08 CANOPY UCW GLAZING ACP CLADDING SOFFIT KEY PLAN

04 05 07 06 09 REFER SEPERATE DRG


SE-604A REFER SEPERATE DRG REFER SEPERATE DRG F

FT-04
SE-603 SE-603 SE-604 SE-604 SE-604A
11 10 9 8
11000 FT 06A 13500 11000
E.2
E.1
E

2nd FLOOR D

TOC : +14.15
C

03

FLOOR HEIGHT
FT-06
B

PE-602 ACP CANOPY (FT06A) 14 13 12 11 10 9 8 7 6 5

4500
GENERAL NOTES

3325

3325

3325

3325
C\O
GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED.
34mm THK (8+16+10)DGU GLASS 2. ALL LEVELS ARE IN METERS & ARE UNFINISHED R.C.C. LEVELS.
650 1500 1500 1500 1500 1500 1500 3. DRAWING NOT TO BE SCALED, WRITTEN DIMENSIONS TO BE
CERAMIC FRETTING GLASS FOLLOWED ONLY.

Ceramic fretting

Ceramic fretting

Ceramic fretting
4. DIMENSIONS TO BE CHECKED AND VERIFIED ON SITE BEFORE
1032 1st FLOOR EXECUTION OF WORK.

1032

1032
TOC : +9.65 5. ANY DISCREPANCIES IN DIMENSIONS TO BE BROUGHT TO THE
GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08
KINLONG J120C11 CLAMP NOTICE OF THE ARCHITECT / SITE ENGINEER/ FACADE
01 CONSULTANTS

2400

2400

2400

2400
C\C
DT-601
01
01 KINLONG J120C71WS CLAMP
GL-08 GL-08 GL-08 01 GL-08 GL-08 GL-08 GL-08 GL-08 DT-604 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08
DT-602 01
DT-603 KINLONG J120C71 CLAMP
DT-612

FLOOR HEIGHT
GL-08

6518 GL-08 GL-08 25.52mm THK FIN GLASS


1200

1200

6000
GL-08 GL-08 GL-08 GL-08 3000 02
MS PORTAL CLADDED
01 PE-602
WITH 2MM THK ALUM SHEET
DT-608

3375
01
FT 06 (FINISH AS PER ARCHITECT APPROVAL)
3600

3600
GL-08

O\C
DT-607 GL-08 GL-08 GL-08 GL-08
2620

2620
2400

2400
GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08 GL-08
GL-08
GL-08 GL-08 PATCH FITTING DOOR
GL-08 GL-08
(DORMA) 2 LEGEND
ACP CLADDING(SHADE ACP CLADDING(SHADE
GROUND FLOOR AS PER ARCHITECT AS PER ARCHITECT
TOC : +3.65 APPROVAL) APPROVAL)

1200 650 1241 1539 3000 1539 1241 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 2 650 1200 STONE CLADDING CLAMP GLAZING
O\O O\C O\C O\C C\C C\O C\O O\O O\C C\C C\C C\C C\C C\C C\C C\O O\O O\C C\C C\C C\C 2560 C\O O\O (BY OTHERS)

220 220 220 C\C 220


ACP CLADDING
AUTOMATIC DOOR
AUTOMATIC SLIDING DOOR MS PORTAL CLADDED 2 STONE CLADDING (BY OTHERS) CANOPY

(ES 200 DORMA) 2 WITH 2MM THK ALUM SHEET 01 FT-06 PART ELEVATION
(FINISH AS PER ARCHITECT APPROVAL) PE-602 SCALE 1:75 DRAWING REVISION
TENDON (BY OTHERS) REV. NO.DATE DESCRIPTION APPROVED
11 10 9 8
11000 13500 11000
GROUND FLOOR

2 22-01-2024 REVISED AS PER COMMENTS


1 20-11-2023 REVISED AS PER COMMENTS
0 14-06-2023 FOR APPROVAL
220 PROJECT
220 650
1500 1500 1500 1500 2560 C\O LSR TUDOR INFRA IT PARK
01 01
O\C C\C C\C C\C C\C
01
DT-601 2 DT-603 DT-608
6518 2 MS PORTAL CLADDED
CLIENT
WITH 2MM THK ALUM SHEET
(FINISH AS PER ARCHITECT APPROVAL)
LSR TUDOR INFRA LLP
1182

