHW plate heat
exchanger as an automatic integral bypass.
6.9 Showers
1. Only water that has NOT been artificially softened must used
when filling or re-pressurising the primary system. If the mains
cold water to the property is fitted with an artificial
softening/treatment device the source use to fill or
re-pressurise the system must be upstream of such a device.
175mm Min 1. The boiler may be fitted to any suitable wall with the flue
(300mm Min if passing through an outside wall or roof and discharging to
using 80/125mm atmosphere in a position permitting satisfactory removal of
flueing system) combustion products and providing an adequate air supply.
The boiler should be fitted within the building unless
otherwise protected by a suitable enclosure i.e. garage or
outhouse. (The boiler may be fitted inside a cupboard-see
Section 7.3).
450mm Min
For Servicing
Purposes
5mm Min
In Operation
Fig. 9
Zone 2
7.5 Electrical Supply
Window
Recess
Zone 1 1. External wiring must be correctly earthed, polarised and
in accordance with relevant regulations/rules. In GB this is
Zone 2
the current I.E.E. Wiring Regulations. In IE reference should
Zone 0
be made to the current edition of ETCI rules.
Fig. 12 In GB Only
Basement or similar
(heated)
vii) to a drain or gully with extended
Boiler external run & trace heating
50mm
per me
tre of
pipe ru
2.5° M n Pipe must terminate above
inimum water level but below
fall
surrounding surface. Cut
end at 45°
Fig. 13
T
J,K Air Inlet
U
Opening Window
or Door
150mm
MIN.
N
R D A
M C E
I I I I
S
F B
F J,K
L A
A
G H H
I
IMPORTANT
SUPPORT - All flue systems MUST be securely
supported a MINIMUM of once every metre. It is
recommended that every straight piece is supported
irrespective of length. Additional supports are available
as accessories.
VOIDS - Consideration must be given to flue systems
in voids and the provision of adequate access for
subsequent periodic visual inspection.
NOTE: Horizontal flue pipes should always be installed with at least a 1.5° fall
from the terminal to allow condensate to run back to the boiler. 6. Read this section in conjunction with the Flue Installation
Guide supplied with the boiler.
This bend is equivalent to
1 metre
C
A
(ii)
B
A+B+C+2x90°Bends
Ensure that no part of the white outer 2. There must be a clearance of at least 50mm between any
chimney duct is visible part of the terminal and the guard.
1. Push the flue deflector over the terminal end. It may point
upwards as shown, or up to 45° either way from vertical.
Secure the deflector to the terminal with screws provided.
Fig. 16
8.6 Flue Accessories (Fig. 16a)
G U I DA N C E N OT E S
Fig. 16a
The gas supply, gas type and pressure must be checked for
suitability before connection (see Section 7.4).
10. Using a spirit level ensure that the plate is level before
finally tightening the screws.
For Side Flue Exit
11. Connect the gas and water pipes to the valves on the
wall plate using the copper tails supplied. Ensure that the
Fig. 19 sealing washers are fitted between the connections.
Wall Plate
Flushing Tube 12. Fit the filling loop as described in the instructions
supplied with it.
9.2 Flushing
Fig. 20
Central Heating Return
Sealing 3. Insert the sealing washers between the valves and pipes
Washers on the wall plate and the boiler connections.
Discharge Pipe
m
5m 9.6 Fitting The Flue
31
‘TOP’ Label
’
ion ‘Y
ens
Dim
Securing Screw
Sealing Tape
Fig. 25 Fig. 26
‘TOP’ Label
12. Two flue trims are supplied, one for internal use, the
Fig. 27 other for outside. The internal trim is packaged and
identified as such - it should not be used externally.
Fig. 28 16. Secure the elbow flue to the boiler adaptor with the
Flue to elbow screws supplied in the boiler fittings pack (Fig. 28).
securing screws
IMPORTANT: It is essential that the flue terminal is fitted
as shown to ensure correct boiler operation and prevent
water entering the flue.
Elbow to adaptor 17. Make good between the wall and air duct outside the
securing screws building, appropriate to the wall construction and fire rating.
Slots at bottom
Fig. 29
Fused Spur
L N 8. Replace the terminal block cover, routing the external
control input cable(s) through the second cut-out.
Room ‘Stat
230V
Fig. 33 N
br
L
8. Pressurise the system to 1.5 bar (Fig. 36) then close and
disconnect the filling loop.
14. The display will now alternate between ‘SF’ and the current
boiler temperature and both green LEDs will flash.
