EEL 2043 LO1 Three Phase Circuits
EEL 2043 LO1 Three Phase Circuits
5
Three Phase AC System
6
Three Phase AC System
[Link]
[Link]
7
Three Phase AC System
The waveform of a three-phase ac generator
8
Three Phase AC System
• Three-phase systems have either three or four
conductors.
9
Three Phase AC System
The abc (or positive) phase sequence
10
Three Phase AC System
The acb (or negative) phase sequence
11
Three Phase AC System
• The two basic connections of ac three-phase source
12
Three Phase AC System
13
Three Phase AC System
• Why use 3-phase?
14
Three Phase AC System
• Why use 3-phase?
15
Three Phase AC System
• Why use 3-phase?
The power delivered by a single-phase system pulsates and falls
to zero. The three-phase power never falls to zero. The power
delivered to the load in a three-phase system is the same at any
instant. This produces superior operating characteristics for
three-phase motors.
16
Three Phase AC System
• Why use 3-phase?
17
Three-Phase Systems
• Relationship between the phases in a three-
phase arrangement
18
Three-Phase Systems
• Three-phase arrangements may use either 3
or 4 conductors
19
Three Phase AC System
Ia
Va
Vab
Vac
Vb
Ib
Ic Vbc
20
Star/Delta Connections
21
Two Common Methods Three-phase Connection
phase voltage
22
Star Connection
• The wye, or star, connection is made by
connecting one end of each of the phase
windings together in a common node.
IL I p
24
Star Connection
IL I p IL
Ip Vp
VL
VL 3 V p Ip Ip
IL
VL
IL
25
Star Connection
• Vector sum of typical wye system voltages
26
Phase and Line Voltages
Vab Va Vb
V p 0 V p 120
V p V p ( 0.5 j 0.866)
3V p 30
The line-to-line voltage Vab of
the Y-connected source
Similarly
Vbc 3V p 90
Vca 3V p 210
27
The Y-to-Y Circuit
28
Four - wire
P PA PB PC
29
When ZA = ZB = ZC the load is said to be balanced
30
There is no current in the wire connecting the neutral node of the
source to the neutral node of the load.
P PA PB PC
V V V
V cos( ) V cos( ) V cos( )
Z Z Z
2
V
3 cos( )
Z
31
The Y-to-Y Circuit (3-wire)
32
Y-Y Three - wire We need to solve for VNn
0 I aA I bB I cC
Va VNn Vb VNn Vc VNn
IaA , IbB , and IcC
ZA ZB ZC
Va VNn Vb VNn Vc VNn
0
ZA ZB ZC
V 0 VNn V 120 VNn V 120 VNn
ZA ZB ZC
Solve for VNn
VL VP
37
Delta Connection
IL
VL VP VL Ip
Ip
Ip
Vp
IL
IL
IL 3 IP
38
The -Connected Source and Load
Circulating
( Vab Vbc Vca )
current
I Unacceptable
3.75 A
1
Total resistance around the loop
39
The -Y and Y- Transformation
Z1Z3
ZA
Z1 Z 2 Z 3
Z2 Z3
ZA ZB
ZB
Z1 Z 2 Z 3
ZC
Z1Z 2
ZC
Z1 Z 2 Z3
Z AZ B Z B ZC Z AZC
Z3
Z1
ZB
Z AZ B Z B ZC Z AZC
Z1 Z2 Z2
ZA
Z AZ B Z B Z C Z AZ C
Z3
ZC
40
The Y- Circuits
VAB
I AB
I aA I AB ICA Z3
VBC
I bB I BC I AB where I BC
Z1
I cC ICA I BC VCA
ICA
Z2 41
The Y- Circuits (cont.)
I aA I AB ICA
I cos j sin I cos( 120) j sin( 120)
3I ( 30)
or
IaA 3 I I L 3I p
42
The Balanced Three-Phase Circuits
Z
ZY
3
per-phase equivalent circuit
43
Instantaneous and Average Power
The total average power delivered to the balanced
Y-connected load is
44
Instantaneous and Average Power in Balanced
Three Phase Circuits
The total average power delivered to the balanced -connected load is
47
Three Phase Power
• Single phase power P V I cos
• In a balanced 3 phase system the
total power is equal to three
times the power in any one P 3 VP I P cos
phase
Apparent Power S V I * VA
S2 = P2 + Q2
49
Active and Reactive Power
• For 3-Phase:
50
Active and Reactive Power
• For 3-Phase:
51
Power Measurement
• When using AC, power is determined not only by the r.m.s.
