You are on page 1of 26

HlY31/IL;CC c.31..

)u- IJO I
(Revision of ANSVIEEE C37.40-1-S)

service conditions a n d definitions for


high-voltage fuses, distribution enclosed
single-pole air switches,
fuse disconnecting switches, a n d accessories
Draft ANSI/IEEE C37.40a-1987
(Supplement to ANSI/IEEE C37.40-1981)

Insert this definition alphabetically in Section grounded neutral (multigrounded) systems *


3.1: where construction conditions are such that two
cutouts wiU normally operate in series to clear
slant-voltage-rated(multiple-voltage-rated)dis- phase-to-phase faults. In applying these cutouts,
tribution cutout. A distribution cutout intended the system line-to-linevoltage must be equal to or
primarily for application on three-phase solidly less than the maximum voltage rating to the right
grounded neutral (multlgrounded) systems where of the slant (/), and the system line-to-ground
prescribed conditions exist. (See ANWIEEE voltage must be equal to or less than the maxi-
C37.40-1981,3.2,slant-voltage (multiple-voltage) mum voltage rating to the left of the slant (/).
ratings of a distribution cutout.) For application in other systems and for more
Insert this definition alphabetically in Section complete application guidance, refer to ANSI/
3.2: IEEE C37.48-1987, 3.7.2.

slant-voltage (multiple-voltage)ratings of a dis-


tribution cutout. A pair of maximum voltage rat- 'Slant-voltage-rated cutouts may be used in single-phase
applications where the normal frequency recovery voltage
ings assigned to a distribution cutout intended across the cutout does not exceed the maximum voltage rat-
primarily for application on three-phase solidly ing to the left of the slant (/).

Approved June 11, 1987


IEEE Standards Board

@ Copyright 1988 by

The Institute of Electrical and Electronics Engineers, Inc


345 East 47th Street, New York, NY 10017, USA

No part of this publication may be reproduced i n any form,


i n an electronic retrieval system OT otherwise,
Februav 25. 1988 without the prior written permission of the publisher.
ANSUIEEE C37.40-1981
(Revisionof ANSI/IEEE C37.40-1969)

An American National Standard

IEEE Standard Service Conditions and


Definitions for High-Voltage Fuses,
Distribution Enclosed Single-Pole Air Switches,
Fuse Disconnecting Switches, and Accessories

Sponsor
IEEE Switchgear Committee of the
IEEE Power Engineering Society

Approved September 18,1980


IEEE Standards Board

Secretariat
Institute of Electrical and Electronics Fngineers
National Electrical Manufacturers Association

Approved January 12,1981


American National Standards Institute

@ Copyright 1981 by

The Institute of Electrical and Electronics, Engineers, Inc


345 East 47th Street, New York, NY 10017

N o part o f this publication may be reproduced in any form,


in an electronic retrieval system or otherwise,
without the prior written permission o f the publisher.
IEEE Standards documents are developed within the Technical Com-
mittees of the IEEE Societies and the Standards Coordinating Commit-
tees of the IEEE Standards Board. Members of the committees serve
voluntarily and without compensation. They are not necessarily mem-
bers of the Institute. The standards developed within IEEE represent
a consensus of the broad expertise on the subject within the Institute
as well as those activities outside of IEEE which have expressed an in-
terest in participating in the development of the standard.
Use of an IEEE Standard is wholly voluntary. The existence of an
IEEE Standard does not imply that there are no other ways to pro-
duce, test, measure, purchase, market, or provide other goods and ser-
vices related t o the scope of the IEEE Standard. Furthermore, the view-
point expressed at the time a standard is approved and issued is subject
t o change brought about through developments in the state of the art
and comments received from users of the standard. Every IEEE Stan-
dard is subjected to review at least once every five years for revision
or reaffirmation. When a document is more than five years old, and has
not been reaffirmed, it is reasonable to conclude that its contents,
although still of some value, do not wholly reflect the present state of
the art. Users are cautioned to check t o determine that they have the
latest edition of any IEEE Standard.
Comments for revision of IEEE Standards are welcome from any
interested party, regardless of membership affiliation with IEEE. Sug-
gestions for changes in documents should be in the form of a proposed
change of text, together with appropriate supporting comments.
Interpretations: Occasionally questions may arise regarding the mean-
ing of portions of standards as they relate to specific applications. When
the need for interpretations is brought to the attention of IEEE, the
Institute will initiate action to prepare appropriate responses. Since
IEEE Standards represent a consensus of all concerned interests, it is
important to ensure that any interpretation has also received the con-
currence of a balance of interests. For this reason IEEE and the mem-
bers of its technical committees are not able t o provide an instant re-
sponse to interpretation requests except in those cases where the matter
has previously received formal consideration.
Comments on standards and requests for interpretations should be ad-
dressed to:
Secretary, IEEE Standards Board
345 East 47th Street
New York, NY 10017
USA
Foreword
(This Foreword is not a part of ANSI/IEEE C37.40-1981, IEEE Standard Service Conditions and Definitions for
High-Voltage Fuses, Distribution Enclosed Single-Pole Air Switches, Fuse Disconnecting Switches, and Acces-
sories.)
This standard is a revision of ANSI C37.40-1969 to bring it up t o date and in line with present
day requirements for high-voltage fuses and switches. The expanded coverage of current limiting
fuses broadens its applicability.
This standard was prepared by the C37 Subcommittee on High-Voltage Fuses with cooperation
from the IEEE Subcommittee on High-Voltage Fuses and National Electrical Manufacturers As-
sociation (NEMA). Liaison was maintained with Edison Electric Institute (EEI) and International
Electrotechnical Commission (IEC) during the development of the revisions in order to incorporate
the latest thinking up t o the time of publication.
This standard is one of a series of complementary American National Standards covering various
type of high-voltage fuses and switches, so arranged that certain of the standards apply to all de-
vices while each of the other standards provide additional specifications for a particular device. For
any device ANSI/IEEE C37.40-1981, ANSI/IEEE C37.41-1981 plus the additional standard cover-
ing that device constitute a complete standard for the device. In addition, ANSI C37.48-1969 is an
application, operation, and maintenance guide for all the devices.
The following American National Standards make up this series:
ANSI/IEEE C37.40-1981, Service Conditions and Definitions for High-Voltage Fuses, Distribu-
tion Enclosed Single-Pole Air Switches, Fuse Disconnecting Switches, and Accessories
ANSI/IEEE C37.41-1981, Design Tests for High-Voltage Fuses, Distribution Enclosed Single-
Pole Air Switches, Fuse Disconnecting Switches, and Accessories
ANSI C37.42-1981, Specifications for Distribution Cutouts and Fuse Links1
ANSI C37.44-1981, Specifications for Distribution Oil Cutouts and Fuse Links
ANSI C37.45-1981, Specifications for Distribution Enclosed Single-Pole Air Switches
ANSI C37.46-1981, Specifications for Power Fuses and Fuse Disconnecting Switches
ANSI C37.47-1981, Specifications for Distribution Fuse Disconnecting Switches, Fuse Supports,
and Current Limiting Fuses
ANSI C37.48-1969, Guide for Application, Operation, and Maintenance of Distribution Cutouts
and Fuse Links, Secondary Fuses, Distribution Enclosed Single-Pole Air Switches, Power Fuses,
Fuse Disconnecting Switches, and Accessories
Suggestions for improvement gained in the use of this standard will be welcome. They should be
sent to:
American National Standards Institute
1430 Broadway
New York, NY 10018

The Standards Committee on Power Switchgear, C37, which reviewed and approved this Guide,
had the following personnel at the time of approval:

C. L. Wagner, Chairman D. J. Polasky, Secretary


J. E. Beehler, Executive Vice-chairman of High Voltage Switchgear Standards
W. E. Laubach, Executive Vice-chairman of L o w Voltage Switchgear Standards
S. H. Telender, Executive Vice-chairman of IEC Activities
Organization Represented Name of Representative
Association o f American Railroads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Vacant
Association o f Iron and Steel Engineers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . J. M . Tillman

lThis revision includes pertinent data formerly contained in ANSI C37.43-1969. The C37.43 standard is dropped
as redundant.
Organization Represented Name of Representative

Electric Light and Power Group. ................................... J. E. Beehler


R. L. Capra ( A l t )
H. F. Frus
K. D. Hendrix
R. L. Lindsey ( A l t )
J. P. Markey ( A l t )
D. 0. Craghead
Institute of Electrical and Electronics Engineers . . . . . . . . . . . . . . . . . . . . . . . . . M. J. Beachy ( A l t )
H. H. Fahnoe
R. E. Friedrich
M. J. Maier
C. A. Mathews ( A l t )
R. A. McMaster ( A l t )
H. W. Mikulecky
D. C. Musgrave ( A l t )
C. A. Schwalbe
G. W. Walsh
National Electrical Manufacturers Association. . . . . . . . . . . . . . . . . . . . . . . . . . . J. L. Drown
R. W. Dunham
D. G. Portman
G. A. Wilson
W. R. Wilson
Tennessee Valley Authority. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Robert C. St. Clair
Testing Laboratory Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L. Frier
E. J. Huber
R. W. Seelbach ( A l t )
U.S. Department of the Army Corp of Engineers. . . . . . . . . . . . . . . . . . . . . . . . . J. S. Robertson
U.S. Department of the Interior, Bureau of Reclamation. . . . . . . . . . . . . . . . . . . . Edward M. Tomsic
U.S. Department of Defense, Defense Communications Agency . . . . . . . . . . . . . . . Vacant
U.S. Department of the Navy, Naval Construction Battalion Center . . . . . . . . . . . . A. R. Hanks
J. N. Montagna

At the time this standard was approved, the IEEE High-Voltage Fuse Subcommittee of the
Switchgear Committee had the following membership :
H . W. Mikulecky, Chairman
R. H. Amundson R. F. Burnett R. E. Koch
J. G. Angelis F. L. Cameron J. R. Marek
E. H. Arjeski A. DuPont H. G. Reid
R. H. Arndt H. H. Fahnoe W. H. Russell
L. R. Beard G. P. Gill W. Schmunk
R. Bennett H. Swanson

The membership of the C37 Subcommittee was as follows:


R. H . Arndt, Chairman D. J. Polasky, Secretary
M. J. Beachy C. H. Griffin A. M. Salazar
R. E. Bennett S. Lampe E. W. Schmunk
F. L. Cameron J. Marek G. D. Smith
L. Cavic H. W. Mikulecky R. B. Steel
A. M. DiCioccio W. W. Olive E. E. Steven
R. A. Few J. G. St. Clair H. E. Swanson
G. P. Gill K. Behrendt ( A l t )

The membership of the NEMA High-Voltage Fuse Technical Committee was as follows:
F . L . Cameron, Chairman D. J. Polasky, Secretary
J. G. Angelis ( A l t ) R. A. Few ( A l t ) W. W. Olive
R. Ball ( A l t ) J. Fox R. L. Robertson
L. R. Beard G. P. Gill R. B. Steel
R. E. Bennett J. R. Marek H. E. Swanson
F. L. Cameron H. L. Miller J. S. Wall
H. A. Norberg
When it approved this standard on September 18, 1980, the IEEE Standards Board had the fol-
lowing membership:
Irvin N. Howell, Jr, Chairman Irving Kolodny, Vice Chairman
Sava I. Sherr, Secretary

Jay Forster
G. Y. R. Allen Kurt Greene F. Rosa
C. N . Berglund H. Mark Grove B. A. Rowley
Edward Chelotti Loering M. Johnson Alan J. Simmons
Edward J. Cohen Joseph L. Koepfinger Robert L. Simpson
Warren H. Cook W. R. Kruesi W. E. Vannah
Len S. Corey Leon Levy Virginius N. Vaughan, Jr
R. 0. Duncan J. E. May Art Wall
Ivan G. Easton Donald T. Michael* Robert E. Weiler

*Member emeritus
Contents
SECTION PAGE
1. ScopeandReferences. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2 . Serviceconditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3. Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.2 Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.3 Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
TABLES
Table 1 Altitude Correction Factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Table 2 Summary of Temperature Limitations ...................................... 16
An American National Standard

IEEE Standard Service Conditions and


Definitions for High-Voltage Fuses,
Distribution Enclosed Single-Pole Air Switches,
Fuse Disconnecting Switches, and Accessories

1. Scope and References 2. Service Conditions

1.1 Scope. This standard applies to high-voltage 2.1 Usual Service Conditions. Equipment con-
fuses (above 600 V), distribution enclosed forming t o this standard shall be suitable for
single-pole air switches, fuse disconnecting operation at its standard rating, provided that
switches, and accessories for ac distribution the ambient temperature of the cooling medi-
systems, as follows: um does not exceed 40 'C, the altitude does
(1)Enclosed, open, and open-link types of not exceed 1000 m (3300 f t ) and the fre-
distribution cutouts and fuses quency is 60 Hz.
(2) Distribution current limiting fuses
(3) Distribution oil cutouts
(4) Distribution enclosed single-pole air
switches 2.2 Unusual Service Conditions. Where equip-
(5) Power fuses, including current-limiting ment is to be used under conditions other than
types those listed in 2.1 as usual conditions, the un-
(6) Outdoor and indoor fuse disconnecting usual conditions should be brought to the at-
switches tention of those responsible for the design and
(7) Fuse supports, fuse mountings, fuse application. Examples of such conditions are:
hooks, fuse tongs, and fuse links, all of the (1)Ambient temperature! exceeding 40 "C
type used exclusively with products listed in (2) Altitudes in excess of 1000 m (3300 ft);
(1)through (6) use corrections in 2.3
(8) Removable switch blades for products (3) Exposure to damaging fumes or vapors,
listed in (1)through (3) excessive or abrasive dust, explosive mixtures
of dust or gases, steam, salt spray, excessive
moisture, or dripping water
(4) Exposure to abnormal vibration, shocks,
1.2 References. When the American National or tilting
Standards referred t o in this standard are (5) Exposure to unusually high or low
superseded by a revision approved by the temperatures
American National Standards Institute, the (6) Exposure to unusual transportation or
revision shall apply. storage conditons
(7) Unusual space limitations
[ l ] ANSI C84.1-1977, Voltage Ratings for (8) Unusual operating duty, frequency of
Electric Power Systems and Equipment (60 operation, difficulty of maintenance, etc
Hz) (9) Frequencies other than 60 Hz
[21 c37.41-1981, Tests for 2.3 Correction of Altitudes in Excess of
High-Voltage Fuses, Distribution Enclosed looo (3300 ft). Equipment that depends
Single-Pole Air Switches, Fuse Disconnecting
on air for its and cooling medium
Switches, and Accessories
will have a higher temperature rise and a lower
[3] ANSI/IEEE C37.100-1981, Definitions for dielectric value when operated at altitudes
Power Switchgear higher than 1000 m (3300 ft). Correction

7
ANSI/IEEE
C37.40-1981 IEEE STANDARD SERVICE CONDITIONS FOR HIGH-VOLTAGE FUSES,

Table 1 A dagger indicates that at the time this stan-


Altitude Correction dard was approved, there were no correspond-
ing definitions in ANSI/IEEE C37.100-1981
Altitude Above Altitude Correction Factor
Sea Level to be Applied t o [31.
These definitions are recognized as Amer-
Rated ican National Standard only for the purposes
Dielectric Continuous Ambient of this particular standard.
Strength Current Temperature