16. The display will show ‘00’, indicating maximum rate, then
revert to ‘P ‘ alternating with the current boiler temperature.
No
1. Ensure that all controls are calling for heat, and the selector
switch is in the central heating and hot water position ( ).
The current boiler temperature is shown on the display.
Central Heating Domestic Hot Water
Temperature Control Fig. 38 Temperature Control 2. It is necessary to set the boiler to ‘Calibration Mode’.
0 4
bar
4. The display will now alternate between ‘SF’ and the current
boiler temperature and both green LEDs will flash (Figs. 63 &
64).
Central Heating Domestic Hot Water
Temperature Control Temperature Control 5. Turn CH temperature control knob fully clockwise. As the
knob is turned the display will change from ‘0’ to ‘00’ (Fig. 65)
indicating maximum rate, then revert to ‘P’ alternating with the
current boiler temperature (Figs 66 & 67).
7. Ensure that this inlet pressure can be obtained with all other
gas appliances in the property working.
Gas Pressure
Test Point
Measure the Gas Rate
8. With any other appliances & pilot lights turned OFF the gas
Fig. 39 rate can be measured. It should be between:-
Gas Valve
25 model 2.76 m3/h
30 model 3.17 m3/h
Fig. 43 Fig. 44
11.1 Completion
Case Front Panel 1. Instruct the user in the operation of the boiler and
system including the integral timer, explaining the
operational sequence.
Facia Panel
Fig. 45
12 .1 Annual Servicing
Case Front Panel 1. For reasons of safety and economy, it is recommended that
the boiler is serviced annually. Servicing must be performed by
a competent person in accordance with B.S. 7967-4.
5. Remove the plug from the flue sampling point, insert the
analyser probe and obtain the CO/CO2 ratio. This must be
less than 0.004.
4. Remove the screws securing the inner door panel. Lift the
panel slightly to disengage it from the studs on top of the case
(Fig. 47).
Gas/Air Inlet
12.0 Servicing
6. Undo the nut on the gas pipe at the gas/air inlet (Fig. 49)
and the gas valve. Remove the pipe, taking care not to lose
Gas Pipe the sealing washers. Also remove the injector.
8. Undo the screw securing the fan air inlet pipe to the
Fan Air Inlet Pipe bracket on the boiler top panel. Remove the pipe (Fig. 50).
9. Undo the five retaining nuts and washers and remove the
fan, gas/air inlet and burner assembly (Figs. 51).
DHW Filter
13. If the flow of domestic hot water is diminished, it may
be necessary to clean the filter.
15. Turn the tap off and draw off from a hot tap. Undo the
blanking cap and remove the threaded bush
(Fig. 52).
Fig. 51
Fan, Gas/Air Inlet & 16. Extract the filter and rinse thoroughly in clean water.
Burner Assembly Reassemble and check the flow. If required clean the
Fig. 52 restricter filter as described below.
Threaded Bush
17. Pull off the Hall Effect sensor. Undo the restricter from
the inlet/return manifold (Fig. 53).
Hall Effect 19. Turn the selector switch fully anticlockwise against the
Sensor spring pressure to the reset position and hold for 5 seconds
to reset the boiler.
Blanking Cold Water 20. Complete the relevant Service Interval Record section of
Cap Inlet Tap the Benchmark Commissioning Checklist at the rear of this
publication and then hand it back to the user.
Restricter
Hydraulic Inlet
Assembly
Fig. 53
Filter
Sealing
Gasket
Spark
Electrode
Electrode
Leads
Fig. 55
1. Undo the nut on the gas pipe at the gas/air inlet (Fig. 56)
and the gas valve. Remove the pipe, taking care not to lose
the sealing washers. Also remove the injector.
Gas Pipe 2. Disconnect the electrode lead caps, remove the strain
relief clip from the sensing lead and disconnect the lead.
Remove the fan electrical plugs and pull the sensing pipe off
the fan.
Fig. 56
3. Undo the screw securing the fan air inlet pipe to the
bracket on the boiler top panel. Remove the pipe (Fig. 57).
4. Undo the five retaining nuts and washers and remove the
fan, gas/air inlet and burner assembly (Fig. 58).
5. Remove the air box and gasket from the fan and transfer
to the new fan. Examine and replace the gasket if necessary.
6. Remove the four nuts and separate the fan from the
gas/air inlet. Note the position of the orifice plate and
examine the gasket, replacing if necessary (Fig. 58).
