0% found this document useful (0 votes)
86 views2 pages

Fire Water Calculation

The document outlines fire water calculations for the development of a Liquid Import Terminal at Jaigarh Port, India, detailing the fire water demand for simultaneous major fires. It specifies the total cooling water and foam water flow rates, supplementary hose requirements, and the total design fire water flow rate, which amounts to 3136 m³/hr. Additionally, it includes information on fire pump and storage requirements, ensuring adequate fire protection measures are in place.

Uploaded by

raviraj.astun
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
86 views2 pages

Fire Water Calculation

The document outlines fire water calculations for the development of a Liquid Import Terminal at Jaigarh Port, India, detailing the fire water demand for simultaneous major fires. It specifies the total cooling water and foam water flow rates, supplementary hose requirements, and the total design fire water flow rate, which amounts to 3136 m³/hr. Additionally, it includes information on fire pump and storage requirements, ensuring adequate fire protection measures are in place.

Uploaded by

raviraj.astun
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd

FIRE WATER CALCULATION

JSW Jaigarh Port Ltd., Maharashtra, India

Project:
Development of Liquid Import Terminal, Jaigarh Port Ltd., Maharashtra, India

Document Name: Fire Water Calculations

Document No.: LAS-118-DFS-02

Project Stakeholders
Role Details

Owner JSW Jaigarh Port Ltd., Ratnagiri, MH

EPC Contractor Ganesh Benzoplast Limited, Infrastructure


Division, Mumbai

Engineering Consultant LAS Engineers & Consultants Pvt. Ltd., Navi


Mumbai - 400705

Revision History:
Rev. Date Prepared By Checked By Description

R0 08.04.2025 Raviraj SLT Issued for


Review

Fire Water Demand for Two Major Fires Simultaneously


(For locations with aggregate storage capacity > 30,000 KL as per OISD 117)

1. Floating Roof Tank Protection


Data:
- Total Storage Capacity: 21,980 m³
- No. of Tanks: 5
- Capacity per Tank: 4,396 m³
- Tank Diameter: 20 m
- Tank Height: 14 m

Cooling Water Flow Rate


Tank on fire (T1103): 159 m³/hr
Tanks within (R + 30 m): 475 m³/hr
Tank beyond (R + 30 m): 53 m³/hr
Total Cooling Water: 687 m³/hr

Foam Water Flow Rate


Rim Seal Area = 48.27 m²
Foam Solution Rate @ 12 lpm/m² = 34 m³/hr

Supplementary Hose Requirement


Hydrant Streams: 144 m³/hr
Monitor Streams (HVLR): 456 m³/hr
Total Supplementary: 600 m³/hr

Total Floating Roof Tank Requirement


687 + 34 + 600 = 1321 m³/hr

Total Design Fire Water Flow Rate


Design Case (Two Major Fires Simultaneously): 1321 + 1815 = 3136 m³/hr

Fire Water Storage Requirement


Storage Requirement (4 hours): 4 x 4176 = 16,704 m³

Tank Storage Provided


Gross Capacity: 17,462 m³
Working Capacity: 16,818 m³

Fire Pump Details


Main Fire Pumps: 5 Nos @ 840 m³/hr each
Standby Fire Pumps: 2 Nos @ 840 m³/hr each
Total: 7 pumps

Jockey Pump Details


No. of Jockey Pumps: 2 Nos (1W + 1S)
Capacity: 210 m³/hr (5% aggregate capacity)

Prepared by:
LAS Engineers & Consultants Pvt. Ltd.