DAEP LOD MATRIX - TABLE 2 - R05 - May 2018 eLOD 100 iLOD 100 eLOD 200 iLOD 200

eLOD 100 iLOD 100 eLOD 200 iLOD 200 eLOD 300 iLOD 300 eLOD 400 iLOD 400 eLOD 500 iLOD 500

Model Element by CSI UniFormat II classification

A SUBSTRUCTURE

Generic elements (walls, slab, columns) to • Non geometrical information is not attached • All structural and architectural elements to • General information describing material and • Composition of element layers to be modeled • Precise information element properties are • Shop drawing and fabrication phase. • All information included on iLOD 400 stage is • As-Built phase. • All information included on iLOD 500 stage
be modeled with assumed dimensions. to the element during the design process. be modeled with all geometrical constraints technical information are attached. and defined. assigned: material type, color, U-value, fire • Elements are represented as a specific updated to follow the main contractor • Elements have accurate quantities, size, is updated to follow the main contractor
A1010 Standard foundations
• Certain automatically generated information assigned. • Concrete grade, reinforcement rate/ratio, steel • All openings are modeled as per coordination rating, and trade related classification. system, have accurate quantities, size, shape, procurement feedback. shape, location, orientation and installation procurement feedback.
may exist if already embedded in the element strength (and similar) are attached to the requirements. • Concrete grade, reinforcement rate/ratio, location and orientation , verified by the • Information about status of subcontractor verified by the main contractor and • Asset Management Information (O&M) to
properties. geometry, with exception to precast elements. steel strength (and similar) are attached to the main contractor. (appointed, pending, nominated) and approved as per site conditions. be linked and referenced to the model
A10 Foundations A1020 Special foundations geometry. • Required fabrication, assembly, detailing subcontractor name to be included. elements.
*Technical specifications to be linked or and installation. Required fabrication, • All information for fabrication, assembly,
referenced to the model objects. assembly, detailing and installation are detailing and installation to be included.
coordinated. • Data related to the construction program to
A1030 Slab on grade be included.

• Volume of excavation to be defined. • General information describing material and • Precise dimensions allowing to issue tender • Type of modelled elements to be defined.
technical information are attached, as applicable. documents. • Properties and technical specification are
• Material to be defined, as applicable. attached , as applicable.
• Soil type data attached • The technical specification to be referenced
• Approximate volume of excavation to be and be accessible as a link to an external data
A2010 Basement excavation N/A N/A provided. base.
• Net Volume of excavation to be provided.

Generic elements (walls, slab, columns) to • Non geometrical information is not attached • All structural and architectural walls to be • General information describing material and • All openings are modelled considering • Precise information element properties are
A20 Basement construction be modeled with assumed dimensions. to the element during the design process. modeled with all geometrical constraints technical information are attached, type mark for coordination requirements. assigned: material type, color, U-value, fire
• Certain automatically generated information assigned. walls, fire rating, thermal parameters (U). rating, and trade related classification.
to exist if already embedded in the element • Composition of element layers to be • Concrete grade, reinforcement rate/ratio,
properties. defined. steel strength (and similar) are attached to the
geometry. With exception to precast elements.
• Reference to specification and regulations.
A2020 Basement walls-Any wall exposed to soil on one side • Waterproofing protection is indicated per
element.

B SHELL

Generic elements (floor, roof, columns) to be • Non geometrical information is not attached •All structural and architectural elements to • General information describing material and •All openings are modelled to consider • Precise information element properties are • Shop drawing and fabrication phase. • All information included on iLOD 400 stage is • As-Built phase. • All information included on iLOD 500 stage
Floor construction
B1010 modeled with assumed dimensions. to the element during the design process. have all geometrical constraints assigned. technical information are attached. coordination requirements. assigned: material type, color, U-value, fire • Elements are represented as a specific updated to follow the main contractor • Elements have accurate quantities, size, is updated to follow the main contractor
• Certain automatically generated information •Composition of element layers to be defined • Concrete grade, reinforcement rate, steel •Precise dimensions are required to issue rating ,fire proofing and corrosion protection system, have accurate quantities, size, shape, procurement feedback. shape, location, orientation and installation procurement feedback.
to exist if already embedded in the element •Openings to have a defined outline. strength (and similar) are attached to the tender documents. and trade related classification. location and orientation , verified by the • Information about status of subcontractor verified by the main contractor and • Asset Management Information (O&M) to
B10 Superstructure
properties. •Steel connection detailing not required. geometry . • Joints of panels or tiles to be addressed • The technical specification to be referenced main contractor. (appointed, pending, nominated) and approved as per site conditions. be linked and referenced to the model
B1020 Roof construction
•All support systems to be addressed in the and be accessible as a link to an external data • Required fabrication, assembly, detailing subcontractor name to be included. elements.
model. For example; steel framing of metal base. and installation. Required fabrication, • All information for fabrication, assembly,
panels to be models as layers having proper • Insulation is part of the element composition assembly, detailing and installation are detailing and installation to be included.
•Generic elements (walls, windows, doors) • Non geometrical information is not attached • All structural and architectural elements to • General information describing material and depth. Modeling the steel framing to be where applicable based on design and project coordinated. • Data related to the construction program to
B2010 Exterior walls to be modeled with assumed dimensions. to the element during the design process. be modelled with all geometrical constraints technical information are attached, type mark for included in case of spatial coordination master specs. be included.
•Type of wall to be specified as a curtain • Certain automatically generated information assigned. walls, fire rating, thermal parameters (U). requirements. • Fireproofing is added as a shared parameter
B2020 Exterior windows wall or generic Arch/Structural wall. to exist if already embedded in the element • Composition of wall layers to be defined •Model to allow for quantification of materials where applicable based on design and project
properties. • If the Façade Secondary Steel support is by type. For example; stone type or colors in master specs.
required, to be included in the depth of wall the facade pattern. • Façade secondary steel support will be
cladding layer. •Secondary steel support not being typical modeled with no connection details.
B20 Exterior enclosure • All walls with studs are modelled as framing to be represented in the model. Major
eLOD200 dedicating 1 layer for stud inside framing elements such as studs, tracks, bracing,
B2030 Exterior doors wall element sheathing or wall boards are modeled.
All exterior walls opening of doors and •All walls with studs are modelled as eLOD 300
windows include required lintels. dedicating 1 layer for stud with exact thickness
inside wall element. No stud details are to be
modelled.
•Roof finishes to be modelled as eLOD 300 at
Generic roof elements to be modeled with • Non geometrical information is not attached •Composition of roof layers to be defined. • General information describing material and FD stage as 1 element with exact thickness and
B3010 Roof coverings assumed dimensions. to the element during the design process. •Openings to have a defined outline. technical information are attached, type mark, fire slope but exact details (corrugated roofing, roof
• Certain automatically generated information rating, thermal parameters (U). fixation etc.) are not modelled.
to exist if already embedded in the element
NA
properties.
B30 Roofing