Meters Feet 1 2 3 3.1 General


1000 3300 1.00 1.00 1.00 air switch. A switch with contacts that separate
1200 4000 0.98 0.99 0.992
1500 5000 0.95 0.99 0.980 in air.*
1800 6000 0.92 0.98 0.968
2100 7000 0.89 0.98 0.956 ambient temperature. The temperature of the
2400 8000 0.86 0.97 0.944 surrounding medium that comes in contact
2700 9000 0.83 0.96 0.932 with the device or equipment.
3000 10000 0.80 0.96 0.920
3600 12000 0.75 0.95 0.896 arc extinguishing medium (fuse filler). Ma-
4300 14000 0.70 0.93 0.872
4900 16 000 0.65 0.92 0.848 terial included in the fuse to facilitate current
5500 18000 0.61 0.91 0.824 interruption.
6100 20000 0.56 0.90 0.800
arcing time of a fuse. The time elapsing from
NOTE: Use one correction factor from Columns 2 or the severance of the current-responsive element
3, but not both, for any one application. If the derating t o the final interruption of the circuit.
as determined from the table is significant, equipment
of suitable higher rating should be chosen to meet re- available (prospective) short-circuit current (at
quirements after the correction factor has been applied.
a given point in a circuit). The maximum cur-
rent that the power system can deliver through
a given circuit point to any negligible impedance
short circuit applied at the given point, or at
any other point that will cause the highest cur-
rent t o flow through the given point.
factors for dielectric strength and rated con-
tinuous current are given in Table 1,columns NOTES: (1) This value can be in terms of either sym-
metrical or asymmetrical, peak or rms current, as
1and 2. specified.
Equipment designed for standard tempera- (2) In some resonant circuits, the maximum avail-
ture iise may be used at its normal rated con- able short-circuit current may occur when the short-
tinuous current without exceeding ultimate circuit is placed at some other point than the given
one where the available current is measured.
standard temperature limits provided that the
ambient temperature does not exceed the back-connected fuse. A fuse in which the cur-
ambient allowed in 2.1, multiplied by the fac- rent carrying conductor are fastened to the
tor shown in Table 1,column 3. studs in the rear of the mounting base.?
back-up current limiting fuse. A fuse capable
of interrupting all currents from the maximum
rated interrupting current down to the rated
3. Definitions minimum interrupting current.?
Most of the following definitions are taken barrier. A partition for the insulation or isola-
from those given in ANSI/IEEE C37.100- tion of electric circuits or electric arcs.
19812 [3]. base. The supporting member to which the in-
An asterisk following a definition indicates sulator unit or units are attached.
that while the term is defined in ANSI/IEEE
C37.100-1981 [3] the two definitions are not basic impulse insulation level (bil) (rated im-
identical. pulse withstand voltage). A reference impulse
insulation strength expressed in terms of the
crest value of the withstand voltage of a stan-
The numbers in brackets correspond t o the refer-
ences listed in 1.2 of this standard. dard full impulse voltage wave.

8
ANSI/IEEE
DISTRIBUTION ENCLOSED SINGLE-POLE AIR SWITCHES C37.40-1981

blade (disconnecting blade of a switch or dis- characteristic curve (of a current limiting fuse).
connecting cutout). The moving contact mem- A curve showing the relationship between the
ber which enters or embraces the content maximum peak current passed by a fuse and
clips.* the correlated rms available current magnitude
under specified voltage and circuit impedance
NOTE: In distribution cutouts the blade may be a non-
fusible member for mounting on a fuse carrier in conditions.
place of a fuse link, or in a fuse support, in place of a
fuse holder. NOTE: The rms available current may be symmetrical
or asymmetrical.
break distance (of a switching device). The
current limiting fuse unit. A fuse unit that
minimum open gap distance between the main
when it is melted by a current within its speci-
circuit contacts or live parts connected thereto
fied current limiting range, abruptly introduces
when the contacts are in the open position.
a high resistance to reduce the current magni-
NOTE: In a multiple-break device, it is the sum of the tude and duration.
breaks in series.
NOTES: (1) The values specified in standards for the
carrier, fuse (for distribution oil cutouts). An threshold ratio, peak let-through current, and 12t
assembly of a cap which closes the top opening characteristics are used as the measures of current-
limiting ability.
of an oil cutout housing, an insulating mem-
(2) There are two classes of current limiting fuse
ber, and fuse contacts with means for making units; power and distribution. They are differentiated
contact with the conducting element and for one from the other by current ratings and minimum
insertion into the fuse contacts of the fuse melting time current characteristic.
support. current-responsive element (of a fuse). That
NOTE: The fuse carrier does not include the conduct- part with predetermined characteristics, the
ing element (fuse link). melting and severance or severances of which
initiate the interrupting function of the fuse.
clearing time (total clearing time) (of a fuse).
The time elapsing from the beginning of a NOTE: The current responsive element may consist of
specified overcurrent to the final circuit inter- one or more fuseable elements combined with a strain
element or other component(s), or both, which af-
ruption at rated maximum voltage.* fect(s) the current responsive characteristics.
NOTE: The clearing time is equal to the sum of melt- cutout. See distribution cutout.
ing time and the arcing time.
disconnecting switch. A switch used for chang-
clips, fuse (contact clips or fuse contacts). The ing the connections in a circuit, or for isolating
current carrying parts of a fuse support which a circuit or equipment from the source of
engage the fuse carrier, fuse holder, fuse unit power. *
or blade.*
NOTE: It is required to carry normal load current con-
condenser fuse. A device that, added to a tinuously and also abnormal or short-circuit currents
vented fuse, converts it to a non-vented fuse for short intervals as specified. It is also required to
open or close circuits either when negligible current is
by providing a sealed chamber for condensa- broken or made, or when no significant change in the
tion of gases developed during circuit inter- voltage across the terminals of each of the switch poles
ruption. occurs. Some disconnecting switches have some in-
herent load-break ability which can best be evaluated
conducting element (fuse link) (of a fuse). The by the user, based on experience under operating
conditions.
conducting means, including the current re-
sponsive element, for completing the electric distribution (used as an adjective). A general
circuit between the terminals of a fuse holder term used, by reason of specific physical or
of fuse unit. electrical characteristics, t o denote application
or restriction of the modified term, or both, t o
current carrying part. A conducting part in-
that part of an electrical system used for con-
tended to be connected in an electric circuit
veying energy to the point of utilization from
t o a source of voltage.
a source or from one or more main receiving
NOTE : Non-current carrying parts are those not in- stations.
tended t o be so connected.
NOTES: (1) From the standpoint of a utility system,
current limiting (peak let-through or cut-off) the area described is between the generating source

