Professional Documents
Culture Documents
Heat Trace
PSD 179
Systems
JULY/AUGUST 2011
PSDMAGAZINE.ORG
CONTINUING EDUCATION
INTRODUCTION and insulation contractors must be made aware of the specific require-
A hot water self-regulating heat trace system can be used for prompt ments affecting each other’s work.
delivery of hot water at the fixtures. A heating cable system is one of The information in this chapter will help the designer understand
several accepted methods of providing prompt delivery of hot water. electric heat tracing as it applies to hot water systems. With this infor-
(See Chapter 14.) mation, a designer should be able to:
Today’s buildings are more architecturally complex than those built 1. Compare the merits of heat tracing and a recirculation system
a decade ago and make ever increasing demands on the interstitial based on the requirements of a specific project.
space occupied by HVAC ductwork, mechanical piping, communica- 2. Identify the extent of piping requiring heat tracing.
tion wiring, and electrical conduits. This, combined with the need to 3. Understand the role of thermal insulation in hot water heat tracing.
conserve energy and water, challenge engineers to provide cost-ef- 4. In coordination with an electrical engineer, determine the circuit
fective, energy-efficient domestic hot water systems. Maintaining the breaker/power requirements based on the estimated heat tracing
temperature of a domestic hot water system may entail establishing circuit lengths.
a means to continuously recirculate the water via pumps, valves, and 5. Translate the design requirements into a complete design for a
additional piping. An alternative method is to use self-regulating heat project.
trace systems. All examples and descriptions in this chapter are based on copper
Water conservation has become a major concern in the past few water piping with fiberglass thermal insulation and other typical
years. The need to conserve water has led to requirements for the use design conditions. While design parameters may differ and pipe and
of low-flow fixtures, including faucets, showers, and water closets. The insulation materials other than those discussed can be and frequently
water wastage that occurs when cooled water is dumped down the are equipped with heat tracing, such jobs should be undertaken with
drain while the user is waiting for hot water to flow can no longer be tol- the design assistance of a qualified manufacturer’s representative.
erated. In addition to wasting a precious resource, this practice incurs
PRODUCT DESCRIPTION
extra energy costs to heat the water and waste treatment costs to pro-
Only Underwriters Laboratories, Inc., listed electric heat tracing systems
cess the wasted water. The ability to keep a pipe warm close to the point
for hot water temperature maintenance should be used. (Note: Thirty
of use is of particular interest with the low-flow fixtures used today.
mA ground fault equipment protection is to be used for all hot water
Variables affecting the performance of a heat trace system include:
heat tracing circuits.) These tested and approved systems are based
the system temperature range, time to tap, water wastage, and energy
on self-regulating heating cables that are specifically designed for hot
efficiency. Designers should consider these factors along with instal-
water temperature maintenance. (See Figure 15.1.) Heat is delivered
lation and life-cycle costs when selecting the proper hot water self-
through a carbon matrix heating element that responds to temperature
regulating heat trace system for a particular building.
changes. Whenever the temperature in the heat traced piping begins to
SYSTEM DESCRIPTION rise, the cable automatically reduces its heat output. Conversely, when
Electric heat tracing systems replace heat lost through the thermal the water temperature begins to drop the cable reacts by increasing its
insulation on hot water supply piping to maintain the water at desired heat output. This self-regulating feature occurs along the entire length
nominal temperatures, eliminating the need for insulated recirculation of a heat tracing circuit to ensure that each point receives the amount
lines, pumps, and balancing valves. Preventing the hot water from cool- of heat necessary to maintain thermal equilibrium.
ing also ensures that hot water is readily available when it is needed. Heating cables, self-regulating or otherwise, intended for pipe freeze
An electrical heat tracing system is not a substitute for a complete, protection or general temperature maintenance should not be used for
efficient domestic hot water system. It does not eliminate the need for hot water temperature maintenance, since their performance has not
an efficient water heater. What a heat tracing system does is provide been matched to the requirements of hot water applications.
another approach to the design and installation of a hot water system.