B3020 Roof openings


DAEP LOD MATRIX - TABLE 2 - R05 - May 2018 eLOD 100 iLOD 100 eLOD 200 iLOD 200 eLOD 300 iLOD 300 eLOD 400 iLOD 400 eLOD 500 iLOD 500

Model Element by CSI UniFormat II classification


C INTERIORS

• Generic elements (walls, windows, doors) • Non geometrical information is not attached •All structural and architectural elements to • General information describing material and • Major framing elements such as studs, tracks, • Precise information element properties are • Shop drawing and fabrication phase. • All information included on iLOD 400 stage is • As-Built phase. • All information included on iLOD 500 stage
to be modeled with assumed dimensions. to the element during the design process. have all geometrical constraints assigned. technical information are attached. Concrete bracing, sheathing or wall boards are modeled. assigned: material type, color, U-value, fire • Elements are represented as a specific updated to follow the main contractor • Elements have accurate quantities, size, is updated to follow the main contractor
C1010 Partitions • All doors are modelled as eLOD 100 • Certain automatically generated information •Composition of wall layers to be defined. grade, reinforcement rate, steel strength (and • Walls modeled as exact layer compositions. rating, fire proofing and corrosion protection system, have accurate quantities, size, shape, procurement feedback. shape, location, orientation and installation procurement feedback.
generic. to exist if already embedded in the element •All walls with studs are modelled as eLOD similar) are included. • All openings are modeled as per coordination and trade related classification. location and orientation , verified by the • Information about status of subcontractor verified by the main contractor and • Information about subcontractor to be
properties. 200 dedicating 1 layer for stud inside wall • Typical information describing door hardware to requirements. • Technical Specification to be referenced and main contractor. (appointed, pending, nominated) and approved as per site conditions. included.
element be included. • Precise dimensions to allow to issue Tender be accessible as a link to an external data base. • Required fabrication, assembly, detailing subcontractor name to be included. • Building Operation (FM) Information, such
•Elements defined by suppliers to have documents. • Door Hardware set to be provided as and installation. Required fabrication, • All information for fabrication, assembly, as manuals or maintenance schedules to be
approximate dimensions. • Joints of panels or tiles to be addressed. detailed information. assembly, detailing and installation are detailing and installation to be included. attached or linked to the model.
•Door transoms are modelled with • All walls with studs are modelled as eLOD 300 coordinated. • Data related to the construction program to
approximate dimensions. dedicating 1 layer for stud with exact thickness be included.
inside wall element. • Hardware set Number to be defined
• Elements defined by suppliers are modeled
with approximate dimensions.
C1020 Interior doors • Interior glazing to be modelled with exact
dimensions.
• Door transoms to be modelled with exact
dimensions.

•All Fittings modeled as approximate • All Fittings modeled as correct geometry


C10 Interior construction
geometry allowing for quantification. allowing for quantification and coordination.
C1030 Fittings

• Zones of special support systems to be • Non geometrical information is not attached •Approximate geometry of elements is • General information describing material and • Special support systems to be modeled as
clearly indicated in the model by to the element during the design process modeled up to level allowing for coordination technical specifications are attached. exact geometries of structural elements. No
approximate 3D volumes. • Certain automatically generated information with other trades and quantification. connections modeled.
to exist if already embedded in the element •Major structural elements to have all • The geometry of special support systems
properties. geometrical constraints assigned in must allow for material quantification and
accordance to design scope. follow general modeling requirements as for
structural elements carrying similar load.
•Project specific decision to be taken to
indicate originator of the special support
systems in the model.
C1040 Special support systems–additional structure (EP) •Examples of special support systems are: large
ceiling bulkhead support, heavy MEP terminals
or equipment, fixings of non-standard wall
mounted objects, non-standard opening lintels.
This list of examples is not exhaustive.