1182
1100

1100

1100
1500 1500 1500 1500 1500 1500 1500 1500 1500 ARCHITECT
650 1241 1539 3000 1539 1241 220 220 B 2
C/C C/C C/C C/C C/C C/C C/C C/O O/O
O\C C\C C\C C\C C\C C\O
R. CHAKRAPANI & SONS
220 6080 220 3000 ARCHITECTS & ENGINEERS
01 PLOT NO.S1,NO:2,32ND CROSS STREET
DT-607 BESANT NAGAR CHENNAI-90.
TEL : 24464406/24464407
MS PORTAL CLADDED 2 02 FT-06 PLAN 12Nos. Ø 88 X5MM THK MS
WITH 2MM THK ALUM SHEET PE-602 SCALE 1:75 CIRCULAR PIPE FOR TIE MEMBER
11 (FINISH AS PER ARCHITECT APPROVAL) 10 9 8

650 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 650
O\C C\C C\C C\C C\C C\C C\O O\O O\C C\C C\C C\C C\C C\C C\C C\O O\O C\C C\C C\C C\C C\C C\C C\O
01
DT-613
CANOPY
REFER SEPERATE DRG
FACADE CONSULTANT
Slope

Slope
1516
2nd FLOOR SLAB EDGE

B
ALUVISION
D
T
L .T
V
PON
SIT
U
O
LSD
A
C
EF
2650

WATER DOWNTAKE PIPE (BY OTHERS)


Slope

Slope
GUTTER
1763

VENDOR / CONTRACTOR :

300X150X6mm THK. M.S. TUBE


(FINISH:-H.D.G 100 MICRON)
7500

2350

(GRADE YST 310)

DRAWING TITLE
300X150X10mm THK. M.S. TUBE FACADE WALL TYPE

(FINISH:-H.D.G 100 MICRON) FT-06 CLAMP GLAZING


FT 06A
SR.No. TYPE DESCRIPTION
2350

(GRADE YST 310) 1


2
FT-06
FT-06A
CLAMP GLAZING
4mm ACP SHEET CLADDED CANOPY
PART ELEVATION
200

200 200 SCHEDULE OF FINISHES


FINISH
SR.No. THICKNESS SPECIFICATIONS LOCATION DRAWN BY K.K. JOB NO. - CS202025
TYPE
1 12mm GLASS 12 mm thick clear float fully tempered glass DOOR GLASS CHECKED BY R.S. SCALE 1:75
650 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 650 8 mm Planitherm Fully toughened Glass + 16
mm Air gap with black anodized spacer + 10 APPROVED BY R.S. DATE 14-06-2023
2 GL-08 34 DGU
C/O C/C C/C C/C C/C C/C C/C C/C C/C C/C C/C C/C C/C C/C C/C C/C C/C C/C C/C C/C C/C C/C C/C C/O mm Clear Float Fully toughened Glass ground & 1st floor
(100% Heat Soak tested) DRAWING NO. REVISION
34300 12 mm Clear Fully toughened Glass + 1.52 mm SGP
GLASS FIN:- ground & 1st
300X150X10mm THK. M.S. TUBE 200X100X6mm THK. M.S. TUBE 100X100X4mm THK. M.S. TUBE
3 GL-09 25.52mm Laminated Lamination + 12 mm Clear Float Fully toughened
Glass (100% Heat Soak tested) floor ALM-SD-LT-PE-602 02
03 FT-06 PLAN ACP CANOPY (FT06A) 8 mm Clear Fully toughened Glass + 1.52 mm SGP
(FINISH:-H.D.G 100 MICRON) (FINISH:-H.D.G 100 MICRON) PE-602
(FINISH:-H.D.G 100 MICRON) AIR LOCK LOBBY SIDE WALL
SCALE 1:75 4 17.52mm Laminated Lamination + 8 mm Clear Float Fully toughened
(GRADE YST 310) (GRADE YST 310) (GRADE YST 310) Glass (100% Heat Soak tested) TENDER APPROVAL GFC AS BUILT
NOTE
KEY PLAN
EXPOSED STEEL / VISIBLE STEEL STRUCTURE FINISH AS BELOW. F

FT-04
1. SURFACE PREPARATION-BLAST CLEANED TO SA 2.5 CONFIRMING TO BS EN ISO 8501-1 E.2
E.1
2. PRIMER : ZINC RICH EPOXY 75 MICRON E

3. BARRIER : EPOXY MIO 125 MICRON


4. FINISH : POLYURETHANE-50 MICRON (ONLY FOR EXPOSED STEEL)
D

FT-06
B

14 13 12 11 10 9 8 7 6 5

GENERAL NOTES

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED.


