160 54-PW1
160 54-PW1
54-PW1 (300)
JOB DATA:
REMARKS:
2
ELEMENTARY DIAGRAM
DWG. 035-15191 (REV. C)
YORK INTERNATIONAL
FORM 160.54-PW1 FORM 160.54-PW1
LD05467
YORK INTERNATIONAL 3 YORK INTERNATIONAL 3A
FORM 160.54-PW1
LD05468
YORK INTERNATIONAL 5
FORM 160.54-PW1
TIMING DIAGRAM
LD05469
** This function is not for all shutdowns. See Operations Manual, Form 160.54-O1.
NOTES:
1. This wiring diagram describes the standard electronic 10. _____________
control scheme for use with an electromechanical starter. 11. Contact rating is 5 Amps resistive @ 120 volts A.C. or
For details of standard modifications, refer to Product 240 volts A.C.
Form 160.54-PW7.
12. Three phase oil pump must be properly phased L1, L2
2. Field wiring to be in accordance with the National Elec- & L3 corresponding to phase sequence A, B & C.
trical Code as well as all other applicable codes and
13. To check motor rotation on initial start-up, install mo-
specifications. See Product Form 160.54-PW4 for field
mentary switch between terminals 24 & 25 (line 41).
wiring connections.
Depress start switch. After approx. 30 seconds, jog mo-
3. Numbers along the left side of diagram are line identifica- tor with momentary switch. When proper rotation is ob-
tion numbers. The numbers along the right side indicate tained, replace momentary switch with jumper. Switch
the line number location of relay contacts. An underlined must have a minimum contact rating of 2 FLA., 10 LRA
contact location signifies a normally closed contact. at 115 Volts A.C.
4. Main control panel Class 1 field wiring terminal connec- 14. Motor overload (CM) is set to trip at 105% FLA. During
tion points are indicated by numbers within a rectangle, momentary power interruption (power fault), contact
i.e. 15 . Main control panel factory wiring terminal con- opens for 1 second.
nection points are indicated by numbers within a triangle,
15. For high and low voltage units, the factory supplied
i.e. 5 . Component terminal markings are indicated by
jumper between 1 & 53 must be removed when
numbers within a circle, i.e. C1 . Numbers adjacent to
electromechanical starter overloads and/or safety de-
circuit lines are the circuit identification numbers.
vices are used. For high voltage (2300-4160) UL and
5. To cycle unit on and off automatically with contacts other CUL approved units only, electromechanical compres-
than those shown, install a cycling device between ter- sor motor starter overloads (normally closed) must be
minals 1 & 13 (line 37) (see note 9). If a cycling device connected between 1 & 53 .
is installed, jumper must be removed between termi-
16. Contact rating is 5 Amps resistive @ 250 Volts A.C. & 30
nals 1 & 13 .
Volts D.C., 2 Amp inductive (.4 PF) @ 250 Volts A.C. & 30
6. Compressor motor starter with starter interlock contacts Volts D.C.
(rated 0.5 to 1.0 amp @ 24 volts A.C.) must be per Form
17. Each 115VAC field-connected inductive load: i.e. relay
160.45-PA5.1. Control panel shall be grounded.
coil, motor starter coil, etc., shall have a transient sup-
7. Units installed in Canada must have a field supplied pressor wired in parallel with its coil, physically located
CSA approved 30 Amp disconnect switch and a 20 Amp at the coil. Spare transient suppressors and control cir-
dual element fuse mounted external to control panel for cuit fuses are supplied in a bag attached to green ground
115 volt control supply. screw in lower left corner of control panel.
8. To stop unit and not permit it to start again, install a stop 18. For units with Flash Miniature Card Software, Version
device between terminals 1 & 8 (Line 33) (see note 9). C.MLM.01.00 through C.MLM.01.03, the condenser
A remote start-stop switch may be connected to termi- water pump should be wired to terminal 164 of TB2
nals 1 , 7 & 8 (Lines 32 & 33) (see note 9). Remote instead of terminal 151, and the wire from terminal 22 of
start-stop switch (Line 32) is operative only in the “re- TB5 to terminal 150 of TB2 shall not be installed. For
mote” operating mode. software version C.MLM.01.04 and higher, the con-
9. Device contact rating to be 5 milliamperes @ 115 volts denser pump connection should be as shown in the
A.C. figure.
YORK INTERNATIONAL 5A
FORM 160.54-PW1
LD05466
LD05466
LD05470
YORK INTERNATIONAL 7
CONNECTION DIAGRAM (Cont’d)
8 YORK INTERNATIONAL
FORM 160.54-PW1
LD05471
YORK INTERNATIONAL 9
WIRING FOR 230V AND 460V UNITS
LD05472
10 YORK INTERNATIONAL
FORM 160.54-PW1
LD05473
YORK INTERNATIONAL 11
DISPLAY INTERFACE BOARD
LD05475
12 YORK INTERNATIONAL
FORM 160.54-PW1
LD05474
YORK INTERNATIONAL 13
14 YORK INTERNATIONAL
FORM 160.54-PW1
YORK INTERNATIONAL 15
Proud Sponsor
of the 2000
U.S. Olympic Team
36USC380
P.O. Box 1592, York, Pennsylvania USA 17405-1592 (717) 771-7890 Subject to change without notice. Printed in USA
Copyright © by York International Corporation 2000 www.york.com ALL RIGHTS RESERVED
Form 160.54-PW1 (300)
Supersedes: 160.54-PW1 (399)