You are on page 1of 39

ANSUIEEE Std 525-1987

(Revision of IEEE Std 525-1978)

IEEE Guide for the Design and


Installation of Cable Systems in
Substations

Published by The Institute of Electrical and Electronics Engineers, Inc 345 East 47th Street, New York, N Y 10017, USA
September IS. 1988 SHlPM
An American National Standard

IEEE Guide for the Design and


Installation of Cable Systems in Substations

1. scope Insulated Shielded Power Cables Rated 5 kV


through 35 kV.2
This document has been developed as a
guide for the design, installation, and pro- [21 AEIC CS6-87, Specifications for Ethylene
tection of wire and cable systems in sub- Propylene Rubber Insulated Shielded Power
stations with the objective of minimizing Cables Rated 5 kV through 69 kV.
failures and their consequences. This guide is
not intended for use in the design of wire and [31 ANSVIEEE C37.90.1-1974, IEEE Guide for
cable systems in generating stations which is Surge Withstand Capability (SWC) Tests
adequately covered in ANSI/IEEE Std 422-1986 (Supplement to ANSVIEEE C37.90-1978).3
[loll and ANSUIEEE Std 690-1984 [ E l .
[41 ANSVIEEE C57.13.3-1983, IEEE Guide for
1.1 Purpose. The purpose of this guide is t o give the Grounding of Instrument Transformer
direction t o the substation engineer in Secondary Circuits and Cases.
established practices for the application and
installation of metallic cables in electric [51 ANSUIEEE Std 80-1986, IEEE Guide for
power transmission a n d d i s t r i b u t i o n Safety in AC Substation Grounding.
substations. This guide emphasises reliable
electrical service during the design life of the [61 ANSI/IEEE Std 81-1983, IEEE Guide for
substation. Measuring of Earth Resistivity, Ground
Solutions presented in this guide may not Impedance, and Earth Surface Potentials of a
represent the only acceptable practices for Ground System.
resolutions of problems.
This guide should not be referred to or used [71 ANSI/IEEE Std 367-1987, IEEE Rec-
as an industry standard. It is being presented ommended Practice for Determining t h e
to aid in the development of wire and cable Electric Power Station Ground Potential Rise
system installations and should not be taken and Induced Voltage from a Power Fault.
as a code-type standard.

1.2 References. This standard shall be used in


conjunction with the following publications: 2AEIC publications can be obtained from the Sales
Department, Association of Edison I l l u m i n a t i n g
[13 AEIC CS5-87, Specifications for T h e r - Company, 51 East 42nd Street, Suite 1202, New York, N.Y.
nio pl a st i c and Cross 1inked P o 1y e t h y 1e n e 10017.
ANSI/IEEE publications can be obtained from the Sales
Department, American National Standards Institute, 1430
'Numbers in brackets correspond to those of the Broadway, New York, NY 10018, or from the Service
references in 1.2 of this standard; when preceded by B, they Center, The Institute of Electrical and Electronics
correspond to t h e bibliography in Section 14 of this Engineers, 445 Hoes Lane, P.O. Box 1331, Piscataway, N J
standard. 08855-1331.

7
ANSI/IEEE
Std 526-IS87 IEEE GUIDE FOR THE DESIGN AND

181 ANSI/IEEE Std 383-1974 (R 1980), IEEE [191 ASTM E119-1983, Standard Methods of
Standard for Type Test of Class 1E Electric Fire Tests of Building Construction and
Cables, Field Splices, and Connections for material^.^
Nuclear Power Generating Stations.
[203 ICEA P-32-382 (1969), Short Circuit
[91 ANSUIEEE Std 400-1980 (R 1987), IEEE Characteristics of Insulated Cable.6
Guide for Making High-Direct-Voltage Tests
on Power Cable Systems in the Field. [21] ICEA P-46-426, Power Cable Ampacities
for Copper and Aluminum Conductors.
[lo] ANSIAEEE Std 422-1986, IEEE Guide for [221 IEC 183-1984, Guide t o the Selection of
the Design and Installation of Cable Systems High-Voltage Cables7
in Power Generating Stations.
[23] IEC 228-1978, Conductors of Insulated
[ll]ANSIAEEE Std 487-1980, IEEE Guide for
Cables.
the Protection of Wire-Line Communication
Facilities Serving Electric Power Stations. [24] IEC 33 1-1970, Fire-Resisting Charac-
teristics of Electric Cables.
[121 ANSIAEEE Std 518-1982, IEEE Guide for
the Installation of Electrical Equipment t o [251 IEC 332-1970, Tests on Electric Cables
Minimize Noise Inputs to Controllers from Under Fire Conditions.
External Sources.
[261 NEMA TC2-1983, Electrical Plastic
[131 ANSI/IEEE Std 575-1988, IEEE Guide for Tubing (EPT), Conduit (EPC-40 and EPC-80)
the Application of Sheath Bonding Methods for and Fittings.8
Single Conductor Cables and the Calculation
of Induced Voltages and Currents in Cable [27] NEMA TC6-1983, PVC and ABS Plastic
Sheaths. Utilities Duct for Underground Installations.
[141 ANSIAEEE Std 643-1980, IEEE Guide for [28] NEMA VE1-1984, Metallic Cable Tray
Power Line Carrier Applications. Systems.
[151 ANSUIEEE Std 690-1984, IEEE Standard [291 NEMA WC 3-1980 (R 1986), Rubber-
for the Design and Installation of Cable
Insulated Wire and Cable for the Trans-
Systems for Class 1E Circuits in Nuclear mission and Distribution of Electrical Energy
Power Generating Stations. (ICEA S-19-817th ed).
[l61 ANSI/IEEE Std 979-1984, IEEE Guide for
[30] NEMA WC 5-1973 (R 1979, 1985),
Substation Fire Protection. Thermoplastic-Insulated Wire and Cable for
t h e Transmission a n d Distribution of
[171 ANSI/NFPA 70-1987, National Electrical Electrical Energy. (ICEA S-61-402 3rd ed).
Code (NEC14

[181 ANSUNFPA 72D-1986, Installation, ASTM publications are available from the American
Maintenance and Use of Proprietary Sig- Society for Testing Materials, 1916 Race Street,
naling Systems. Philadelphia, PA 19103.
ICEA publications are available from t h e Insulated
Cable Engineers Association, Inc, P.O. Box P, South
Yarmouth, MA 02664.
' IEC publications are available in the US from the Sales
Department, American National Standards Institute, 1430
Broadway, New York, NY 10018, USA. The IEC
NFPA publications are available from the National publications are also available from t h e International
Fire Protection Association, Publications Sales Division, Electrotechnical Commission, 3, rue de Varemb6, Case
Batterymarch Park, Quincy, MA 02269. Copies are also postale 131, 1211-Geneve 20, Switzerlandsuisse.
available from t h e Sales Department of' American * NEMA publications are available from t h e National
National Standards Institute, 1430 Broadway, New York, Electrical Manufacturers Association (NEMA), 2101 L.
NY 10018. Street, N.W., Washington, DC 20037.

8
ANSIlIEEE
INSTALLATION OF CABLE SYSTEMS IN SUBSTATIONS Std 626-1987

[311 NEMA WC 7-1982, Cross-Linked- wireways above ground. Cable should be


Thermosetting-Polyethylene-InsulatedWire suitable for operation in wet and dry locations.
and Cable for t h e Transmission and
Distribution of Electrical Energy (ICEA S-66- 2.3 Cable Performance
524). 2.3.1 Service Life. The service life of the
cable should be at least equal to the design life
[321 NEMA WC 8-1976 (R 19821, Ethylene- of the substation.
Propylene-Rubber-InsulatedWire and Cable 2.3.2 Thermal Stability. The cable should
for the Transmission and Distribution of maintain its required insulating properties
Electrical Energy (ICEA S-68-516). when subjected t o its rated thermal limit (the
combination of i t s maximum ambient
[33] NEMA WC 51-1986, Ampacities in Open- temperature and its own generated heat)
Top Cable Trays (ICEA P-54-440). during the service life.
2.3.3 Moisture Resistance. The cable should
maintain its required insulating properties
for its service life when installed in wet
locations, especially underground.
2. Cable Performance 2.3.4 Chemical Resistance. The cable
should maintain i t s required insulating
properties when exposed to chemical envi-
This section provides guidance for es- ronments.
tablishing cable performance and should be 25.5 Flame Propagation Resistance. Cables
considered in specifying cable for installation installed in open o r enclosed cable trays,
in substations. No single cable characteristic wireways, or in other raceway systems where
should be emphasized t o the serious detriment flame propagation is of concern should pass
of others. A balance of cable characteristics, as the ANSVIEEE Std 383-1974 (R 1980) [81 flame
well a s good installation, design, and tests.
construction practices, is necessary t o provide
a reliable cable system.

2.1 Definitions 3. Conductor Sizing andvoltage Rathgof


Power cables
design life of a substation. The time during
which satisfactory substation performance
can be expected for a specific set of operating This section provides guidance for the
conditions. determination of conductor sizing and voltage
ratings of power cables for various types of
service life of cable. The time during which installations.
satisfactory cable performance can be expected
for a specific set of service conditions. 3.1 Design Considerations. The proper design
of power cable systems requires t h e
2 2 Service Conditions consideration of many factors. These factors
(1) Cables should be suitable for all en- include ambient temperature, conductor
vironmental conditions that occur in the areas temperature, earth thermal resistivity, load
where they are installed. factor, current loading, system fault level,
(2) Cable operating temperatures in voltage drop, system nominal voltage and
substations are normally based on 40 "C grounding.
ambient air, or 20 "C ambient earth. Special 3.1.1 Ambient Temperature.This factor is
considerations should be given t o cable a n i m p o r t a n t design p a r a m e t e r i n
installed in areas where ambient tem- establishing the continuous current-carrying
peratures differ from these values. capability (ampacity) of a cable of a given size
(3) Cables may be directly buried, installed in a particular type of installation. Where
in duct banks, conduits, and trenches below cables are routed through several types of
grade, or in cable trays, conduits, and environmental conditions (buried, s u n

9
ANSVIEEE
Std 5251987 IEEE GUIDE FOR THE DESIGN AND

exposure, exposed conduit, covered cable trays, derating because of circulating currents in the
wireways, near heating equipment, etc), the shields of high-voltage cables with shields
conductor size, insulation and jacketing grounded a t more than one point, refer to 6.2.5.
materials should be selected for the most The ampacities for single-conductor triplexed
severe environmental condition. and three-conductor cables are based on short-
3.1.2 C o n d u c t o r T e m p e r a t u r e . The rated circuited shields. It should be noted that power
conductor temperature is dependent upon the cable spacing in trays requires a minimum of
type of cable insulation utilized. The one cable diameter between cables and
maximum conductor temperature limit is the sidewalls t o avoid derating.
highest conductor temperature attained by any Ampacities for nonspaced cables in open top
part of the cable under operating conditions, trays should be determined from NEMA WC
but not greater than the rated conductor 51-1986 (ICEA P-54-440) [331, rather than from
temperature. ICEA P-46-426 [21].
3.1.3 E a r t h T h e r m a l Resistivity. The
The application of fire-retardant coverings,
thermal resistivity of the soil in which cables penetration fire stops, etc, may affect cable
ampacities and should be considered.
are installed may vary greatly from location
to location. It is affected primarily by the type 3.1.6 System Fault Level. It is necessary to
and density of the soil and the amount of consider the effect of short circuit currents on
moisture present. For a typical loam or clay the heating of cables. The conductor size must
containing normal amounts of moisture, the be large enough to carry the short circuit
resistivity is usually in the range of 60-120 "C current for sufficient length of time t o permit
per watt per cm3. When the earth resistance is the circuit breakers t o open before the
not known, a value of 90 "C per watt per cm3 conductor is heated t o the point where i t
ICEA P-46-426 [211 i s suggested for damages the insulation. F a u l t current
determining the cable ampacity. capabilities of insulated conductors are given
3.1.4 Load Factor. The ampacity of a cable
in ICEA P-32-382 (1969) [201.
is also dependent upon the load factor for the 3.1.7 Voltage Drop. Voltage regulation
cable. The load factor of a circuit is the ratio of requirements should be considered in the
the average hourly load t o the maximum selection of conductor size. Motor feeder
hourly load for a given time period, usually voltage drop under starting and running
24 h. ICEA P-46-426 [211 utilizes possible load conditions should be limited to allow the motor
factors of 30, 50, 75, and 100% for single- t o operate within its design specifications.
conductor cables and 50, 75, and 100% load 3.1.8 S y s t e m N o m i n a l V o l t a g e and
factors for all other cables. The ampacity of a Grounding. These factors determine the cable
cable decreases as the load factor increases. voltage rating and insulation level. ICEA and
3.1.5 C u r r e n t Loading. Power cables should AEIC standards provide guidelines for the
be capable of carrying normal and emergency proper selection of cable rating and insulation
load currents. ICEA P-46-426 [2 11 provides level as well as the overvoltage capabilities
cable ampacity tables for various cable associated with cable voltage ratings.
constructions and methods of installation.
These tables are based on 40 "C ambient air
and 20 "C ambient earth and include data for
various conductor temperature ratings. 4. Electrical Segregation of Cable &stems
Appropriate factors for cable and conduit
grouping are also given as well as a n
adjustment formula for change in conductor This section provides guidance for the
temperature and ambient temperature electrical segregation of cable systems ac-
parameters. It is to be noted that the ampacities cording to voltage levels, signal levels, and
for cables in underground duct banks are vulnerability t o electrical noise pickup.
based on all ducts being peripherally located
with 30 in cover. The ampacities of single- 4.1 Cable Classifications. High-voltage power
conductor nontriplexed cables are based on cables a r e designed t o supply power t o
shields grounded at one point. For ampacity s u b s t a t i o n utilization devices, o t h e r

10
ANSUIEEE
INSTALLATION OF CABLE SYSTEMS IN SUBSTATIONS Std 525-1987

substations, or customer systenis rated higher calculated as if all the cables were power
than 1000 V. cables.
4.2.3 Instrumentation Cables. These cables
NOTE: Oil-filled and gas-insulated cables are excluded should be installed t o minimize noise pickup
from this definition and are not covered in this guide. from adjacent circuits a n d equipment.
Low-voltage power cables are designed to
Methods for achieving segregation are
supply power to utilization devices of the
(1) Installations t h a t provide physical
substation auxiliary systems rated 1000 V or separation between the instrumentation cables
less. and any electrical noise source CB161 [B381.
Control cables are applied at relatively low
(2) Installation in separate enclosed
current levels or used for intermittent magnetic raceways.
operation to change the operating status of a (3) Cable construction configurations, such
utilization device of the substation auxiliary as twisted conductors and shielding.
system. (4) Installation of analog signal cables
NOTE: As used in this document, leads from current and separate from all power and control cables,
voltage transformers are considered control cables since and from unshielded cables carrying digital
in most cases they are used in relay protection circuits.
o r pulse type signals. Shielded voice
Instrumentation cables a r e used for communications cable (without power supply
transmitting variable current or voltage conductors) may be included in raceways with
signals (analog) or transmitting coded in- analog signal cables.
formation (digital). (5) Telephone and other communication type
cables should be kept segregated from all other
NOTE: As used in this document, instrumentation cables substation cables.
consist of paired cables for supervisory systems o r event
recorders, and thermocouple and i.esistance temperature
detector cables.
NOTE: This document excludes fiber optic cables and
their installations which are covered in IEEE 83 WM025-4
[B58]and telephone type cables, whelher owncd or leased 5. Separation of Redundant Cable Systems
and used for voice communication or intersubstation
relaying, such as pilot wire.