2. ALL LEVELS ARE IN METERS & ARE UNFINISHED R.C.C. LEVELS.
3. DRAWING NOT TO BE SCALED, WRITTEN DIMENSIONS TO BE
FOLLOWED ONLY.
4. DIMENSIONS TO BE CHECKED AND VERIFIED ON SITE BEFORE
EXECUTION OF WORK.
5. ANY DISCREPANCIES IN DIMENSIONS TO BE BROUGHT TO THE
NOTICE OF THE ARCHITECT / SITE ENGINEER/ FACADE
CONSULTANTS

B ACP CLADDING SOFFIT B ACP CLADDING SOFFIT


REFER SEPERATE DRG REFER SEPERATE DRG
1400 2598 1400 2598
SLAB EDGE SLAB EDGE

FT-01 UCW GLAZING


FT-01 UCW GLAZING
REFER SEPERATE DRG
REFER SEPERATE DRG
300X150X10THK MS TUBE GRADE
YST 310 (FINISH - REFER NOTE) LEGEND
300X150X10THK MS TUBE GRADE
YST 310 (FINISH - REFER NOTE) 12Nos. Ø 88 X5MM THK MS
2nd FLOOR 2nd FLOOR
DRAINAGE DRAINAGE

CIRCULAR PIPE FOR TIE MEMBER

489

489
70

70
TOC : +14.15 12Nos. Ø 88 X5MM THK MS TOC : +14.15 (FINISH - REFER NOTE)
CIRCULAR PIPE FOR TIE MEMBER ACP CANOPY 100X100X4mm THK.
2068 100 (FINISH - REFER NOTE) 2068 100
165

165
(FT06A) M.S. TUBE (FINISH:-
700

700
ACP CANOPY (FT06A) H.D.G 100 MICRON)
Ceramic fritting

Ceramic fritting
Slope 100X100X4mm THK. M.S. TUBE (GRADE YST 310)
Slope 1763 2350 2350 200 (FINISH:-H.D.G 100 MICRON) Slope 1763 2350 Slope 2350 200
1163

1163
(GRADE YST 310)
760

760
315

315
23 200X100X6mm THK. M.S. TUBE 23 DRAWING REVISION

409

409
65 36 65 36
200

200
22 22
4500

4500
32 (FINISH:-H.D.G 100 MICRON) 32 REV. NO.DATE DESCRIPTION APPROVED
1342 2350 2350 1342 53 (GRADE YST 310) 1342 2350 2350 1342 53
650 7384 650 7384 650
8684 8684
2400

2400
2200

2200
3325

3325
7500 7500
2 22-01-2024 REVISED AS PER COMMENTS
300X150X6mm THK. M.S. TUBE
1 20-11-2023 REVISED AS PER COMMENTS
(FINISH:-H.D.G 100 MICRON) 200X100X6mm THK. M.S. TUBE
WATER DOWNTAKE PIPE (GRADE YST 310) 0 14-06-2023 FOR APPROVAL
Ceramic fritting

Ceramic fritting
BY OTHERS 300X150X6mm THK. M.S. TUBE (FINISH:-H.D.G 100 MICRON)
1st FLOOR 1st FLOOR (FINISH:-H.D.G 100 MICRON) (GRADE YST 310) PROJECT
TOC : +9.65 TOC : +9.65
1032

1032
KINLONG J120C11 CLAMP (GRADE YST 310) LSR TUDOR INFRA IT PARK
1200

1200
01 CANOPY
DT-605 WATER DOWNTAKE PIPE BY OTHERS CANOPY
REFER SEPERATE DRG
2400

2400
REFER SEPERATE DRG CLIENT
KINLONG J120C11 CLAMP
KINLONG J120C71WS CLAMP LSR TUDOR INFRA LLP
1200

1200
25.52mm THK FIN GLASS
25.52mm THK FIN GLASS
KINLONG J120C71 CLAMP ARCHITECT
KINLONG J120C71 CLAMP
01

980
DT-606
927

1182
R. CHAKRAPANI & SONS
6000

6000
896 204 ARCHITECTS & ENGINEERS
KINLONG J120C71WS CLAMP

220
PLOT NO.S1,NO:2,32ND CROSS STREET
BESANT NAGAR CHENNAI-90.
TEL : 24464406/24464407
3600

3600
34mm THK GLASS AUTOMATIC SLIDING DOOR
(ES 200 DORMA)
2673

2620

2400
01
DT-612 MS PORTAL CLADDED WITH 2MM THK ALUM
SHEET (FINISH AS PER ARCHITECT APPROVAL)

