You are on page 1of 11

BoQ of 20 & 0.

4 kV TAGAB from SUROBI SUBSTATION- Transformer -39 Station Phase 1


unit price
physical Total price USD
Description of Goods Qty USD
unit DDP
DDP

Distribution Transformer with oil cooling system, Conservator tank,copper coil,Suitable for installation in outdoor (25kVA, Dyn5, ,20/0.4 kV, ±2x2.5 % off-load tap changer, ONAN-3
PCS 3 $ -
1 phase ;voltage impedance of 4%)*Refer to Annexure# L
Distribution Transformer with oil cooling system, Conservator tank,copper coil,Suitable for installation in outdoor (50kVA, Dyn5, ,20/0.4 kV, ±2x2.5 % off-load tap changer, ONAN-3
PCS 18 $ -
2 phase ;voltage impedance of 4%)*Refer to Annexure# L
Distribution Transformer with oil cooling system, Conservator tank,copper coil,Suitable for installation in outdoor (100kVA, Dyn5, ,20/0.4 kV, ±2x2.5 % off-load tap changer, ONAN-3
PCS 17 $ -
3 phase ;voltage impedance of 4%)*Refer to Annexure# L
Distribution Transformer with oil cooling system, Conservator tank,copper coil,Suitable for installation in outdoor (160kVA, Dyn5, ,20/0.4 kV, ±2x2.5 % off-load tap changer, ONAN-3
PCS 1 $ -
4 phase ;voltage impedance of 4%)*Refer to Annexure# L
MV disconnect Switch fuse combination for out door installation on the pole with handle and other required clamp and accessories for installation on the pole, with one meter fiber glass
PCS 1 $ -
5 insulation handle (20-24 kV,630A,fuse ampere 10A for 160KVA transformer as per CEF-Fuse linke for transformer and capaciter protection) .
MV disconnect Switch fuse combination for out door installation on the pole with handle and other required clamp and accessories for installation on the pole, with one meter fiber glass
PCS 38 $ -
6 insulation handle (20-24 kV,630A,fuse ampere 5A for 50KVA and 100KVA transformers as per CEF-Fuse linke for transformer and capaciter protection) .

LV Switchboard IP 54 (for out door installation),having all measuing devices such as ampere meter, voltage meter, kWh meter, electrostatic painted (Incomer 160A MCCB,Five outgoing Circuit )
PCS 11 $ -
with Maine Swich (5x63A) adjustable protection relay and 200/5 Current meter *Refer to Annexure# E
7

LV Switchboard IP 54 (for out door installation),having all measuing devices such as ampere meter, voltage meter, kWh meter, electrostatic painted (Incomer 160A MCCB,THREE outgoing
PCS 6 $ -
Circuit ) with Maine Swich (2x100A)1(63)A adjustable protection relay and 200/5 Current meter *Refer to Annexure# E
8

LV Switchboard IP 54 (for out door installation),having all measuing devices such as ampere meter, voltage meter, kWh meter, electrostatic painted (Incomer 100A MCCB,THREE outgoing
PCS 13 $ -
Circuit ) with Maine Swich (3x63A) adjustable protection relay and 100/5 Current meter *Refer to Annexure# E
9

LV Switchboard IP 54 (for out door installation),having all measuing devices such as ampere meter, voltage meter, kWh meter, electrostatic painted (Incomer 100A MCCB,foure outgoing
PCS 1 $ -
Circuit ) with Maine Swich (3x160A)1(63)A adjustable protection relay and 300/5 Current meter *Refer to Annexure# E
10

LV Switchboard IP 54 (for out door installation),having all measuing devices such as ampere meter, voltage meter, kWh meter, electrostatic painted (Incomer 100A MCCB,foure outgoing
PCS 8 $ -
Circuit ) with Maine Swich (3x160A)1(63)A adjustable protection relay and 300/5 Current meter *Refer to Annexure# E
11
Lighting Arrester (20-24 kV) including installation clamp,complete*Refer to Annexure# G SET 39 $ -
12

