Part II, Section 2 – Tender Appendices

TENDER APPENDIX F1 – 1,500KVA 0.415/11kV STEP-


UP TRANSFORMER
Technical Particulars

All the technical particulars of the equipment offered which are listed here are to be given
at the time of the Tender. Such particulars will be binding on the supplier/manufacturer
and shall not be departed from without the written consent of the Company.

The shop drawings for each item are to be submitted together with the tender submission
for evaluation purposes.

Item Company Tenderer


Description
No. Requirements Specifications
Ratings and Electrical Requirements
1 Rated frequency Hz 50
2 Rated power (ONAN) kVA 1500
3 Rated voltages:
3.1 High voltage windings kV(rms) 11
3.2 Low Voltage windings kV(rms) 0.415
4 Rated insulation level:
4.1 Highest voltages:
4.1.1 High voltage windings kV(rms) 12
4.1.2 Low voltage windings kV(rms) < 1.1
4.2 Induced PF withstand voltage:
4.2.1 High voltage windings kV(rms) 22
4.2.2 Low voltage windings kV(rms) 0.830
4.3 Separate source withstand voltage:
4.3.1 High voltage windings kV(rms) 28
4.3.2 Low voltage windings kV(rms) 3
4.4 Impulse withstand voltages:
4.4.1 High voltage windings kVp 75
4.4.2 Low voltage windings kVp 30
5 Rated voltage ratio, LV/HV winding V/V 415/11000
6 Tap Changer:
6.1 Type Rotary/Linear -
6.2 Tapping range on 11kV windings &
Rated Step Voltage:
6.2.1 Range % +5
6.2.2 Size of tapping steps % 2.5
6.3 Rated through current of tap changer A -

Tender for Supply, Delivery, Installation, and Commissioning of 8 x 1,250kVA Containerised Diesel Engine
Generating Sets and 5 x 1,500kVA 0.415/11kV Step-up Transformer for Limbang Power Station (Sarawak
Energy Ref. No. DTS/LMN/NGD-M1)
Part II, Section 2 – Tender Appendices

Item Company Tenderer


Description
No. Requirements Specifications
7 Impedance voltage at rated voltage, rated frequency, 4 to 6
rated power and at principal
Tap at 75 °C %
8 Winding Resistance at 75 °C:
8.1 High Voltage Winding ohm/phase -
8.2 Low Voltage Winding ohm/phase -
9 Electrical connection and vector group:
9.1 High Voltage Winding connection Star
9.2 Low Voltage Winding connection Delta
9.3 Vector Group YNd11
10 Temperature rise when operating at rated power:
10.1 In top oil °C ≤ 50
10.2 In winding °C ≤ 55
11 Maximum hot spot temperature:
11.1 When operating at rated power under -
ambient air temperature of 30 °C and
top oil temperature as per item 10.1
11.2 After operating at 25 % overload for two -
hours (at ambient air temperature 30
°C & after 100 % continuous load)
12 Maximum continuous permissible overload % of -
when transformer is operated at temp. rise
rated of 50°C in top oil and 55°C in winding
power
13 Maximum flux density in iron at
rated voltage and rated frequency:
13.1 Limbs wb/m 2 -
13.2 Yokes wb/m 2 -
14 Magnetising current of high voltage winding A -
at rated voltage and rated frequency and on
principal tap
15 No-load loss at rated voltage and rated W ≤ 1,600
frequency
16 Load loss at rated frequency and rated W ≤ 13,750
power at 75 °C
17 Efficiency at rated power at 75 °C:
17.1 Unity power factor % -
17.2 0.8 power factor % -
Tender for Supply, Delivery, Installation, and Commissioning of 8 x 1,250kVA Containerised Diesel Engine
Generating Sets and 5 x 1,500kVA 0.415/11kV Step-up Transformer for Limbang Power Station (Sarawak
Energy Ref. No. DTS/LMN/NGD-M1)
Part II, Section 2 – Tender Appendices

