RAPPORT CND PROVISOIRE Lieu SABC Ydé

Date of test:
02/05/2024

PROJET: Inspection /contrôle qualité des soudures raccordement


Client : SABC YAOUNDE
nouveau groupe froid positif HANSA Yaoundé

Techniques Defects Result


ISO NUMBER WELD ID OD Welder Stamp Remarks
RT PT N° Type Pos (cm) L (mm) Acc Rej

S11R1 3" - x - - - - - x - Accepted

S12R1 3" - x - - - - - x - Accepted

S13R1 3" - x - - - - - x - Accepted

RESEAUX S14R1 3" - x - - - - - x - Accepted


D'AMMONIAC NH3:
Liquid Pipe S34R1 3" - x - - - - - x - Accepted

S35R1 3" - x - - - - - x - Accepted

S36R1 3" - x - 1 Cp 8 30 - x Rejected

S37R1 3" - x - - - - - x - Accepted

S16R1 5" - x - - - - - x - Accepted

S17R1 5" - x - - - - - x - Accepted

RESEAUX S18R1 5" - x - - - - - x - Accepted


D'AMMONIAC NH3:
Discharge Pipe S19R1 5" - x - 1 Ap 19 10 - x Rejected

S20R1 5" - x - 1 Ip 41 5 - x Rejected

S24R1 5" - x - - - - - x - Accepted

Legend

Ec: Elongated crack Eu: External undercut F: insufficient/excess


Ip: Isolated Gas pores Cc: Crater crack Iu: Internal undercut penetration
Ap: Aligned porosities Tb: Transverse crack Lop: Lack of penetration NRI: Non relevant indication
Cp: Cluster porosities Si: Slag inclusions Ws: Weld spatter If: Incomplete fill
Sp: Scattered porosities Sl: Slag lines Ss: Stop and start Mf: Material flow
Wh: Worm holes Ti: Tungsten inclusions Rc: Root concavity
Lof: Lack of fusion

Inspector Client

Name: EBOLA Arnaud

Qualification: RT Niveau 3

Visa:

Date: 03/05/2024