• Generic Stair elements to be modeled with • Non geometrical information is not attached • Separation of stair structural elements and • General information describing material and •Precise dimensions to allow to issue Tender
C2010 Stair construction assumed dimensions. to the element during the design process finishes to be defined. technical information are attached. documents.
• The stairs to be associated to related levels • Certain automatically generated information • Position, height and type of balustrade to be • Concrete grade, reinforcement rate/ratio, steel •Stair types to be modeled to allow for cost
and have proper formulas assigned. to exist if already embedded in the element defined. strength (and similar) are attached to the estimation of all structural components and
properties. geometry. finishes.
•Joints of panels or tiles shall be addressed.
• All step details and steel/concrete
C20 Stairs connections not requiring additional
geometrical space will not be modeled.
C2020 Stair finishes

• Generic elements (walls, ceiling, floor) to • Non geometrical information is not attached •Modeled as part of composite elements. • General information describing material and •Finishes are modeled separately from
C3010 Wall finishes be modeled with assumed dimensions. to the element during the design process. •In case of non generic geometry, additional technical information are attached and fire rating. structural elements.
• Modeling of finishes to be avoided • Certain automatically generated information modeling in place, or object families to be •Tiles of different color or materials are
to exist if already embedded in the element added. modeled separately for quantity take-off.
C3020 Floor finishes properties. • Information about not modeled finishes •The precise line pattern as design intent and
C30 Interior finishes shall be provided in room element. for construction use is shown.
•Precise dimensions to allow to issue Tender
documents.
• Joints of panels or tiles to be addressed.
C3030 Ceiling finishes
DAEP LOD MATRIX - TABLE 2 - R05 - May 2018 eLOD 100 iLOD 100 eLOD 200 iLOD 200 eLOD 300 iLOD 300 eLOD 400 iLOD 400 eLOD 500 iLOD 500

Model Element by CSI UniFormat II classification


D SERVICES

Generic architectural families to be used. • Non geometrical information is not attached Architectural elements allowing for spatial •Type of system to be clearly defined. •Geometries of elements are exact. • Precise information element properties are • Shop drawing and fabrication phase. • All information included on iLOD 400 stage is • As built Phase. • All information included on iLOD 500 stage
D1010 Elevators and lifts Typical families for airport systems to be to the element during the design process. coordination with architectural, structural and •Element protection to be defined: fire rating and •Relationships with structural systems are assigned: material type, color, fire rating, fire • Elements are represented as a specific updated to follow the main contractor • Elements have accurate quantities, size, is updated to follow the main contractor
developed – Baggage handling systems, • Certain automatically generated information MEP elements. thermal insulation. defined. proofing and corrosion protection . system, have accurate quantities, size, shape, procurement feedback. shape, location and orientation verified by procurement feedback.
cargo handling systems to exist if already embedded in the element Static envelopes representation for space • Dependency from MEP systems to be defined. •Connections to related MEP systems are • The specification to be referenced and be location and orientation , verified by the • Information about status of subcontractor the main contractor and approved as per • Information about subcontractor to be
D1020 Escalators and moving walks properties. allocation are modeled. indicated. accessible as a link to an external data base. main contractor. (appointed, pending, nominated) and site conditions. included.
D10 Conveying
•Modelled to correct shape and overall • Required fabrication, assembly, detailing subcontractor name to be included.• All • Required fabrication, assembly, detailing • Building Operation (FM) Information, such
dimensions based on assumed model, but not and installation. Required fabrication, information for fabrication, assembly, detailing and installation. Required fabrication, as manuals or maintenance schedules to be
necessarily specific to the exact final assembly, detailing and installation are and installation. assembly, and detailing are coordinated attached or linked to the model.
D1030 Other conveying systems manufacturers dimensions. coordinated. • Data related to the construction program to
be included.
Generic elements (pipes, accessories, • Non geometrical information is not attached • Position of fixtures and pipes to be • Type of system to be clearly defined. • Geometries of elements are exact. •Technical data allows for technical
D2010 Plumbing fixtures fittings) to be used with assumed dimensions to the element during the design process. coordinated with architectural scope. • Approximate flow and head for pumps to be • System Elements allowing for spatial verification of the systems.
to satisfy single layout diagram • Certain automatically generated information • System elements allowing for spatial specified. coordination with architectural, structural and • Precise information, element properties are
D2020 Domestic water distribution requirements. to exist if already embedded in the element coordination with architectural, structural and MEP elements. assigned: material type, color, fire rating and
properties. MEP elements will be modeled, without • Instrumentation and Controls modeling trade related classification.
accessories, to approximate size. limited to equipment and devices without • Technical specifications to be linked or
D2030 Sanitary waste System Elements will include: routing or wiring. referenced to the model objects.
• Mechanical Equipment in mechanical rooms • Piping for gravity networks will be modeled • Slope for gravity pipes is indicated.
D2040 Rainwater drainage modeled to approximate size with estimated with correct size, level *Pipes level is specified
clearance. • Piping for gravity networks will be modeled
• EWH equipment in toilets is modeled to with sloping where pipes are larger than
approximate size 150mm and/or pipes running more than 150m.
• Sump pits and submersible pumps are • Cable trays, cable ducts or special conduits
modeled to approximate size when their size exceeds 50mm, electrical
• Domestic water and grey water distribution equipment, devices and fixtures to be modeled
piping, where their sizes is equal or exceeding to allow for spatial coordination with
150mm, are modeled from mechanical rooms architectural, structural and other MEP
through shafts and up to wet areas. elements.
• Waste, raindrain, soil and vent piping with • All elements are connected in consistent
corresponding cleanouts, where their sizes is systems.
equal or exceeding 150mm, are modeled from • Proper connection with external utilities.
served zones through shafts up to grey water • Equipment space reservations and clearances
treatment plant and/or external network. to be include
• Sloping of main drainages pipes connected
to external network will be modeled.