4.2 Segregation. Cables installed in stacked This section provides guidance for the
cable trays should be arranged by descending separation of redundant cable systems.
voltage levels, with the higher voltages a t the
top.
4.2.1 High-Voltage P o w e r Cables. These 5.1 Redundant Cable Systems. Redundant
cables should be installed so that the high- cable systems are two or more systems serving
voltage cannot be impressed on any lower the same objective. They may be systems
voltage system. Methods for achieving this where personnel or public safety is involved,
segregation are such as fire pumps, o r systems provided with
(1) Installation of high-voltage cables in redundancy because of t h e severity of
raceways that are separated from low-voltage economic consequences of equipment damage
power and control cables and from or system reliability.
instrumentation cables. Installation of dif- NOTE: Primary and back-up relaying, breaker failure
ferent voltage classes of high-voltage power relaying, etc are examples of equipment which may utilize
redundant cable systems.
cables in separate raceways is also suggested.
(2) Utilization of armored shielded cables
(separate raceways are not required). 5.2 Design Considerations. Redundant cable
4.2.2 Low-Voltage P o w e r and C o n t r o l systems should be separated to ensure that no
C a b l e s . These cable classifications may be single event will prevent a required particular
mixed if their respective diameters do not substation operation. The degree of separation
differ greatly and they have compatible required varies with the potential hazards to
operating temperatures and voltage ratings. the cable systems in particular areas of the
When this is done, the power cable ampacity is substation.

11
ANSYIEEE
Std 62bl987 IEEE GUIDE FOR THE DESIGN AND

NOTE: Administrative controls should be taken for the cable spreading area should be limited to
transient fire loads such as temporary storage of
flammable materials, etc. control and instrument functions and those
power supply circuits and facilities serving
These areas may be classified as follows: the control room and instrument systems.
(1) Mechanical damage area Power supply feeders t o instrument and
(2) Fire hazard area control room distribution panels should be in-
(3) Cable spreading area (or areas above or stalled in enclosed metallic raceways.
below control and relay panels or racks, etc) Other power circuits that are required t o
traverse this area should be assigned routes
6.2.1 Potential Hazard Areas. Potentially consistent with their separation requirements
hazardous a r e a s r e q u i r i n g special and allocated solely for these power circuits.
consideration are Such power circuits should be separated from
(1) Mechanical Damage Area. Physical
other circuits in this area in accordance with
arrangement or protective barriers, or both,
4.2.
should be provided so that no event can cause
the destruction of the redundant cable systems. NOTE: An acceptable alternative routing for such
traversing power circuits would be to route them in
Such events include vehicle movement and embedded conduit or in a separate enclosure which, in
failure of equipment, such as effect, removes them from the cable spreading area.
(a) Large rotating equipment (synchro-
nous condensers, diesel generators, etc)
(b) Transformers and switchgear
(c) Surge arresters, cable potheads, etc 6. Shielding and Shield Grounding
(2) Fire Hazard Areas. Redundant cable
systems should be arranged so that a fire
cannot This section provides information on the
(a) Damage more than one system. origin of transients in substations and
Routing of redundant cable systems through guidance for shielding and shield grounding
a n a r e a where there is potential for of high-voltage power, instrumentation,
accumulation of large q u a n t i t i e s of control, coaxial, and triaxial cable systems.
combustible material should be avoided.
(b) Propagate from one system to another. 6.1 Origin of Transients in Substations.
Cables of redundant systems should have ( 1 ) High-Voltage Switching. Opening or
sufficient horizontal and vertical separation closing a disconnecting switch to deenergize
to prevent ignition of the cables in one system or energize a section of substation bus is
by a fire in the other. If this separation is not accompanied by arcing and will initiate a
attainable, a fire-resistant barrier should be high-frequency transient. The frequency will
installed. be determined by the self-inductance and
( 3 ) Cable Spreading Area. The cable s h u n t capacitance of t h e high-voltage
spreading area is normally adjacent t o or part conductors involved. The resulting over-
of the control room where cables leaving the voltages can exceed two per unit. Both electric
panels are dispersed into various cable trays and magnetic coupling between high-voltage
for routing to all parts of the substation. and low-voltage conductors can result in high-
(a) Where cables of redundant systems, level transients in the low-voltage system.
approach each other with space less than (2) Capacitor Switching. Switching a ca-
adequate to prevent ignition of one redundant pacitor bank causes a current transient which
cable system by a fire in the other, the cables of is a function of the bank size and the circuit
one system should be installed in metallic constants back t o the source. If other capacitors
conduit until sufficient separation exists, or are already connected nearby to the same line
barriers should be installed as necessary. or bus, they lower the impedance seen by the
(b) The cable spreading area should not switched capacitor, increasing the magnitude
contain equipment such as switchgear, and frequency of the transient. Energy stored
transformers, rotating equipment, or potential in the nearby bank may contribute further to
sources of projectiles, and should not be used the severity. The circuit between banks is
for storing flammable materials. Circuits in likely to ring a t high frequency because of the

io
ANSVEEE
INSTALLATION OF CABLE SYSTEMS IN SUBSTATIONS Std 526-1987

low inductance in the short line connecting the proportional t o the height of the conductor above
banks and the reduced effective capacitance the ground grid. Conduction of power system
considering the banks in series [B391. This transients t o the ground grid is typically
phenomenon further enhances the tendency of provided through metallic groundings of
the transient t o interfere with nearby circuits. transformer neutrals and capacitive paths,
(3) Transmission Line Switching. This such as bushings, coupling capacitors, and
phenomenon is similar to capacitor bank CCVTs. These are low-impedance high-
switching, with the difference being the energy sources that can induce common-mode
distributed nature of the inductance and voltages on control circuits ANSIAEEE Std
capacitance of the line. The magnitude of the 367-1987 [71.
line charging current tends to be substantially (7) Other Switching Type Operations. Other
less than that for capacitor bank switching. switching type operations t h a t generate
The frequency of the transient current or transients occur in power systems. Some
voltage is inversely proportional to the line examples are undesirable time spans between
length [B381. the closing of the poles of a circuit breaker,
( 4 ) Coupling Capacitor Voltage Trans- fault occurrence, fault clearing, load tap-
formers (CCVT). The capacitors in these changing, line reactor deenergizing, series
devices, in conjunction with inductances of capacitor gap flashing, and capacitor
the power system conductors, constitute a reinsertion. Normally, the magnitudes of
resonant circuit whose frequency can be in the such transients are less than those of other
megahertz range. Unless the base of the CCVT phenomena described herein.
has a low-surge impedance to the substation
ground grid, a high-voltage can appear 6.2 High-Voltage P o w e r Cable. The use of
between the CCVT secondary terminals and shielding and shield grounding of high-
the grid. The high voltage will be generated voltage power cables is a common practice to
primarily during air-break (disconnecting) reduce the hazard of shock t o personnel, t o
switch operations. confine the dielectric field within the cable, to
(5) Ground Potential Rise (GPR). GPR is the minimize deterioration of cable insulation or
voltage rise proportional to the magnitude of jackets caused by surface discharges and to
the ground current and to the ground minimize radio interference. The selection of
resistance. Under normal conditions, the the shield grounding locations and the effects
grounded electrical equipment operates a t zero of single and multiple grounds are points t o be
ground potential. That is, the ground potential considered for the proper installation of
of a grounded neutral conductor is nearly shielded cable.
identical t o the potential of remote earth. 6.2.1 Definition. The following definition is
During a fault, the portion of fault current used in this standard.
which is conducted by a ground electrode into
the earth causes a rise of the electrode potential cable shielding. An electrical conducting
with respect to remote earth ANWIEEE Std 80- material applied over the insulation of the
1986 [51, [B201. conductor or conductors to confine the electric
(6) Ground Potential Rise Differences. Both field of the cable t o the insulation of the
electromagnetic coupling and conduction can conductor or conductors.
contribute t o substantial ground potential rise 6.2.2 Shielding Practices. Cables rated
differences, particularly a t the higher above 5 kV should be shielded, except for
frequencies typical of many transients special applications or cable designs. Cable
occurring on a high-voltage power system, applications in the operating range of 2 kV to 5
Even well designed grounding grids t h a t kV require careful judgement, and each
extend over the large areas needed for high- installation should be evaluated based on the
voltage switchyards have sufficient induc- existing a n d a n t i c i p a t e d conditions.
tance to cause high-potential differences. Shielding can be used to monitor or test cable
Electromagnetic coupling t o the ground grid is installation for additional assurance of
directly proportional t o the rate of change of insulation integrity. The shielding recom-
flux and the length and orientation of the mendations contained in the ICEA-NEMA
current-carrying conductor and inversely Standards Publications for t h e type of
ANSYIEEE
Std 6251987 IEEE GUIDE FOR THE DESIGN AND

insulation being utilized should be followed (4) Single-conductor lead sheathed cables
NEMA WC 3-1980 (R 1986) (ICEA S-19-81 7th 250 kcmil copper or smaller installed together
ed) [291, NEMA WC 5-1973 (R 1979, 1985) (ICEA in a common duct.
S-61-402 3rd ed) [301, NEMA WC 7-1982 (ICEA Because of the frequent use of window type or
S-66-524) [31], NEMA WC 8-1976 (R 1982) zero-sequence current transformers for
(ICEA S-68-516) [321. ground overcurrent protection, care must be
Cable shielding should be considered in the taken in the termination of cable shield wires
2 kV to 5 kV range where any of the following at the source. If the shield wire i s passed
conditions exist: through the window-type current transformer,
(1) Transition from conducting t o non- it should be brought back through this current
conducting environment transformer before connecting t o ground in
(2) Transition from moist t o dry envi- order to give correct relay operation.
ronment 6.2.5 Shield Losses that Affect Ampacity.
(3) Dry soil, such as in a desert Shields or sheaths that are grounded at more
(4) Damp conduits than one point carry induced circulating
(5) Connections t o overhead lines currents. Compensation for the heating effect
(6) Locations where cable surface collects of the induced circulating current should be
conducting materials, such as soot or salt considered when calculating t h e cable
deposits ampacity. The magnitude of circulating
(7) Electrostatic discharges are sufficient in currents flowing in shields grounded at more
magnitude to interfere with control and than one point depends on t h e mutual
instrumentation circuit functions inductance between the cable shielding and
(8) Safety to personnel is involved the cable conductors, the mutual inductance to
(9) Long underground cables the conductors in other cables, the current in
(10) Single-conductor cables in trays these conductors, and the impedance of the
(11)Direct earth burial shield. Circulating currents heat the shield
6.2.3 Shield Termination Practices. The and reduce the effective ampacity of the cable.
insulation shield system must be removed Table 6-1 gives formulae for calculating the
carefully and completely, and proper stress shield loss for single-conductor cables.
control materials or devices used. Manu- Table 6-1 has been derived from Chapter 10,
facturer's instructions and recommenda- Table 26, of [Bll.
tions a s t o termination of shielded cables To facilitate calculating the mutual re-
should be followed in detail. If all elements of actance and shield resistance, the following
the shield are not removed, excessive leakage formulae which neglect proximity loss, may
current with tracking or flashover may result. be used for practical purposes:
6.2.4 G r o u n d i n g Practices. Cable shields S
and metallic sheath/armor should be solidly XM = 2 r f (0.1404 log,, r
m
pR/ft
grounded a t one or more points so that they a = 2 r f (0.1404 log,$) pR/ft
operate a t or near ground potential at all times b = 2 r f (0.1404 log,ff) pR/ft
ANSUIEEE Std 575-1988 [13J. The length of
cable run should be limited by the acceptable - -
- /LR/ft
8r, t
voltage rise of the shield if the shield is
grounded a t only one point. The derating of where
ampacity due to multiple-point short circuited XM = mutual inductance of shield and con-
shields has a negligible effect in the following ductor (pR/ft)
cases for three-phase circuits: a, b = mutual inductance correction factors
(1) Three-conductor cables encased by a (PR/ft)
common shield or metallic sheath. pR = micro-ohm - R X
(2) Single-conductor shielded cables R, = resistance of shield (pR/ft)
500 kcmil copper or smaller installed together t = thickness of metal tapes used for shield-
in a common duct. ing (inches)
(3) Triplexed or three-conductor individu- f = frequency (Hertz)
ally shielded cables 500 kcmil copper or S = spacing between center of cables (inches)
smaller. r, = mean radius of shield (inches)

14
ANSMEEE
INSTALLATION OF CABLE SYSTEMS IN SUBSTATIONS Std 626-1987

U
@7-@
cn nlhl ala
.r.