Electrode copper rod Ф=30mm/3m length for earth 2 nos. for each transformer PCS 78 $ -
13
Copper cable -4x120mm2-NYY-(0.6/1kV) from Transformer to switch board m 30 $ -
14
Copper cable -4x 70mm2-NYY-(0.6/1kV) from Transformer to switch board m 150 $ -
15
Copper cable -4x50mm2-NYY-(0.6/1kV) from Transformer to switch board m 140 $ -
16
Copper cable -4x10mm2-NYY-(0.6/1kV) from Pole to Meter Boxes m 10 $ -
17
Copper Cable log (50mm2) for copper cable (1x120 mm2) PCS 30 $ -
18
Copper Cable log (50mm2) for copper cable (1x70 mm2) PCS 120 $ -
19
Copper Cable log (50mm2) for copper cable (1x35 mm2) PCS 185 $ -
20
Copper tempole for cable (120mm)2 PCS 40 $ -
21
Copper tempole for cable (70mm)2 PCS 192 $ -
22
Copper tempole for cable (50mm)2 PCS 296 $ -
23
Copper tempole for cable (10mm)2 PCS 3068 $ -
24
Russian I-Beam (7x14) cm m 1014 $ -
25
26 Angle iron (6x6cm) for fence of Transformer station m 1014 $ -
27 flat strip Zinc coated (3x30mm) 30m length for earth of transformer station m 1170 $ -
28 Steel Rebar 20mm for stair and fence of Transformer Station m 1014 $ -
29 Bolt made of reinforced bar (Ф=30mm), 80cm length threaded in both side with nut PCS 312 $ -
30 Excavation of well for earthling purpose, in a depth to reach soil moisture* 2 nos. for each transformer Ring 78 $ -
31 Coal kg 1950 $ -
32 lime kg 1950 $ -
33 salt kg 1950 $ -
34 Wood plate with thichness of 3cm m2 234 $ -
35 Nut and bolt (10x40 mm) including washer PCS 780 $ -
36 Nut and bolt (12x40 mm) including washer PCS 780 $ -
37 Nut and bolt (16x100 mm) including washer PCS 780 $ -
38 Anti-rust prime coating paint PCS 117 $ -
39 Flat iron stripe (5cmx3mm) m 234 $ -
40 RCC Pole 12m length and 800 Kgf *Refer to Annexure# I PCS 417 $ -
41 RCC Pole 12m length and 400 Kgf *Refer to Annexure# I PCS 1050 $ -
Iron pole (8 -10) inches wtih 6mm thicknes 9m length and 700 kgf Galvanized*Refer to Annexure# P metal pole. 9m length, 6m of 10 inches and 3m of 8 inches like that. Better to be in
PCS 700 $ -
42 Khada(6m)
Iron pole (6- 8 )inches with 6mm thicknes 9m length and 300 kgf Galvanized*Refer to Annexure# P metal pole. 9m length, 6m of 10 inches and 3m of 8 inches like that. Better to be in
PCS 737 $ -
43 Khada(6m) not in PCS
44 ACSR -185mm2 for over head Conductor*Refer to Annexure# J m 80363 $ -
45 ACSR -35mm2 for over head Conductor*Refer to Annexure# J m 62307.95 $ -
46 ACSR -50mm2 for over head Conductor*Refer to Annexure# J m 30292 $ -
47 ACSR -95mm2 for over head Conductor*Refer to Annexure# J m 50096.25 $ -
48 Guy wire 70mm2 including 15m zinc type wire with all accessories and insulator complete set same as 20kV equipment SET 466 $ -
49 Guy wire 50mm2 including 12m zinc type wire with all accessories and insulator complete set same as 0.4kV equipment SET 274 $ -
suspension cross arm(20kV) russian angle iron 7x7 cm with and 6mm thickness, 2.2m length including 2 PCS clump (5cmx3mmx85cm) including nut and bolt with washer and spring*Refer to
PCS 1050 $ -
50 Annexure# A