Item Company Tenderer


Description
No. Requirements Specifications
18 Class of winding insulation in accordance
with BS 171 and permissible temperature
rise measured by resistance:
18.1 Class A
18.2 Permissible temperature rise °C -
19 Calculated thermal time constant : ONAN -
20 Maximum noise level of transformer when dB(A) 60
Measured in accordance with IEC 60551
Technical Data –Constructional Features
21 Windings used Copper
22 Type of windings construction (eg. disc, foil, layer):
22.1 High Voltage -
22.2 Low Voltage Foil/sheet
22.3 Location of tapping sections -
22.4 Arrangement of windings with -
respect to the core
23 If rectangular windings used, state whether -
coils are clamped along horizontal axis to
restrict bursting out to circular configuration
24 Maximum bending stress on conductor -
under 3-phase short circuit
25 Insulating material for:
25.1 High voltage winding -
25.2 Low voltage winding -
26 Insulating material for:
26.1 Tappings -
26.2 Tappings connections -
27 Type of magnetic circuit (core/shell) Core
28 Type of corner joint for magnetic circuit -
29 Method of securing laminations -
30 Insulating material for:
30.1 Core bolts -
30.2 Core bolts washers -
30.3 Side plate -
30.4 Core laminations -
31 Method of clamping magnetic circuit winding -
assembly to tank

Tender for Supply, Delivery, Installation, and Commissioning of 8 x 1,250kVA Containerised Diesel Engine
Generating Sets and 5 x 1,500kVA 0.415/11kV Step-up Transformer for Limbang Power Station (Sarawak
Energy Ref. No. DTS/LMN/NGD-M1)
Part II, Section 2 – Tender Appendices

Item Company Tenderer


Description
No. Requirements Specifications
32 Material used for:
32.1 Axial support end blocks -
32.2 Intermediate coil spacers 32.3 Magnetic -
circuit/winding and winding/winding cylinders -
33 Minimum Clearance of Live Conductors in Oil:
33.1 High Voltage:
33.1.1 Phase to Earth mm -
33.1.2 Phase to Phase mm -
33.2 Low Voltage: -
33.2.1 Phase to Earth mm -
33.2.2 Phase to Phase mm
34 Type of transformer terminals:
34.1 HV line terminals Cable box
34.2 LV line terminals Cable box
35 Type of Cooling Plant (State whether cooling -
Fins or tubes or corrugated tank)
36 Materials of Cooling Plant:
36.1 Type of material -
36.2 Thickness mm -
37 Thickness of Transformer Tank:
37.1 Base mm -
37.2 Sides mm -
38 Thickness of tank cover mm -
39 Transformer Oil:
39.1 Type Inhibited
39.2 In accordance with IEC 60296 Yes
39.3 Is the transformer oil PCB free Yes
40 Method of Sealing Transformer Tank -

Technical Data – Thermal Dynamic


Ability Under External Short Circuit
41 Maximum fault current for 3-phase short-
circuit and line to ground fault:
41.1 HV Winding kA -
41.2 LV Winding kA -

42 Current density at maximum short circuit current:


42.1 HV Winding kA -
42.2 LV Winding kA -

Tender for Supply, Delivery, Installation, and Commissioning of 8 x 1,250kVA Containerised Diesel Engine
Generating Sets and 5 x 1,500kVA 0.415/11kV Step-up Transformer for Limbang Power Station (Sarawak
Energy Ref. No. DTS/LMN/NGD-M1)
Part II, Section 2 – Tender Appendices

Item Company Tenderer


Description
No. Requirements Specifications
43 Thermal ability at maximum short circuit current:
43.1 HV Winding secs ≥3
43.2 LV Winding secs ≥3
44 Mechanical withstand current rms/
peak with no residual strain:
44.1 HV Winding kA -
44.2 LV Winding kA -
45 Materials used for gaskets for oil tight joints -
46 Volumes, Weights and Dimensions
Total oil Litres -
47 Weight of core and winding assembly kg -
48 Total weight of transformer kg -
49 Overall dimensions of transformer:
49.1 Length m -
49.2 Width m -
49.3 Height m -
50 Minimum thickness and type of paint for:
50.1 Primer coat (µm/type) -
50.2 Undercoat (µm/type) -
50.3 Finishing coat (µm/type) -
51 Minimum total paint thickness – 140 micron Yes
52 Paint system used: -
- External paint system on tank cover flange
53 Materials used for bolts and nuts -
(state stainless steel or hot dip galvanized steel)
If galvanized, minimum thickness – 50/60
Micrometer of galvanized coating
54 Derusting method:
54.1 Shot blasting (Yes/No) -
54.2 Others (To specify) -
55 Describe leakage test used -
56 Describe each stage of the drying out procedure -
57 Type of welding used -
58 HV Cable Box:
58.1 Insulating medium Air
58.2 Minimum phase-phase & phase-earth within -
the cable box to comply with BS 6435/IEC

Tender for Supply, Delivery, Installation, and Commissioning of 8 x 1,250kVA Containerised Diesel Engine
Generating Sets and 5 x 1,500kVA 0.415/11kV Step-up Transformer for Limbang Power Station (Sarawak
Energy Ref. No. DTS/LMN/NGD-M1)