D20 Plumbing

D2090 Other plumbing systems

Generic elements (ducts, accessories, • Non geometrical information is not attached • System elements to allow for spatial •Type of system to be clearly defined.
D3010 Energy supply
equipment, terminals) to be modeled with to the element during the design process. coordination with architectural, structural and •Element protection to be defined: fire rating and
assumed dimensions to satisfy single layout • Certain automatically generated information MEP elements to be modeled, without thermal insulation.
D3020 Heat generating systems diagram requirements. to exist if already embedded in the element accessories, to approximate size with
• BMS: Main controllers (BACnet/IP rooters properties. estimated clearance.
D3030 Cooling generating systems or NAC's and DDC panels in plant rooms System Elements will include
• AHUs, pumps, fans
D3040 Distribution systems • Chilled water and condensate drain piping
where their sizes are equal or exceeding
D3050 Terminal and package units 150mm to allow for spatial coordination with
architect and MEP element
D3060 Controls and instrumentation • Main ducts and pipes runs are modeled
from mechanical rooms/shafts up to the zone
served.
D3070 Systems testing and balancing-Not relevant at design stage
• Position of air terminals to be coordinated
with architectural scope. Modeling of ceiling
D30 HVAC
devices to follow agreed scope of work.
• BMS: System elements including unitary
controllers (for FCU's, VAV's and other
terminal devices), wall mounted space
thermostats (for FCU's & VAV's), wall
mounted CO2 sensors (for density occupied
spaces) and wall mounted space temperature
D3090 Other HVAC systems & equipment sensors (for electrical, telecom, battery, UPS
rooms), modeled to approximate size with
estimated clearance.
DAEP LOD MATRIX - TABLE 2 - R05 - May 2018 eLOD 100 iLOD 100 eLOD 200 iLOD 200 eLOD 300 iLOD 300 eLOD 400 iLOD 400 eLOD 500 iLOD 500

Generic elements (pipes, accessories, • Non geometrical information is not attached • System elements to allow for spatial •Type of system to be clearly defined.
D4010 Model
Sprinklers Element by CSI UniFormat II classification fittings) to be modeled with assumed to the element during the design process. coordination with architectural, structural and •Element protection to be defined: fire rating and
D4020 Standpipes dimensions to satisfy single layout diagram • Certain automatically generated information MEP elements. thermal insulation.
requirements. Cylinders for clear agent to exist if already embedded in the element • Position of sprinklers to be coordinated with
D4030 Fire protection specialties systems are modeled as generic elements for properties. architectural scope as per agreed scope of
space reservation. work.
Cylinders for Clean Agent system are • Main Fire Protection equipment is modeled
modeled as generic elements for space with approximate sizes with estimated
reservation clearances
D40 Fire protection • Main Fire Pipes feeders will be modeled
with approximate sizes.
• Fire pipes will be modelled to approximate
D4090 Other fire protection systems sizes in shafts, pumps rooms and main runs
from pump room to ZVs, preaction, deluges

Generic elements to be modeled with • Non geometrical information is not attached •Cable trays, cable ducts or special conduits •Type of system to be clearly defined.
D5010 Electrical service and distribution
assumed dimensions to satisfy single layout to the element during the design process. when their size exceeds 150mm, electrical •Element protection to be defined: fire rating and
diagram requirements. • Certain automatically generated information equipment, devices and fixtures to be thermal insulation.
D5020 Lighting and branch wiring to exist if already embedded in the element modeled to allow for spatial coordination with
properties. architectural, structural and other MEP
elements.
D5030 Airport Specific, Communication, Security, ELV/IT Systems •Decision has to be clear regarding minimal
size of modeled conduits.
D50 Electrical
• Position of electrical equipment, devices and
fixtures to be coordinated with architectural
scope.
• Equipment space reservations and
D5090 Other electrical systems clearances to be included.

•Zones of special support systems to be • Non geometrical information is not attached •Approximate geometry of elements is • General information describing material and • Special support systems to be modeled as • Precise information element properties are
clearly indicated in the model by to the element during the design process. modeled up to level to allow for coordination technical information is attached. exact geometries of structural elements. No assigned: material type, fire rating, fire
approximate 3D volumes. • Certain automatically generated information with other trades and quantification. connections modeled. proofing and corrosion protection and trade
to exist if already embedded in the element •Major structural elements to have all • The geometry of special support systems to related classification.
properties. geometrical constraints assigned. allow for material quantification and follow • Technical specifications to be linked or
general modeling requirements for structural referenced to the model objects.
elements carrying similar load.
•Project specific decision to be taken to
indicate originator of the special support
D60 - MEP Special support D6010 MEP Special support (EP) systems in the model.
•Examples of special support systems are:
heavy MEP terminals or equipment, unitized
systems and particular complicated and
congested locations. This list of examples is not
exhaustive.

E EQUIPMENT & FURNISHINGS

Generic architectural families to be used. • Non geometrical information is not attached •Schematic object representation to allow for • General information describing material and •Geometries of families are exact •Technical data to allow for functional • Shop drawing and fabrication phase. • All information included on iLOD 400 stage is • As built Phase. • All information included on iLOD 500 stage
E1010 Commercial equipment
Typical families for airport systems to be to the element during the design process. spatial coordination with architectural, technical information are attached, type mark and • System elements allowing for spatial verification of the object. • Elements are represented as a specific updated to follow the main contractor • Elements have accurate quantities, size, is updated to follow the main contractor
developed – security screening systems. • Certain automatically generated information structural and MEP elements. fire rating. coordination with architectural, structural and • Precise information, element properties are system, have accurate quantities, size, shape, procurement feedback. shape, location and orientation verified by procurement feedback.
E1020 Institutional equipment to exist if already embedded in the element •All structural and architectural elements to • Dependency from MEP systems to be defined. MEP elements. assigned: material type, color, fire rating and location and orientation , verified by the • Information about status of subcontractor the main contractor and approved as per • Information about subcontractor to be
E10 Equipment properties. have all geometrical constraints assigned. trade related classification. main contractor. (appointed, pending, nominated) and site conditions. included.
E1030 Vehicular equipment •Relation with other elements to be defined: • Technical specifications to be linked or • Required fabrication, assembly, detailing subcontractor name to be included. • Required fabrication, assembly, detailing • Building Operation (FM) Information, such
host, face based, fixed dimensions or referenced to the model objects. and installation. Required fabrication, • All information for fabrication, assembly, and installation. Required fabrication, as manuals or maintenance schedules to be
E1090 Other equipment proportions . • Dependency from MEP systems to be assembly, detailing and installation are detailing and installation to be included. assembly, and detailing are coordinated. attached or linked to the model.
defined. coordinated. • Data related to the construction program to
Generic Architectural families to be used. • Non geometrical information is not attached
E2010 Fixed furnishings be included.
to the element during the design process
• Certain automatically generated information
E20 Furnishings to exist if already embedded in the element
properties.
E2020 Moveable furnishings