Fan Air Inlet Pipe
7. Fit the new fan, ensuring that the orifice plate is correctly
Fig. 57 fitted, and that the gasket is in position.
Gasket
Orifice Plate
Air Box
Gasket
Fig. 58
Fan
1. Undo the nut on the gas pipe at the gas/air inlet and the
gas valve. Remove the pipe, taking care not to lose the
sealing washers. Also remove the injector.
3. Undo the screw securing the fan air inlet pipe to the
bracket on the boiler top panel. Remove the pipe.
4. Undo the five retaining nuts and washers and remove the
fan, gas/air inlet and burner assembly.
6. Fit the new burner and gasket, examine the insulation and
heat exchanger gasket, replacing if necessary.
1. Undo the nut on the gas pipe at the gas/air inlet and the
gas valve. Remove the pipe, taking care not to lose the
sealing washers. Also remove the injector.
3. Undo the screw securing the fan air inlet pipe to the
bracket on the boiler top panel. Remove the pipe.
4. Undo the five retaining nuts and washers and remove the
fan, gas/air inlet and burner assembly.
Electrode Assembly
5. Remove the electrode assembly and draw the insulation
piece away. Replace the insulation and reassemble in
Fig. 59 reverse order. Examine the heat exchanger gasket and
replace as necessary.
1. Drain the boiler primary circuit. Pull the plug off the safety
Fig. 60 thermostat and disconnect the in-line plug in the sensor wire.
1. Turn off the mains cold water supply tap and draw off the
residual domestic hot water.
4. Reassemble in reverse order. The plug will only fit one way.
Pressure Sensor
Plate Heat
Exchanger
Fig. 62
DHW Temperature
Sensor
© Baxi Heating UK Ltd 2015 37
13.0 Changing Components
Heat Exchanger
Air Vent
13.11 Heat Exchanger Automatic Air Vent (Fig. 63 )
Pump Body
3. Reassemble in reverse order.
2. Undo the two screws securing the body to the pipe and
manifold and draw the pump forwards.
Pump Head 4. Examine the ‘O’ ring seals on the return pipe and manifold,
replacing if necessary.
Fig. 64
6. Fit the air vent to the pump body and reassemble in reverse
order.
Automatic Air
1. Drain the boiler primary circuit and unscrew the automatic
Vent
air vent from the pump body.
Fig. 65
3. Connect the plug to the new sensor. Carefully fit the new
Fig. 67
Pressure Gauge sensor to the hydraulic assembly, ensuring it is fully down.
Capillary
Hall Effect
Sensor 14.17 Pressure Relief Valve (Fig. 69)
4. Fit the new valve and ‘O’ ring seal and set to the
previously noted orientation. Reassemble in reverse order.
Fig. 68
Grub Screw
Pressure Relief Valve
Fig. 69
Discharge Pipe
Plate Heat Exchanger 1. Drain the boiler primary circuit and remove the gas valve
as described in section 13.23.
Seals
4. There are four rubber seals between the manifolds and
LH Location Stud
heat exchanger which may need replacement.
6. When fitting the new heat exchanger note that the left
hand location stud is offset towards the centre more than the
right hand one.
2. Pull off the retaining clip and remove the motor unit.
Motor Unit
Retaining Clip 4. Drain the primary circuit and draw off any hot water once
the isolating taps are closed.
5. Undo the nuts on the tap rail under the boiler. Remove
Valve the screws securing the valve assembly to the boiler bottom
Assembly panel and plate heat exchanger.
3. Note the position of all plugs and wires on the P.C.B. and
disconnect them.
2. Note the position of all plugs and wires on the P.C.B. and
disconnect them. Undo the securing screws and remove the
Drive Pins P.C.B.
1. Turn the gas cock off and undo the nut on the gas feed
elbow under the boiler.
3. Pull off the power lead, earth lead and sensing pipe.
Earth Lead
4. Undo the nut on the gas pipe at the gas/air inlet and the gas
valve. Remove the pipe, taking care not to lose the sealing
Gas Feed washers. Remove the valve.
Elbow
1. Drain the boiler primary circuit and undo the nut on the
Fig. 75 vessel connection pipe.
Retaining Bracket
2. Remove the screw retaining the air inlet pipe, and swing the
pipe to one side.
Spring
Washer
Lock Nut
Boiler Chassis
Fig. 76
2
Reset
1 3 2. Ensure that all external controls are calling for heat. The
0 4
bar
actual current boiler temperature is shown on the display.