E
5b
I

cd
I

cd 105
+ +
E x" x"

PIN nlco
+ I

cd cdlm
+ +
p"0 x
E
x
E

cd elm
+ I

E E

"1
m
t: x x
5c
I-
.I
cd
N

cdlw
CdIN cdlco
- - + I
E
pz" d
x" x
N
U N
U

II II

E E
* N

E E
e:, d d
N
U
N
U N
U
m

E E
E E

co a v)

I I I
ANSI/IEEE
Std 5251987 IEEE GUIDE FOR THE DESIGN AND

p = apparent resistivity of shield in n-cmil/ grounding of signal cables used with in-
ft at operating temperature (assumed strumentation systems.
50 "C). This includes allowance for the The general rules set forth should be
spiraling of the tapes or wires. tempered by specific manufacturer's rec-
Typical values of p: ommenda tions.
Overlapped helical copper tape 30 n-cmil/ft 6.3.1 Definitions
Lead sheath 150 fkmil/ft common-mode noise (longitudinal). The
Aluminum sheath 20 R-cmil/ft noise voltage which appears equally and in
Bare copper wires 10.6 n-cmil/ft phase from each signal conductor t o ground.
For 60 Hz: Common-mode noise may be caused by one or
S more of the following:
X, = 52.92 r
m
pWft (1) EZectrostatic induction. With equal
a = 15.93 pn/ft capacitance between the signal wires and the
b = 36.99 pWft surroundings, the noise voltage developed will
be the same on both signal wires.
It is assumed that the cables are carrying
(2) Electromagnetic induction. With the
balanced currents.
magnetic field linking the signal wires
For cables installed three per conduit, use
equally, the noise voltage developed will be the
Arrangement I1 in Table 6-1. The spacing, S,
same on both signal wires.
in this case will be equal to the outside
diameter of the cable increased by 20% to allow common mode to n o d - m o d e conversion. In
for random spacing in the conduit. addition t o the common-mode voltages which
All three phases of a circuit should be are developed in the single conductors by the
installed in the same conduit. When i t is general environmental sources of
necessary t o run only one phase per conduit, electrostatic and electromagnetic fields,
then nonmetallic or nonmagnetic metallic differences in voltage exist between different
conduit should be used. If nonmagnetic ground points in a facility due to the flow of
metallic conduits are used, the reduction of ground currents. These voltage differences
cable ampacity due t o conduit heating should a r e considered common mode when
be considered. Also, no magnetic metal, such connection is made t o t h e m e i t h e r
as clamps or rebar, should form a closed ring intentionally or accidentally, a n d t h e
around the conduit. currents they produce are common mode.
6.2.6 Induced Shield Voltages. Shields of These common-mode currents can develop
single-conductor cable carrying alternating normal-mode noise voltage across unequal
current will have a voltage buildup if circuit impedances.
grounded a t only one point. Table 6-1 can be
used to calculate the induced shield voltage. A crosstalk. The noise or extraneous signal
maximum voltage of 25 V, under normal caused by ac or pulse-type signals in adjacent
operating conditions, is a commonly accepted circuits.
limit.
Table 6-2 gives the maximum lengths of normal-mode noise (transverse or dif-
single conductor cable with shields grounded ferential). The noise voltage which appears
a t one point to stay within the 25 V maximum differentially between two signal wires and
for the conditions stated. Other conditions will which acts on the signal sensing circuit in the
permit different lengths. For example, cables same manner as the desired signal. Normal-
operated at less than rated ampacity will allow mode noise may be caused by one or more of
longer lengths. Direct-buried cables operating the following:
a t their rated ampacity, with all other condi- (1) Electrostatic induction and differences
tions being the same, will require shorter in distributed capacitance between the signal
lengths t o stay below the 25 V maximum. wires and the surroundings.
(2) Electromagnetic induction and mag-
6.3 Instrumentation Cable. This section netic fields linking unequally with the signal
provides guidance for shielding a n d wires.

16
ANSVIEEE
INSTALLATION OF CABLE SYSTEMS IN SUBSTATIONS Std 525-1987

Table 6-2
Maximum Lengths for Single-ConductorCables Operating at
Rated Ampacity with Single-Point Shield Grounding
One Cable Per Duct (1) Three Cables Per Duct (2)
Conductor Copper Aluminum Copper Aluminum
Size (A) (ft) (A) (ft) (A) (ft) (A) (ft)
1/o 249 1465 194 1875 214 4965 167 3655
4/0 371 1055 290 1350 278 3530 248 4480
350 496 820 387 1050 418 2610 329 3310
500 608 695 472 890 504 2200 400 2770
750 762 595 601 750 626 1800 497 2260
1000 890 565 707 710
2000 1237 420 1022 508

NOTES: (1)15 kV cables in ducts on 7.5 in centers operating at 75% load factor.
(2) Three single-conductor 15 kV cables in one duct operating at 75% load factor. The length listed is the duct length.

(3) Junction or thermal poteritials due to the the circuits from ground effectively opens the
use of dissimilar metals in the connection ground common-mode voltage path through
system. the signal circuit. If an intervening amplifier
(4) Common mode to normal-mode noise is a single-ended amplifier, the low side of the
conversion. signal circuit is not broken and is grounded a t
the terminal. Therefore, the situation is not
changed, so the same procedure should be
shield (cable systems) ( i n s t r u m e n t a t i o n followed with the terminal as indicated above.
cables). A metallic sheath (usually copper o r A guarded isolated differential amplifier
aluminum), applied over the insulation of a provides isolation of both input terminals from
conductor or conductors for the purpose of the chassis (or ground) and from the output.
providing means for reducing electrostatic This amplifier is capable of high-common-
coupling between the conductors so shielded mode rejection and provides the input-output
and others which may be susceptible to or isolation so that the output ground will not
which may be generating unwanted (noise) affect the input circuit.
electrostatic fields. Typically, the common-mode rejection ratio
NOTE: When electromagnetic shielding is intended, the of an isolated differential amplifier used in
term electromagnetic is usually included to indicate the instrumentation systems is about 106:1 (120
difference in shielding requirement as well as material.
To be effective a t power system frequencies, dB) and is the ratio of common-mode voltage
electromagnetic shields would have to be made of high- applied t o the amount of normal-mode voltage
permeability steel. Such shielding material is expensive developed in the process.
and is not normally applied. Other less expensive means
for reducing low-frequency electromagnetic induction, as When an ungrounded transducer is used, it
described herein, are preferred. may be possible t o obtain satisfactory results
by leaving the transducer circuit ungrounded,
6.38 Methods for Noise &duction connecting the cable shield t o the amplifier
6.3.2.1 G r o u n d S i g n a l Circuit at O n e guard shield, and grounding the shield at
P o i n t . The signal circuit may originate a t a either the transducer end or the amplifier end.
source such as a transducer and terminate a t a However, it is considered that connecting the
load such as a recorder, supervisory remote cable shield to the amplifier guard shield and
terminal unit, etc, either directly or through grounding both transducer cable shield and
an intervening amplifier. circuit at the transducer will result in a less
If the recorder, supervisory remote ter- noisy, more stable system. See 6.3.2.6 for
minal, etc, is fed directly from a grounded additional information on shield grounding.
voltage generating transducer such a s a 6.3.22 Electrostatically Coupled Noise.
thermocouple, the terminal circuits must be Shielding of signal cables will reduce
capable of high-common-mode rejection, o r electrostatically coupled noise voltage. See
they should be isolated from ground. Isolating 6.3.2.6 for additional information on shield

17
ANSUEEE
Std 5251987 IEEE GUIDE FOR THE DESIGN AND

grounding. A properly grounded shield will in ground potential will drive current through
greatly reduce the capacitance between the the shield. In either case, shield current can
signal conductors and external sources of induce common-mode noise current into the
electrostatic noise so that very little noise signal leads, and by conversion t o normal-
voltage can be coupled in the signal circuit. mode noise, voltage proportional t o signal
6.3.2.3 E l e c t r o m a g n e t i c a l l y I n d u c e d circuit resistance unbalance can reduce
Noise. The use of twisted pair cables is an accuracy of signal sensing. In a system with
effective method of electromagnetic noise grounded transducer and isolated-input
reduction. By alternately presenting each differential amplifier, the cable shield should
conductor to the same electromagnetic field, connect t o the amplifier guard shield, but
voltages of equal magnitude and opposite grounding the shield at the amplifier will
polarity are induced in each conductor with reduce t h e amplifier's common-mode
respect to ground. The common-mode voltage rejection capability. Grounding the shield
so developed is converted t o a small amount of only at the transducer will maintain the
normal-mode noise a s determined by the shield at the same ground potential as the
common-mode rejection ratio of the signal transducer, which will minimize shield-
amplifier (isolated d i f f e r e n t i a l or induced common-mode c u r r e n t while
equivalent). The frequency of twisting (lay) permitting the amplifier t o operate a t
affects noise reduction ability and, therefore, maximum common-mode rejection
should be considered in specifying twisted capability. Also see 6.3.2.1 for shield and
pair cable. signal circuit grounding of ungrounded
The materials normally used for shielding transducers.
of instrumentation cable are nonferrous and 6.3.2.7 O t h e r Methods. Other methods for
cannot shield against power frequency reducing noise voltages are
electromagnetic fields. The steels normally (1) Drainage unit (drainage reactor/mutual
used in conduit or tray are not of high enough drainage reactor) is a center-tapped inductive
permeability t o provide very effective device designed t o relieve conductor-to-
shielding a t power frequencies. However, conductor and conductor-to-ground voltage
some benefit may accrue from the use of rigid stress by draining extraneous currents t o
steel conduit or steel trays with solid bottoms ground.
and tightly fitting solid steel covers. (2) Isolating (insulating) transformers
6.3.2.4 C r o s s t a l k . Using cables with provide longitudinal (common mode) isola-
twisted pair conductors and individually tion for the facility. They can also be used in a
insulated shields over each pair is a method to combined isolating-drainage transformer
minimize crosstalk. configuration.
6.3.2.5 S e p a r a t i o n ( Se gre ga t i o n ) . (3) Neutralizing transformers introduce a
Physical separation of instrumentation cables
voltage into a circuit pair t o oppose a n
can be utilized to reduce noise pickup.
unwanted voltage. They neutralize extra-
However, physical separation in itself, unless
neous longitudinal voltages resulting from
carefully analyzed, may not achieve the
desired degree of immunity. Cables should be ground potential rise o r longitudinal in-
duction, or both, while simultaneously al-
run in accordance with Section 4.
lowing ac or dc metallic signals to pass.
6.3.2.6 Shield G r o u n d i n g . The shield
should be connected to ground a t only one (4) Optical couplers (isolators) provide
point, preferably, where the signal equipment isolation using a short length, optical path.
is grounded. An exception to this is where the For additional information on these
shield is used for the excitation of a methods, refer to Ah?SI/IEEEStd 487-1980 [lll.
neutralizing transformer. If the shield is 6.3.3 ShieldingPractices
grounded a t some point other than where the (1)The cable for computer or high-speed data
signal equipment is grounded, charging logging applications, using low-level analog
currents may flow in the shield because of signals, should be made up of twisted and
differences in potential between signal and shielded pairs. For noncomputer type
shield ground locations. If the shield is applications, such as annunciators, shielding
grounded a t more than one point, differences may not be required.

la
ANSVIEEE
INSTALLATION O F CABLE SYSTEMS IN SUBSTATIONS Std 525-1987

(2) Twisting and shielding requirements insulated shields so that each shield may be
for both digital input and digital output signals maintained at the particular thermocouple
vary between different manufacturers of ground potential.
computerized instrumentation systems. (6) Each resistance temperature detector
Separation of digital input cables and digital (RTD) system consisting of one power supply
output cables from each other and from power and one or more ungrounded RTDs should be
cables may be required. Where digital inputs grounded only a t the power supply.
originate in close proximity to each other, (7) Each grounded RTD should be on a
twisted pair multiple conductor cables with separate ungrounded power supply except as
overall shield should be used o r multiple follows:
conductor cable with common return may be Groups of RTDs embedded in the windings
permitted, and overall shielding may not be of transformers and rotating machines should
required. Digital output cables of similar be grounded at the frame of the respective
constructions may also be permitted. equipment for safety. A separate ungrounded
Individual twisted and shielded pairs should power supply should be furnished for the group
be considered for pulse-type circuits. of RTDs installed in each piece of equipment.
( 3 ) Cable shields should be electrically (8) When a signal circuit is grounded, the
continuous except where specific reasons low or negative potential lead and the shield
dictate otherwise. When two lengths of should be grounded a t the same point.
shielded cable are connected together a t a
terminal block, an insulated point on the 6.4 C o n t r o l Cable. This section provides
terminal block should be used for connecting information on surge voltages which
the shields. originate in control circuits and guidance for
(4)Shields should be isolated and insulated shielding and grounding control cable.
except a t their selected grounding point to 6.4.1 Sources Within the Control Circuit.
prevent stray and multiple grounds t o the During interruption of direct current in a n
shield. inductor, such as a relay coil, a large induced
( 5 ) At the point of termination, the shield voltage may appear across the inductor due to
should not be stripped back any further than the L di/dt effect [B521. Normally, the
necessary from the terminal block. maximum voltage will exist at the instant of
(6) The shield should not be used as a n interruption. Magnitude is very dependent on
electrical conductor except for neutralizing supply circuit impedance. If impedance i s
transformer excitation. high, voltage will be proportionally high. The
(7) For signal circuits, the shield must not be surge voltage will equal the extinction voltage
part of the signal circuit. Furthermore, the use across the contact plus the drop through the rest
of shielded, twisted pairs into balanced of the circuit. The higher the speed of
terminations greatly improves transient interruption, the higher the surge voltage
suppression. It is never acceptable t o use a generated. Voltages in excess of 10 kV have
common line return both for a low-voltage been observed across a 125 V coil in laboratory
signal and a power circuit [B141. tests, but 2.5 kV is a more typical value t o be
6.3.4 Grounding Practices expected.
(1) All shields should be grounded in ac- Direct-current circuit energization has an
cordance with 6.3.2.6. effect on adjacent circuits where capacitive
(2) Signal circuits, if grounded, should be coupling exists. Full battery voltage appears
grounded a t orily one point. initially across the impedance of the adjacent
( 3 ) Digital signal circuits should be circuit and then decays exponentially in
grounded only a t the power supply. accordance with the RC time constant of the
(4) The shields of all grounded junction circuit [B381.
thermocouple circuits and the shields of The extensive use of surge capacitors on
thermocouple circuits intentionally grounded solid-state equipment and the longer cable
at the thermocouple should be grounded a t o r runs associated with EHV stations have
near the thermocouple well. substantially increased the capacitance be-
( 5 ) Multipair cables used with thermocouples tween control wiring and ground. Inadvertent
should have twisted pairs with individually momentary grounds on control wiring cause a
ANSUIEEE
Std 62bl987 IEEE GUIDE FOR THE DESIGN AND

discharge or a redistribution of charge on this and mutual inductance are greatly influenced
capacitance. Although this seldom causes by circuit spacing, small increases in
failure, misoperation of equipment may distance may produce substantial decreases in
occur. interaction between circuits [Blll.
Saturation of current transformers by high- Where possible, control cables should be
magnitude fault currents, including the dc routed perpendicular to high-voltage buses
offset, can result in the induction of very high [B181, [B381. When control cables must be run
voltages in the secondary windings. This parallel- t o high-voltage buses, maximum
phenomenon is repeated for each transition practical separation should be maintained
from saturation in one direction to saturation between the cables and the buses [Blll.
in the other. The voltage appearing in the
secondary consists of high-magnitude spikes NOTE: Tests indicate that in some cases, nonshielded
control cables may be used without paralleling ground
with alternating polarity persisting for a n cables when they are parallel and are located at a dktance
interval of a few milliseconds every half cycle greater than 50 ft from or are perpendicularto a typical 346
[B381. kV bus [B14].

