Professional Documents
Culture Documents
PROPRIETARY NOTICE
1996 - 2015 Kongsberg Maritime AS. All rights reserved. No part of this work covered
by the copyright hereon may be reproduced or otherwise copied without prior permission
from Kongsberg Maritime AS
DOCUMENT STATUS
Issue No. Year/Date Inc. by Change description
A 25.08.2015 LPH
ADDRESS
Kongsberg Maritime AS
Bekkajordet 8 A
P.O. Box 1009
N-3194 Horten, NORWAY
Telephone: +47 81 57 37 00
www.km.kongsberg.com
TABLE OF CONTENTS
Section Page
1 INTRODUCTION .................................................................. 1
2 OPERATION SIMULATED TRAPPED KEY INTERLOCK SYSTEM: .......... 3
3 OPERATION REAL HV BREAKER. (DG 1) ................................. 7
3.1 Take the breaker out of Service ......................................... 8
3.2 Put breaker back in service: ............................................ 11
1 INTRODUCTION
The hardware supplied allows the participants to undertake practical procedures and
maintenance on marine high voltage equipment. This is to allow as a minimum for the
isolation and removal of a main circuit breaker in accordance with the correct safety
procedures, this includes the correct use of interlock keys as appropriate.
The simulator model contains a Mimic Diagram representing the High Voltage
Switchboard. This process diagram can be operated from a Touch screen or from the
instructor station.
In real life, trapped key interlocks are widely used to ensure safe access to potentially live
equipment in a high voltage system. An example of use is to prevent access to the inside of
an electric breaker while it is operating. A trapped key is then used to lock the breaker
from being pulled out. Whenever the power switch is turned on, the key is held by the
interlock, and cannot be manually removed. In order to open the lock, the power switch
must first be turned off, which releases a key and allows it to be removed from the
interlock. The key can then be used to unlock the breaker. While the key is removed from
the switch interlock, it mechanically prevents the power switch from being turned on.
Power cannot be re-applied to the system until the breaker is locked in normal position,
releasing the key, and the key is then returned to the power switch interlock.
The above explained procedure is one of the training scenarios that are possible in the High
Voltage Switchboard module in Kongsberg engine room simulators. Another possible
training scenario is to access a transformer or a converter due to a malfunction. The key
lock system forces the users in such cases to isolate and earth down the equipment. When
the key pop-up has changed position to “pull out” position, access is allowed. Earth down
of the generators and main bus bars can also be practiced on the new switchboard mimic.
The Synchronising Panel and all breakers are available from pop-up panels.
To ensure safe access to potentially live equipment, an integrated trapped key interlock
system is included in the model. The main principle is as follows; any switchgear that may
cause live parts in areas to be accessed must be isolated, earthed and locked without any
possibility for re-connection as long as that particular area is accessible. The simulated key
lock system is based on “one click” philosophy. As an example, clicking on an open key
(green) will pull it out of the lock (for example earth down device) and place itself in the
trapped key lock system. The other way around is valid when putting the equipment back
to operation.
Fig. 2 in the illustration shows the trapped key lock system where five (5) keys from
various breakers/equipment are needed to unlock the trapped key (number 6 from left). The
trapped key will then turn green and may be removed from the trapped key system to
unlock the Earthing CB (fig.4) which in turn is used to earth down the 6.6 kV bus.
The fig. 3 in the illustration shows the pop-up earthting device in earth position with key in
“free” to pull out (green) position.
The earths down devices are accessible from the 6.6 kV Main Switchboard Mimic and the
Propulsion Power Drive mimic
Operation
Converter is earthed
Insert the key into the PEM enclosure lock and open the door.
Any motor failure may now be “repaired”
Illustration shows a trapped key lock system where five (5) keys from various
breakers/equipment are needed to unlock the trapped key. The trapped key will then turn
green and may be removed from the trapped key system to unlock the PEM enclosure.
To put the various propulsion units back to normal operating condition, follow the
described procedures in the opposite order;
NOTE! All keys shall be IN and LOCKED (Red Color) when restored the plant.
NOTE! When running half motor because of faulty transformer or converter, the
affected motor half must be isolated from the converter by putting the breaker to
TEST position.
Real Breaker DG 1
Breaker Control
3. Stop and activate Emergency Stop for DG. (LOCAL Control in Engine room)
4. Push the Rack in/out Button.
7. Open Locker.
Locker Opened.
8. Place the trolley in front of the cabinet.
9. Disconnect the breakers power supply
Power Supply
10. Pull the two grip handles towards center of breaker and slide the breaker out to the
trolley.
Grip Handles
Grip Handles
2. Remove the trolley and connect the breakers power supply.
Power Supply
3. Close Locker. And confirm that the Key is in located in the breakers key hole at
Simulator Hi Voltage Mimic.
5. Pull small black handle and cower the “Key Hole” for the big crank handle.
6. Push the Rack in/out Button.
Breaker Control