9
ANSI/IEEE
C37.40-1981 IEEE STANDARD SERVICE CONDITIONS FOR HIGH-VOLTAGE FUSES,

or intervening substations and the customer’s entrance (a) Dielectric withstand (bil) strengths at distribution
equipment. level
( 2 ) From the standpoint of a customer’s internal ( b ) Application primarily on distribution feeders
system, the area described is between a source or re- and circuits
ceiving station within the customer’s plant and the (c) Mechanical construction basically adapted to
points of utilization. crossarm mounting
( d ) Operating voltage limits correspond t o distribu-
distribution current limiting fuse, A fuse con- tion voltages
(e) Unless incorporating load-break means, it has n o
sisting of a fuse support and a current limiting interrupting load-break current rating
fuse unit. ( 2 ) Some load-break ability is inherent in the device.
This ability can best be evaluated by the user based on
NOTE: In addition, the distribution current limiting experience under operating conditions.
fuse is identified by the following characteristics: (1)
Dielectric withstand (bil) (basic impulse insulation
level) strengths a t distribution levels distribution fuse cutout. A distribution cutout
( 2 ) Application primarily on distribution feeders and having a fuse holder or fuse carrier and fuse
circuits link or a fuse unit.*
( 3 ) Operating voltage limits correspond to distribu-
tion system voltage NOTE: A fuse cutout is a fuse disconnecting switch.
It has some inherent load break ability but does not
distribution cutout. A fuse or disconnecting have a load-break rating. The load-break ability can
device consisting of any one of the following best be evaluated by the user, based on experience
under operating conditions.
assemblies:
(1)A fuse support and fuse holder which drop-out fuse. A fuse in which the fuse holder
may or may not include the conducting ele- or fuse unit automatically drops into an open
ment (or fuse link) position after the fuse has interrupted the
(2) A fuse support and disconnecting blade circuit.
(3) A fuse support and fuse carrier which
may or may not include the conducting ele- electrical interchangeability (of fuse links or
ment (fuse link) or disconnecting blade fuse units). The characteristic that permits
the designs of various manufacturers to be
NOTE: In addition, the distribution cutout is identi- used interchangeably so as to provide a uni-
fied by the following characteristics: (1) Dielectric
withstand (bil) (basic impulse insulation level) form degree of overcurrent protection and
strengths at distribution levels fuse coordination.
( 2 ) Application primarily on distribution feeders
and circuits enclosed cutout. A cutout in which the fuse
( 3 ) Mechanical construction basically adapted to pole clips and fuse holder or disconnecting blade
or crossarm mounting except for the distribution are mounted completely within an insulating
oil cutout
enclosure.
( 4 ) Operating voltage limits correspond to distribu-
tion system voltage entrance terminal (for distribution oil cutouts).
distribution disconnecting cutout. A distribu- A terminal with an electrical connection t o the
tion cutout, having a disconnecting blade, fuse contact and suitable insulation where
which is used for closing, opening, or changing the connection passes through the housing.
the connections in a circuit or system, or for expansion chamber (for a distribution oil cut-
isolating purposes.* out). A sealed chamber separately attachable
NOTE: Some load-break ability is inherent in the de- to the vent opening t o provide additional air
vice but it has no load-break rating. This ability can space into which the gases developed during
best be evaluated by the user, based on experience circuit interruption can expand and cool.
under operating conditions.
expendable-cap cutout. An open cutout hav-
distribution enclosed single-pole air switches ing a fuse support designed for, and equipped
(distribution enclosed air switches). A single- with, a fuse holder having an expendable cap.
pole disconnecting switch in which the con-
tacts and blade are mounted completely within expendable cap (of an expendable-cap cut-
an insulated enclosure (cannot be converted out). A replacement part or assembly for
into a distribution cutout or disconnecting clamping the button head of a fuse link and
fuse). closing one end of the fuse holder. It includes
NOTES: ( 1 ) The distribution enclosed air switch is a pressure-responsive section which opens to
identified by the following characteristics : relieve the pressure within the fuse holder

10
ANSI/IEEE
DISTRIBUTION ENCLOSED SINGLE-POLE AIR SWITCHES C37.40-1981

when a predetermined value is exceeded dur- fuse holder. An assembly of a fuse tube or
ing circuit interruption. tubes together with parts necessary t o enclose
the conducting element and provide means of
explosion-proof fuse. A fuse, so constructed
making contact with the conducting element
or protected, that for all current interruptions
and the fuse clips. The fuse holder does not
within its rating shall not be damaged nor
include the conducting element (fuse link or
transmit flame t o the outside of the fuse.
refill unit).
expulsion fuse. A vented fuse in which the
fuse hook (switch hook). A hook provided
expulsion effect of gases produced by the arc
with an insulating handle for opening and
and lining of the fuse holder, either alone or
closing fuses or switches and for inserting
aided by a spring, extinguishes the arc.*
the fuse holder, fuse unit, or disconnecting
expulsion fuse unit (expulsion fuse). A vented blade into, and for removing it from, the fuse
fuse unit in which the expulsion effect of support.
gases produced by the arc and lining of the
fuse holder, either alone or aided by a spring, fuse link. A replaceable part or assembly, com-
extinguishes the arc. prised entirely or principally of the conducting
element required to be replaced after each
factory renewable fuse unit. A fuse unit that, circuit interruption to restore the fuse to op-
after circuit interruption, must be returned t o erating condition.
the manufacturer t o be restored for service.
fuse muffler. An attachment for the vent of a
field renewable fuse unit. A fuse unit that, fuse, or a vented fuse, that confines the arc and
after circuit interruption, may be readily re- substantially reduces the venting from the fuse.
stored for service by the replacement of the
fuse support (fuse mounting). An assembly of
fuse link or refill unit.*
base or mounting support or oil cutout hous-
front and back-connected fuse. A fuse in which ing, insulator(s) or insulator unit(s), and fuse
one or more current carrying conductors are clips for mounting a fuse carrier, fuse holder,
connected directly to the fixed terminals lo- fuse unit, or blade and connecting it into the
cated at the front of the mounting base, the circuit.*
remaining conductors being connected t o the
fuse time-current characteristic. The correlated
studs on the back of the mounting base.?
values of time and current that designate the
front-connected fuse. A fuse in which the performance of all or a stated portion of the
current-carrying conductors are fastened t o the functions of the fuse.
fixed terminals in front of the mounting base.?
NOTE: The time-current characteristics d a fuse are
fuse. An overcurrent protective device with a usually shown on a curve.
circuit opening fusible part that is heated and
severed by the passage of overcurrent through fuse tube. A tube of insulating material which
it. encloses the conducting element.*

NOTE: A fuse comprises all the parts that form a unit


fuse unit. An assembly comprising a conduct-
capable of performing the prescribed functions. It ing element mounted in a fuse holder with
may or may not be the complete device necessary t o parts and materials in the fuse holder essential
connect it into an electric circuit. to the operation of the fuse.
fuse disconnecting switch (disconnecting fuse). fusible element (of a fuse). That part, having
A disconnecting switch in which a fuse unit or predetermined current responsive melting char-
fuse holder and fuse link form all or part of acteristics, which may be all or part of the cur-
the blade. rent responsive element.
fuse enclosure package (FEP). An enclosure general purpose current limiting fuse. A fuse
supplied with one or more current limiting capable of interrupting all currents from the
fuses as a package for which application data rated interrupting current down to the current
covering the specific fuse(s) and enclosure that causes melting of the fusible element in
are supplied. 1h . t