6.4.2 P r o t e c t i v e Measures. The design of Great care should be exercised in routing


control, protection, and metering circuits in cables through areas of potentially high
modern substations must include provisions ground grid current (either 60 Hz o r high-
for reducing unwanted interference t o frequency currents) [B181.
tolerable levels. The most significant All cables from the same equipment should
interference comes from voltages or currents, be close together, particularly t o the first
or both, induced in the circuits as a result of manhole or equivalent in the switchyard
exposure to nearby conductors in which [B 181.
transient currents or voltages appear as a Cables connected t o equipment having
result of switching or faults. Although comparable sensitivities should be grouped
voltages used in the transmission of power together and then the maximum separation
have been increasing over the years, the level should be maintained between groups. High-
of control voltages and signal power has had a voltage cables should not be in duct runs or
tendency to remain constant or even decrease. trenches with control cables [Blll, [B181, [B381.
Since induced interference increases with the Radial arrangement of control circuitry
use of higher voltages and increased fault will reduce transient voltages. Circuits routed
current levels, the ratio of unwanted signal into the switchyard from the control house
(noise) t o useful signal will be increased if must not be looped from one piece of apparatus
precautions are not taken to protect the signal to another in the switchyard with the return
circuits. conductor in another cable. All supply and
Transient voltages on cables cannot be return conductors must be in a common cable
completely eliminated, but can be limited in to avoid the large electromagnetic induction
magnitude. In the interest of compatibility possible because of the very large flux-
with solid-state relaying systems, one linking-loop t h a t t h e loop arrangement
suggested limit is the peak of the surge provides [Blll, [B381.
withstand capability (SWC) test ANSMEEE
C37.90.1-1974 [31. Many different things can be 6.4.3 Grounding. The design of ground grid
done separately or in combination t o reduce systems, the methods of grounding equipment,
the magnitude of the transients, depending and shielding of control circuits have a large
upon economics and equipment influence on transient voltages which will be
configuration, The following methods are impressed on control equipment.
primarily confined t o control cable The ground grid, even when designed with a
installation. very low resistance, cannot be considered as
6.4.2.1 Physical Location and Grouping. an equipotential surface. Substantial grid
Physical separation between transient source potential rise differences may occur which
and control cables is an effective means of will be directly influenced by a number of
transient control. Because mutual capacitance factors, for example, grid resistance, grid
ANSI/IEEE
INSTALLATION OF CABLE SYSTEMS IN SUBSTATIONS Std 525-1987

geometry distribution of ground currents closest possible proximity t o the control cables,
ANSI/IEEE Std 80-1986 [51, earth resistivity particularly where unshielded cables are
[B521, ANSI/IEEE Std 81-1983 [61, and used.
frequency of the transient [B151. (7) Instrument transformer secondaries
Since it is impractical t o eliminate grid should be connected to ground at only one point
potential rise differences, their effects must be ANSUIEEE C57.13.3-1983 [41. Making the
neutralized. Neutralization can be ground connection at the relay or control
accomplished by a low resistance shield building has the following advantages:
conductor parallel t o and in close proximity to (a) Potential rise is minimized near the
the affected control circuits. Such a conductor relay equipment
may be the shield of a shielded control cable, (b) The shock hazard to personnel in the
unused conductors of an unshielded control building is reduced
cable, or a separate shield conductor. These (c) All grounds are at one location, facili-
conductors will carry currents proportional t o tating checking
the grid potential rise differences and induce (8) High-voltage shunt capacitor banks of a
a counter voltage in the control circuits, thus given voltage should have the neutrals from
effecting neutralization. individual banks connected together and then
Grounding, neutralizing, and shielding connected to the station ground grid at only
methods which have been found to be effective one point. To facilitate one point grounding,
are as follows: all capacitor banks of a given voltage should
(1) In trench systems, shield conductors be at one location.
which are grounded t o the substation grid as If shield resistance is neglected, the fraction
necessary, should be attached to the top sides of of the induced voltage on a control cable which
the trench. This places the shield conductors is cancelled by the shield current is equal to
between the transient source and the control the ratio of the mutual impedance between
cables [B521. These shield conductors should shield and conductor to the self-impedance of
have sufficient conductivity t o carry fault the shield. For a concentric shield, this ratio
currents without damage and have adequate should be one. For an adjacent shield wire, the
mechanical strength. ratio must always be less than one.
(2) In substation manholes, ground buses If the resistance of the shield is considered,
should be established around the perimeter of then the cancelling voltage generated by the
the manhole with a t least t w o ties t o the shield current is reduced by the ratio of the
substation grid. This ground bus provides a self-inductive reactance of the shield t o the
convenient means of grounding individual total complex self-impedance of the shield.
cable shields. The resistance becomes significant at low
(3) Where duct runs are used, a minimum of frequencies where the inductive reactance of
two grounded shield conductors should be the shield is low and can generally be ne-
included a t the top edges of the duct run. glected at high frequencies. ANSI/IEEE Std
(4) For direct-burial control cables, several 518-1982 [121
grounded shield conductors should be buried 6.4.4 Metallic Shielding of Control Cables
with each cable r u n . For equivalent Can Reduce Induced Transient Voltages.
conductivity, several smaller shield con- Protection may take the form of surrounding
ductors are more effective than a single large the sensitive circuits with a n equipotential
conductor. surface to prevent capacitive coupling to high-
(5) Unused conductors, grounded a t both voltage conductors, and magnetic shielding to
ends, in an unshielded control cable may be mitigate the effect of strong magnetic fields.
used as shield conductors [B521 on a n When shielded control cable is used,
equivalent conductivity basis. Provisions grounding the shield at both ends is rec-
should be made for replacement with shield ommended [B141. Care should be exerted in
conductors should the unused conductors later keeping the shield intact, as a broken or
be used for active circuits. separated shield can greatly reduce the shield
( 6 ) Shield conductors are effective for either efficiency.
shielded or unshielded control cables. To be If only one end of the shield is grounded,
most effective, shield conductors must be in the large transient shield-to-ground and con-

21
ANSyIEEE
Std 525-1987 lEEE GUIDE FOR THE DESIGN AND

ductor-to-ground voltages may be present a t the other will introduce excessive stray
the ungrounded end [Blll, [B341. capacitance.
Grounding a shield a t both ends allows Since a single conductor is at a high
shield current to flow. The shield current impedance point when connected between a
resulting from magnetic induction creates a coupling capacitor and a line tuner, stray
counter-flux which will tend t o cancel the flux capacitance to ground and leakage currents
that created the shield current. The net effect of can affect the coupling circuit performance.
the shield on the lead is to reduce the noise The stray capacitance can cause a reduction
level. An exception to this is that the current in bandwidth, and the leakage currents can
flowing in shields not produced by flux cause a loss in carrier power.
linking the lead will cause the surge or noise To reduce stray capacitance and leakage
voltage on the lead to be higher than it would be currents, either of the following methods may
if there were no shield [B38J, [B141, LB521. be used:
The lower the shield impedance, the greater (1)An insulated single conductor should be
is the amount of transient voltage cancellation run as directly as possible between its required
because of greater current flow. Generally a terminations. I t should be mounted on
lower surge impedance permits larger insulators and fed through bushings at each
induced transient currents to flow in the end. The conductor insulation should be
shield [B341. unbroken between its ends to maintain low
A grounding conductor may be run parallel leakage.
to the shielded cable to help protect the shield (2) An insulated single conductor can be
from being damaged when fault currents are installed in a nonmagnetic flexible metal
present [B521. conduit which is sheathed in a vinyl jacket.
If electrostatic shields are required, they The insulated single conductor should be
should be within the outer shield [B341. isolated from the flexible metal conduit with
Auxiliary power and yard lighting circuits Teflon washers spaced about 6 in (150 mm)
should not be installed without adequate apart. If the conductor h a s a significant
shielding near shunt capacitor banks [Bill. portion of its length outside the flexible metal
Experience has shown that in high-voltage conduit, it should be mounted on insulators
substations, steps should be taken to reduce the and fed through bushings at its ends as in (1).
transients in auxiliary power cables, lighting A typical insulated carrier lead, 0.48 in
cables, etc, in addition to control circuits [B31. (12.2 mm) in diameter, consists of a single
AWG No. 8, 19-strand conductor having
rubber insulation and a neoprene outer jacket.
6.5 Coaxial a n d Triaxial Cable a n d T u n i n g 6.5.2 Coaxial Cables. This type of cable is
L e a d s . Coaxial cable and leads are an sometimes used for a low-impedance
integral part of the coupling and tuning interconnection between a line tuner and a
portions of a power-line carrier channel. transmitterheceiver or between line tuners in
Three specific types of conductors are a long bypass. It is sometimes used between an
normally used: insulated single conductor, impedance-matching transformer in a
coaxial cable, and triaxial cable. For coupling capacitor base and a
additional guidance on tuning units, refer to transmittertreceiver.
ANSUIEEE Std 643-1980 [14]. In these applications, the copper braid
(shield) which forms the outer conductor of the
6.5.1 Insulated Single Conductors. An cable should be grounded a t the trans-
insulated single conductor is used to connect a mitterlreceiver end only (or at only one end of
coupling capacitor to line-tuning equipment or a bypass). If both shield ends are grounded,
outdoor t r a n s m i t t i n g a n d receiving large surge currents can flow under certain
equipment. I t can also be used as the conditions, causing s a t u r a t i o n of t h e
interconnecting lead for short bypasses. impedance-matching t r a n s f o r m e r a n d
Bare conductors and coaxial cables should resulting in an inoperative carrier channel.
be avoided for these applications, since one 6.5.3 T r i a x i a l Cables. On transmission
will introduce excessive leakage currents and lines operating at voltages greater t h a n

22
ANSI/IEEE
INSTALLATION O F CABLE SYSTEMS IN SUBSTATIONS Std 525-1987

230 kV, triaxial cable may be used instead of NOTE: Several types of fire stops, cable system
enclosures, fire barriers and coatings a r e made from
coaxial cable. This cable provides a n materials which are thermal insulators. Their use can
additional heavy shield which does not carry result in significant cable derating which should be
signal currents. The outer shield is capable of considered in sizing cables.
carrying large induced surge currents under
fault conditions and is grounded a t both ends.
This arrangement provides very effective 7.1 Definitions
shielding a g a i n s t both magnetic and
electrostatic induction so that surges induced cable f i r e break. Material, devices, or a n
in the signal leads are small. assembly of parts installed in a cable system,
6.5.4 I n s u l a t i o n R e q u i r e m e n t s . In some other than a t a cable penetration of a fire-
cable installations, specifications may call resistive barrier, t o prevent the spread of fire
for safe operation under high-temperature along the cable system.
conditions. Polyethylene has a maximum
service temperature of 80 "C, and, therefore, it cable penetration. An assembly or group of
must be replaced by other dielectrics where assemblies for electrical conductors t o enter
high-temperature operation is required. and continue through a fire-rated structural
Chlorosulfonated polyethylene and silicone wall, floor, or floor-ceiling assembly.
rubber compounds are examples of materials
that have been used in high-temperature cables cable penetration fire stop. Material, devices,
or where cable fire propagation is a con- o r a n assembly of parts providing cable
sideration. penetrations through fire-rated walls, floors,
and floor-ceiling assemblies and
6.6 Coupling Capacitor Voltage Transformer maintaining their required fire rating.
C o n s i d e r a t i o n s . CCVTs can produce high
transient common-mode secondary voltages
cable system enclosure (cocoon).An assembly
because of the surge impedance that exists
installed around a cable system t o maintain
between the CCVT base and the ground grid,
circuit integrity, for a specified time, of all
and between phases. This voltage can be
circuits within the enclosure when it i s
reduced by lowering the surge impedance,
exposed t o the most severe fire that may be
which is achieved by mounting the CCVTs as
expected to occur in the area.
close t o the ground as permitted by clearance
standards and by providing multiple low-
resistance conductors between the CCVT base fire-protective coatings. A material applied to
and the station ground grid, and between a completed cable or assembly of cables t o
phases. All secondary circuits from the prevent the propagation of flame. Fire-
CCVTs should be radial and contained within protective coatings include liquids, mastics,
a single shielded cable t o provide cancellation and tapes.
of the differences in ground grid potential
[ B l l l . The secondary cables should follow the fire-resistive barrier. A wall, floor, or floor-
ground conductor as closely as possible. ceiling assembly erected t o prevent the spread
of fire.

NOTE: To be effective, fire barriers must have sufficient


fire resistance to withstand the effects of the most severe
7. Cable Penetration Fire Stops, Fire fire that may be expected t o occur in the area adjacent to the
Breaks,System Enclosures, and Cable fire barrier, and must provide a complete barrier to the
Coatings spread of fire.

f i r e - r e s i s t i v e barrier rating. This is ex-


This section provides guidance for the pressed in time (hours and minutes) and
selection and application of cable penetration indicates that the wall, floor, or floor-ceiling
fire stops, cable fire breaks, cable system assembly can withstand, without failure,
enclosures (cocoons), and coatings for cable exposure t o a standard fire for that period of
sys tems. time.

23
ANSIlIEEE
Std 6261987 IEEE GUIDE FOR THE DESIGN AND

NOTE:The test fire procedure and acceptance criteria are Cable penetration fire stops should be used
defined in ASTM E119-1983 [193. where sleeve or tray penetrations are used
beneath control boards or other panels.
7 8 Cable Penetration &e Stops. The fire stop
should prevent fire propagation along a cable
system through a fire-rated wall, floor, or 7.3 Cable Fire Breaks. When cable does not
floor-ceiling barrier while maintaining the meet the flame propagation characteristics of
integrity of the fire barrier through which the 2.3.5, cable fire breaks should be installed in
cable system penetrates. the tray at intervals not exceeding 20 ft.
7.2.1 Design Considerations. In selecting
materials for use as fire stops, the following 7.4 Cable S y s t e m Enclosure. Consideration
factors should be considered: should be given t o utilizing cable system
(1) Physical and chemical compatibility enclosures when redundant or critical cables
between the penetration fire stop material and are routed through fire hazard areas.
the cable covering and raceway materials.
(2) Reduce heat dissipation resulting in 7.5 Cable Coatings. Consideration should be
power cable ampacity derating. given to applying flame-retardant coatings on
(3) Thermal expansion which might crush all cables in open raceways that do not meet the
insulation or jacket during installation and flame propagation characteristics of 2.3.5.
operation.
(4) Toxic or corrosive gases developed
7.6 Practices. For additional fire protection
during installation or during a fire.
practices, see ANSVIEEE Std 979-1984 [l61.
( 5 ) Ability t o withstand pressure differ-
en tials.
(6) Aging.
(7) Temperature rise during curing of
material.
(8) Ease of installation.
(9) Provision for the installation of addi- This section provides guidance or infor-
tional cables. mation for the selection of fire detection
(10) Ability to withstand a hose-stream test systems for cable systems.
that is acceptable for use on an electrical fire.
The cable penetration fire stop should have a 8.1 D e t e c t i o n S y s t e m s . Automatic fire
fire rating equal to or greater than the detection systems may be installed in areas of
required fire rating of the wall, floor, or high cable concentration. One method of
ceiling. Modifications or additions of cables determining a n a r e a of high cable
through the fire stop should not compromise the concentration is as follows:
integrity of the fire stop. An area of high cable concentration (actual
7.23 Sleeve a n d Tray Penetrations. Where or potential) exists for horizontal cable trays
pressure integrity or liquid seals are required, when more than 7-1/2 ft of total cable tray
conduit sleeves may be used with a fire- width exists in the zone of influence. The zone
resistive sealant o r a compound packed into of influence is determined by extending lines
the area between the cable and sleeve walls. A from the bottom of the side rails of the lowest
special example of this method is using a solid cable tray a t a 30 degree angle from vertical
section of tray which is then filled with (see Fig 8-11.
sealant. The sealant or compound should be Fire detection systems may also be con-
compatible with the cable outer surface sidered in areas of lesser cable concentration
material. which provide vital service, or areas where,
Where penetrations are made into areas because of its location, a cable fire may go
classified a s NEC Class I Hazardous unnoticed for a relatively long period of time.
(Classified) Are as, explosion-pro of fittings For additional information on heat, smoke,
should be used. The void around the cable and fire detectors, see ANSIAEEE Std 979-1984
should be filled with a fire-resistive seal. [161.

