Example of General Layout Firewater Network
Firewater How to determine
Pumps total firewater demand,
capacity +- 3.000
m3/hr foam needed, and fire
pump capacity for
this plot plan area?
LPG storage
tank with Floating roof
diameter +- storage tank
25m with diameter
+- 88m Let’s calculate
Process area with
firewater demand for
Fixed roof storage tank 2
stacked equipment with diameter +- 50m this area!
Case Study #1 – Floating Roof Storage Tank on Fire
4
Case Study #1 – Calculation Result
5
Case Study #1 – Calculation Result
6
Case Study #2 – Fixed Roof Storage Tank on Fire
Foam demand for fire fighting of 37-T-101 IFO/MFO (tank on fire) Cone Roof
Tank surface area (top), (0.25ꙥD^2) = 2563.46 m2
Foam application rate (water +foam), = 10.50 LPM/m2
Include wastage factor
Total application rate (water +foam) = 26916.30 LPM
= 1614.98 m3/hr
= 7110.48 GPM
Foam concentrate rate = 3 (w/w)%
Foam application time = 65 min
9
Case Study #3 – Pressurized Storage Tank on Fire
10
Case Study #3 – Calculation Result
11
Case Study #4 – Process Area on Fire
15 m
12
Case Study #4 – Calculation Result
Calculation firewater demand for process area
area Flow
Dia Height App rate Flow
No Equipment within 15 m radius 2
water Spray
(m) (m) (m ) (lpm/m2) (LPM)
(lpm)
1 11C1 Crude Splitter (Replace Top Section 5.80 12.00 218.54 10.2 2,229.15
2 11C3 HEAVY GASOIL DRIER 1.20 5.74 23.89 10.20 243.67
3 11C4 LIGHT GASOIL STRIPPER (NEW TRAYS) 1.40 5.02 25.15 10.20 256.48
4 11C5 LIGHT GASOIL DRIER 1.40 5.50 27.23 10.20 277.78
5 11C2 HEAVY GASOIL STRIPPER (NEW) 1.60 6.90 38.68 10.20 394.58
6 11V9 CAUSTIC MAKE-UP PIT 1.00 3.00 10.99 10.20 112.10
7 11E16A EJECTOR SET CONDENSERS 1.00 2.00 7.85 10.20 80.07
8 11E16B EJECTOR SET CONDENSERS 1.00 2.00 7.85 10.20 80.07
9 11E16C EJECTOR SET PRECONDENSER 1.00 2.00 7.85 10.20 80.07
10 11E50 CRUDE SPLITTER OVERHEAD CONDENSER 1.00 2.00 7.85 10.20 80.07
11 11P4A LONG RESIDUE PUMP 2.00 20.40 40.80
12 11P4B LONG RESIDUE PUMP 2.00 20.40 40.80
13 11P3 UPPER CIRC. REFLUX PUMP 2.00 20.40 40.80
14 11P9A STABILIZER REFLUX PUMP 2.00 20.40 40.80
15 11P9B STABILIZER REFLUX PUMP 2.00 20.40 40.80
16 11P2A LOWER CIRC. REFLUX PUMP 2.00 20.40 40.80
17 11P2B LOWER CIRC. REFLUX PUMP 2.00 20.40 40.80
18 11P2C LOWER CIRC. REFLUX PUMP 2.00 20.40 40.80
19 12P1A NAPHTHA FEED PUMP 2.00 20.40 40.80
20 12P1B NAPHTHA FEED PUMP 2.00 20.40 40.80
21 12P1 NAPHTHA FEED PUMP 2.00 20.40 40.80
22 11P56 2.00 20.40 40.80
23 11P13A OIL SLOPS PUMP 2.00 20.40 40.80
24 11P13B OIL SLOPS PUMP 2.00 20.40 40.80
25 11P12 SOUR WATER PUMP 2.00 20.40 40.80
26 11P5HEAVY GASOIL PUMP (REPLACE) 2.00 20.40 40.80
27 11P6A LIGHT GASOIL PUMP (REPLACE IMPELLER) 2.00 20.40 40.80
28 11P18A 2.00 20.40 40.80
29 11P18B 2.00 20.40 40.80
Total Flowrate (LPM) 3,834.04 775.20 13
Case Study #4 – Calculation Result
Calculation firewater demand for process area
Flowrate water spray
system = 775.20 LPM = 46.51 m3/hr = 204.78 GPM
Flowrate using hydrant or
monitor = 3,834.04 LPM = 230.04 m3/hr = 1,012.84 GPM
Fire Water Demand:
14
Case #5 - Offshore Production Platform Firewater Demand
South Elevation
The required capacity of firewater demand will be the single largest fire area. In determining the
single largest fire area, the limitations of the area may be based on fire divisions (DNV-OS-D301, para 4.1.1)
15
Case #5 - Offshore Production Platform Firewater Demand
Monitor = NA
Deluge System = 1073.03 GPM
Supplemental
hose = 500.00 GPM additional by 2 supplemental hose @250gpm
Total Fire
Water Demand = 1,573.03 GPM
= 5,954.62 LPM
= 357.28 m3/hr
17
Evaluation
Summary Firewater demand for refinary unit
FireWater Demand (m3/hr)
Foam needed
Cooling Fighting (foam (m3)
(defensive) system)
Floating Roof Storage Tank 2,706.05 3,384.29 113.39
Fixed Roof Storage Tank 2,301.94 1,566.53 52.49
Pressurized Storage Tank 2,744.14 0 0
Process Area 443.98
• Site condition
Fire Pump Maximum Demand Total Capacity Diesel Electric Status
No
Area GPM m3/hr m3/hr m3/hr m3/hr (Min 50% Diesel) (n+1) phylosophy
1 Refinery 11,914 2,706 3,080 1,880 1,200 Comply Not comply
2 RFCCU 10,488 2,382 2,180 1,460 720 Comply Not comply
3 New Plant 38 8,313 1,888 2,272 568 1,704 Not comply Not comply 18
Line Sizing for firewater network
• The maximum velocity of firewater should not exceed 4.6 m/s (15 fps) <NFPA 20,
table 4.26a>. The following table is simple guidance for selection of firewater line
sizing.
Diameter Flowrate
(in) LPM GPM m3/hr
6 5,001.52 1,321.25 300.09
8 8,891.60 2,348.89 533.50
10 13,893.12 3,670.15 833.59
12 20,006.10 5,285.01 1,200.37
14 27,230.52 7,193.49 1,633.83
16 35,566.39 9,395.57 2,133.98
18 45,013.71 11,891.27 2,700.82
20 55,572.49 14,680.58 3,334.35
22 67,242.71 17,763.51 4,034.56
24 80,024.38 21,140.04 4,801.46
26 93,917.50 24,810.19 5,635.05
28 108,922.07 28,773.94 6,535.32
30 125,038.10 33,031.31 7,502.29
19
Hydraulic Simulation Result for Floating Roof T101/102/103
T101/2/3
More than
15 fps
20