SYSTEM COMPONENTS
It does this by simplifying the hot water distribution system, thereby
A hot water temperature maintenance system (such as the one shown
minimizing the amount of piping required. Items such as additional
in Figure 15.2) typically includes the following components:
piping and balancing valves are unnecessary.
1. Self-regulating heating cable.
In a heat trace system, a self-regulating heating cable is attached
2. Power connection kit.1
directly to the hot water supply piping and insulated. A self-regulating
3. Tee/inline splice kit (permits 2 or 3 cables to be spliced together).
heating cable adjusts its power at each point along its length to main-
4. Cable end termination.
tain nominal temperature throughout the piping system. Electrical
5. Attachment tape (secures cable to pipe, use at 12 to 24 in. [305 to
energy input is controlled by the cable’s construction to maintain the
610 mm] intervals).
required water temperature at the fixtures. No return piping or circula-
6. Electric heat tracing label (peel and stick label that attaches to
tion pump is required.
insulation vapor barrier at 10 ft [3.05 m] intervals, or as required
Successful installation of a heat tracing system requires coordina-
by code or specification).
tion among the various tradespeople involved. Plumbers and electrical
7. Fiberglass thermal insulation and vapor barrier.2
Note: All decimal equivalencies in the metric calculations are rounded. Therefore, the metric conversions shown in the text may vary slightly from the
answers shown in the metric equations.
Table 15.2(M) Water Wasted While Waiting for Hot Water to Reach
Fixture (mL)
Nom. Diam. Distance from End of Temperature Maintenance to Point of Use
Type L (m)
Copper
4.6 6.1 7.6 9.1 12.2
DN22 1420 1895 2365 2870 3815
Source: Courtesy of Thermon Manufacturing Co. Figure 15.3 Symbols Used to Indicate Components of a
Notes: Heat Traced Hot Water Supply System.
1. Remember to add up all the fixtures in a facility and to multiply by both the
waste number shown and the expected number of usages per day. Source: Courtesy of Thermon Manufacturing Co.
2. Numbers based on line diameter and distance from end of temperature Note: The numerals inside the symbols refer to circuit numbers.
maintenance.
Multiple Temperature Systems based on the desired maintenance temperature. If temperatures differ
For systems requiring multiple temperatures, heating cable can be from those shown, contact the manufacturer.
installed on the supply piping after the mixing valve to maintain the
CHOOSING THE RIGHT CABLE
different temperatures independently.
After determining the extent of the hot water supply piping to be heat
Remodels and Additions traced, the designer should decide the lengths to be maintained at 105,
For buildings with existing return systems, heating cable systems can be 120, and/or 140°F (42, 49, and/or 60°C). At this point, the total length
installed in the additions so that hot water temperature is maintained of each type of heating cable can be determined. Using the manufac-
in the new piping without affecting the performance of the existing hot turer’s published maximum circuit length for the desired temperature
water systems. cable, the designer can figure the required number of circuits. These
maximum circuit lengths should not be exceeded; otherwise, there will
COORDINATING DESIGN INFORMATION be excessive electrical currents in the bus wires of the heating cable.
To get the most from each heat tracing circuit, the designer should The maximum circuit length is the total length of cable that can be fed
establish the maximum circuit length based on the number of circuit from a single power connection point, inclusive of all splices, includ-
breakers available for the project. (Note: Maximum circuit lengths ing tees. Note that circuit lengths that are longer than these maximum
vary according to the voltage and temperature selection.) Regardless lengths may require larger circuit breakers. The designer must be sure
of a building’s shape and size, it is recommended that the heat tracing to check with the electrical engineer the available amperages of the
circuits be organized to follow the layout of the cable. For ease of iden- branch circuit breakers supplying power to the heat tracing. After the
tification during the layout process and for effective communication, required number of circuits is determined, that information should
the designer should identify the piping requiring heat tracing on the also be checked with the electrical engineer. This will ensure that the
plumbing drawings. While indication of the heating cable, power con- proper number of circuits has been allotted in the power distribution
nection, end termination, and tee splice kits is given on the plumbing system.