24
ANSI/IEEE
INSTALLATION OF CABLE SYSTEMS IN SUBSTATIONS Std 525-1987

TRAYS WITH A VERTICAL SEPARATION


OF FIVE FEET OR MORE ARE EXCLUDED
FROM THE ZONE OF INFLUENCE.

\
\ U /
/
/
\ /
\ /
/ /
/
\ /
\ /
/
‘\I//
Determination of Zone of Influence
NOTES (1) N W 5 7% ft no protection.
~
NOTES (1) 5 18 in = 7% ft - no protection.
(2) N W > 7% ft - protection suggested. (2) 5 * 24 in = 10 ft - protection suggested.
(3) N = number of trays within zone of influence. (3) Trays that are partially within the zone of influence are
(4) W = width of tray. considered as being totally within the zone.

U U
U
U
U
NOTES ( 1 ) 5 . 18 in = 7% ft - no protection. NOTES (1) 18 in + 3(24 in) = 7%ft - no protection.
(2) 5 . 24 in = 10 ft - protection suggested. (2) 18 in + 3(30 in) = 9 ft - protection suggested.

Fig 8-1
Determination of Potential High-Cable Concentration

25
ANSIJIEEE
Std 626-1987 IEEE GUIDE FOR THE DESIGN AND

9. Fire Extinguishing Systems store cables in a heated building a t least 24 h


prior t o installation.
Table 10-1 provides cable manufacturers'
This section provides guidance for the recommended low temperature limits for
selection and application of fire extinguishing handling and pulling cables with various
systems protecting cable systems. types of jackets or insulations.
(2) Cable pulling lubricants should be
9.1 F i x e d Fire E x t i n g u i s h i n g S y s t e m compatible with cable outer surface and should
Application a n d Design. Fire extinguishing not set up or harden during cable installation.
systems may be utilized for the protection of The lubricant should not set up so as to prevent
cable systems. Additional information may the cable from being pulled out of the conduit at
be found in ANSVIEEE Std 979-1984 [161. a later time.
(3) Pulling winches and other necessary
equipment should be of adequate capacity t o
ensure a steady continuous pull on the cable.
10. Instabtion and Handling (4)Cable reels should be supported so that the
cable may be unreeled and fed into the
raceway without subjecting the cable to a
This section provides guidance for the reverse bend as it is pulled from the reel.
construction methods, materials, and pre- (5) A tension measuring device should be
cautions in handling and installing cable used on runs when pulling-force calculations
systems . indicate allowable s t r e s s e s may be
approached.
10.1 Storage. Reels should be stored upright on (6) Pulling tension will be increased when
their flanges and handled in such a manner the cable is pulled off the reel. Turning the reel
as to prevent deterioration of or physical and feeding slack cable t o the duct entrance
damage t o the reel or to the cable. During will reduce the pulling tension.
storage, the ends of the cables should be sealed (7) The direction of pulling h a s a large
against t h e entrance of moisture or influence on the pulling tension in conduit
contamination. Reels should be stored on solid runs containing bends. Whenever a choice is
ground to prevent the flanges from sinking possible, the cable should be pulled so that the
into the earth. bend or bends are closest to the reel. The worst
condition possible is to pull out of a bend at or
108 Installation. near the end of the run.
(1) The cable manufacturers' recommended (8) Sufficient cable slack should be left in
temperature limits should be followed when each manhole and temporarily supported so
pulling or handling cables during extreme t h a t the cable can be trained to its final
low temperatures. Handling or pulling cables location on racks, hangers, or trays along the
in extremely low temperatures can cause sides of the manhole. Cable splices should not
damage t o the cable sheathing, jacketing or be placed directly on racks or hangers.
insulation. To prevent damage of this nature, (9) The use of single-roller or multi-roller
cable sheaves of the proper radius should be
Table 10-1 used when installing cable around corners o r
Low Temperature Limits for obstructions.
Cable Handling and Pulling (10) Guidance on conduit fill can be found in
Low Temperature Limits
ANSI/NFPA 70-1987 [171.
Cable Insulation or (11) Cables should be identified by a
Jacket Material Celsius Fahrenheit
permanent marker at each end, in accordance
EPR (Ethylene Propylene Rubber) -40 - 40 with the design documents.
CPE (Chlorinated Polyethylene) - 35 - 31
(12) Careful consideration should be given
PVC (Polyvinyl Chloride) - 10 +14
CSPE (Chlorosulfonated Polyethylene) - 20 -4 not only t o design engineering and material
Neoprene (Polychloroprene) - 20 -4 cost, but also to the installed cost for the initial
XLP (Cross-Linked Polyethylene) - 40 - 40
Paper Insulated, Lead Sheathed - 12 + 10 a s well a s t h e ultimate installation.
Maintenance and replacement costs also
ANSYlEEE
INSTALLATION OF CABLE SYSTEMS IN SUBSTATIONS Std 525-1987

should be considered. It is desirable that the and sidewall pressures for cable installations
system be designed so t h a t additions and are not violated. Guidance for the number of
changes can be made with ease, economy, and bends between pull points can be found in
minimum outages. ANSI/NFPA 70-1987 [171.
(13) If the cable manufacturers' recom- (9) Pulling instructions for all cable should
mended maximum pulling tension, sidewall follow the cable manufacturers' recommen-
pressure, o r t h e minimum bending o r dations.
training radius is violated, damage could (10) Cables should not be pulled around sharp
occur to the cable conductor, insulation, shield, corners or obstructions.
or jacket. (11)The cable end within a pulling device
10.2.1 Pmtection of Cable should be removed from the cable prior to
(1)Special care should be exercised during termination.
welding, soldering, and splicing operations to (12) After the cable pull is complete, cable
prevent damage to cables. If necessary, cables manufacturers' recommendations for mini-
should be protected by fire-resistant material. mum training radii should be followed.
(2) After cable installation has started, trays (13) Where single conductors are used in
and trenches should be periodically cleaned as trays for two-wire or three-wire power circuits,
necessary t o prevent the accumulation of these conductors should be securely bound in
debris. circuit groups t o prevent excessive movements
(3) A suitable feeder device should be used to caused by fault-current magnetic forces and to
protect and guide the cable from the cable reel minimize inductive heating effects in tray
into the raceway. The radius of the feeder sidewalls and bottom.
devices should not be less than the minimum 10.22 Supporting Cables in Vertical Runs.
bending radius of the cable. If a feeder device The weight of a vertical cable should not be
is not used, the cable should be hand-guided supported by the terminals t o which i t is
into the raceway. connected. To prevent damage by deformation
(4) Bare wire rope should not be used to pull due to excessive bearing pressure or cable
cables in conduits. tension, vertically run cables should b e
(5) The ends of high-voltage power cables supported by holding devices in the tray, in the
should be properly sealed during and after ends of the conduit, or in boxes inserted at
installation. The ends of all other cables intervals in the conduit system.
should be properly sealed during and after Cables, regardless of their voltage class,
installation in wet locations. Cables such as installed in vertical runs should be supported
aluminum, mineral-insulated, paper, a n d in accordance with the following:
varnished cambric should be resealed after
pulling regardless of location.
If water has entered the cable, a vacuum Conductor Sizes Maximum Distance
should be pulled on the cable or the cable should
be purged with nitrogen to extract the water. 14 to 110 100 30
(6)A swivel should be attached between the YO to 4/0 80 24
pulling eye and the pulling cable. Projections 250 to 350 60 18
and sharp edges on pulling hardware should Over 350 to 500 50 15
be taped or otherwise covered to protect against Over 500 to 750 40 12
snagging at conduit joints and t o prevent Over 750 35 10
damage to conduit.
(7) Cable should be pulled only into clean Recommendations for supporting special
raceways. A mandrel should be pulled through cables such as armored, shielded, coaxial, etc,
all underground ducts prior t o cable pulling. should be obtained from the cable manu-
Any abrasions or sharp edges which might facturer.
damage the cable should be removed. 10.2.3 Securing Cables in Vertical Runs.
(8) Cables should be installed in raceway Cable installed in vertical cables trays should
systems that have adequately sized bends, be secured to the cable tray at least every 5 ft.
boxes, and fittiqgs so that cable manufac- 10.2.4 Training Cables. Cables installed in
turers' minimum allowable bending radii trays should be neatly trained t o facilitate

27
ANSI/IEEE
Std 5251987 IEEE GUIDE FOR THE DESIGN AND

identification and removal and to maximize following formula, unless otherwise indicated
tray fill. by the cable manufacturer.
Based on a pull on the conductor or by a
device attached t o the conductor
10.3 C a b l e P u l l i n g Design L i m i t s and
C a l c u l a t i o n s . The following design limits T,,, = K XNXcmil (Eq 2)
and formulae provided in this section should
be utilized when determining the maximum where
safe pulling lengths and tensions. Raceway T,, = maximum allowable pulling tension, in
fill, maximum sidewall pressure, jam ratio, pounds
and minimum bending radius are design cmil = circular mil area of each conductor
limits which should be examined in K = 0.008 lb/cmil for annealed copper and
designing a proper cable pull. These design hard aluminum
limits are prerequisites needed in designing a K = 0.006 lb/cmil for 3h hard aluminum
cable raceway system. Once these limits are N = number of conductors
determined for a particular cable, the raceway
system can then be designed. If the system has In pulling three single conductors of equal
already been designed, modifications may be size in parallel, triangular or cradled
required in order to pull the cable without configuration, a value of N equal to 2 should be
damage. used since two of the conductors may sustain
Conduit and duct system design should the total pulling tension. When more than
consider the maximum pulling lengths of three single conductors of equal size are pulled
cable to be installed. The maximum pulling in parallel, the maximum tension should be
length of a cable or cables is determined by the limited to 60% of the value determined by the
maximum allowable pulling tension and equation.
sidewall pressure. The pulling length will be When pulling conductors of different sizes,
limited by one of these factors. consult the cable manufacturerb).
Pull points or manholes should be installed When pulling using a pulling eye, the
wherever calculations show that expected maximum tension for a single-conductor
pulling tensions exceed either maximum cable should not exceed 5000 lbs, and the
allowable pulling tension or sidewall maximum tension for two or more conductors
pre s u r e . should not exceed 6000 lbs. The cable
A sample calculation for determining cable manufacturer should be consulted when
pulling tensions is shown in Appendix A. tensions exceeding these limits are expected.
Based on pull by basket grip applied over
10.3.1 Design Limits nonleaded jacketed cable
10.3.1.1 Raceway Fill a n d Determining
R a c e w a y S i z e s . Raceways should be T,,, = 1000 lb
adequately sized as determined by the When using a basket-weave type pulling
maximum recommended percentage fill of the grip applied over a lead-sheathed cable, the
raceway area. Raceway fill is based on the force should not exceed 1500 lb as determined
following equation: by the following formula:
T,,, = K,Tt (D-t) (Eq 4)
C Cable Area
%Fill =
Raceway Area
x 100%
where
Raceway fill limitations are given in the t = lead sheath thickness, in inches
National Electrical Code, ANSINFPA 70- 1987 D = outside diameter of lead sheath, in
[171. If the fill limitations and cable area are inches
known, the raceway area can be calculated K, = maximum allowable pulling stress in
and an adequate size can be selected. pounds per square inch (1500 psi to
10.3.1.2 Maximum Allowable P u l l i n g 2000 psi depending on lead alloy).
T e n s i o n . The maximum allowable pulling NOTE: For lead-sheathed cables with neoprene jackets,
tension should be determined from the T,, equals 1000 lb.
ANSI/IEEE
INSTALLATION OF CABLE SYSTEMS IN SUBSTATIONS Std 626-1987

When using a pulling grip, the maximum subject t o verification by t h e cable


pulling tension should not exceed the smaller manufacturer. For instrumentation cable, the
of the values calculated above. cable manufacturer's recommendations
Pulling instructions for coaxial, triaxial, should be obtained.
and other special cables should follow the 10.3.1.4 Jam Ratio. Jamming is the
manufacturers' recommendations. wedging of cables in a conduit when 3 cables
10.3.1.3 Maximum Allowable Sidewall lay side-by-side in the same plane. J a m ratio
Pressure. Sidewall pressure, P, is defined as is defined for three cables of equal diameter as
the tension out of a bend expressed in pounds the ratio of the conduit inside diameter (D) to
divided by the radius of the bend expressed in the cable outside diameter (d). The jam ratio is
feet. The sidewall pressure on a cable can be a concern because jamming in the conduit
calculated by the following equations: could cause damage t o one o r more of the
cables. The possibility of jamming is greater
p = -TO Single cable in when the cables change direction. Therefore,
r conduit. (Eq 5 ) the inside diameter of the conduit at the bend is
used in determining the jam ratio.
(3c - 2) To Three cables in
P= 3r cradle configu- (Eq 1
' D
Jamming cannot occur when - >3.0 (Eq 9)
ration where d
the center cable
presses hardest D
against the conduit. Jamming is not likely when - <2.8 (Eq 10)
d
c To Three cables in
p= - D
2r triangular configu- (Eq 7, Jamming is probable when 2.8 5 - (3.0 (Eq 11)
ration where the d-
pressure is divided A 40% conduit fill gives a jam ratio of 2.74,
between the two which is in the region where jamming is not
bottom cables. likely. The inside diameter of a field bent
Four cables in conduit is usually increased by 5% to account
(e - 1) To
P= 2r diamond configu- (Eq for the oval cross-section which occurs.
ration where the Adding 5% for a field bent conduit yields a
bottom cable is jam ratio of 2.87, which is in the region where
subjected to the jamming is probable.
greatest crushing 10.3.1.5 Minimum Bending Radius. The
force. minimum bending radius is the minimum
radius a cable can be bent to while under a
where pulling tension, providing the maximum
sidewall pressure is not exceeded. The values
P = sidewall pressure, in lbs/ft of radius given are usually stated as a multiple of cable
To = tension out of the bend, in lbs diameter and are a function of the cable
c = weight correction factor (refer to diameter, a n d whether t h e cable i s
10.3.2.1) nonshielded, shielded, armored, or single or
r = inside radius of bend, in feet multiple conductor. Guidance for minimum
bending radii can be obtained from the Na-
Equations (61, (71, and ( 8 ) calculate the tional Electrical Code ANSUNFPA 70-1987 [171
sidewall pressure for the worst case cable. or the cable manufacturer.
The maximum allowable sidewall pressure 10.3.2 Cable Pulling Calculations. The
is 500 lb per ft of radius for multiconductor equations used to calculate the expected cable
power and control cables and single-conductor pulling tension are based on the number of
power cables #6 AWG and larger, subject to cables t o be pulled, the type of raceway, the
verification by the cable manufacturer. The cable configuration in the raceway and the
recommended maximum allowable sidewall raceway layout.
pressure for single-conductor power cable #8 103.2.1 Straight Sections of Conduit or Duct.
AWG and smaller is 300 lb per ft of radius For a straight section of conduit o r duct,
ANSI/IEEE
Std 525-1987 IEEE GUIDE FOR THE DESIGN AND

3.2 28.4

G
\

eI 3.0 33.5

E
8‘ a
2.8 38.5 5
$
Y
0
0
EW
E8 2.6 44.5 a
0
e:
W

;j
k
sz
8 2.4 32.8

2.2 32.0
1.o 1.2 1.4 1.6 1.8 2.0
WEIGHT CORRECIION FACTOR (c)

NOTES (1) Curve “ A is for cradle formation.


