Fan-coil Selection Report

Project Information
Project Name 1 Country Romania
Region Bucharest Building Type Residence
Altitude 91.00m Atmospheric pressure 100.22Kpa
Fan Coil Location
Series FC3+1 Low Static Ducted(3+1 Rows,4pipes)

Model FC3+1-35

Plenum box Rear return box

Filter Nylon

Water pipe position default

Drain Pan General


Air Volume
Fan Speed Medium Speed Air Volume 523 m3/h
Static Pressure(ESP) 50 Pa
Cooling Condition
Air Inlet Air Outlet
Air Inlet DB 27.0 C Air Outlet DB 14.1 C
Air Inlet WB 19.1 C Air Outlet WB 12.9 C
Air Humidity(%) 47.00 Air Humidity% 87.61
Water Inlet 7.0 C Water outlet 12.0 C Water DT 5C
Total Cooling Capacity 2.95 kW Sensible cooling capacity 2.18 kW
Water Flow 0.51 m3/h Water pressure drop 14.83 kPa
Heating Condition
Air Inlet DB 20.0 C Air Outlet DB 38.9 C
Water Inlet 80.0 C Water Outlet 70.0 C Water DT 10C
Heating Capacity 3.32 kW
Water flow 0.29 m3/h Water pressure drop 4.54 kPa
Electrical Heater Power 0 KW
Electrical/Sound Data
number of fans 2 The number of Motor 1
Voltage/Phase/Frequency 220V/1P/50HZ Input power 55W
Sound level(H/M/L) d B(A) 37/29/25

1/3
Water Pipe
Connection size 3/4" FTP
Drain pipe size 3/4"MTP
Valve package/control
control type Three speed control valve package None
Dimension Drawing

A B C D E F G H I J K L M N P
840 622 570 570 245 130 192 150 517 390
Air volume Vs ESP

2/3
Packaging Information
Packaging Carton Qty per carton 1
Package size(mm)/Volume(CMB) 880/527/265/0.12
G.W/N.W(KG) 23/21
Container Loading (40ft) 447 pcs