11
ANSI/IEEE
C37.40-1981 IEEE STANDARD SERVICE CONDITIONS FOR HIGH-VOLTAGE FUSES,

granular-filled fuse unit. A fuse unit in which materials or combinations of materials may be
the arc is drawn through powdered, granular, included in this class if, by experience or ac-
or fibrous material. cepted tests, they can be shown t o be capable
of operation at 105 "C.
groundable parts. Those parts which may be
Class 130. Materials or combinations of
connnected to ground without affecting op-
materials such as mica, glass fiber, asbestos, etc,
eration of the device.
with suitable bonding substances. Other ma-
grounded parts. Parts that are intentionally terials or combinations of materials, not neces-
connected to ground. sarily inorganic, may be included in this class
if, by experience or accepted tests, they can
guide. An attachment used to secure proper
be shown t o be capable of operation at 130 "C.
alignment when operating a fuse or switch.
Class 155. Materials or combinations of ma-
homogeneous series (of current limiting fuse terials such as mica, glass fiber, asbestos, etc,
units). A series of fuse units, deviating from with suitable bonding substances. Other ma-
each other only in such characteristics that, terials or combinations of materials, not neces-
for a given test, the testing of one or a re- sarily inorganic, may be included in this class
duced number of particular fuse unit(s) of if, by experience or accepted tests, they can
the series may be taken as representative of be shown to be capable of operation at 155°C.
all the fuse units of the series. Class 180. Materials or combinations of ma-
terials such as silicone elastomer, mica, glass
housing (body) (of an oil cutout). A part of
fiber, asbestos, etc, with suitable bonding sub-
the fuse support that contains the oil and
stances such as appropriate silicone resins.
provides means for mounting the fuse carrier,
Other materials or combinations of materials
entrance terminals, and fixed contacts. The
may be included in this class if, by experience
housing includes the means for mounting the
or accepted tests, they can be shown to be
cutout on a supporting structure and openings
capable of operation at 180 "C.
for attaching accessories such as a vent or an
expansion chamber. Class 220. Materials or combinations of ma-
terials that by experience or accepted tests
indicating fuse. A fuse that automatically in- can be shown t o be capable of operation
dicates that the fuse has interrupted the cir- at 220 "C.
cuit. Over Class 220. Insulation that consists
entirely of mica, porcelain, glass, quartz, and
indoor. Designed for use only inside buildings.
similar inorganic materials. Other materials or
insulator unit. An insulator assembled with combinations of materials may be included in
such metal parts as may be necessary for at- this class if, by experience or accepted tests,
taching it to other insulating units or device they can be shown t o be capable of operation
parts. at temperatures over 220 "C.
insulation. A material having the property of
an insulator used t o separate parts of the same NOTES: (1)Insulation is considered to be impregnated
or different potential.? when a suitable substance provides a bond between
components of the structure and also a degree of
classes of insulating materials. For the purpose filling and surface coverage sufficient to give ade-
of establishing temperature limits, insulating quate performance under the extremes of tempera-
ture, surface contamination (moisture, dirt, etc), and
materials shall be classified as follows: mechanical stress expected in service. The impregnant
Class 90. Materials or combinations of ma- shall not flow or deteriorate enough at operating
terials such as cotton, silk, and paper without temperature so as to seriously affect performance in
service.
impregnation. Other materials, or combina- ( 2 ) The electrical and mechanical properties of the
tions of materials may be included in this class insulation shall not be impaired by the prolonged
if, by experience or accepted tests, they can application of the limiting insulation temperature per-
mitted for the specific insulation class. The word
be shown to be capable of operation at 90 "C. impaired is here used in the sense of causing any
Class 105. Materials or combinations of ma- change that could disqualify the insulating material
terials such as cotton, silk and paper when for continuously performing its intended function,
whether creepage, spacing, mechanical support, or
suitably impregnated or coated or when im- dielectric barrier action.
mersed in a dielectric liquid such as oil. Other ( 3 ) In the above descriptions the words accepted

12
ANSI / IEE E
DISTRIBUTION ENCLOSED SINGLE-POLE AIR SWITCHES C37.40-1981

tests are intended to refer to recognized test pro- between clearance and spacing or center-to-center
cedures established for the thermal evaluation of ma- distance.
terials by themselves or in simple combinations. Ex-
perience or test data, used in classifying insulating minimum clearance t o ground. The shortest
materials, are distinct from the experience or test distance between any live part and adjacent
data derived for the use of materials in complete in-
sulation systems. The thermal endurance of complete grounded parts.
systems may be determined by test procedures speci-
fied by the responsible technical committees. A ma- minimum melting current. The smallest current
terial that is classified as suitable for a given tempera- at which a current responsive fuse element will
ture in the above tabulation may be found suitable melt at any specified time.?
for a different temperature, either higher or lower, by
an insulation system test procedure. For example, it mounting position (of a switch or fuse sup-
has been found that some materials suitable for op-
eration at one temperature in air m a y be suitable for port). A position determined by and cor-
a higher temperature when used in a system operated responding to the position of the base of
in an inert gas atmosphere. the device.
( 4 ) I! is important t o recognize that other character-
istics, in addition to thermal endurance, such as me-
chanical strength, moisture resistance, and corona NOTE: The usual positions are: (1)Vertical
endurance, are required in varying degrees in different ( 2 ) Horizontal upright (when the fuse holder or fuse
applications for the successful use of insulating ma- unit is mounted above the supporting insulators)
terials. ( 3 ) Horizontal underhung (when the fuse holder
or fuse unit is mounted below the supporting insula-
tors)
latch. An attachment used t o hold a fuse or ( 4 ) Angle (from vertical)
switch in the closed position.
multipole fuse. An assembly of two or more
lifting eye (of a fuse holder, fuse unit, or dis-
single-pole fuses.?
connecting blade). An eye provided for re-
ceiving a fuse hook or switch hook for insert- nondisconnecting fuse. An assembly consisting
ing the fuse or disconnecting blade into and for of a fuse unit or fuse holder and a fuse support
removing it from the fuse support.? having clips for directly receiving the associ-
ated fuse unit or fuse holder, which has no pro-
link-break cutout. A load-break fuse cutout
that is operated by breaking the fuse link t o vision for guided operation as a disconnecting
interrupt the load current. switch.

liquid filled fuse unit. A fuse unit in which nonrenewable fuse unit. A fuse unit that, after
the arc is drawn through a liquid. circuit interruption, cannot readily be restored
for service.*
live parts. Those parts which are designed t o
operate at voltage different from that of the nonvented fuse (or fuse unit). A fuse without
intentional provision for the escape of arc
earth.
gases, liquids, or solid particles, t o the atmos-
load-break cutout. A cutout with means for phere during circuit interruption.
interrupting load currents.
normal-frequency recovery voltage. The normal-
mechanical interchangeability (of fuse links). frequency rms voltage that occurs across the
The characteristic that permits the designs terminals of an ac circuit interrupting device
of various manufacturers t o be interchanged after the interruption of the current and after
physically so that they fit into and withstand the high-frequency transients have subsided.
the tensile stresses imposed by various types
oil cutout (oil-filled cutout). A cutout in which
of prescribed cutouts made by different
all or part of the fuse support and its fuse link
manufacturers.
or disconnecting blade are mounted in oil with
melting time of a fuse. The time required for complete immersion of the contacts and the
overcurrent t o sever the current-responsive fusible portion of the conducting element (fuse
element. link) so that arc interruption by severing of
the fuse link or by opening of contacts will
minimum clearance between poles (phases).
occur under oil.
The shortest distance between any live parts
of adjacent poles (phases). oil immersible current limiting fuse unit.
A current limiting fuse unit suitable for appli-
NOTE : Cautionary differentiation should be made caton requiring total or partial immersion