(2) Curve “B” is for triangular formation.
(3) Curve “B” usually joins curve “ A at point shown.
(4) Dotted portion shows where both formations can exist.

Pig 10-1
Weight Correction Factor (c)

the pulling tension is equal to the length of the The weight correction factor takes into
straight run multiplied by the weight per foot account the added frictional forces that exist
of cable, the coefficient of friction and the between triangular or cradle arranged
weight correction factor. cables resulting in a greater pulling tension
than when pulling a single cable. The weight
correction factor can be calculated by the
T = Lwfc (Eq 12) following equations:

where
T = total pulling tension of straight run, in lbs
= + 4/3 (A) Three single cables
in cradled con- (Eq 13)
figuration
L = length of the straight run, in f t
w = weight of the cable(s), in lbs/ft 1 Three single cables
f = coefficient of friction in triangular (Eq 14)
c = weight correction factor configuration
The coefficient of friction is usually assumed to be
as follows:
Dry cable or ducts
Well lubricated cable and ducts 0.35
0.5 c=1+2 (A) Four single cables
in diamond con- (Eq 15)
figuration
30
ANSI/IEEE
INSTALLATION OF CABLF: SYSTEMS IN SUBSTATIONS Std 626-1987

where did not occur during storage and installation


and that the cable was properly spliced and
D = conduit inside diameter
d = single conductor cable outside diameter terminated. It should be noted, however, that
these tests may not detect damage that may
The weight correction factor for three sin- eventually lead t o cable failure in service,
gle-conductor cables can be determined from for example, damage to the cable jacket or
Fig 10-1. insulation shield on high-voltage cable, or to
10.3.28 Inclined Sections of Raceway. low-voltage cable insulation.
The expected pulling tension of a cable in an
inclined section of duct may be calculated 11.2 Tests. Safety precautions should be
from the following formulae: observed during all phases of testing. Cable
ends should be properly cleaned of all
Tup = w L (cf COS a + sin a ) (Eq 16) conducting material. Cable test results,
environmental conditions, and data should
Tdown= w L (cf COS a - sin cx) (Eq 17) be recorded and filed for maintenance ref-
where erence. The following tests should be per-
formed, a s applicable, in conjunction with
a is the angle of the incline from horizontal the cable manufacturer's recommendations:
10.3.2.3 Horizontal and Vertical Bends. (1) Low-voltage power, control, and in-
The tension out of a horizontal or vertical strumentation cables should be either in-
conduit bend is normally calculated from the sulation-resistance tested prior t o connecting
following approximate formula: cables t o equipment or functionally tested (at
equipment operation voltage) as part of the
To,, = Tinecfe (Eq 18) checkout of the equipment system.
where (2) The low-voltage power cable insulation
To,, =tension out of bend, in lbs resistance t e s t s should measure t h e
insulation resistance between any possible
Tin =tension into the bend, in lbs
8 =angle of the change in direction pro- combination of conductors in the same cable
duced by bend, in radians and between each conductor and station
ground, with all other conductors in the same
This is a simplified equation which ig- cable grounded.
nores the weight of the cable. It is very ac- The test voltage should be a minimum of
curate where the incoming tension a t a bend 500 V dc. The minimum acceptable in-
is equal to or greater than 10 times the product sulation resistance is:
of cable weight per foot times the bend radius
(10 w r) expressed in feet. If the tension into a R in megohms = (rated voltage in kV +
bend is less than 10 w r, the exact equations 1)x 1000Aength in feet
can be found in reference IB421. Cases in
which the exact equations may become (3) Testing of control cable and prefabri-
necessary are where light tensions enter cated cable assemblies in a similar manner
large radii bends. Usually equation (18) is is suggested. Cable manufacturers' recom-
precise enough for normal installations. mendations should always be considered.
(4) Shielded high-voltage power cables
should be dc high-potential tested in ac-
11.Acceptance Testing of Installed cordance with ICEA, ANSUIEEE Std 400-1980
Cables (R 1987) [91, or AEIC standards prior t o
equipment connection. Unshielded high-
This section provides guidance for the voltage cables should not be subjected to high-
testing of cables after installation, but before voltage dc tests; insulation resistance tests
their connection to equipment, and includes are suggested.
cable terminations, connectors, and splices. ( 5 ) Instrumentation cables should be
subjected t o insulation resistance mea-
11.1 Purpose. The purpose of these tests is to surements if circuit performance is de-
verify that major cable insulation damage pendent upon insulation resistance. Cable

31
ANSVIEEE
Std 6261987 IEEE GUIDE FOR THE DESIGN AND

manufacturers' testing recommendations Type 11. Designed for underground in-


should always be considered. stallation without encasement in concrete.
Type 111. Designed for wrmal-duty appli-
cations above grade.
Type IV. Designed for heavy-duty appli-
12. Raceways cations above grade.

12.2 Conduit
126.1 Conduit Application
This section provides guidance for both a
(1)RMC or IMC zinc-coated conduit may be
means of supporting cable runs between
used exposed in wet and dry locations,
electrical equipment and physical protection
embedded in concrete, and directly buried in
t o the cables. Raceway systems consist
soil. If they are installed directly buried in
primarily of cable tray and conduit.
soil, consideration should be given to the zinc
coating having a limited life, and corrosion
12.1 Definitions. NEMA TC2-1983 [261, may be rapid after the zinc coating is
NEMA TC6-1983 [271. consumed or damaged.
When used in cinder fills, the conduit
ABS. Conduit fabricated from acryloni- should be protected by noncinder concrete at
trile-butadiene-styrene. least 2 in thick. When used where excessive
alkaline conditions exist, the conduit should
EMT. Electrical metallic tubing. be protected by a coat of bituminous paint or
EPT. Electrical plastic tubing for type I similar material. PVC-coated steel conduit
applications, fabricated from PVC. may be used in corrosive environments.
Plugs should be used t o seal spare conduits in
EPC-40. Electrical plastic conduit for type wet locations.
I1 applications, fabricated from PE; or for (2) EPC-40 or EPC-80 conduit may be used
type I1 and I11 applications, fabricated from exposed. EPT and Type EB duct must be
PVC. encased in concrete, and Type DB duct may
be direct buried without concrete encasement.
EPC-80. Electrical plastic conduit for type Since ABS and PVC conduit may have
IV applications, fabricated from PVC. different properties, a review should be made
of their brittleness and impact strength
FRE. Conduit fabricated from fiberglass characteristics. Coefficient of expansion
reinforced epoxy. should also be considered for outdoor
IMC. Intermediate metal conduit. applications. Flammability of such conduits
is of particular concern in indoor exposed
PE. Conduit fabricated from polyethylene. locations. Burning o r excessive heating of
PVC in the presence of moisture may result
PVC. Conduit fabricated from polyvinyl in the formation of hydrochloric acid which
chloride. can attack reinforcing steel, deposit
chlorides on stainless steel surfaces, o r
RMC. Rigid metal conduit. attack electrical contact surfaces. The use of
Type DB. Duct designed for direct burial exposed PVC conduit indoors should
without encasement in concrete (also re- generally be avoided, but may be considered
ferred t o as Type I1 duct), fabricated from for limited use in corrosive environments.
PVC or ABS. (3) EMT may be used in dry accessible
locations t o perform the same functions as
Type EB. Duct designed to be encased in RMC conduit except in hazardous areas (as
concrete when installed (also referred t o as defined by NEC).
Type I duct), fabricated from PVC or ABS. (4) Aluminum conduit (Alloy 60611,
plastic-coated steel conduit, Type DB PVC o r
Application s : ABS duct, EPC-40 or EPC-80 PVC conduit and
'&pe I. Designed t o be encased in concrete. Type FRE conduit may be used in areas

32
ANSyIEEE
INSTALLATION OF CABLE SYSTEMS IN SUBSTATIONS Std 625-1987

where a high corrosive environment may anticipated or where the use of rigid conduit
exist and for other applications where is not practical. Liquid-tight flexible conduit
uncoated steel conduit would not be suitable. is commonly used for this application.
Aluminum conduit may be used exposed in Flexible conduit length should be as short as
wet and dry locations. Aluminum conduit practical, but consistent with its own
should not be embedded in concrete or minimum bending radius, the minimum
directly buried in soil unless coated bending radius of the cable to be installed,
(bitumastic compound, etc) to prevent and the relative motion expected between
corrosion. Aluminum conduit may be used, connection points. A separate ground wire
exposed o r concealed, where a strong should be installed if the flexible conduit is
magnetic field exists; however, conduit not p a r t of the grounding and bonding
supports should not form a magnetic circuit system. See ANSI/NFPA 70-1987 [171 for
around the conduit if all the cables of the additional guidance.
electrical circuit are not in the same conduit. (2) Where it is possible for water or other
( 5 ) The cable system should be compatible liquids t o enter conduits, sloping of conduit
with drainage systems for surface water, oil, runs and drainage of low points should be
or other fluids, but preferably should be provided.
installed to avoid accumulated fluids. (3) Electrical equipment enclosures should
(6) The cable system should be capable of have conduit installed in a manner t o
operating in conditions of water immersion, prevent t h e entrance of water a n d
a m b i e n t t e m p e r a t u r e s , a n d limited condensation. Drain fittings and air vents
concentrations of chemicals. Protection in the equipment enclosure should also be
should be provided against attack by insects, considered. Expansion couplings should be
rodents, or other indigenous animals. installed in t h e conduit r u n or at the
(7) Cable trays, conduits, and troughs are enclosure to prevent damage caused by frost
sometimes run above grade in substations, heaving or expansion.
supported from equipment structures or (4) The entire metallic conduit system,
specially designed g r o u n d - m o u n t e d whether rigid o r flexible, should be
structures. Troughs constructed of concrete electrically continuous and grounded.
or other material may be laid on the grade. (5) When installed in conduit of magnetic
Cost savings may be realized when material, all phases of three-phase ac circuits
comparing above grade trays, conduit and and both legs of single-phase ac circuits
troughs to similar below-grade systems. should be installed in the same conduit or
Care should be taken in routing above - sleeve.
grade systems to minimize interference with (6) All conduit systems should have
traffic and equipment access, and to avoid a suitable pull points (pull boxes, manholes,
reduction in minimum electrical etc) to avoid over-tensioning the cable during
clearances. installation.
These systems are more vulnerable to 12.2.2.2 Embedded Conduits and
fires, mechanical damage, environmental Manholes
elements, and seismic forces, and offer (1) Spacing of embedded conduits should
greater susceptibility to electrostatic and permit fittings to be installed.
electromagnetic coupling than if the cables (2) Conduit in duct runs containing one
were below grade. phase of a three-phase power circuit or one leg
(8) Above ground pull boxes are sometimes of a single-phase power circuit should not be
used for distribution panels and for common supported by reinforcing steel forming closed
connections such as current or potential magnetic paths around individual conduits.
leads. The judicious location of these boxes Reinforcing steel in the manhole walls
may result in considerable savings. should not form closed loops around
12.23 Conduit System Design individual nonmetallic conduit entering the
122.2.1 Exposed Conduit manhole. Nonmetallic spacers should be
(1)Flexible conduit should be used between used.
rigid conduit a n d equipment connection (3) Concrete curbs or other means of
boxes where vibration o r settling is protection should be provided where other

33
ANSI/IEEE
Std 5251987 IEEE GUIDE FOR THE DESIGN AND

than RS conduits turn upward out of floor (2) When embedded in concrete, installed
slabs. indoors in wet areas, and in all outdoor
(4) The lower surface of' concrete-encased locations, threaded conduit joints and
duct banks should be located below the frost connections should be made watertight and
line. Where this is not practical, lean rustproof by means of the application of a
concrete or porous fill can be used between the conductive thread compound which will not
frost line and the duct bank. insulate the joint. Each threaded joint should
(5) Concrete-encased duct banks should be be cleaned to remove all of the cutting oil
adequately reinforced under roads and in before the compound is applied. The
areas where heavy equipment may be moved compound should be applied only t o the male
over the duct bank. conduit threads t o prevent obstruction.
(6) Directly buried nonmetallic conduits (3) Running threads should not be utilized,
should not be installed under roadways or in and welding of conduits should not be done.
areas where heavy equipment may be moved (4) Field bends should not be of lesser
over them unless the conduits are made from radius than suggested by ANSIBFPA 70-
resilient compounds suitable for this service 1987 C171, and should show no appreciable
or are protected structurally. flattening of the conduit.
(7) Conduits in duct banks should be sloped (5) Large radius bends should be used t o
downward toward manholes or drain points.
reduce the cable sidewall pressure during
(8) Duct lengths should not exceed those cable installation and in conduit runs when
which will develop pulling tensions or the bending radius of the cable to be contained
sidewall pressures in excess of those allowed in the conduit exceeds the radius of standard
by the cable manufacturers' recommenda- bends.
tions.
(9) Manholes should be oriented to (6) Conduits installed in concrete should
minimize bends in duct banks. have their ends plugged or capped before the
(10) Manholes should have a sump, if concrete is poured.
necessary, to facilitate the use of a pump. (7) All conduit interiors should be free of
(11) Manholes should be provided with burrs and should be cleaned after instal-
means for attachment of cable-pulling lation.
devices t o facilitate pulling cables out of (8) Exposed conduit should be marked in a
conduits in a straight line. distinct permanent manner at each end and
(12) Provisions should be made t o facilitate a t points of entry to and exit from enclosed
racking of cables along the walls of the areas.
man hole.
(13) Exposed metal in manholes, such as (9) Flexible conduit connections should be
conduits, racks, and ladders, should be used for all motor terminal boxes and other
grounded . equipment which is subject t o vibration. The
(14) End bells should be provided where connections should be of minimum lengths
conduits enter manholes or building walls. and should employ at least the minimum
(15) Manholes and manhole openings bending radii established by the cable
should be sized so that the cable manufac- manufacturer.
turers' minimum allowable cable bending (10) Conduit should not be installed in close
radii are not violated. proximity to hot pipes or other heat sources.
(16) When installed in conduit of magnetic (11) Proper fittings should be used at
material, all phases of three-phase ac circuits conduit ends t o prevent cable damage.
and both legs of single-phase ac circuits
should be installed in the same conduit or (12) Conduits should be installed so as to
sleeve. prevent damage to the cable system from the
128.3 Conduit Installation movement of vehicles and equipment.
(1) Supports of exposed conduits should (13) Conduit entrances to control buildings
follow NEC recommendations or industry should be provided with barriers against
standards. rodents and fire.