F SPECIAL CONSTRUCTION & DEMOLITION

F1010 Special structures Generic architectural and structural families • Non geometrical information is not attached •Schematic object representation to allow for • General information describing material and • Geometries of elements are exact. • Precise information element properties are • Shop drawing and fabrication phase. • All information included on iLOD 400 stage is • As built Phase. • All information included on iLOD 500 stage
to be used. Typical families for airport to the element during the design process. spatial coordination with architectural, technical information are attached. • Relationships with structural systems are assigned: material type, color, U-value, fire • Elements are represented as a specific updated to follow the main contractor • Elements have accurate quantities, size, is updated to follow the main contractor
F1020 Integrated construction systems to be developed. • Certain automatically generated information structural and MEP elements. • Concrete grade, reinforcement rate, steel defined. rating and trade related classification. system, have accurate quantities, size, shape, procurement feedback. shape, location and orientation verified by procurement feedback.
to exist if already embedded in the element strength (and similar) are included. • Connections to related MEP systems are • The Specification to be referenced or be location and orientation , verified by the • Information about status of subcontractor the main contractor and approved as per • Information about subcontractor to be
F1030 Special construction systems properties. • Structural or MEP systems to be clearly defined. indicated. accessible as a link to an external data base. main contractor. (appointed, pending, nominated) and site conditions. included.
Dependency from MEP systems to be defined. • Required fabrication, assembly, detailing subcontractor name to be included. • Required fabrication, assembly, detailing • Building Operation (FM) Information, such
and installation. Required fabrication, • All information for fabrication, assembly, and installation. Required fabrication, as manuals or maintenance schedules to be
F1040 Special facilities assembly, detailing and installation are detailing and installation to be included. assembly, and detailing are coordinated. attached or linked to the model.
coordinated. • Data related to the construction program to
be included.
• Generic elements to be used with assumed • Non geometrical information is not attached • Generic Elements with approximate • Type of system / network configuration used to • Geometries of elements are exact. • Size of ducts to be provided with specific
dimensions. Representation of the surfaces to the element during the design process. dimensions. be defined • Conduits, cables and wires not to be modeled routing.
is symbolic only and to be limited to 2D • Certain automatically generated information • Conduits, cables and wires not to be • General information describing element if not necessary for coordination and future use • Precise information describing
surfaces located at average terrain level for to exist if already embedded in the element modeled, only Duct-banks (concrete or sand properties and technical specification are attached of the BIM model. element properties and technical specification
the area. properties. encasement) to be modeled. , as applicable. • Duct-banks (concrete or sand encasement) to are attached , as applicable.
• Generic control equipment (for example, • Material to be defined, as applicable. be modeled. • The specification to be referenced or be
RIO cabinets in tunnels) to be modeled for accessible as a link to an external data base.
F10 Special construction spatial coordination. • Material to be defined, as applicable.

F1050 Special controls & instrumentation

Generic architectural and structural families • Non geometrical information is not attached • Schematic object representation to allow for •Type of material with note for potential hazard •Geometries of families are exact. • Precise information describing element
F2010 Building elements demolition
to be used. to the element during the design process. spatial coordination and planning of during demolition work. •Relationships with structural systems are properties and technical specification are
• Certain automatically generated information demolition work methodology. •Structural value Y/N to be clearly defined. defined. attached , as applicable.
to exist if already embedded in the element •Connections to related MEP systems are • The specification reference to be accessible
properties. indicated. as a link to an external data base.
F20 Selective build. Demo
• Note for potential hazard during demolition
F2020 Hazardous components abatement
work to be included.
DAEP LOD MATRIX - TABLE 2 - R05 - May 2018 eLOD 100 iLOD 100 eLOD 200 iLOD 200 eLOD 300 iLOD 300 eLOD 400 iLOD 400 eLOD 500 iLOD 500