13
ANSI/IEEE
C37.40-1981 IEEE STANDARD SERVICE CONDITIONS FOR HIGH-VOLTAGE FUSES,

directly in oil or other dielectric liquid of a of a fuse support. and a fuse unit or fuse holder
transformer or switchgear. which may or may not include the refill unit
or fuse link.
oil switch. A switch with contacts that separate
in oil.* NOTE: The power fuse is identified by the following
characteristics: ( 1 ) Dielectric withstand (bil) strengths
open cutout. A cutout in which the fuse clips at power levels
and fuse holder, fuse unit, or disconnecting ( 2 ) Application primarily in stations and substations
( 3 ) Mechanical construction basically adapted t o sta-
blade are exposed. tion and substation mountings.
opening eye (of a fuse holder, fuse unit, or proof (used as a suffix). So constructed, pro-
disconnecting blade). An eye provided for tected or treated that successful operation is
receiving a fuse hook or switch hook for not interfered with when the device is subjected
opening and closing the fuse.? to the specified material or condition.
open link cutout. A cutout that does not NOTE: Explosion-proof requires that the fuse shall not
employ a fuse holder and in which the fuse be injured and flame shall not be transmitted to the
support directly receives an open-link fuse outside of the fuse for all current interruptions within
the rating of the fuse.*
link or a disconnecting blade.
open-link fuse link. A replaceable part or as- quick-break switch. A switch that has a high
sembly comprised of the conducting element contact opening speed independent of the op-
and fuse tube, together with the parts neces- erator.*
sary t o confine and aid in extinguishing the
reclosing fuse. A combination of two or more
arc and to connect it directly into the fuse
fuse holders, fuse units, or fuse links mounted
clips of the open-link fuse support.
on a fuse support or supports, mechanically
open-link fuse support. An assembly of base or electrically interlocked, so that one fuse
or mounting support, insulators or insulator can be connected into the circuit at a time and
unit, and fuse clips for directly mounting an the functioning of that fuse automatically con-
open-link fuse link and for connecting it into nects the next fuse into the circuit, with or
the circuit. without intentionally added time delay, there-
by permitting one or more service restorations
outdoor. Designed for use outside buildings.
without replacement of fuse links, refill units,
peak let-through (cutoff) current (of a cur- or fuse units.
rent-limiting fuse). The highest instantaneous
current passed by the fuse during the inter- recovery voltage. The voltage which occurs
across the terminals of a pole of a circuit inter-
ruption of the circuit.
rupting device upon an interruption of the
peak overvoltages for current-limiting fuses. current .
The peak value of the voltage that can exist
across a current-limiting fuse during its arcing refill unit (of a fuse unit). An assembly com-
prised of a conducting element, the complete
interval.?
arc extinguishing medium, and parts normally
performance characteristics (of a device). An required t o be replaced after each circuit
operating characteristic, the limit or limits, of interruption to restore the fuse unit to its
which are given in the design test specifica- original operating condition.
tions.
resistant (used as a suffix). So constructed,
phase spacing. The distance between center- protected or treated that damage will not
lines of adjacent devices of differing phases. readily occur when the device is subjected t o
the specified material or condition.
power (used as an adjective). A general term
used by reason of specific physical or elec- solid material fuse unit. A fuse unit in which
trical characteristics to denote application or the arc is drawn through a hole in solid ma-
restriction, or both, to generating stations, terial.
switching stations, or substations.
speed ratio. The ratio between 0.1 s and 300 s
power fuse. A fuse consisting of an assembly or 600 s minimum melting currents, whichever

14
ANSI/IEEE
DISTRIBUTION ENCLOSED SINGLE-POLE AIR SWITCHES C37.40-1981

is specified, which designates the relative vent (of a fuse). The means provided for the es-
speed of the fuse link.* cape of the gases developed during circuit inter-
ruption.
strain element (strain wire) (of a fuse). That
. part of the current-responsive element, con- NOTE: In distribution oil cutouts, the vent may be an
nected in parallel with the fusible element in opening in the housing, or an accessory attachable t o
a vent opening in the housing, with suitable means to
order to relieve it of tensile strain. prevent loss of oil.
NOTE: The fusible element melts and severs first and 3.2 Ratings.
then the strain element melts during circuit inter-
ruption. allowable continuous current (of a fuse link,
fuse unit or refill unit). The maximum rms cur-
submersible entrance terminals (cableheads) rent in amperes at rated frequency and at a
(for distribution oil cutouts). A hermetically specific ambient temperature which a device
sealable entrance terminal for the connection will carry continuously without exceeding the
of cable having a submersible sheathing or allowable total temperature as listed in Table 2.
jacket.
intermediate current ratings of distribution
submersible fuse (subway oil cutout). A fuse fuse links. A series of distribution fuse link
that is so constructed that it will operate suc- ratings chosen from a series of preferred
cessfully when submerged in water under speci- numbers which are spaced between the pre-
fied conditions of pressure and time.? ferred current ratings, but which may not pro-
switch. A device designed to close or open, vide coordination therewith. Coordination be-
or both, one or more electric circuits. tween adjacent intermediate ratings may be
secured to the same degree as between adja-
terminal (terminal connector). A connector for cent preferred current ratings.?
attaching a conductor t o electrical apparatus.
preferred current ratings of distribution fuse
terminal pad. A usually flat conducting part of links. A series of distribution fuse link ratings
a device to which a terminal connector is so chosen from a series of preferred numbers
fastened. that a specified degree of coordination may be
tight (used as a suffix). So constructed that the obtained between adjacent sizes.?
specific material is excluded under specified rated continuous current. The maximum rms
conditions. current in amperes, at rated frequency which
tongs, fuse. Tongs provided with an insulating a device will carry continuously without ex-
handle and jaws. Fuse tongs are used t o insert ceeding the allowable temperature rise and
the fuse holder or fuse unit into the fuse sup- total temperature as listed in Table 2.
port or t o remove it from the support. rated 15-cycle current (15cycle current rat-
transient recovery voltage. The voltage transient ing) (of a disconnecting device or assembly).
that occurs across the terminals of a pole of a The rms symmetrical current of an asym-
circuit switching device upon interruption of metrical wave produced by a circuit having a
the current. prescribed X l R ratio, which the device or as-
sembly is required to carry for 1 5 cycles.?
NOTE: It is the difference between the transient
voltages t o ground occurring o n the terminals. It may NOTE: This rating is an index of the ability of the
be a circuit transient recovery voltage, a modified disconnecting device to withstand heat that may be
circuit transient recovery voltage, or an actual transient generated under short-circuit conditions.
recovery voltage.
rated frequency (frequency rating) (of a fuse).
universal fuse links. Fuse links that for each The system frequency for which it is de-
rating provide mechanical and electrical inter- signed.?
changeability within prescribed limits over the
rated interrupting current (rated interrupting
specified time-current range.
capacity) (current interrupting rating) (of a
vented fuse (or fuse unit). A fuse with provi- fuse). The designated value of the highest avail-
sion for the escape of arc gases, liquids, or solid able rms short-circuit current which the fuse is
particles t o the surrounding atmosphere dur- required t o interrupt successfully under stated
ing circuit interruption. conditions.?

15
ANSI/IEEE
C37.40-1981 IEEE STANDARD SERVICE CONDITIONS FOR HIGH-VOLTAGE FUSES,

Table 2
Summary of Temperature Limitations
Allowable Temperature Rise (and Total Temperature Shown in Parenthesis)
Temperatures Shown in "C

All Conducting All Parts Made Up of


Parts, Except or in Contact with Insulating
Conducting Element Materials Except
of Fuse Link Fuse Link
~~

Type of Contact
Class of Temperature
Device AG-AG AG-CU CU-CU Sn-Sn Insulation Limits

Distribution 40 30 Bone fiber


cutouts With fuse link (80) (70) 90 30 (70)
(except oil 105 50 (90)
cutouts and 40 35 35 130 6 5 (105)
open link With switch blade (80) (75) (75) 90 (130)
cutouts)