drawings, only the power connection points need to be referenced on
the electrical drawings. THERMAL INSULATION
The symbols shown in Figure 15.3 are routinely used to indicate While frequently overlooked, thermal insulation plays a critical role in
components of a heat traced hot water supply system. ensuring that hot water is available at the point of use. This is true for
both recirculation and heat traced hot water systems.
DETERMINING THE TEMPERATURE TO MAINTAIN The standard design for heat traced piping (the design that manufac-
The desired temperatures for most applications are given in Table 15.3 turers’ design guides are based on) utilizes fiberglass thermal insula-
along with the ambient temperature ranges of the space surrounding tion with a kraft paper vapor barrier. Thicknesses range from 1 to 2 in.
the insulated pipe. The appropriate self-regulating cable is chosen (25.4 to 50.8 mm) based on line diameter. If a heat traced hot water
Figure 15.4 Partial Simplified System Typical of Hospitals, Correc- HOT WATER HEAT TRACING TERMS
The following terms apply to all hot water heat tracing systems and
tional Facilities, and Hotels.
may aid in the selection of the appropriate system for each project.
Source: Courtesy of Thermon Manufacturing Co. 1. System temperature range. For a return system, this is the
system is designed to use only one cable for each temperature range, allowable temperature drop to the end of the system plus any
the thickness of the insulation will vary. additional variability caused by improper system balancing. With
Manufacturers of hot water heat tracing systems have established return systems, there is a trade-off between desired system per-
insulation schedules that outline the thicknesses required to keep the formance and the life-cycle cost of the system. For a heating cable
heat loss within the desired range. Note that in these schedules the system, the system temperature range is the range around the
insulation on piping 1 ¼ in. (DN35) in diameter and smaller is over- nominal maintenance temperature.
sized to allow space for the heating cable. 2. Unheated distance. This is the distance in feet (meters) between
After the installation of the heating cable and thermal insulation the last maintained leg of hot water piping and the point of use.
is completed, the piping is identified with stick-on labels to note the For example, if hot water temperature is maintained only for the
presence of electric heat tracing. This labeling gives notice to facility main run, the distance from the main to the point of use is the
maintenance workers that heating cable has been installed under the unheated distance.
insulation should any pipe maintenance or renovations be required. 3. Time to tap. This is the time required for hot water to reach the
fixture when the fixture is turned on. If the hot water temperature
HEAT TRACING HOT WATER PIPING
is not maintained all the way to the fixture, the cold water in the
The design of a heat tracing temperature maintenance system for mains
pipe must be drawn out before the user gets hot water. The length
and branch lines can be done on the plumbing drawings. (See Figure
of the wait is called time to tap. It is a function of the unheated
15.4.) By referring to the manufacturer’s heating cable selection chart
distance, the gpm (L/sec) flow rate, and the diameter of the pipe.
for the desired maintenance temperature, the designer can determine
the maximum heating cable circuit length for circuit break-
ers of different sizes. Taking this information into account
when laying out the hot water lines will ensure optimum
use of the circuit lengths.
Note, in Figure 15.4, that the main and branch lines are
heat traced and insulated while the short runouts are only
insulated. (Runouts that feed individual points of use typi-
cally contain less than ½ gal [1.89 L] of water. If the faucet
flow rate is above 1½ gpm [0.1 L/sec], hot water will reach
the point of use within 10 sec.) If the distance between the
branch line and the point of use is much longer than 40 ft
(12.19 m) or the flow rate is lower, the potential for water
wastage and the time required for hot water to reach the
point of use may be beyond the levels considered accept-
able for the facility. To remedy this situation, simply heat
trace closer to the point of use.