couple Tension cross arm(20kV) russian angle iron 7x7 cm with and 6mm thickness, 2.2m length , including nut and bolt with washer and spring*Refer to Annexure# A same as 20kV equipment couple 417 $ -
51
52 Pin insulator (20-24 kV) Fiber type with all required accessorie*Refer to Annexure# H same as 20kV equipment PCS 3150 $ -
53 Tension insulator (20-24kV) Fiber type with all required accessorie*Refer to Annexure# H same as 20kV equipment PCS 2502 $ -
54 U type clamp size 50mm (wire locker) PCS 370 $ -
55 U type clamp size 35mm (wire locker) PCS 400 $ -
56 ABC cable 150 ABC (4x150)mm2+1x16 (0.6/1kV)*Refer to Annexure# B m 65509 $ -
57 ABC cable 95ABC (4x95)mm2+1x16 (0.6/1kV)*Refer to Annexure# B m 10376 $ -
58 ABC cable 70ABC (4x70)mm2+1x16 (0.6/1kV)*Refer to Annexure# B m 17304 $ -
59 ABC cable Connector (70x95x150x50x35x16)mm2 Water proof joint for ABC 4X70mm2 PCS 3568 $ -
60 Aluminum Cable lug (16mm2) PCS 2083 $ -
61 Dead End clamp for ABC cable with all accessories complete PCS 274 $ -
62 Suspension clamp for ABC cable with all accessories complete PCS 787 $ -
63 Tension clamp for ABC cable with all accessories complete PCS 734 $ -
required equipment for tapping from ABC cable (50-35mm2) 4 PCS for each meter box PCS 892 $ -
64
65 Meter box (6 meter),color electrostatic water proof, completely wired by 1x6 mm2 to be installed on the pole( outdoor) *Refer to Annexure# F PCS 600 $ -
66 Pad-lock for meter box PCS 892 $ -
67 Electrode copper rod Ф=20mm/1m length with all required clamp for earthing of meter box *Pole mounted. m 1755 $ -
68 Stone for construction work m3 2308.2 $ -
69 Gravel m3 959.97 $ -
70 Cement pack 5898 $ -
71 marking red Color spray PCS 80 $ -
Grand total $ -
Schedule No. 2: Plant and Mandatory Spare Parts Supplied from Within the Employer’s
Country
Descriptio
Item n
Code1 Unit Qty. Unit Price2 Total Price2 Remarks

EXW EXW
Unit Total
Price in Prices in
AFN AFN
-1 -2 -3 (1) x (3)
Schedule No. 3. Design Services

Item Description

Unit

Design services for complete package LUMP SUM

Sub-Total
Unit Price1 Total Price1 Remarks

Qty.
inclusive of all Taxes inclusive of
all Taxes

Local Foreign
Currency Currency
Portion Portion

$ -
Schedule No. 4. Installation and other services

Item

D
1
Schedule No. 4. Installation and other services

Description

General Section

Mobilization and De-mobilization including all necessary activities e.g. transportation, in-transit accommodation,
VISAs, Work Permits etc.

Provision of all Necessary Insurances in accordance with the Contract.

Sub-Total

Excavation of foundation for erection of the pole*

Concrete pouring and Water Curing for pole foundation*

Provision of security for contractor’s site camp, warehouse, personnel during the project period to be reflected in
the security plan.

Sub-Total
ESMP
ESMP Items to be considered during implementation of the project. Attached as an annex
Sub-Total
Unit Price1 Total Price1 Remarks
inclusive of all Taxes inclusive of all Taxes
Unit Qty.
Foreign Currency Local
Portion Currency Foreign Local
Portion
-1 -2 -3 (1) x (2) (1) x (3)

Lump Sum 1

Lump Sum 1

M3 5012.1

Foundation 2949

Lump Sum 1

LS 1
0.00
TOTAL (to Schedule No. 5. Grand Summary)
Schedule No. 5. Grand Summary
Item Description

1 Total Schedule No. 1. Plant and Mandatory Spare Parts Supplied from Abroad

2 Total Schedule No. 2: Plant and Mandatory Spare Parts Supplied from Within the Emp

3 Total Schedule No. 3. Design Services

4 Total Schedule No. 4. Civil works, Installation and Other Services

Contingency cost for unforeseen conditions of 10%of the overall bid Prices ( on a
5
bases)

TOTAL (to Bid Form)


rand Summary
Description Total Price1
Foreign Local

1. Plant and Mandatory Spare Parts Supplied from Abroad $ -

2: Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country 0

3. Design Services $ -

4. Civil works, Installation and Other Services $ -

for unforeseen conditions of 10%of the overall bid Prices ( on actual necessity

$ -
TOTAL (to Bid Form)
Price1
Local

You might also like