8. Guaranteed Technical Particulars (GTP) for Harmonic & Power Quality Analyzer
(To be filled up with the Sealed & Signed by both manufacturer and bidder in Manufacturer’s Letterhead Pad, otherwise the bid will be
rejected)
Bidder’s
Sl.
Description Required Specification Guaranteed
no.
Particulars
8 Features Display TFT, 1024 x 600 pixels with capacitive touch that
supports operation with PPE gloves user configurable
Voltage source measurement 0 to 1000 volts 3 phases and
neutral, in put impedance 10 MΩ between P-P and P-N, 5
MΩ between P-PE and N-P
Current Inputs 3 phases and neutral wit clamps with 15 mV
output or Rogowski Coil 15 mV input impedance 11 kΩ
Bandwidth DC to 30 kHz
Measurement IEC 61010-2-030: Overvoltage CAT IV 300
V, CAT III 600 V
Trigger Adjustable Volts, current, frequency, power, reactive
power,
Data Storage 8 GB or more Internal 64 GB or more micro
SD card 10 logging sessions of 8 weeks with 1minute
intervals and100 events
Real-Time Accuracy <1 ms absolute to UTC
Harmonics ih0 to ih50
Events, Voltage Dip, swell, interruption, rapid voltage
change, wave shape deviation, transients Current Inrush
current
Triggered Recordings Half cycle RMS of voltage and
current for 10 s
Transients 1 MS/s
Ethernet 1 Gbit/s 1000BASE-T
USB 2.0 high speed for USB flash drives to transfer
measurement data, firmware updates, and license installation
9 Environment -10 to 60°C, indoor/outdoor in fair weather
al Conditions Humidity <95% non-condensing
Altitude <3300 ft (1000 meters)
10 Warranty Standard one year