COMBINING HORIZONTAL MAINS WITH
SUPPLY RISERS
Designers of multilevel facilities often duplicate floor
plans over several levels, which simplifies the layout of
electrical, HVAC, and mechanical equipment. This practice
Figure 15.5 Typical Layout for 2 to 4-Story Hos-
also simplifies the layout of hot water supply lines, unless
there is a maze of recirculation piping and balancing valves
pitals, Research Labs, Correctional Facilities, and
are required. Figure 15.5 shows a layout typical of two to Dormitories.
Source: Courtesy of Thermon Manufacturing Co.
SD 179
CE Questions — “Self-regulating Heat Trace Systems” (PSD 179)
1. A designer should consider ________ when selecting the proper 7. Using ¾-inch Type L copper pipe, how much water is wasted in
self-regulating heat trace system for a particular application. the time it takes hot water to reach a fixture that is 25 feet from
a. life-cycle costs the end of the temperature maintenance?
b. energy efficiency a. 48 ounces
c. time to tap b. 64 ounces
d. all of the above c. 80 ounces
d. 97 ounces
2. Electric heat trace systems eliminate the need for ________.
a. a water heater 8. Which of the following should be referenced on both the
b. balancing valves plumbing and the electrical drawings?
c. pumps a. power connection
d. both b and c b. end termination
c. tee splice kits
3. A typical heating cable consists of which of the following?
d. heating cable
a. insulating jacket
b. power source 9. A _______ is used to indicate a power connection point on
c. nonconductive core plumbing drawings.
d. none of the above a. triangle
b. square
4. Which of the following is part of a hot water temperature
c. diamond
maintenance system?
d. circle
a. power connection kit
b. electrical junction box 10. The desired nominal maintenance temperature for a school is
c. self-regulating heating cable what?
d. both a and c a. 105°F
b. 120°F
5. Heat-traced lines should be thermally insulated with _______.
c. 140°F
a. copper
d. none of the above
b. foam
c. fiberglass 11. The standard vapor barrier for heat trace piping is made of
d. kraft paper _______.
a. copper
6. How long will it take hot water to reach a 1.5-gpm fixture if the
b. fiberglass
end of the heat-tracing circuit is 30 feet from the fixture?
c. kraft paper
a. 18 seconds
d. foam
b. 23 seconds
c. 30 seconds 12. For a heating cable system, _______ is the range around the
d. 45 seconds nominal maintenance temperature.
a. time to tap
b. unheated distance
c. system temperature range
d. none of the above
Please print or type; this information will be used to process your credits.
Name_________________________________________________________________________________________________________
Title __________________________________________________ ASPE Membership No._____________________________________
Organization___________________________________________________________________________________________________
Billing Address_ ________________________________________________________________________________________________
City_ _________________________________________ State/Province_________________________ Zip_______________________
Country_______________________________________________ E-mail_ _________________________________________________
Daytime telephone_ ____________________________________ Fax_____________________________________________________
PE State _ _____________________________________________ PE No._ _________________________________________________
Notice for North Carolina Professional Engineers: State regulations for registered PEs in North Carolina now require you to complete ASPE’s
online CEU validation form to be eligible for continuing education credits. After successfully completing this quiz, just visit ASPE’s CEU Valida-
tion Center at aspe.org/CEUValidationCenter.
I am applying for the following continuing education credits: ❏ ASPE Member ❏ Nonmember
Each examination: $25 Each examination: $35
I certify that I have read the article indicated above. Limited Time: No Cost to ASPE Member
Payment: ❏ Personal Check (payable to ASPE) $
❏ Business or government check $
Signature ❏ DiscoverCard ❏ VISA ❏ MasterCard ❏ AMEX $
Expiration date: Continuing education credit will be given If rebilling of a credit card charge is necessary, a $25 processing fee will be charged.
for this examination through August 31, 2012. ASPE is hereby authorized to charge my CE examination fee to my
Applications received after that date will not be processed. credit card