values of the voltage and current, but also by the phase
angle (which determines the power factor)
– consequently, you cannot determine the power
from independent measurements of current and
voltage
52
Power Measurement
• In single-phase systems power is normally measured
using a watt-meter
– measures power directly using a single meter
which effectively multiplies instantaneous
current and voltage
53
Power Measurement
• In three-phase systems we need
to sum the power taken from the
various phases
– in a four-wire system it may be
necessary to use 3 single-phase
watt-meters
– in balanced systems (systems that
take equal power from each phase)
a single wattmeter can be used, its
reading being multiplied by 3 to get
the total power
54
Power Measurement
– In three-wire arrangements
we can deduce the total
power from measurements
using 2 single-phase watt-
meters
– The watt-meters are supplied
by the line current and the
line-to-line voltage.
– The total power is the
algebraic sum of the two
watt-meters reading.
55
Two-Wattmeter Power Measurement
cc = current coil
vc = voltage coil
W1 read
P1 VAB I A cos1
W2 read
P2 VCB I C cos2
P1 P2 VL I L 2cos cos30
P1 P2 VL I L (2sin sin 30)
P1 P2 VL I L 2 cos cos30 3
P1 P2 VL I L ( 2sin sin 30) tan
P1 P2 P1 P2
tan 3 or tan 3
1
P1 P2 P1 P2
57
Power Measurement
– Some wattmeters, such as
those used on switchboards,
are specially designed to give a
direct read out of the 3-phase
power . The Figure shows a
megawatt-range wattmeter
circuit that measures the power
in a generating station. The
current transformers (CT) and
potential transformers (PT) step
down the line currents and
voltages to values compatible
with the instrument rating.
58
Electrodynamic Wattmeter
59
Digital Power Meter VAR Meter
pf Meter
60
VARmeter
– A VARmeter indicates the reactive power in a circuit. It is
built the same way as a wattmeter is, but an internal
circuit shifts the line voltage by 90°before it is applied to
the potential coil.
61
VARmeter
– In 3-phase, 3-wire balanced
circuits, we can calculate the
reactive power from the two
wattmeter readings by simply
multiplying the difference of the
two readings by √3.
– For example, if the two
wattmeters indicate +5950 W and
+2380 W respectively, the reactive
power is (5950 -2380) × √3 = 6176
VAR.
– Note that this method of VAR
measurement is only valid for
balanced 3-phase circuits.
62
Example 1
• A balanced star
connected 3 phase load
of 10Ω per phase is
supplied from a 400V 50
Hz mains supply at unity
power factor
• Calculate the phase
voltage, the line current
and the total power
consumed
63
Example 1
• A balanced star
connected 3 phase load IL I p
of 10Ω per phase is VL 3 V p
supplied from a 400V 50
VL
Hz mains supply at unity VP
power factor 3
• Calculate the phase 400
VP 230.9V
voltage, the line current 3
and the total power
consumed
64
Example 1
• A balanced star
connected 3 phase load IL I p
of 10Ω per phase is
supplied from a 400V 50 V
Hz mains supply at unity I
power factor R
VP
• Calculate the phase IL IP
voltage, the line current RP
and the total power
consumed 230
IL IP 23 A
10 65
Example 1
• A balanced star P 3 VL I L cos
connected 3 phase load
of 10Ω per phase is
supplied from a 400V
50Hz mains supply at
unity power factor
• Calculate the phase P 3 400 23 1 16kW
voltage, the line current
and the total power
consumed
66
Example 2
• A 20 kW 400V balanced
delta connected load has
a power factor of 0.8
• Calculate the line current
and the phase current
67
Example 2
• A 20 kW 400V balanced P 3 VL I L cos
delta connected load has
a power factor of 0.8 P
• Calculate the line current
IL
3 VL cos
and the phase current
20000( w)
IL
3 400 0.8
I L 36 A
68
Example 2
• A 20 kW 400V balanced I L 36 A
delta connected load has Delta connection therefore
a power factor of 0.8
• Calculate the line current IL 3 IP
and the phase current
IL
IP
3
36
IP
3
I P 20.78 A
69
Example 3
• A 3Ph, 60 Hz wye connected
generator generates a line
to-line voltage of 23,900 V.