Model Element by CSI UniFormat II classification

G BUILDING SITEWORK

• Generic objects to be used. • Non geometrical information is not attached • The method of modeling to allow for initial • General information describing material and • Geometries of elements are exact. • Type of modeled elements to be defined. • Shop drawing and fabrication phase. • All information included on iLOD 400 stage is • As built Phase. • All information included on iLOD 500 stage
G1010 Site clearing • Representation of the surfaces is symbolic to the element during the design process. quantity take-off by CQS technical information are attached, as applicable. • Relationships with structural systems are • Precise information describing element • Elements are represented as a specific updated to follow the main contractor • Elements have accurate quantities, size, is updated to follow the main contractor
only and to be limited to 2D surfaces located • Certain automatically generated information • Surfaces are displayed as 3D surfaces based • Material to be defined, as applicable. defined. properties and technical specification are system, have accurate quantities, size, shape, procurement feedback. shape, location and orientation verified by procurement feedback.
at average terrain level for the area. to exist if already embedded in the element on points manually (total station) measured in • Soil type data attached • Connections/Interfaces with related MEP attached , as applicable. location and orientation , verified by the • Information about status of subcontractor the main contractor and approved as per • Information about subcontractor to be
G1020 Site demolition and relocations properties. the terrain every 10/20m. • Approximate volume of excavation and earth fill systems are indicated. • The specification reference to be accessible main contractor. (appointed, pending, nominated) and site conditions. included.
to be provided if applicable per agreed scope of • Pavement connections and jointing details not as a link to an external data base. • Required fabrication, assembly, detailing subcontractor name to be included. • Required fabrication, assembly, detailing • Building Operation (FM) Information, such
G10 Site preparation work. to be modeled in 3D. • Material to be defined, as applicable. and installation. Required fabrication, • All information for fabrication, assembly, and installation. Required fabrication, as manuals or maintenance schedules to be
• Specific objects to be used. • Volume of excavation and earth fill to be assembly, detailing and installation are detailing and installation to be included. assembly, and detailing are coordinated. attached or linked to the model.
G1030 Site earthwork
provided if applicable as per agreed scope of coordinated. • Data related to the construction program to
work. be included.

G1040 Hazardous waste remediation

G2010 Roadways • Generic objects to be used. Representation • Non geometrical information is not attached The following method of modeling have to • Type of modeled elements to be defined. • Geometries of elements are exact. •Type of modeled elements to be defined.
of the surfaces is symbolic only and to be to the element during the design process. allow for initial quantity take off by CQS:: • Material to be defined, as applicable. • Relationships with structural systems are • Precise information describing element
G2020 Parking lots limited to 2D surfaces located at average • Certain automatically generated information • Generic elements with approximate • General information describing element defined. properties and technical specification are
terrain level for the area. to exist if already embedded in the element dimensions. properties and technical specification are attached • Connections/Interfaces with related MEP attached , as applicable.
properties. • Composite elements to have clarified layers. , as applicable. systems are indicated. • The specification reference to be accessible
G2030 Pedestrian Facilities
• Functional geometry (slopes, dimensions) to • Pavement connections and jointing details not as a link to an external data base.
Bridges : be defined and have reference points to be modeled in 3D. • Material to be defined, as applicable.
• Generic 3D element without upper specified every 10/20m • Specific objects to be used.
G2040 Site development
elevation, box girder voids not to be
G2050 Landscaping modeled, sheets to include all necessary Bridges : Bridges:
details • Approximate elements sizing to be provided. • Precise shape and Size .
G2060 Airfields (EP) • Rebar and expansion joints not to be • Rebars not to be modelled if not necessary for
modeled coordination
• Structural expansion joint voids to be
G20 Site improvements
modelled
G2070 Athletic, Recreational, and Playfield Areas (EP)

Generic elements to be modeled with Generic elements with approximate Specific objects to be used for the rail plinths,
assumed dimensions to satisfy single layout dimensions to be used for the top of running Walkways and the vertical clearance.
G2080 Rails (EP) diagram requirements. surface/ Top of rail, Walkways and the
vertical clearance.

Generic elements to be modeled with Generic elements with approximate Specific objects to be used for the rail plinths,
assumed dimensions to satisfy single layout dimensions to be used for the top of running Walkways and the vertical clearance.
G2090 APM (EP) diagram requirements. surface/ Top of rail, Walkways and the
vertical clearance.

G3010 Water supply & distribution systems • Generic elements (pipes, ducts, Chambers, • Non geometrical information is not attached • System elements to allow for spatial • Type of system to be defined. • Geometries of elements are exact. • Type of system to be defined.
G3020 Sanitary sewer systems Manholes) to be to the element during the design process. coordination with architectural, structural and • If applicable, Element protection to be defined: • System elements allowing for spatial • If applicable, Element protection to be
G3030 Storm sewer systems modeled with assumed dimensions to satisfy • Certain automatically generated information MEP elements with approximate size and fire rating and thermal insulation. coordination with architectural, structural and defined: fire rating and thermal insulation.
G3040 Heating distribution single layout diagram requirements. to exist if already embedded in the element location. • Material to be defined, as applicable. MEP elements. • Material to be defined, as applicable.
G3050 Cooling distribution • Fittings not to be modeled properties. • Position of elements to be coordinated with • General information describing element • Fittings might not be identified as separate • Precise information describing element
G30 Site civil/mech. Utilities G3060 Fuel distribution architectural scope. properties and technical specification are attached element, but network is continuous. properties assigned, as applicable.
• Fittings might not be identified as separate , as applicable. • The specification reference to be accessible
G3070 Treated Sewage Effluent (TSE) (EP)
element, but network is continuous. as a link to an external data base.