34
ANSUIEEE
INSTALLATION OF CABLE SYSTEMS IN SUBSTATIONS Std 525-1987

12.3 Cable ' h a y structure and the trays should be considered.


12.3.1 T r a y Design Ice, snow, and wind loadings must be added
(1)Cable tray design should be based upon t o loads described in 12.3.4. Aluminum
the required loading and the maximum Alloys 6061-T6, 6063-T6, and 5052-M34 are
spacing between supports. Loading acceptable, with careful recognition of the
calculations should include the static weight differences in strength. Mill-galvanized
of cables and a concentrated load of 200 lb a t steel should normally be used only for indoor
midspan. The tray load factor (safety factor) applications in noncorrosive environments.
should be a t least 1.5 based on collapse of the Hot-dipped galvanized-after-fabrication
tray when supported as a simple beam NEMA steel should be used for outdoor and damp
VE 1-1984 [281. locations.
(2) When ladder-type tray is specified, (3) When the galvanized surface on the
rung spacing should be a nominal 9 in. For steel tray is broken, the area should be coated
horizontal elbows, rung spacing should be to protect against corrosion.
maintained a t the centerline.
(3) Design should minimize the possibility (4) Consideration should be given t o the
of the accumulation of fluids and debris on relative structural integrity of aluminum
covers or in trays. versus steel tray during a fire.
12.3.2 Tray System Desiga 12.3.4Tray Load Capacity
(1) In general, vertical spacing for cable (1) The quantity of cable installed in any
trays should be 12 in, measured from the tray may be limited by the structural capacity
bottom of the upper tray to the top of the lower of the tray and its supports. Tray load
tray. A minimum clearance of 9 in should be capacity is defined as the allowable weight of
maintained between the top of a tray and wires and cables carried by the tray. This
beams, piping, etc, t o facilitate installation of value is independent of the dead load of the
cables in the tray. tray system. In addition t o and concurrent
(2) Cables installed in stacked cable trays with the tray load capacity and the dead load
should be arranged by descending voltage of the tray system, any tray should neither
levels, with the higher voltage at the top. fail nor be permanently distorted by a
(3) When stacking trays, the structural concentrated load of 200 lb a t midspan a t the
integrity of components and the pullout centerline of the tray or on either side rail.
values of support anchors and attachments (2) A percentage fill limit is needed for
should be verified. randomly filled trays, because cables are not
(4) Provisions for horizontal and vertical laid in neat rows and secured in place. This
separation of redundant system circuits are results in cable crossing and void areas,
described in Section 5. which take up much of the tray cross-
12.3.3 Tray A p p l i c a t i o n . The usual sectional area. Generally, a 30% t o 40% fill
materials from which tray is fabricated are for power and control cables and a 40% to 50%
aluminum, galvanized steel, and fiberglass. fill for instrumentation cables is suggested.
In selecting material for trays, the following This will result in a tray loading in which no
should be considered: cables will be installed above the top of the
(1) Galvanized tray will corrode in side rails of the cable tray, except as
locations such as outdoors near the ocean or necessary at intersections and where cables
immediately adjacent to a cooling tower enter o r exit the cable tray systems.
where the tray is continuously wetted by (3) The quantity of cables in any tray may
chemically treated water. If aluminum tray be limited by the capacity of the cables at the
is used for such applications, a corrosive- bottom of the tray t o withstand the bearing
resistant type should be specified. Special load imposed by cables located adjacent and
coatings for steel tray may also serve as above. This restraint is generally applicable
satisfactory protection against corrosion. t o instrumentation cables, but may also apply
The use of nonmetallic tray should also be to power and control cables.
considered for such applications. 12.3.5 Cable Tray Installation
(2) For cable trays and tray supports located 12.3.5.1 Dropouts
outdoors, the effect of the elements on both the (1)Drop-oat fittings should be provided
ANSI/ZEEE
Std 6251987 IEEE GUIDE FOR THE DESIGN AND

where required t o maintain the minimum cables. Wireways a r e for exposed


cable training radius. installations only and should not be used in
(2) Where conduit is attached to the tray to hazardous areas. Consideration should be
carry exiting cable, the conduit should be given t o the wireway material where
rigidly clamped to the side rail. When corrosive vapors exist. In outdoor locations,
conduit is rigidly clamped, consideration wireways should be of raintight construction.
should be given to the forces a t the connection The sum of the cross-sectional areas of all
during dynamic (seismic) loading of the conductors should not exceed 40% of the
t r a y a n d conduit system. Conduit interior cross-sectional area of the wireway.
connections through the tray bottom or side Taps from wireways should be made with
rail should be avoided. rigid, intermediate metal, electrical
12.3.5.2 Covers metallic tubing, flexible-metal conduit, or
(1) Horizontal trays exposed t o falling armored cable.
objects or to the accumulation of debris should
have covers.
(2) Covers should be provided on exposed 13. Direct Burial, Tunnels, and Trenches
vertical tray risers a t floor levels and other
locations where possible physical damage to
the cables could occur. This section provides guidance for the
(3) Where covers are used on trays installation of cables that are direct buried or
containing power cables, consideration installed in permanent tunnels or trenches.
should be given to ventilation requirements
and cable ampacity derating. 13.1 Direct Burial. Direct burial of cables is a
12.3.5.3 Grounding. Cable tray systems method whereby cables a r e laid in a n
should be electrically continuous and solidly excavation in t h e e a r t h with cables
grounded. When cable trays are used a s branching off t o various pieces of equipment.
raceways for solidly grounded or low- The excavation is then backfilled.
impedance grounded power systems, A layer of sand is usually installed below
consideration should be given t o the tray and above the cables t o prevent mechanical
system ampacity as a conductor. Inadequate damage. Care m u s t be exercised in
ampacity o r discontinuities in the tray backfilling t o avoid large or sharp rocks,
system may require that a ground conductor cinders, slag, or other harmful materials.
be attached t o and run parallel with the tray A warning system t o prevent accidental
or a ground strap be added across the damage during excavation is advisable.
discontinuities or expansion fittings. The Several methods used are treated wood
ground conductor may be either bare, coated, planks, a thin layer of colored lean concrete,
o r insulated, depending upon metallic a layer of sand, strips of plastic, and
compatibility. markers above ground. Untreated wood
12.3.5.4 Ide n t i f i ca t i o n . C ab1e tray p l a n k s may a t t r a c t t e r m i t e s , b u t
sections should be permanently identified overtreatment may result in leaching of
with the tray section number as required by chemicals harmful t o the cables.
the drawings or construction specifications. Spare cables or empty capped ducts for
12.3.5.5 Supports. The type and spacing future cables may be installed before
of cable tray supports will depend on the backfilling.
loads. Tray sections should be supported near This system has low initial cost, but does
section ends and a t fittings such as tees, not lend itself t o changes or additions, and
crosses, and elbows NEMA VE1-1984 1281. provides limited protection against the
12.3.5.6 Location. Trays should not be environment. Damage t o cables i s more
installed in close proximity t o heating pipes difficult to locate and repair in a direct burial
and other heat sources. system than in a permanent trench system.

12.4 Wireways. Wireways are generally 13.2 Cable Tunnels. Walk-through cable
sheet metal troughs with hinged or removable tunnels can be used where there will be a
covers for housing and protecting wires and large number of cables.

36
ANSyIEEE
INSTALLATION OF CABLE SYSTEMS IN SUBSTATIONS Std 525-1987

This system h a s the advantages of with conduits branching to various pieces of


minimum interference to traffic and equipment.
drainage, good physical protection, ease of Removable covers may be made of metal,
adding cables, shielding effect of the ground plywood, or other materials. Nonmetallic
mat, and the capacity for a large number of cover materials should be fire retardant.
cables. Trenches cast into concrete floors should be
Disadvantages include high first cost and covered. It should be noted that metal covers
danger t h a t fire could propagate between in the rear of switchboards present a
cable trays and along the length of the handling hazard; and nonmetallic, fire-
tunnel. If fire stops are provided, hazards retardant material should be used.
can be minimized. Where cables pass through holes cut in
covers, for example, in rear or inside of
13.3 P e r m a n e n t Trenches. Trench systems switchboards, the edges should be covered to
consist sf main runs located to bring large prevent cable damage from sharp edges.
groups of cables through the centers of 13.3.2 Raised Floors. Raised floors provide
equipment groups, with short runs of conduit, maximum flexibility for additions o r
smaller trenches, or direct-burial cable changes. Entrance from the outside into the
branching off to individual pieces of raised floor system may be made at any point
equipment. along the control house wall.
Duct entrances may be made a t the bottom Use of a fire protection system under the
of open-bottom trenches or through knockouts floor should be considered.
in the sides of solid trenches.
Trenches may be made of cast-in-place
concrete, bituminized fiber pipes, o r precast
material. 14. Bibliography
Where trenches interfere with traffic in the
substation, vehicle crossovers, permanent o r
temporary, may be provided as needed. [Bll EEl Underground Systems Reference
Warning posts or signs may be used to warn Book-1957.
vehicular traffic of the presence of trenches.
The trenches may interfere with surface [B2] BAUMGARTNER, E. A. Transient
drainage and can be sloped t o storm sewers, Protection of Pilot Wire Cables Used for High
sump pits, or French drains. Open-bottom Speed Tone and AC Pilot Wire Relaying,
trenches may dissipate drainage water but presented a t 20th Annual Conference for
are vulnerable t o rodents. A layer of sand Protective Relay Engineers, Texas A&M
applied around the cables in the trench may University, College Station, Apr 24-26,1967.
protect the cables from damage by rodents.
Trenches a t cable entrances into control [B3] I E E E COMMITTEE REPORT,
buildings should be sloped away from the Bibliography on Surge Voltages in AC Power
building for drainage purposes. The trenches Circuits Rated 600 Volts and Less. IEEE
also should have a barrier to prevent fire or Transactions on Power Apparatus and
rodents from entering the control building. Systems, vol PAS-89, pp 1056-1061, JuVAug
The tops of the trench walls may be used to 1970.
support hangers for grounded shield
conductors. The covers of trenches may be [B41 BIRCH, F. H., BURROWS, G. H., and
used for walkways. Consideration should be TURNER, H. J . Experience With
given t o grounding metal walkways and Transistorized Protection in Britain, Part 11:
also to providing safety clearance above Investigations into Transient Overvoltages
raised walkways. Added concern should be on Secondary Wiring at EHV Switching
given t o the flammability of wood. Stations, presented at CIGRE, Paper 31-04,
13.3.1 Floor Trenches. Trenches cast into 1968.
concrete floors may be extensive, with
trenches run wherever required; o r a few [B51 BLOSE, J. B. Construction Methods to
trenches may be run under the switchboards, Minimize Transient Interference in Control

37
ANSYIEEE
Std 625-1987 IEEE GUIDE FOR THE DESIGN AND

Circuits. Philadelphia Electric Company [B141 GARTON, H. L., and STOLT, H. K.


Research Division Report E-202, Apr 1971. Field Tests and Corrective Measures for
Suppression of Transient; on Solid State
[B6] BORGVALL, T., HOLMGREN, B., Devices in EHV Stations. Proceedings of the
S U N D E N , 3 . , WISTROM, T. a n d American Power Conference, vol 31, pp 1029-
NORBACK, K. Voltages in Substation 1038,1969.
Control Cables During Switching
Operations, presented a t CIGRE, Paper 36-05, [B15] GILLIES, D. A., and RAMBERG, H. C.
pp 1-23,Aug 24, 1970. Methods for Reducing Induced Voltages in
Secondary Circuits. TEEE Transactions on
[B71 BUCKINGHAM, R. P., and GOODING, Power Apparatus and Systems, vol PAS-86, pp
F. H. The Efficiency of Nonmagnetic 907-916, Jul 1967.
Shields on Control and Communication
Cable. I E E E T r a n s a c t i o n s on Power [B161 GILLIES, D. A., and ROGERS, E. J.
Apparatus and Systems, vol PAS-89, pp 1091- Shunt Capacitor Switching EM1 Voltages,
1099,1970. Their Reduction i n Bonneville Power
Administration Substations. IEEE
[B8] COMSA, R. P., and LUKE, Y. M. Yu. Transactions on Power Apparatus a n d
Transient Electrostatic Induction by EHV Systems, vol PAS-93, pp 1849-1860, Nov/Dec
Transmission Lines. IEEE Transactions on 1974.
Power Apparatus and Systems, vol PAS-88, pp
1783-1787, Dec 1969. [B17] GILLIES, D. A,, ROGERS, E. J., and
RAMBERG, H. D. Transient Voltages-High
[B91 DAWES, C. L. Induced Voltage on De- Voltage Capacitor Switching, presented a t the
energized Lines a n d Equipment. Doble 12th Annual Conference f o r Relay
Conference 1969, Sec, 3-101 to 120. Engineers, Texas A&M University, College
Station, Apr 1967.
[BlOI DIETCH, DIENNE, WERY. Progress
Report of Study Committee No. 4 (Protection
a n d Relaying), Appendix I1 Induced [B181 GILLIES, D. A., and ROGERS, E. J.
Interference in Wiring Feeding Protective Induced Transient Voltage Reductions in
Relays, presented a t CIGRE, paper 31-01, Bonneville Power Administration 500 kV
Section 1968. Substation. Paper C 72-522-1, presented at the
IEEE PES Summer Power Meeting, San
[ B l l l DIETRICH, R. E., RAMBERG, H. C. Francisco, CA, Jul 9-14, 1972.
and BARBER, T. C. BPA Experience with
EM1 Measurement and Shielding in EHV [B191 GOODING, F. H., and SLADE, H. B.
Substations. Proceedings of the American Shielding of Communication Cables. AIEE
Power Conference, vol 32, pp 1054-1061, Apr Transactions (Communication a n d
1970. Electronics), vol 75, pp 378-387, Jul 1955.