Calculate
a. The line-to-neutral voltage
b. The voltage induced in the
individual windings
c. The time interval between
the positive peak voltage of
phase A and the positive
peak of phase B
d. The peak value of the line
voltage
70
Example 3
• A 3Ph, 60 Hz wye connected (a) The line-to-neutral voltage is:
generator generates a line
Ep =EL / √3 = 23,900 / √3 = 13,800 V
to-line voltage of 23,900 V.
Calculate
(b) The windings are connected in wye,
a. The line-to-neutral voltage consequently, the voltage induced in
each winding is 13,800 V.
b. The voltage induced in the
individual windings (c) One complete cycle (360°)
c. The time interval between corresponds to 1/60 s. Consequently,
a phase angle of 120° corresponds to
the positive peak voltage of an interval of
phase A and the positive T = 120 / 360 x 1/ 60 = 5.55 ms
peak of phase B
d. The peak value of the line (d) The peak line voltage is:
voltage El(peak) = √2 EL = 23,900 √2 = 33,800 V
71
Example 4
• The generator in the Figure
generates a line voltage of
865 V, and each load
resistor has an impedance
of 50 Ω. Calculate
a. The voltage across each
resistor
b. The current in each resistor
c. The total power output of
the generator
72
Example 4
(a) The voltage across each resistor is:
• The generator in the Figure
generates a line voltage of Ep =EL / √3 = 865 / √3 = 500 V
865 V, and each load
resistor has an impedance (b) The current in each resistor is:
of 50 Ω. Calculate
a. The voltage across each Ip = Ep / R = 500 / 50 = 10 A
resistor
All the line currents are equal to10 A.
b. The current in each resistor
c. The total power output of (c) Power absorbed by each resistor is:
the generator P = Ep Ip = 500 x 10 = 5000 W
74
Example 5
• Three identical impedances are
connected in delta across a 3-
phase, 550 V line. If the line
current is 10 A, calculate the
following:
a. The current in each impedance
b. The value of each impedance
(a) The current in each impedance is:
Iz = 10 / √3 = 5.77 A
Z = E / Iz = 550 / 5.77 = 95 Ω 75
Example 6
• A 3-phase motor, connected
to a 440 V line, draws a line
current of 5 A. If the power
factor of the motor is 80
percent, calculate the
following:
a. The total apparent power
b. The total active power
c. The total reactive power
absorbed by the machine
76
Example 7
• Three identical resistors dissipating
a total power of 3000 W are
connected in wye across a 3-
phase, 550 V line. Calculate:
a. The current in each line
b. The value of each resistor
c. In Figure shown, the phase
sequence of the source is known
to be A-C-B. Draw the phasor
diagram of the line voltages.
77
Example 7
• Three identical resistors
dissipating a total power of 3000
W are connected in wye across a
3-phase, 550 V line. Calculate:
a. The current in each line
b. The value of each resistor
(c) The voltages follow the sequence A-C-B, which is the same as the
sequence AC-CB-BA-AC.... Consequently, the line voltage sequence is
EAC-ECB- EBA and the corresponding phasor diagram is shown. We can
reverse the phase sequence of a 3-phase line by interchanging any two
conductors.
79
Example 8
• In the circuit shown, calculate the
following:
a. The current in each line
b. The voltage across the inductor
terminals
80
Example 8
• In the circuit shown, calculate the
following:
a. The current in each line
b. The voltage across the inductor
terminals
81
Example 9
• A 3-phase, 550 V, 60 Hz line is
connected to three identical
capacitors connected in delta. If
the line current is 22 A, calculate
the capacitance of each
capacitor.
82
Example 9
• A 3-phase, 550 V, 60 Hz line is
connected to three identical
capacitors connected in delta. If
the line current is 22 A, calculate
the capacitance of each
capacitor.
83
Example 10
• A manufacturing plant draws a
total of 415 kVA from a 2400 V
(line-to-line), 3-phase line. If the
plant power factor is 87.5 percent
lagging, calculate:
a. The impedance of the plant, per
phase
b. The phase angle between the line-
to-neutral voltage and the line
current
c. The complete phasor diagram for
the plant
84
Example 10
• A manufacturing plant draws a (a) We assume a wye connection composed
total of 415 kVA from a 2,400 V of three identical impedances Z.