G3090 Other civil/mechanical utilities

• Generic elements to be modeled with • Non geometrical information is not attached • Generic elements with approximate • Type of modeled elements to be defined. • Specific objects to be used. • Type and material of modeled elements to
G4010 Electrical distribution assumed dimensions to satisfy single layout to the element during the design process. dimensions. • If applicable, element protection to be defined: • Electrical ducts, conduits, cables and wires be defined.
diagram requirements. • Certain automatically generated information • Electrical ducts, conduits, cables and wires fire rating and thermal insulation. within duct bank not to modeled only Duct • If applicable, element protection to be
• Electrical ducts, conduits, cables and wires to exist if already embedded in the element within duct bank not to be modeled. • Material to be defined, as applicable. banks (concrete or sand encasement) to be defined: fire rating and thermal insulation.
G4020 Site lighting within ducktbank not to be modeled, only properties. • Duct banks (concrete or sand encasement) • General information describing element modeled • Precise information describing element
Duct banks (concrete or sand encasement) to be modeled. properties and technical specification are attached • Specific raceways, electrical equipment to be properties and technical specification are
to be modeled. • Generic raceways, electrical equipment, , as applicable. modeled with defined size , shape, location and attached , as applicable.
• Generic raceways, electrical equipment, electrical structures to be modeled with orientation. • The specification reference to be accessible
G4030 Site communications and security
electrical structures to be modeled as approximate size , shape to allow for spatial • Control equipment for outdoor lighting as a link to an external data base.
generic elements. coordination with transportation, structural including photocells, timers ,and contactors
• Control equipment for outdoor lighting and other utilities. within the feeder pillar not to be modeled , only
including photocells, timers ,and contactors • Control equipment for outdoor lighting feeder pillar cabinet to be modeled.
within the feeder pillar not to be modeled , including photocells, timers, and contactors • High mast head assembly and floodlights to
only feeder pillar cabinet to be modeled. within the feeder pillar not to be modeled , be modeled as generic placeholders.
• High mast head assembly and floodlights only feeder pillar cabinet to be modeled. • Prefabricated substations to be modeled with
G4040 Other electrical utilities to be modeled as generic placeholders. • High mast head assembly and floodlights to defined size and location.
• Prefabricated substations to be added in be modeled as generic placeholders. • Street lighting fixtures to be modeled as
the model as 3D element reflecting outer • Prefabricated substations to be modeled as generic object, along with the arm.
dimensions. 3D volumetric element reflecting • Counterpoise earthing system to be modeled
• Street lighting fixtures to be modeled as aproximate outer dimensions. as generic placeholders.
generic objects, along with the arm. • Street lighting fixtures to be modeled as • Cathodic Protection system to be modeled as
• Counterpoise earthing system to be generic object, along with the arm. a generic placeholder.
modeled as a generic placeholder. • Counterpoise earthling system to be Airfield lighting:
• Cathodic Protection system to be modeled modeled as a generic placeholder. • Airfield Lighting equipment within manholes
G40 Site electrical utilities as a generic placeholder. • Cathodic Protection system to be modeled or bases i.e. "power supply and control cabling
as a generic placeholder. and devices" to be modeled as a generic
Airfield lighting: Airfield lighting: objects.
• Airfield Lighting equipment within • Airfield Lighting equipment within manholes • Airfield Lighting ducts, conduits, cables and
manholes or bases i.e. "power supply and or bases i.e. "power supply and control wires within duct banks not to be modeled, only
control cabling and devices" to be modeled cabling and devices" to be modeled as generic Duct bank to be modeled.
as generic objects. objects. • Approach Lighting Frangible Structures to be
• Airfield Lighting ducts, conduits, cables and • Airfield Lighting ducts, conduits, cables and modeled as typical system objects.
wires within duct banks not to be modeled, wires within duct banks not to be modeled • Elevated approach lights to be modeled as
only Duct bank to be modeled. • Duct bank to be modeled. lights at the appropriate height with an
• Approach Lighting Frangible Structures not • Approach Lighting Frangible Structures to be elevated column for each light.
G4050 Special Airport System (SAS) (EP)
to be modeled. modeled as generic objects.
• Elevated approach lights to be modeled as • Elevated approach lights to be modeled as
lights at the appropriate height with an lights at the appropriate height with an
elevated column for each light. elevated column for each light.

Dynamic envelop of Vehicle allowing for Type of Transportation Vehicle has to be clearly The static envelop to present schematic level Type of Transportation vehicle has to be clearly The static envelop to present schematic level of Type of Transportation vehicle has to be
concept stage design of clearance and proof stated. of the vehicle detailing exceptional stated. General information about design the vehicle detailing exceptional dimensions clearly stated. Precise information about
G8010 Land Transport (EP) of access. dimensions and constrains necessary to requirements that have impact to associated and constrains necessary to coordinate the design requirements that have impact to
The level of accuracy has to be sufficient to coordinate the vehicle model geometry with buildings and infrastructure. For example, general vehicle model geometry with the building or associated buildings and infrastructure. For
present and coordinate: turn and the building or infrastructure. The vehicle mechanical load, MEP connection to building and infrastructure. The vehicle general dimensions, example, mechanical load necessary for
maneuvering clearance and radiuses, general dimensions, access levels, opening infrastructure requirements, safety requirements access levels, opening sizes or other dimensions structural calculation, MEP connection to
clearance of roads, tunnels, taxiways, sizes or other dimensions to link the vehicle have to be provided. to link the vehicle with the building or building and infrastructure requirements
G8020 Aviation Transport (EP) Parking places, aprons and similar. with the building or infrastructure to be If the model is provided by Design and Build infrastructure to be precise. indicating necessary MEP parameters, safety
G80 Transportation vehicles precise. contractor, general reference to type of the actual The kinetic envelope representation to allow requirements have to be provided.
(EP) The kinetic envelope representation to allow unit to be provided. the coordination of disciplines and design check If the model is provided by Design and Build
the coordination of disciplines and design in critical zones of design to be included. contractor, exact reference to type of the
check in critical zones of design to be actual unit to be provided.
included.