[B121 FILLENBERG, R. R., CLEAVELAND, [sa01 IEEE COMMITTEE REPORT, A Guide


G. W., and HARRIS, R. E. Exploration of for t h e P r o t e c t i o n of Wire L i n e
Transients by Switching Capacitors. IEEE Communications Facilities Serving Electric
Transactions on Power Apparatus and Power Stations. IEEE Transactions on Power
Systems, vol PAS-90, pp 250-260, Jan/Feb Apparatus and Systems, vol PAS-85, pp 1065-
1971. 1083, Oct 1966.
[B131 Fire Protection a n d Prevention
Practices Within t h e Electric Utility [Ball HALMAN, T. R., and HARRIS, L. K.
Industry. Edison Electric Institute Insurance Voltage Surges in Relay Control Circuits.
Committee Report of the Fire Protection and AIEE Transactions, p t 2, vol67, pp 1693-1701,
Prevention Task Force, Mar 1960. 1948.

38
ANSI/IEEE
INSTALLATION OF CABLE SYSTEMS IN SUBSTATIONS Std 626-1987

IB221 HAMMERLUND, B. Noise and Noise Transients. Proceedings of t h e American


Rejection Methods i n Control Circuits, Power Conference, vol21, pp 1021-1028,1969.
Particularly for H.V. Power Stations,
Proceedings of the IEEE Electromagnetic [B321 KOTHEIMER, W. C. Theory of
Compatibility Symposium, pp 216-227, J u l Shielding and Grounding of Control Cables
1968. t o Reduce Surges. Pennsylvania Electric
Association, Stroudsburg, PA, Oct 5, 1973.
[B231 HAMPE, G. W. Power System
Transients with Emphasis on Control and [B331 MARTZLOFF, F. D., and HAHN, G. J.
Propagation a t Radio Frequencies, presented S u r g e Voltages i n R e s i d e n t i a l a n d
at the 21st Annual Conference for Protective Industrial Power C i r c u i t s . IEEE
Relay Engineers, Texas A&M University, Transactions on Power Apparatus a n d
College Station, Apr 1968. Systems, vol PAS-89, pp 1049-1056, JuVAug
1970.
[B241 HICKS, R. L. Transient Interference [B341 Methods of Reducing T r a n s i e n t
on Station Control Wiring. Ontario Hydro Overvoltages in Substation Control Cables.
Research Quarterly, 1st Quarter, 1969. British Columbia Hydro a n d Power
Authority, Report NO. 6903, J u n 15,1969.
[B251 HICKS, R. L. Control of Transient
Interference of Power Station Wiring. [B351 MCKENNA, D., and O'SULLIVAN, T.
Ontario Hydro Research Quarterly, vol 22, C. Induced Voltages in Coaxial Cables and
4th Quarter, 1970. Telephone Lines, presented at CIGRE, Paper
36-01, pp 1-10,A u 24,
~ 1970.
[B261 HICKS, R. L., and JONES, D. E.
T r a n s i e n t Voltages on Power Station [B361 MILDNER, R.C., ARENDS C.B., and
Wiring. IEEE Transactions on Power WOODLAND, P.C. T h e S h o r t - c i r c u i t
Apparatus and Systems, vol PAS-90, pp 261- Rating of Thin Metal Tape Cable Shields.
269, Jan/Feb 1971. IEEE Transactions on Power Apparatus and
Systems, vol PAS-87, pp 749-759, Mar 1968.
[B271 AIEE COMMITTEE REPORT,
Insulation Level of Relay a n d Control [B371 PESONEN, A., and KATTELUS, J.,
Circuits. AIEE Transactions, p t 2, vol 68, pp ALATALO, P., a n d GRAND, G. E a r t h
1255-1257,1949. Potential Rise and Telecommunication
Lines, presented at CIGRE, Paper 36-04, pp 1-
21, Aug 24,1970.
[B281 JACZEWSKI, M. arid PILATOWICZ,
A. Interference Between Power and
[B381 Protection Against Transients. Silent
Telecommunication Lines, presented a t
Sentinels (Westinghouse), RPL 71-4, Aug
CIGRE, Paper 36-03, pp 1-8,Aug 24,1970.
1971.
[B291 KOTHEIMER, W. C., Control Circuit [B391 RACKOWSKI e t al. Effect of Switching
Transients in Electric Power Systems, S h u n t Capacitors on Buses Protected by
presented a t the 21st Annual Conference for Linear Coupler Differential Relays. Electric
P r o t e c t i v e E n g i n e e r s , T e x a s A&M Utility Engineering Report No. 59-70,
University, College Station, Apr 22-24, 1968. Westinghouse E l e c t r i c C o r p o r a t i o n ,
Pittsburgh, PA.
[B301 KOTHEIMER, W. C. Control Circuit
Transients. Power Engineering, vol 73, pp [B401 Recommended Good Practice for the
42-45, Jan 1969, and pp 54-56, Feb 1969. Installation of Nonmetallic Jacketed Cables
in Troughs and the Protection of Electrical
[B311 KOTHEIMER, W. C. The Influence of C e n t e r Rooms. F a c t o r y I n s u r a n c e
S t a t i o n Desipn on Control C i r c u i t Association, 9-69-15C.

39
ANSHEEE
Std 5251987 IEEE GUIDE FOR THE DESIGN AND

[B411 RORDEN, 13. L., DILLS, J . M., Protection. General Electric Company GEZ-
GRISCOM, S. B., SKOOGLUND, J. W. and 4919A, Appendix IV and V, Oct 1970.
BECK, E. Investigations of Switching Surges
Caused by 345 kV Disconnecting Switch [B501 Substation Fire Prevention a n d
Operation. AIEE Transactions, (Power Protection. Fire Protection and Prevention
Apparatus and Systems), vol 77, pp 838-844, Task Force, EE1 Insurance Committee, Nov
Oct 1958. 1969.

[B421 RIFENBURG, R. C., Pipe-Line Design [B511 SULLIVAN, R. J . Transient and Solid
for Pipe-Type Feeders, AIEE Transactions State Circuits, presented at the Pennsylvania
(Power Apparatus and Systems) vol 72, pp Electric Association Conference, May 21,
1275-1288, Dec 1953. 1971.

[B43] SONNEMANN, W. I<. Voltage Surges [E621 SUTTON, H. J. Transient Pickup in


in Relay Control Circuits, presented a t the 500 kV Control Circuits. Proceedings of the
13th Annual Conference for Protective Relay American Power Conference, April 1970.
Engineers, Texas A&M University, College
Station, Apr 1960. [B531 SUTTON, H. J. Transients Induced in
Control Cables Located in EHV Substation,
[B44] SONNEMANN, W. K. Transient IEEE Transactions on Power Apparatus and
Voltages in Relay Coiitrol Circuits. AIEE Systems, vol PAS-89, pp 1069-1081, JuVAug
T r a n s a c t i o n s , (Power Apparatus a n d 1970.
Systems), vol80, pp 1155-1162, Feb 1962.
[B541 WILLIAMS, K. L., and LAWTHER,
[B451 SONNEMANN, W. K. Transient M. A. Installing Substation Control Cable.
Voltages in Relay Control Circuits-Part 11, Transmission and Distribution, May 1971.
presented a t the 16th Annual Conference for
Protective Relay Engineers, Texas A&M [B551 WOODLAND, F., Jr. Electrical
University, College Station, Apr 1963. Interference Aspects of Buried Electric Power
and Telephone Lines. IEEE Transactions on
LB461 SONNEMANN, W. K. A Laboratory Power Apparatus and Systems, vol PAS-89, pp
Study of High-Voltage High-Frequency 275-280, Feb 1970.
Transients, presented a t the 18th Annual
Conference for Protective Relay Engineers, [I3561 Ontario Hydro Research Report 74-386-
Texas A&M University, College Station, Apr K. Wiring Practices to Provide Surge
1965. Protection for Solid-state Equipment in

[B471 SONNEMA", W. K., and MARIENI, Transformer Stations, Switching Stations


G. I. A Review of Transients Voltages in and Power House Switchyards.
Control Circuits. Silent Sentinels
(Westinghouse), RPL 67-3, Apr 1973. [B571 HARVEY, S. M., and PONKE, W. J.
Electromagnetic Shielding of a System
[B481 SONNEMA", W. I<., and PELTON, Computer in a 230 kV Substation. Paper F 75
R. J. T r a n s i e n t Voltage Measurement 442-4 presented a t the IEEE PES Summer
Techniques. IEEE Transactions on Power Meeting, San Francisco, CA, J u l 20 to 25,
Apparatus and Systems, vol PAS-87, pp 1173- 1975.
1179,Apr 1968.
[B581 IEEE 83 WMO25-4, Fiber Optic
[B491 Static Relays for Power Systems Applications in Electrical Substations.

40
ANSYIEEE
INSTALLATION OF CABLE SYSTEMS IN SUBSTATIONS Std 525-1987

Appendix
(This Appendix is not a part of ANSYIEEE Std 525-1987, IEEE Guide for the Design and Installation of Cable Systems in
Substations.)

AppendixA
Sample Calculation for Cable Pulling Tension

This Appendix is intended to illustrate the This is a n acceptable fill.


calculations required t o determine cable The jam ratio as discussed in 10.3.1.4 of
pulling tensions in a typical run from a this guide should be calculated next.
nianhole t o a riser pole. The typical duct run Assuming field bending of the conduit,
used for the calculations is shown in Fig Al.
The cable to be used in this example 1.05D
Jam Ratio = -
installation is 3-l/c 750 kcmil triplexed d
aluminum cable with 1/3 concentric neutral.
The completed weight of this cable is 5.375 where
lb/ft and the outside diameter (OD) for each D = conduit inside diameter
conductor is 1.61 in. Plastic conduit suitable d = single conductor cable outside diameter
for direct burial (Type DB) is to be used for
this example installation. 1.05 (5.047)
Jam Ratio = = 3.29
1.61
AL Conduit Fill and Jam Ratio
Jamming cannot occur based on equation
In determining t h e size of c o n d u i t (9) of this guide. Also, where triplexed cable
required, consideration should be given to is used, jamming is not a problem since
conduit fill and jam ratio. Using equation j a m m i n g is t h e wedging of cables in a
(1) of this guide, the % fill is conduit when three cables lay side by side in
2 Cable Area the same plane.
%Fill =
Raceway Area
x 100%
A2. Maximum Allowable Pulling Tension
Using 4 in conduit (with a n internal
diameter of 4.026 in), The maximum allowable pulling tension
for this example cable is calculated by using
equation (2) of this guide.
%Fill = X 100 = 47.98%
( 4.026 )
7r (21 T m a = (0.006)(3)(750000) = 13 500 lb
Since 47.98% exceeds t h e maximum
allowable fill of 40% by ANSVNFPA 70-1987 However, as indicated in 10.3.1.2 of this
U71, the % fill should be calculated for the guide, the maximum tension for two or more
next larger size conduit, 5 in. conductors should not exceed 6000 lb, when
pulling using a pulling eye.
a,(+). A3. Minimum Bending Radius
%Fill = X 100 = 30.5%
The minimum bending r a d i u s in
accordance with ANSVNFPA 70-1987 [171 for
the example cable is 12 times the overall
ANSI/IEEE
Std 526-1987 IEEE GUIDE FOR THE DESIGN AND

RISER
MANHOLE

C D

A-B = 10 ft. Vertical Rise


B - C = go",4 ft. Inside Radius Vertical Curve
C-D = 500 ft
D-E = 45", 12.5 ft. Inside Radius Horizontal Curve
E - F = 100 ft
F-G = 45", 12.5 ft. Inside Radius Horizontal Curve
G-H = 200 ft

Fig A1
Duct Layout for Example Calculations

diameter of the cable. The cabling factor for is calculated using equation (14) of this
three conductors triplexed is 2.155. guide.
Minimum Bending Radius =
(12)(2.155)(1.61) = 41.6 in 1

A4.Pulling Tension =Jqq


The pulling tensions for the example are
calculated using equation (12) for straight 1
r u n s and equation (18) for vertical or
horizontal bends. (5.047 - 1.61)
Pulling from A to H c = 1.13
Since pulling down the vertical section A-B Therefore, assuming a dry cable or duct
and around the curve B-C would require a with a coefficient of friction of 0.5,
negligible tension, the calculations are
started at C. TD = (500)(5.375)(0.5)(1.13) = 1518 lbs
TE = TDeCfe
TD = Lwfc
where
where
6 = Angle of the change in direction produced
by bend in radians.
L = length of straight run, in feet
w = weight of cable, in lbs/ft NOTE: Conversion factor from degrees to radians is 0.01745.
f = coefficient of friction
c = weight correction factor TE = 1518 e(1.13)(0.5)(45)(0.01745)
TE = 1518
The weight correction factor (c) for three TE = 2366 lbs
single cables in a triangular configuration TF = TE + (100)(5.375)(0.5)(1.13)
ANSIAEEE
INSTALLATION OF CABLE SYSTEMS IN SUBSTATIONS Std 626-1987

TF = 2366 + 3 0 4 Pulling from H to A


TF = 2670 lbs
TG = TFeCfe TG = Lwfc
T = 2670 e(l.l3)(0.5)(45)(0.01745) TG = (200) (5.375) (0.5) (1.13)
G
TG = 2670 e0.4437 TG = 607 lbs
TG = 4161 lbs TF = TGeCfe
TH = TG + (200) (5.375) (0.5) (1.13) TF = 607 e(1.13)(0.5)(45)(0.01745)
TH = 4161 + 607 T, = 607 e0.4437
TH = 4768 lbs TF = 946 lbs
TE = TF + (100) 5.375) (0.5 (1.13)
This is within the maximum allowable TE = 946 + 304
tension of 6000 lb. However, the maximum Tp = 1250 Ibs
sidewall pressure of 500 lb/ft should also be Ti = 1250 ecfe
checked. The maximum sidewall pressure TD = 1250 e(1.13)(0.5)(45)(0.01745)
for this pull will occur a t curve F-G and is TD = 1250 eO.4437
calculated using equation (7) of this guide. TD = 1948 Ibs
TC = TD + (500)(5.375)(0.5)(1.13)
T, = 1948 + 1518
T, = 3466 lbs
TB = 3466 ecfe
where TB = 3466 e(1.13)(0.5)(90)(0.01745)
P = sidewall pressure, in lbs/ft of radius TB = 3466 eO.8873
c = weight correction factor TB = 8417 lbs
To = tension out of the bend, in lbs
r = inside radius of bend, in ft This tension exceeds t h e maximum
allowable tension of 6000 lbs. Therefore, a
cable pull from H t o A should not be
(1.13)(4161)
P = permitted. The cable should be pulled from A
(2)(12.5) to H. The let-off reel should be at the riser pole
and the cable should be pulled toward the
P = 188 lbs/ft manhole, in order not t o exceed t h e
maximum allowable pulling tension or
This is acceptable. sidewall pressure.

43

You might also like