PowerCube 1000 Hybrid Power Solution

ICC330-H1-C8 Datasheet

Introduction

ICC330-H1-C8 is an outdoor cabinet system used for solar/diesel/grid


hybrid scenario, it integrates a HEX cooling system. The system
configures DCDU-600AN1, maximum 675 A system capacity, supports
max. 9 rectifiers, the equipment cabin reserves 19-inch rack space for
other equipments, occupies small footprint, easy installation and
deployment.

Features

⚫ High Power Density


36kW power @ only 5U high
⚫ Innovative Architecture Power
The Power adopts innovative architecture design, supports energy
multiple inputs (solar, mains or D.G.), supports multiple output
modes (AC:220V, DC:12/24/36/48/57V) and multiple service
scenarios.
⚫ AI Synergy
iGrid/iDiesel/iSolar intelligent system scheduling improves system
efficiency and reliability
⚫ Intelligent Load management
Enabling precise metering & device-level precise power backup
⚫ Smart Site ICC330-H1-C8
Online remote maintenance reduces site visits and O&M costs

Scenarios

⚫ Outdoor scenario
⚫ Solar/diesel/grid hybrid system

Note: Preliminary issue. Any datasheet issued previously is invalid when new version releases. Issue date of this version: 2020-08-25
Specifications
Product Type ICC330-H1-C8
Dimension (W × D × H) 650 mm × 810 mm × 1600 mm (including base and protruding part)

Base (W × D × H) 650 mm × 650 mm × 100 mm

Weight <155 kg (without rectifier modules, other optional equipment)

Installation Mode Ground installation

Cabling Mode From the bottom

System Maintenance Mode From the front

Cabinet Material Hull and inside frame: steel, base: SMC

Cabinet color Light grey: RAL 7035

Grounding Bar 7 × M6, 1 × M8

Cable Entry Detail Cable entry from base of cabinet, 8 x 43 mm diameter holes

EMC EN 300386 Class A

Inner Rack & Space 24 U, 19-inch rack (according to the actual configuration of ATO pre-installation)

Equipment Cabin Protection Level IP55 (EN 60529)

Cooling Mode Heat exchanger 250W/K

Power Model DCDU-600AN1


Configures AC input unit
Three-phase: 200-240 Vac/346-415 Vac
Input AC Input
Single-phase: 200-240 Vac
Dual live-wire: 200-240 Vac
Normal mode : 42VDC - 58VDC, rated value: 53.5VDC
Voltage
Supports 57VDC constant (must be used together with BoostLi lithium battery)
Output
Capacity Max. 36 kW (675 A)
Power System
Battery Branch 3 × 200 A

LLVD Branch 2 × 125 A MCB, 3 ×63A MCB (LLVD1)

BLVD Branch 2 × 63 A MCB, 2 × 32 A MCB, 2 × 16 A MCB (LLVD2)

AC Input 30 kA (8/20 μs)


SPD
DC Output 10/20 kA (8/20 μs)

Operating Temperature -20 ºC to +45 ºC + solar radiation

Storage Temperature -40 ºC to +70 ºC


Environment
Operating Relative Humidity 5% to 95% (no condensation)

Altitude 0 to 4000 m (1ºC per 200 m temperature derating from 2000 to 4000 m)

Remark:

◼ DCDU: Direct Current Distribution Unit ◼ SPD: Surge Protective Device

◼ DC1 Input: 3rd part DC input, such as: solar energy input, reused existing -48V DC power input etc.

Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved. HUAWEI TECHNOLOGIES CO., LTD.
No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Huawei Industrial Base
Ltd.
Bantian Longgang
General Disclaimer
Shenzhen 518129, P.R. China
The information in this document may contain predictive statements including, without limitation, statements regarding the future financial and
operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual results and developments to Tel: +86-755-28780808
differ materially from those expressed or implied in the predictive statements. Therefore, such information is provided for reference purpose only
and constitutes neither an offer nor an acceptance. Huawei may change the information at any time without notice. www.huawei.com

You might also like