Distribution With link or 45 30 30


oil cutouts blade (85) (70) (70) 50 (90)
90 6 5 (105)
Distribution 40 35 35 40 105 90 (130)
air switches (80) (75) (75) (80) 130
Distribution 65 30 55
current limiting fuses (105) (70) (95) 90 50 (90)
105 65 (105)
Current limiting 65 30 55 130 90 (130)
(105) (70) (95) 155 115 (155)
Power Fuses 180 140 (180)
All others 45 30 45 220 180 (220)
(85) (70) (85)

rated load-break current (load break current rated minimum interrupting current. The
rating). The designated value of the maximum designated value of the smallest current that
rms current which a device having operable a fuse is required to interrupt at a designated
means for interrupting load currents is required voltage under prescribed conditions.?
to interrupt successfully under stated condi-
rated momentary current (momentary cur-
tions when opened by manual or remote con-
rent rating). The maximum current measured
trol means.?
at the major peak of the maximum cycle,
rated making current. The maximum rms cur- which the device or assembly is required to
rent against which the device is required to carry .?
close successfully when switched from the NOTES: (1) The current is expressed as the rms
open to the closed position.? value including the direct-current component, as de-
termined from the envelope of the current wave by
rated maximum voltage (maximum voltage the method shown in Appendix A of ANSI/IEEE
rating). The highest rms voltage at which the C37.41-1981 [ 21.
(2) This rating is an index of the ability of the dis-
device is designed to operate.? connecting device t o withstand electromagnetic forces
under short-circuit conditions.
NOTE: This voltage corresponds to the maximum
tolerable zone primary voltage at distribution trans- rated short-time current (short-time current
formers for distribution cutouts and single-pole air rating) (of a disconnecting device). The maxi-
switches, and at substations and on transmission
systems for power fuses given in ANSI (284.1-1977 mum rms total current (including the direct-
[I]. current component) which the device is re-

16
ANSI/IEEE
DISTRIBUTION ENCLOSED SINGLE-POLE AIR SWITCHES C37.40-1981

quired t o carry successfully for a specified impulse withstand voltage. The crest voltage of
short time interval.? an impulse that, under specified conditions,
NOTE : The ratings recognize the limitations imposed can be applied without causing flashover or
by both thermal and electromagnetic effects. puncture.
rated three-second current (three-second cur- interrupting tests. Tests that are made t o deter-
rent rating). The rms total current, including mine or check the interrupting performance of
the direct-current component which the de- a device.
vice, or assembly, is required t o carry for 3 s.?
load-break tests (load-interrupting tests). Tests
NOTE: For practical purposes, this current is mea- that consist of manual or remote control
sured at the end of the first second. This rating is an
index of the ability of the disconnecting device to
opening of a device, which is provided with a
withstand heat that may be generated under short- means for breaking load, while the device is
circuit conditions. carrying a prescribed current under specified
rating. The designated limit(s) of the rated op- conditions.?
erating characteristic(s) of a device. making-current tests. Tests that consist of
NOTE: Such operating characteristics as current, volt- manual or remote control closing of the de-
age, frequency, etc, may be given in the rating. vice against a prescribed current.?
3.3 Tests normal (low) frequency dew-withstand volt-
available (prospective) short-circuit test cur- age. The rms voltage that can be applied to
rent (at the point of test). The maximum short- an insulator or a device, completely covered
circuit current for any given setting of a testing with condensed moisture, under specified
circuit that the test power source can deliver conditions for a specified time without caus-
at the point of test, with the test circuit short- ing flashover or puncture.*
circuited by a link of negligible impedance at
the line terminals of the device t o be tested. normal (low) frequency dry-withstand volt-
age. The rms voltage that can be applied to
NOTE: This value can be in terms of either sym-
metrical or asymmetrical, peak or rms current, as a dry device under specified conditions for a
specified. specified time without causing flashover or
puncture.*
conformance tests. Those tests that are specif-
ically made t o demonstrate the conformity of normal (low) frequency wet-withstand volt-
switchgear or its component parts with applic- age. The rms voltage that can be applied to
able standards. a wetted device under specified conditions
for a specified time without causing flashover
design tests. Those tests made to determine the or puncture.*
adequacy of the design of a particular type,
style, or model of switchgear or its component radio influence tests. Tests that consist of the
parts t o meet its assigned ratings and t o operate application of voltage and the measurement of
satisfactorily under normal service conditions the corresponding radio-influence voltage pro-
or under special conditions if specified. duced by the device being tested.
NOTE: Design tests are made only on representative routine tests (production tests). Those tests
apparatus to substantiate the ratings assigned to all made t o check the quality and uniformity of
other apparatus of basically the same design. These
tests are not intended to be used as a portion of normal the workmanship and materials used in the
production. The applicable part of these design tests manufacture of switchgear or its components.
may also be used to evaluate modifications of a previ-
ous design and to assure that performance has not been short-time current tests. Tests that consist of
adversely affected. Test data from previous similar de-
signs may be used for current designs, where appropri- the application of a current higher than the
ate. rated continuous current for specified short
periods to determine the adequacy of the de-
dielectric withstand-voltage tests. Tests made vice to withstand short-circuit currents for the
to determine the ability of insulating materials specified short times.?
and spacings t o withstand specified overvolt-
ages for a specified time without flashover or temperature-rise tests. Tests to determine the
puncture. temperature rise, above ambient, of various

17
ANSI/IEEE
C37.40-1981 IEEE STANDARD SERVICE CONDITIONS FOR HIGH-VOLTAGE FUSES,

parts of the tested device when subjected to time-current tests. Tests that consist of the ap-
specified test quantities. plication of current to determine the relation
between the rms alternating current or direct
NOTES: ( 1 ) The test quantities may be current, load, current and the time for the fuse to perfom
etc
( 2 ) Values for various types of devices are shown in the Or Some specified Part Of its inter-
Table 2 rupting function.

18
C37.42-1981 Specifications for Distribution Cutouts C37.63-1969 (R 1 9 7 4 ) Requirements for Automatic
and Fuse Links (ANSI) Line Sectionalizers for Alternating-Current Systems,
(includes supplement C37.63a-1973) (ANSI)
C37.44-1981 Specifications for Distribution Oil Cut-
outs and Fuse Links (ANSI) C37.66-1969 (R 1 9 7 4 ) Requirements for Oil-Filled
Capacitor Switches for Alternating-Current Systems
(237.45-1981 Specifications for Distribution Enclosed (ANSI)
Single-Pole Air Switches (ANSI)
C37.85-1972 (R 1 9 7 8 ) Safety Requirements for X-
(237.46-1981 Specifications for Power Fuses and Fuse Radiation Limits for AC High-Voltage Power Vacuum
Disconnecting Switches (ANSI) Interrupters Used in Power Switchgear (includes sup-
C37.47-1981 Specifications for Distribution Fuse Dis- plement C37.85a-1972) (ANSI)
connecting Switches, Fuse Supports, and Current-
C37.90-1978 Relays and Relay Systems Associated
Limiting Fuses (ANSI) with Electric Power Apparatus ( ANSI/IEEE)
C37.48-1969 (R 1974) Guide for Application, Opera- C37.90a-1974 (R 1979) Guide for Surge Withstand Ca-
tion, and Maintenance of Distribution Cutouts and pability (SWC) Tests (Supplement to ANSI/IEEE
Fuse Links, Secondary Fuses, Distribution Enclosed
C37.90-1978) (ANSI/IEEE)
Single-Pole Air Switches, Power Fuses, Fuse Discon-
necting Switches, and Accessories (ANSI) C37.91-1972 (R 1 9 7 9 ) Guide for Protective Relay Ap-
C37.48a Trial-Use Standard Application of Fuses in plications to Power Transformers ( ANSI/IEEE)
Enclosures (Revision of Section 8, ANSI C37.47- C37.93-1976 Guide for Protective Relay Applications
1969) (ANSI/IEEE) of Audio Tones over Telephone Channels (ANSI/
C37.50-1973 Test Procedures for Low-Voltage AC IEEE)
Power Circuit Breakers Used in Enclosures, (includes C37.95-1974 (R 1 9 7 9 ) Guide for Protective Relaying
supplements C37.50a-1975 and C57.50b-1975) (ANSI) of Utility-Consumer Interconnections (ANSI/IEEE)
C37.51-1979 Conformance Testing of Metal-Enclosed C37.96-1975 Guide for AC Motor Protection (super-
Low-Voltage AC Power Circuit Breaker Switchgear As- sedes C37.92-1972 and C37.94-1972) (ANSI/IEEE)
semblies (ANSI)
C37.97-1979 Guide for Protective Relay Applications
C37.52-1974 Test Procedures for Low-Voltage AC
t o Power System Buses (ANSI/IEEE)
Power Circuit Protectors Used in Enclosures (ANSI)
C37.60-1981 Requirements for Overhead, Pad Mounted, C37.98-1978 Standard for Seismic Testing of Relays
Dry Vault, and Submersible Automatic Circuit Re- (This standard complements ANSI/IEEE 344-1975)
closers and Fault Interrupters for AC Systems (ANSI/ (ANSI/IEEE)
IEEE) C37.99-1980 Guide for the Protection of Shunt Capa-
C37.61-1973 Guide for the Application, Operation, citor Banks (ANSI/IEEE)
and Maintenance of Automatic Circuit Reclosers C37.100-1981 Definitions for Power Switchgear (ANSI/
(ANSI/IEEE) IEEE)
Related Standards in the C37 Series