4. The display will now alternate between ‘SF’ and the current
boiler temperature and both green LEDs will flash (Figs. 78 &
79).
7. Remove the plug from the flue adaptor test point. Insert the
analyser probe and allow time for the reading to settle (Fig.
Fig. 80 Fig. 81 Fig. 82 83).
The CO2 should be 9.0% + 0.0 - 0.4 (25)
Flue Adaptor Test
The CO2 should be 9.1% + 0.0 - 0.4 (30)
Point
Plug
8. It is possible to alter the CO2 by adjustment of the gas valve.
Remove the plastic cover from the Throttle Adjustment Screw.
Analyser Probe At maximum rate the Throttle Adjustment Screw should be
turned, using a suitable hexagon key, until the correct reading is
Fig. 83
obtained (Fig. 84). Turning clockwise will reduce the CO2.
Anticlockwise will increase the CO2.
Offset 9. The CO2 must then be checked at minimum rate. Turn the
Adjustment Screw CH temperature knob fully anticlockwise. As the knob is
Throttle
(cap fitted)
Adjustment Screw turned the display will change, indicating the fan speed. When
(cover removed) the display reads ‘ 0’ the boiler runs at minimum rate.
Reduce CO2 Increase CO2 Reduce CO2 Increase CO2 10. With the boiler on minimum, the ‘Min. Rate’ adjustment
at min. rate at min. rate at max. rate at max. rate screw must be altered, using a suitable hexagon key, after
removing the cap (Fig. 84). If the CO2 is reset at either boiler
Gas Valve Fig. 84
rate it must be rechecked at the other rate and also adjusted if
If the CO2 is reset at minimum required.
rate it must be rechecked at
maximum rate again and adjusted Do not turn the adjustment
11. The ‘Calibration Function’ is maintained for 20 minutes
if required. If the CO2 is reset at screws more than 1/8 of a turn at
unless the maximum CH temperature is exceeded. The
maximum rate it must be a time. Allow the analyser reading
function can be disabled at any time by turning the DHW
rechecked at minimum rate and to settle before any further
knob.
adjusted if required. adjustment
12. Check the Combustion Performance (CO/CO2 ratio).
This must be less than 0.004.
© Baxi Heating UK Ltd 2015 43
15.0 Electrical
Central Heating
NTC Sensor
DHW gr gr
NTC Sensor Overheat Stat
Hall Effect
Sensor
b
Water Pressure b
Switch 1
r 4
g r 2
r br bk 5
w
b b g 3 Fan
g
1
2
b
g/y
b
b br
bk
4
3
X400 2
X401 1
9 87 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1
bk
4
Control PCB br
3
bk
2
X501
b
1
X9
g/y
1 2 1 2 3 4 5 1 2 3 4 5 6 7 8 9
X1 X2 X3
Pump
PCB b br
r bk
br br b
6 Way
b b
Connector bk
Pump
br bk w
br
b r
X1
br
b
X2 X3
w
r
Spark
L
N Generator bk
br b a b
b Diverter Valve
br
bk
br
br
br
Gas Valve
bk
b
Link
g/y b Ignition
br Electrode
bk
Mains Input Cable
r
br - brown g - green
bk - black g/y - green / yellow
b - blue r - red
w - white gr - grey
326
404 419
421 NTC Sensor DHW 5114725
422
420 Overheat Thermostat 5114729
415
505
421
420
503
504
6. Ensure all external controls are calling for heat and check
all external and internal fuses. Before any servicing or
replacement of parts, ensure the gas and electrical supplies
are isolated.
4. If this does not have any effect, or the codes are displayed
regularly further investigation is required.
YES
NO
YES
Error 20, 28 or 50 flashing Go to section ‘E’
NO
YES
Error 119 flashing Go to section ‘C’
Ensure controls are set to
demand and verify the
NO NO contacts are closed
YES
Ensure that primary
YES
Error 125 flashing circulation is OK & that
there is no blockage
NO
YES
YES
Go to section ‘F’
YES
NO
YES Burner does not stay alights YES Error 133 flashing
Burner lights
after 5 seconds Go to section ‘I’
YES
YES
Error 110 flashing YES Turn the selector switch to YES If the error 110 is still flashing.
Error 133 flashing reset position for 5 seconds Go to section ‘J’
NO
YES
Error 20, 28 or 50 flashing Go to section ‘E’
NO
YES
Error 119 flashing Go to section ‘C’
NO Go to section ‘B’
Turn Domestic Hot Water YES
thermostat to Maximum.