GROUND FLOOR GROUND FLOOR


2
TOC : +3.65 TOC : +3.65 FACADE CONSULTANT

ALUVISION
D
T
L .T
V
PON
SIT
U
O
LSD
A
C
EF

2
VENDOR / CONTRACTOR :
04 FT-06 PART SECTION AT CANTILEVER FIN LOCATION 05 FT-06 PART SECTION AT AUTOMATIC DOOR LOCATION
PE-602 SCALE 1:50 PE-602 SCALE 1:50

DRAWING TITLE

FT-06
SECTION -04 & 05
DRAWN BY K.K. JOB NO. - CS202025

CHECKED BY R.S. SCALE 1:50

APPROVED BY R.S. DATE 14-06-2023

DRAWING NO. REVISION

ALM-SD-LT-SE-603 02
TENDER APPROVAL GFC AS BUILT
NOTE
KEY PLAN
EXPOSED STEEL / VISIBLE STEEL STRUCTURE FINISH AS BELOW. F

FT-04
1. SURFACE PREPARATION-BLAST CLEANED TO SA 2.5 CONFIRMING TO BS EN ISO 8501-1 E.2
E.1
2. PRIMER : ZINC RICH EPOXY 75 MICRON E

3. BARRIER : EPOXY MIO 125 MICRON


4. FINISH : POLYURETHANE-50 MICRON (ONLY FOR EXPOSED STEEL)
D

FT-06
B

14 13 12 11 10 9 8 7 6 5

GENERAL NOTES

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED.


2. ALL LEVELS ARE IN METERS & ARE UNFINISHED R.C.C. LEVELS.
3. DRAWING NOT TO BE SCALED, WRITTEN DIMENSIONS TO BE
FOLLOWED ONLY.
4. DIMENSIONS TO BE CHECKED AND VERIFIED ON SITE BEFORE
EXECUTION OF WORK.
5. ANY DISCREPANCIES IN DIMENSIONS TO BE BROUGHT TO THE
NOTICE OF THE ARCHITECT / SITE ENGINEER/ FACADE
CONSULTANTS

B ACP CLADDING SOFFIT B ACP CLADDING SOFFIT


REFER SEPERATE DRG REFER SEPERATE DRG
1400 2598 1400 2598
SLAB EDGE SLAB EDGE

FT-01 UCW GLAZING FT-01 UCW GLAZING


REFER SEPERATE DRG REFER SEPERATE DRG

300X150X10THK MS TUBE GRADE 300X150X10THK MS TUBE GRADE LEGEND


YST 310 (FINISH - REFER NOTE) YST 310 (FINISH - REFER NOTE)
12Nos. Ø 88 X5MM THK MS
2nd FLOOR
DRAINAGE

12Nos. Ø 88 X5MM THK MS 2nd FLOOR


DRAINAGE

CIRCULAR PIPE FOR TIE MEMBER

489

489
70

70
TOC : +14.15 CIRCULAR PIPE FOR TIE MEMBER TOC : +14.15 (FINISH - REFER NOTE)
(FINISH - REFER NOTE)
900

900
ACP CANOPY (FT06A) 100X100X4mm THK.
2068 100 2068 100
165

165
M.S. TUBE (FINISH:-
700

700
ACP CANOPY (FT06A)
H.D.G 100 MICRON)
Ceramic fritting

Ceramic fritting
100X100X4mm THK. M.S. TUBE Slope
Slope 1763 2350 Slope 2350 200 (FINISH:-H.D.G 100 MICRON) Slope 1763 2350 2350 200 (GRADE YST 310)
1163

1163
(GRADE YST 310)
760

760
315

315
23 200X100X6mm THK. M.S. TUBE 23 DRAWING REVISION

409

409
65 6 65 36
200

200
23 22
4500

4500
32 2 (FINISH:-H.D.G 100 MICRON) 32 REV. NO. DATE DESCRIPTION APPROVED
01 1342 2350 2350 1342 53 (GRADE YST 310) 53
DT-609 7384 650 1342 2350 2350 1342 650
8684 7384
2400

2400
8684
3325
2200

2200
7500

3325
7500 2 22-01-2024 REVISED AS PER COMMENTS
300X150X6mm THK. M.S. TUBE
01 1 20-11-2023 REVISED AS PER COMMENTS
(FINISH:-H.D.G 100 MICRON) 200X100X6mm THK. M.S. TUBE
DT-610 WATER DOWNTAKE PIPE 0 14-06-2023 FOR APPROVAL
(GRADE YST 310)
Ceramic fritting