C37.04-1979 Rating Structure for AC High-Voltage C37.16-1979 Preferred Ratings, Related Requirements
Circuit Breakers Rated o n a Symmetrical Current Basis for and Application Recommendations for Low-
(Consolidated edition, Including supplements C37.04a, Voltage Power Circuit Breakers and AC Power Cir-
C37.04b, and C37.04~).(ANSI/IEEE) cuit Protectors (revision of C37.16-1973) (ANSI)
C37.06-1979 Preferred Ratings and Related Required C37.17-1979 Trip Devices for AC and General Purpose
Capabilities for AC High-Voltage Circuit Breakers DC Low-Voltage Power Circuit Breakers (ANSI)
Rated o n a Symmetrical Current Basis (Consolidated
edition, ANSI) C37.18-1979 Standard Field Discharge Circuit Breakers
C37.09-1979 Test Procedure for AC High-Voltage Used in Enclosures for Rotating Electric Machinery
Circuit Breakers Rated o n a Symmetrical Current (ANSI/IEEE)
Basis (Consolidated edition, ANSI/IEEE) C37.20-1974 Switchgear Assemblies, Including Metal-
C37.010-1979 Application Guide for AC High-Voltage Enclosed Bus (includes supplement C37.20a-1970,
Circuit Breakers Rated o n a Symmetrical Current C37.20b-1972, C37.20~-1974, C37.20d-1978) (Con-
Basis (Consolidated edition, ANSI/IEEE) solidated edition, ANSI/IEEE)
C37.011-1979 Application Guide for Transient Re-
covery Voltage for AC High-Voltage Circuit Breakers C37.23-1970 (R 1977) Guide for Calculating Losses in
Rated o n a Symmetrical Current Basis (Consolidated Isolated-Phase Bus (ANSI/IEEE)
edition, ANSI/IEEE) (Revision of C37.0721-1971) C37.24-1971 (R 1 9 7 6 ) Guide for Evaluating the Effect
C37.012-1979 Application Guide for Capacitance Cur- of Solar Radiation o n Outdoor Metal-Clad Switchgear
rent Switching of AC High-Voltage Circuit Breakers ( ANSI/IEEE)
Rated o n a Symmetrical Current Basis, (Consolidated
C37.26-1972 (R 1 9 7 7 ) Guide for Methods of Power
edition) (ANSI/IEEE) (Revision of C37.0731-1973)
Factor Measurement for Low-Voltage Inductive Test
C37.081-1981 Guide for S y n h e t i c Fault Testing of AC Circuits ( ANSI/IEEE)
High-Voltage Circuit Breakers Rated o n a Symmetrical
Current Basis ( ANSI/IEEE) C37.27-1972 Application Guide for Low-Voltage AC
C37.1-1979 Standard Definition, Specification and Non-Integrally Fused Power Circuit Breakers (Using
Analysis of Manual, Automatic, and Supervisory Sta- Separately Mounted Current-Limiting Fuses) (ANSI/
tion Control and Data Acquisition (ANSI/IEEE) IEEE)
C37.29-1974 Standard for Low-Voltage AC Power
4237.2-1979 Standard Electrical Power System Device Circuit Protectors Used in Enclosures (ANSUIEEE)
Function Numbers (ANSI/IEEE)
C37.4-1953 (R 1 9 7 6 ) Definitions and Rating Struc- C37.30-1971 Definitions and Reauirements for High-
ture for AC High-Voltage Circuit Breakers Rated o n a Voltage Air Switches, Insulators: and Bus Suppcks
Total Current Basis [includes supplements C37.4a- (ANSI/IEEE)
1958 (R 1966) and C37.4b-1970 (R 1971) (reaffirmed
with change in title)] (ANSI) and C37.4~-1980(ANSI/ C37.30a-1975 Supplement to C37.30-1971, (ANSI/
IEEE) IEEE) (sold separately)
C37.5-1979 Guide for Calculation of Fault Currents C37.31-1962 (R 1969) Electrical and Mechanical Char-
for Application of AC High-Voltage Circuit Breakers acteristics of Indoor Apparatus Insulators (ANSI)
Rated o n a Total Current Basis (ANSI/IEEE) C37.32-1972 Schedules of Preferred Ratings, Manu-
C37.6-1971 (R 1 9 7 6 ) Schedules of Preferred Ratings facturing Specifications, and Application Guide for
for AC High-Voltage Circuit Breakers Rated o n a Total High-Voltage Air Switches, Bus Supports, and Switch
Current Basis (ANSI) Accessories (ANSI)
C37.7-1960 (R 1 9 7 6 ) (reaffirmed with change in title) C37.33-1970 (R 1 9 7 6 ) Rated Control Voltages and
Interrupting Rating Factors for Reclosing Service their Ranges for High-Voltage Air Switches (ANSI)
for AC High-Voltage Circuit Breakers Rated o n a Total C37.34-1971 ( R 1977) Test Code for High-Voltage Air
Current Basis (ANSI) Switches (ANSI/IEEE)
C37.9-1953 (R 1976) (reaffirmed with change in title) C37.34a-1975 supplement to C37.34-1971, sold
Test Code for AC High-Voltage Circuit Breakers Rated separately
o n a Total Current Basis [includes supplement C37.9a-
1970 (R 1 9 7 1 ) l (ANSI) C37.35-1976 Guide for the Application, Installation,
Operation, and Maintenance of High-Voltage Air Dis-
C37.11-1975 Requirements for Electrical Control for connecting and Load Interrupter Switches (ANSI)
AC High Voltage Circuit Breakers Rated o n a Sym-
metrical Current Basis and a Total Current Basis C37.37-1979 Loading Guide for AC High-Voltage Air
(ANSI) Switches (In Excess of 1000 Volts) (revision of (337.37-
1971) (ANSI/IEEE)
C37.12-1969 (R 1 9 7 4 ) Guide Specifications for AC
High-Voltage Circuit Breakers Rated o n a Symmetrical C37.40-1981 Service Conditions and Definitions for
Current Basis and a Total Current Basis (ANSI) High-Voltage Fuses, Distribution Enclosed Single-Pole
Air Switches, Fuse Disconnecting Switches, and Ac-
C37.13-1981 Low-Voltage AC Power Circuit Breakers cessories ( ANSI/IEEE)
Used in Enclosures (ANSI/IEEE)
C37.41-1981 Design Tests for High-Voltage Fuses,
C37.14-1979 Low-Voltage DC Power Circuit Breakers Distribution Enclosed Single-Pole Air Switches, Fuse
Used in Enclosures (ANSI/IEEE) Disconnecting Switches, and Accessories (ANSI/IEEE)

You might also like