(line-to-line), 3-phase line. If the The voltage per branch is:
plant power factor is 87.5 percent Ep = 2,400 / √3 = 1,386V
lagging, calculate: The current per branch is: Ip = S / (3 Ep)
a. The impedance of the plant, per Ip = 415,000 / (3 x 1,386) = 100 A
phase The impedance per branch is:
b. The phase angle between the line- Z = Ep / Ip = 1,386 / 100 = 13.9 Ω
to-neutral voltage and the line
current (b) The phase angle between the line-to-
c. The complete phasor diagram for neutral voltage (1386 V) and the
the plant corresponding line current (100 A) is
given by:
cos = 0.875 = 29˚
The current in each phase lags 29° behind
the line-to-neutral voltage.
85
Example 11
• A 5000 hp, wye-connected motor is
connected to a 4000 V, 3-phase, 60 Hz
line. A delta-connected capacitor bank
rated at 1800 kvar is also connected to
the line. If the motor produces an output
of 3594 hp at an efficiency of 93% and a
power factor of 90% (lagging), calculate
the following:
a. The active power absorbed by the motor
b. The reactive power absorbed by the motor
c. The reactive power supplied by the
transmission line
d. The apparent power supplied by the
transmission line
e. The transmission line current
f. The motor line current
g. Draw the complete phasor diagram for one
phase 86
Example 11
• A 5000 hp, wye-connected motor is (a) Active power output is:
connected to a 4000 V, 3-phase, 60 Hz P2=3594 hp × 0.746 =2681 kW
line. A delta-connected capacitor bank
Active power input to motor:
rated at 1800 kvar is also connected to
the line. If the motor produces an output Pm = P2 / η = 2681 / 0.93 = 2883 kW
of 3594 hp at an efficiency of 93% and a
power factor of 90% (lagging), calculate (b) Apparent power absorbed by the
the following: motor:
a. The active power absorbed by the motor Sm = Pm / cos = 2883 / 0.90 = 3203 kVA
b. The reactive power absorbed by the
motor Reactive power absorbed by the motor:
c. The reactive power supplied by the Qm = √(Sm 2- Pm 2) = 1395 kvar
transmission line
d. The apparent power supplied by the
transmission line
e. The transmission line current
f. The motor line current
g. Draw the complete phasor diagram for
87
one phase
Example 11
• A 5000 hp, wye-connected motor is (c) Reactive power supplied by the
connected to a 4000 V, 3-phase, 60 Hz capacitor bank: Qc = -1800 kvar
line. A delta-connected capacitor bank Total reactive power absorbed by the load:
rated at 1800 kvar is also connected to
QL = Qc + Qm = -1800 + 1395 = -405 kvar
the line. If the motor produces an output
of 3594 hp at an efficiency of 93% and a
power factor of 90% (lagging), calculate This is an unusual situation because
the following: reactive power is being returned to the
a. The active power absorbed by the motor line. In most cases the capacitor bank
furnishes no more than Qm kilovars of
b. The reactive power absorbed by the
reactive power.
motor
c. The reactive power supplied by the
transmission line (d) Active power supplied by the line is
d. The apparent power supplied by the PL = Pm =2883 kW
transmission line Apparent power supplied by the line is:
e. The transmission line current SL = √(PL 2+ QL 2) = 2911 kVA
f. The motor line current
g. Draw the complete phasor diagram for
88
one phase
Example 11
• A 5000 hp, wye-connected motor is (e) Transmission line current is:
connected to a 4000 V, 3-phase, 60 Hz IL = SL / (EL x √3) = 420 A
line. A delta-connected capacitor bank
rated at 1800 kvar is also connected to
the line. If the motor produces an output (f) Motor line current is:
of 3594 hp at an efficiency of 93% and a Im = Sm / (EL x √3) = 462 A
power factor of 90% (lagging), calculate
the following: (g) The line-to-neutral voltage is
a. The active power absorbed by the motor Ep = 4000/ √3 = 2309V
b. The reactive power absorbed by the Phase angle between the motor current
motor and the line-to-neutral voltage is:
c. The reactive power supplied by the cos = 0.9 = 25.8°
transmission line
(The motor current lags 25.8°behind the
d. The apparent power supplied by the
voltage, as shown in the phasor diagram.)