Ceramic fritting
BY OTHERS 300X150X6mm THK. M.S. TUBE (FINISH:-H.D.G 100 MICRON)
1st FLOOR 1st FLOOR (FINISH:-H.D.G 100 MICRON) (GRADE YST 310) PROJECT
TOC : +9.65 TOC : +9.65
1032

1032
(GRADE YST 310) LSR TUDOR INFRA IT PARK
1200

1200
KINLONG J120C11 CLAMP
CANOPY
REFER SEPERATE DRG WATER DOWNTAKE PIPE BY OTHERS CANOPY
KINLONG J120C71WS CLAMP
2400

2400
REFER SEPERATE DRG CLIENT
KINLONG J120C11 CLAMP
LSR TUDOR INFRA LLP
1200

1200
01 25.52mm THK FIN GLASS 25.52mm THK FIN GLASS
DT-611
KINLONG J120C71 CLAMP
ARCHITECT
KINLONG J120C71 CLAMP
980

927
1182 R. CHAKRAPANI & SONS
6000

6000
896 204 ARCHITECTS & ENGINEERS
KINLONG J120C71WS CLAMP
220

PLOT NO.S1,NO:2,32ND CROSS STREET


BESANT NAGAR CHENNAI-90.
01 TEL : 24464406/24464407

3375
PATCH FITTING DOOR
3600

3600
DT-617
(DORMA)

2673
2620

2400

MS PORTAL CLADDED WITH 2MM THK ALUM


SHEET (FINISH AS PER ARCHITECT APPROVAL)
01
DT-615
2

400

325
Required R.C.C

Required R.C.C
GROUND FLOOR GROUND FLOOR
TOC : +3.65 TOC : +3.65 FACADE CONSULTANT
850

850
684 275
75 75
R.C.C REQ. R.C.C REQ.
ALUVISION
D
T
L .T
V
PON
SIT
U
O
LSD
A
C
EF

2
VENDOR / CONTRACTOR :

06 FT-06 PART SECTION AT PATCH FITTING DOOR LOCATION 07 FT-06 PART SECTION AT UPSTAND LOCATION
PE-602 SCALE 1:50 PE-602 SCALE 1:50

DRAWING TITLE

FT-06
SECTION-06 & 07
DRAWN BY K.K. JOB NO. - CS202025

CHECKED BY R.S. SCALE 1:50

APPROVED BY R.S. DATE 14-06-2023

DRAWING NO. REVISION

ALM-SD-LT-SE-604 02
TENDER APPROVAL GFC AS BUILT
NOTE
KEY PLAN
EXPOSED STEEL / VISIBLE STEEL STRUCTURE FINISH AS BELOW. F

FT-04
1. SURFACE PREPARATION-BLAST CLEANED TO SA 2.5 CONFIRMING TO BS EN ISO 8501-1 E.2
E.1
2. PRIMER : ZINC RICH EPOXY 75 MICRON E

3. BARRIER : EPOXY MIO 125 MICRON


4. FINISH : POLYURETHANE-50 MICRON (ONLY FOR EXPOSED STEEL)
D

FT-06
B

14 13 12 11 10 9 8 7 6 5

GENERAL NOTES

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED.


2. ALL LEVELS ARE IN METERS & ARE UNFINISHED R.C.C. LEVELS.
3. DRAWING NOT TO BE SCALED, WRITTEN DIMENSIONS TO BE
FOLLOWED ONLY.
4. DIMENSIONS TO BE CHECKED AND VERIFIED ON SITE BEFORE
EXECUTION OF WORK.
5. ANY DISCREPANCIES IN DIMENSIONS TO BE BROUGHT TO THE
NOTICE OF THE ARCHITECT / SITE ENGINEER/ FACADE
CONSULTANTS

B ACP CLADDING SOFFIT B ACP CLADDING SOFFIT


REFER SEPERATE DRG REFER SEPERATE DRG
1400 2598 1400 2598
SLAB EDGE SLAB EDGE

FT-01 UCW GLAZING FT-01 UCW GLAZING


REFER SEPERATE DRG REFER SEPERATE DRG
300X150X10THK MS TUBE GRADE
300X150X10THK MS TUBE GRADE LEGEND
YST 310 (FINISH - REFER NOTE)
YST 310 (FINISH - REFER NOTE)
12Nos. Ø 88 X5MM THK MS
2nd FLOOR
DRAINAGE