G8030 Water Transport (EP)


DAEP LOD MATRIX - TABLE 2 - R05 - May 2018 eLOD 100 iLOD 100 eLOD 200 iLOD 200 eLOD 300 iLOD 300 eLOD 400 iLOD 400 eLOD 500 iLOD 500

• Generic elements to be modeled with • Non geometrical information is not attached • Schematic object representation to allow for • Type of system to be clearly defined. • Geometries of Elements are exact. • Type of system to be clearly defined.
Model Element by CSI UniFormat II classification assumed dimensions to satisfy single layout to the element during the design process. spatial coordination with architectural, • If applicable, element protection to be defined: • Relationships with structural systems are • If applicable, element protection to be
diagram requirements. • Certain automatically generated information structural and MEP elements. fire rating and thermal insulation. defined. defined: fire rating and thermal insulation.
to exist if already embedded in the element • Generic 3D object with approximate size • Material to be defined, as applicable. • Connections to related MEP systems are • Material to be defined
• Generic 3D element (mass concrete, slab properties. and location • General information describing element indicated. • Precise information describing element
and walls openings, shafts and hollow core • Rebar not to be modeled properties and technical specification are attached • Precise shape and Size. properties and technical specification are
G9010 Tunnels voids not to be modeled) , sheets to include • Major openings such as culverts, staircases, , as applicable. • Rebars will not be modeled attached , as applicable.
all necessary details walls and doors will be modeled • The specification reference to be accessible
• Small openings for pipes, cable trays as well as a link to an external data base.
as equipment recesses will not be modeled
G90 Other site construction

G9090 Other site systems and equipment

Additional Comments:
1. U-Value:The U-value parameter added to the object to specify thermal property of: external walls, façades, roofs, floors, slabs, relevant partitions and similar zone separation boundaries. The boundary to be treated as a composition of layers. U-value of materials to be incorporated in specification if relevant.

2. Geometry of certain elements such as waterproofing, paint or various types of coating, if not required by the LOD matrix, the information is to be included. In This type of situation the information to be attached to objects related with the information.
For example:
- The geometry of (A2020210) Foundation Damp proofing is not modeled, but the information regarding the Damp proofing have to be attached to the foundation geometry as required by the iLOD to allow for quantity take-off.
- (B1010910 / B1010920) Layer of fire proofing does not have to be modeled but has to be specified in the steel element parameters iLOD.
- The model originator to provide explanation of the process in the project specific BIM Execution Plan.
- If accessories are represented graphically in non-quantifiable form, the information describing the accessory have to be attached to the relevant elements (for example, as room data).
- Layers that have less than 5mm thickness do not have to be modeled as an element. Its thickness to be included in the overall dimension of the object.
- ( B1020500 / B1020600 / B1020800 ) for special items and those with material other than steel will not include fire proofing or other insulation information in Design stage BIM models.
3. According to DAEP EIR and International BIM standards as PAS1192-2, each element representation and design have to be represent the space allocation for the product’s access space for maintenance, installation and replacement space in addition to its operational space. Equipment’s clearances, operation maintenance pathways, relevant required kinetic envelopes critical to design to be
included in the modeled elements and models. for example (eLOD/iLOD):
- Grids, Levels, Setting out lines, Plots, etc.
- Volume and Space reservation. (e.g. Door Swings, Rooms, Fire compartments)
- Clearances for operation and maintenance (maintainable assets)
- Accessibility paths (critical paths only)
- Other elements for coordination (e.g. complex elements geometry set-out)
4. Layer of fire proofing does not have to be modeled but has to be specified in the steel element parameters iLOD. In case of fire protection casing, to follow interior finishes requirements.
5. Openings for cable trays and ducts to be modeled when penetrating through structural walls and when size of opening in a non-structural wall requires additional structural elements such as lintels beams, secondary steel… etc.
6. The model originator to describe in the project specific BEP the type of information and the method of providing the information to fulfil the requirements of iLOD matrix.

7. Kinetic envelopes for vehicles will be part of the the road/tunnel model and other critical interface areas will be modeled in critical locations such as GSE roads or tunnels in basement.

8. Uniformat II/Assembly Code (DAEP Specific) reference to be attached to model elements beginning from concept design stage to be utilized for Cost Planning development by the appointed CQS.

9. Technical specification to be linked or referenced to the model elements at Draft Final/Final Design Stage. The use of Keynote to identify Masterformat specification of each product from the construction assembly is to be used.

10. If an object i.e. ( NAVAIDS, Airfield Signaling and Control Equipment, Counterpoise Earthing, Cathodic Protection) is not part of a design consultants scope, the development of the BIM model is the responsibility of the appointed specialist contractor starting from the stage of appointment – design or construction. This point does not apply to Special Support Systems as C1040 or D6010100.

11. Special Support Systems to be considered:


• Special support systems elements to be modeled from PD stage as per design scope of works.
• Lintels
- Lintel area reservation to be modeled for coordination purposes in design stages, in later stages the lintels to be modeled as per eLOD definitions.
• Seismic bracing, from PD stage as per design scope of works.

12. Existing site, building elements and components described in F20 and G10 for Uniformat II Assembly code (DAEP Specific):
- Site infrastructures and installations that are existing and to be retained are to be modeled from PD Stage.
- Building services and installations that are existing and to be retained are to be modeled from PD Stage.
- Existing infrastructure and installations that fall within the project boundaries and affected zones to be modeled.

13. Miscelleneous details as well as hangers and supports, if not related to Special Support Systems, will not modeled in design stage BIM models.
14. No cable routing/wiring/sizing will be included for BMS system in Design Stage BIM models. Cable trays or conduits with sizes exceeding 100mm to be modeled.
15. For Graphical representation, value in table 1 is indicative only and will not supersede the drawing standard currently approved by DAEP.
16. Thermal Insulations for Pipes and Ducts will be modeled as per design scope where required and referred to as the standard element insulation, in BIM Models of Design Stage.
17. For composite elements such as Roofs, floors, walls, partitions, sub-elements will be added as layers to the element and material classification will follow DAEP master specifications, with the use of keynote to identify Masterformat specification of each product of the construction assembly.
18. In Construction stage, steel structures to be modeled for Pre-camber and Non-Pre-Camber