Open DHW tap fully. Is mains water filter and
DHW Hall Effect sensor NO YES assembly clean?
DHW flow rate more than 2
operated (red neon on the Is the magnetic detector free
l/min
sensor illuminated to move in the Hall Effect
YES sensor
YES
NO Error 125 flashing
Pump runs Go to section ‘B’
YES
NO Error 160 flashing
Fan runs
Go to section ‘D’
YES
YES
Go to section ‘F’
YES
NO
YES Burner does not stay alights YES Error 133 flashing
Burner lights
after 5 seconds Go to section ‘I’
YES
NO Reduce DHW flow rate NO Clean DHW NTC sensor
Burner output modulates to
maintain the temperature set Burner modulates and DHW heat exchanger
YES
NO
1. Main terminals L and N Check electrical supply
NO
2. Main terminal fuse Replace fuse NO
Display
Replace PCB
NO illuminated
3. Check wiring
PCB - X1 connector
terminals 1,2
NO
1. X3 Connection Pump PCB Check incoming wiring
YES
NO
X2 Connection Pump PCB Replace Pump PCB
YES
NO
X1 Control PCB Check wiring
YES
NO
X3 Control PCB, T3, T4 Replace Control PCB
YES
NO
X1 Pump PCB Replace Pump PCB
YES
Replace Pump
D 1.
Fan connections correct at fan. PCB -
X2 connector, is 230V AC across
YES
Fan jammed or faulty winding
YES
Replace fan
terminals 5 & 7
NO
Replace PCB
F 1.
Check and correct the connection of the
tube between the venturi and gas valve
NO
2. Gas at burner Ensure gas is on and purged
G 1.
Ensure that the Hall Effect Sensor is in position. YES Check the voltage between red wire and blue
Check the connection between the PCB - X400 wire is more than 5V DC
connector terminals 3,6,7 and the electronic sensor
NO YES
YES
Replace PCB
YES
1. Motor 3-way valve Replace motor 3-way valve
L 1.
Fan connections correct at fan. YES
Replace fan
PCB - X401 connector terminals 5,6,7 & 8
M 1.
Temperature sensors faulty.
Cold resistance approximately NO
Replace sensor
10k @ 25° C (CH sensor)
(resistance reduces with increase in temp.)
YES
2. Replace heat exchanger
If pump is running the heat exchanger could be
obstructed
This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating
compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.
Failure to install and commission according to the manufacturer’s instructions and complete this Benchmark Commissioning Checklist will invalidate the
warranty. This does not affect the customer’s statutory rights.
ALL SYSTEMS
’s instructions Yes
What system cleaner was used?
What inhibitor was used? Quantity litres
Yes No
ALL INSTALLATIONS
At max. rate: CO ppm AND CO/CO² Ratio
Record the following:
At min. rate: (where possible) CO ppm AND CO/CO² Ratio
The heating and hot water system complies with the appropriate Building Regulations Yes
The boiler and associated products have been installed and commissioned in accordance with the manufacturer’s instructions Yes
The operation of the boiler and system controls have been demonstrated to and understood by the customer Yes
The manufacturer’s literature, including Benchmark Checklist and Service Record, has been explained and left with the customer Yes
*All installations in England and Wales must be to Local Authority Building Control (LABC) either directly or through a
Competent Persons Scheme. A Building Regulations Compliance will then be issued to the customer.
54
© Heating and Hotwater Industry Council (HHIC) www.centralheating.co.uk
SERVICE RECORD
It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed.
Service Provider
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s instructions.
Signature Signature
Signature Signature
Signature Signature
Signature Signature
Signature Signature
*All installations in England and Wales must be to Local Authority Building Control (LABC) either directly or through a
Competent Persons Scheme. A Building Regulations Compliance will then be issued to the customer.
55
© Heating and Hotwater Industry Council (HHIC) www.centralheating.co.uk
Baxi Customer Support
0344 871 1525
Opening hours
Monday - Friday, 8.00am-6.00pm
Weekends and Bank Holidays, 8.30am-2.00pm
Please note calls may be recorded for training and monitoring purposes
baxi.co.uk
Baxi
Brooks House,
Coventry Road,
Warwick, CV34 4LL
0086
e&oe
All descriptions and illustrations provided in this document have been
carefully prepared but we reserve the right to make changes and
improvements in our products which may affect the accuracy of the
information contained in this leaflet. All goods are sold subject to our
standard Conditions of Sale which are available on request. part of