CIRCULAR PIPE FOR TIE MEMBER 2nd FLOOR


DRAINAGE

12Nos. Ø 88 X5MM THK MS


489

489
70

70
TOC : +14.15 (FINISH - REFER NOTE) TOC : +14.15 CIRCULAR PIPE FOR TIE MEMBER
(FINISH - REFER NOTE)

900
ACP CANOPY 100X100X4mm THK. M.S. TUBE
2068 100 2068 100
165

165
(FT06A)
700

700
(FINISH:-H.D.G 100 MICRON) ACP CANOPY (FT06A)
Ceramic fritting

Ceramic fritting
(GRADE YST 310) 100X100X4mm THK. M.S. TUBE
1763 2350 Slope 2350 200 1763 2350 Slope 2350 200
Slope Slope (FINISH:-H.D.G 100 MICRON)
1163

1163
(GRADE YST 310)
760

760
315

315
23 23 200X100X6mm THK. M.S. TUBE DRAWING REVISION

409

409
65 36 65 36
200

200
22 22
4500

4500
32 32 (FINISH:-H.D.G 100 MICRON) REV. NO.DATE DESCRIPTION APPROVED
1342 2350 2350 1342 53 01 1342 2350 2350 1342 53 (GRADE YST 310)
DT-609 7384 650
7384 650
8684 8684
2400

2400
3325
2200

2200
3325

7500 7500
2 22-01-2024 REVISED AS PER COMMENTS
300X150X6mm THK. M.S. TUBE
01 1 20-11-2023 REVISED AS PER COMMENTS
300X150X6mm THK. M.S. TUBE (FINISH:-H.D.G 100 MICRON)
DT-610 WATER DOWNTAKE PIPE 0 14-06-2023 FOR APPROVAL
200X100X6mm THK. M.S. TUBE (GRADE YST 310)
Ceramic fritting

Ceramic fritting
(FINISH:-H.D.G 100 MICRON) BY OTHERS
1st FLOOR (FINISH:-H.D.G 100 MICRON) 1st FLOOR PROJECT
(GRADE YST 310) (GRADE YST 310)
TOC : +9.65 TOC : +9.65
1032

1032
KINLONG J120C11 CLAMP LSR TUDOR INFRA IT PARK
1200

1200
KINLONG J120C11 CLAMP
CANOPY
WATER DOWNTAKE PIPE BY OTHERS CANOPY REFER SEPERATE DRG
2400

2400
REFER SEPERATE DRG KINLONG J120C71WS CLAMP CLIENT
KINLONG J120C71WS CLAMP
LSR TUDOR INFRA LLP
1200

1200
25.52mm THK FIN GLASS 01 25.52mm THK FIN GLASS
DT-611
ARCHITECT
2 KINLONG J120C71 CLAMP KINLONG J120C71 CLAMP
2
980

980
1182 R. CHAKRAPANI & SONS
6000

6000
896 204 896 204 ARCHITECTS & ENGINEERS
MS PORTAL CLADDED WITH 2MM THK ALUM MS PORTAL CLADDED WITH 2MM THK ALUM
220

220
PLOT NO.S1,NO:2,32ND CROSS STREET
SHEET (FINISH AS PER ARCHITECT APPROVAL) SHEET (FINISH AS PER ARCHITECT APPROVAL) BESANT NAGAR CHENNAI-90.
TEL : 24464406/24464407

2 PATCH FITTING DOOR 2


3600

3600
AUTOMATIC SLIDING DOOR
(DORMA)
(ES 200 DORMA)
2620

2620
2400

2400

2400

2400
01
DT-612

Required R.C.C
GROUND FLOOR GROUND FLOOR
TOC : +3.65 TOC : +3.65 FACADE CONSULTANT

850
75
R.C.C REQ. ALUVISION
D
T
L .T
V
PON
SIT
U
O
LSD
A
C
EF

VENDOR / CONTRACTOR :
08 FT-06 PART SECTION AT AUTOMATIC DOOR LOCATION
PE-602 SCALE 1:50 09 FT-06 PART SECTION AT PATCH FITTING DOOR LOCATION
PE-602 SCALE 1:50

DRAWING TITLE

FT-06
SECTION -08 & 09
DRAWN BY K.K. JOB NO. - CS202025

CHECKED BY R.S. SCALE 1:50

APPROVED BY R.S. DATE 14-06-2023

DRAWING NO. REVISION

ALM-SD-LT-SE-604A 02
TENDER APPROVAL GFC AS BUILT