transmission line
Line current drawn by the capacitor bank is:
e. The transmission line current
Ic = Qc / (EL x √3) = 1800000 / (4000 x √3)
f. The motor line current
= 260 A
g. Draw the complete phasor diagram for
89
one phase
Example 11
• A 5000 hp, wye-connected motor is
connected to a 4000 V, 3-phase, 60 Hz
line. A delta-connected capacitor bank
rated at 1800 kvar is also connected to
the line. If the motor produces an output
of 3594 hp at an efficiency of 93% and a
power factor of 90% (lagging), calculate
the following:
a. The active power absorbed by the motor
b. The reactive power absorbed by the
motor
c. The reactive power supplied by the
transmission line
d. The apparent power supplied by the
transmission line
e. The transmission line current
f. The motor line current
g. Draw the complete phasor diagram for
90
one phase
Example #12
Calculate the total apparent power for three-phase Y-Y connected
balanced system shown if the phase voltage is 110 V, and load
impedance per phase is 50 600 Ω.
Va 1100 Vrms
Vb 110 120 Vrms
Vc 110120 Vrms
91
S 3 V I * 311000 2.2600
726 60 VA0
92
Example #13
Calculate the total apparent power for three-phase 4-wire Y-Y
connected shown in if the phase voltage is 110 V, and load
impedances are: Z A 50 j80
Z B j50
ZC 100 j 25
Va 1100 Vrms
Vb 110 120 Vrms
Vc 110120 Vrms
93
Unbalanced 4-wire
S A I*aA Va 68 j109 VA
S B I Vb j 242 VA
*
bB
SC I*cC Vc 114 j 28 VA
S S A SB SC 182 j379 VA
94
Example #14
Calculate the total apparent power for three-phase 3-wire Y-Y
connected shown if the phase voltage is 110 V, and load
impedances are: Z A 50 j80
Z B j50
ZC 100 j 25
95
(110 120) Z AZC 110120Z AZ B 1100Z B ZC
VNn
Z AZC Z AZ B Z B ZC
56 151 Vrms
Va VNn Vb VNn Vc VNn
IaA , IbB , and IcC
ZA ZB ZC
S S A SB SC 287 j364 VA
96
Example #15
Calculate the total source real power, the total power delivered to
the load, and the total power loss in the transmission line for three-
phase 3-wire Y-Y connected shown in the Figure.
97
Va 220 00
I aA _____
Z Line Z load A (1.5 j 0.315) (100 j 50)
PT 3 Pa ______ watt
98
2
PLoad A I aa Real (Z L A ) _______ watt
99
Example -16 IP = ? IL = ?
220
Va 30 Vrms
3
220
Vb 150 Vrms
3
220
Vc 90 Vrms
3
The -connected load is balanced with Z 1050
VAB
I AB 2250 A rms
VAB Va Vb 2200 Vrms Z
VBC Vb Vc 220 120 Vrms
I BC
VBC
22 70 A rms
VCA Vc Va 220 240 Vrms Z
VCA
ICA 22 190 A rms
The line currents are Z
IaA I AB ICA 22 320, IbB 22 3 100, IcC 22 3 220
100
Example - 17 IP = ?
Va 1100 Vrms
Vb 110 120 Vrms
Vc 110120 Vrms
Z L 10 j5
Z 75 j 225
Z
ZY
3
25 j 75
Va
IaA 1.26 66 A rms
Z L ZY
101
IbB 1.26 186 Arms and IcC 1.26 54 Arms
The voltages in the per-phase equivalent circuit are
102
Example 18 P=?
Va 1100 Vrms
Vb 110 120 Vrms
Vc 110120 Vrms
Z L 10 j5
Z 75 j 225
Va
IaA 1.26 66 A rms
Z L ZY
VAN IaAZY 99.65 Vrms
103
Example 19 P = ?
Z 1045
line-to-line voltage = 220Vrms
220
VA 30
3
The line current
105
Example 20
• A full-load test on a 10 hp, 3-phase motor yields the following
results: P1 = + 5,950 W; P2 = + 2,380 W; the current in each of
the three lines is 10 A; and the line voltage is 600 V. Calculate
the power factor of the motor.
106
Example 21
• When the motor in the previous example runs at no-load, the
line current drops to 3.6 A and the wattmeter readings are P1
= +1295 W; P2 = -845 W.
Calculate the no-load losses and power factor.
107
Example 21
• When the motor in the previous example runs at no-load, the
line current drops to 3.6 A and the wattmeter readings are P1
= +1295 W; P2 = -845 W.
Calculate the no-load losses and power factor.
108